(E)MSB-A
3000A
277/480V, 3ɸ, 4W
T
(E)UTILITY TRANSFORMER
T
(E)1000kVA
XFMR
(E)DP-DA2
3000A
120/208V, 3ɸ,
4W
(E)
DP-RC3
(E)
DP-RC5
(N)
PP-RC
6.3
LEVEL 1
LEVEL 3
LEVEL 5
LEVEL 6
SCALE: 1 EXISTING ELECTRICAL ONE-LINE DIAGRAM
NOT TO SCALE
MECHANICAL EQUIPMENT SCHEDULE
MARK DESCRIPTION
VOLT /
PHASE
HP WATTS FLA MCA MOCP
DISCONNECT/
FUSE SIZE
FEEDER SPECIFIC NOTES
FC-1 BEDROOM 4 FAN COIL UNIT 120/1 1/12 156 1.3 1.7 20A1P
1P MOTOR RATED
SWITCH
(2#12, 1#12GRD)
3/4"C
GENERAL NOTES:
A. SEE SPECIFICATIONS FOR ELECTRICAL DIVISION AND MECHANICAL DIVISION MOTOR STARTER COORDINATION.
B. WHEN EQUIPMENT IS LISTED WITH ONLY A HORSEPOWER RATING THE DISCONNECT AND FEEDER ARE SIZED PER THE N.E.C.
SPECIFIC NOTES:
(1)
(2)
(3)
(4)
FLAG NOTES:
1 REPLACE EXISTING 42-SPACE PANEL WITH NEW
54-SPACE PANEL.
1
F1
F2
F3
F4
PANEL: (E) PP-RC6.3
VOLTAGE:
120/208V, 3PH, 4W
MINIMUM BUS: 225
LOCATION: UNIT 6103 MAIN: 225/3 CB
MOUNTING: RECESSED MINIMUM AIC: 22,000
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION
LOAD
NO. A B C POLE TRIP A B C TRIP POLE A B C
1 A (N)WARMING DRWR 1 20 + 20 1 EXISTING LOAD 2
3 A (N)WARMING DRWR 1 20 + 20 1 EXISTING LOAD 4
5 A (N)COFFEE MAKER 1 20 + 20 1 EXISTING LOAD 6
7 R (N)REC 1 20 + 20 1 EXISTING LOAD 8
9 R (N)REC 1 20 + 20 1 EXISTING LOAD 10
11 EXISTING LOAD 1 20 + 20 1 EXISTING LOAD 12
13 EXISTING LOAD 1 20 + 20 1 EXISTING LOAD 14
15 R (N)BED 2 1 20 + 20 1 EXISTING LOAD 16
17 EXISTING LOAD 1 20 + 20 1 EXISTING LOAD 18
19 EXISTING LOAD 1 20 + 20 1 L (N)LTG C.P./SAFE/DRAP 20
21 EXISTING LOAD 1 20 + 20 1 EXISTING LOAD 22
23 EXISTING LOAD 1 20 + 20 1 EXISTING LOAD 24
25 EXISTING LOAD 1 20 + 20 1 SPARE 26
27 R (N)MASTER BED 1 20 + 50 2 EXISTING LOAD 28
29 EXISTING LOAD 1 20 + -- -- -- 30
31 EXISTING LOAD 1 20 + 30 2 EXISTING LOAD 32
33 R (N)MASTER BED 1 20 + -- -- -- 34
35 M (N)FC-1 1 20 + 20 1 EXISTING LOAD 36
37 R (N)BED 4/BED 3 BATH 1 20 + 20 1 EXISTING LOAD 38
39 R (N)BED 2 BATH 1 20 + 30 2 A (N)OVEN 40
41 R (N)MASTER BATH 1 20 + -- -- A -- 42
43 L (N)LIGHTING 1 20 + 20 1 L (N)LIGHTING 44
45 L (N)LIGHTING 1 20 + 20 1 SPARE 46
47 SPARE 1 20 + 20 1 SPARE 48
49 SPARE 1 20 + 20 1 SPARE 50
51 SPARE 1 20 + 20 1 SPARE 52
53 SPARE 1 20 + 20 1 SPARE 54
LOAD TYPE PANEL TOTAL
FEED THRU
TOTAL
SUBFEED
TOTAL
FEEDER
SUBTOTAL
DEMAND FEEDER TOTAL
GENERAL NOTES:
A. NEW LOADS NOTED WITH (N).
(L) LIGHTING 0 0 125% 0 B.
(R) RECEPTACLES 0 0 NEC 220 0 C.
(LM) LARGEST MOTOR 0 0 25% 0 D.
(M) MOTORS (ALL) 0 0 100% 0 E.
(E) EQUIPMENT 0 0 100% 0 SPECIFIC NOTES:
(A) APPLIANCES 0 0 0 0 (1)
PANEL TOTAL (KVA): 0.0 (2)
(3)
PANEL TOTAL (A): 0 (4)
(5)
SHORT CIRCUIT / VOLTAGE DROP CALCULATION SUMMARY
POINT
TAG
VOLTAGE /
PHASE
LENGTH
(FT)
COPPER /
ALUMINUM
CONDUIT
WIRE
SIZE
# OF
SETS
FEEDER
VOLTAGE
DROP (%)
TOTAL
VOLTAGE
DROP (%)
Isc
AVAILABLE
UPSTREAM
Isc (FAULT)
F1 (E)DP-DA2 208V, 3Ø 40 A S 600 9 0.4% 0.4% 52,500 47,871
F2 (E)DP-RC3 208V, 3Ø 80 A S 500 3 0.9% 1.3% 47,871 30,554
F3 (E)DP-RC5 208V, 3Ø 150 A S 250 2 2.2% 3.5% 30,554 11,869
F4 (N)PP-RC6.3 208V, 3Ø 145 A S 300 1 2.0% 5.4% 11,869 5,846
** FOR DESIGN PURPOSES, A 1000kVA TRANSFORMER WITH A MAXIMUM AVAILABLE (SYMMETRICAL) FAULT AT THE SECONDARY OF 52,500 AMPS HAS
BEEN ASSUMED. ACTUAL FAULT CURRENT INFORMATINO SHALL BE PROVIDED TO THE ELECTRICAL ENGINEER, PRIOR TO PURCHASING ANY ELECTRICAL
EQUIPMENT, TO ALLOW VERIFICATION OF THESE CALCULATIONS. SHORT CIRCUIT CALCULATIONS ARE FURNISED FOR ALL FAULT LEVELS ABOVE 10,000
AMPS @ 208 VOLTS. ANY FAULT CURRENT BELOW THIS LEVEL IS CONSIDERED SAFE FOR THE ELECTRICAL SYSTEM TO CLEAR OR EQUIPMENT IS BUILT
TO WITHSTAND THIS LEVEL OF FAULT SAFELY.
LUMINAIRE SCHEDULE
TYPE DESCRIPTION MOUNTING
RECESS
DEPTH
LAMPS
INPUT WATTS VOLT MANUFACTURER CATALOG NUMBER
SPECIFIC
NOTES
QTY TYPE
LA-101A
RECESSED MOUNTED, ADJUSTABLE WARM-DIM LED
ACCENT LIGHT WITH 1" CONICAL REGRESSED
FLANGELESS TRIM
RECESSED 7 1/4" -- LED W/ UNIT 14.5 120-277
SPECIALTY
LIGHTING
INDUSTRIES
GR-IC-AD14-A-AD-NF-L5-GRT-RD-
ZT-WHT-91A
LA-101B
RECESSED ADJUSTABLE 3" WARM-DIM LED ACCENT
LIGHT WITH BEVELED TRIM. WET LISTED FIXTURE
RECESSED 7 1/4" -- LED W/ UNIT 14.5 120-277
SPECIALTY
LIGHTING
INDUSTRIES
GR-IC-AD14-A-AD-NF-DRIVER-GRT-
RD-FT-WHT-91A
LA-102
LINEAR LED LIGHT STRIP. WET-LISTED FIXTURE,
REQUIRES REMOTE POWER SUPPLIES
SURFACE -- -- LED W/ UNIT 5.2 W/FT 24VDC LUMINII KMW-12-27K-HO-M-F-F1 (2)
LA-103 SURFACE MOUNTED, NARROW PROFILE LED LINEAR SURFACE -- -- LED W/ UNIT 12.6 120-277 PRULITE LIGHTING
HSS-LED3-LO-3'-SAL-SC-UNV-SUR-
LDE5-205-DM
LA-104
SURFACE MOUNTED IN ARCHITECTURAL AND MILLWORK
DETAIL, LED LIGHT STRIP, REQUIRES REMOTE POWER
SUPPLIES
SURFACE -- -- LED W/ UNIT 3 W/FT 24VDC LUMINII LL36-27K-F-M-SL7-F-SA-MC-SL7-S (2)
LA-105
MILLWORK DETAIL, LED LIGHT STRIP, REQUIRES REMOTE
POWER SUPPLIES
SURFACE -- -- LED W/ UNIT 4.5 W/FT 24VDC LUMINII LL54-27K-F-M-SL7-F-SA-MC-SL7-S (3)
12-LT-02
A CLUSTED OF 5 PENDANTS, 3 SMALL AND 2 LARGE LATH
LAMPS
PENDANT -- 5
GREEN CREATIVE
#4.5FG25DIM/827
300 120 ATELIER-D 2xBIG LATH LAMP
12-LT-05 BIRCH CEILING FIXTURE PENDANT -- 1
GREEN CREATIVE
#7.5A19DIM/827
20 120 SECTO DESIGN KONTORO 6000
12-LT-10
ROUND FLUSH CEILING MOUNTED FIXTURE WITH ALL
FABRIC
CONSTRUCTION
SURFACE -- 3
GREEN CREATIVE
#9.5A19DIM/8CCTD
29 120 CUSTOM
REFER TO
LIGHTING DESIGNERS
SPECIFICATIONS FOR MORE
INFORMATION.
12-LT-14 WALL-MOUNTED LINEAR SCONCE SURFACE -- -- LED W/ UNIT 13 120 MODULIGHTER AL02 MINILUX HR MM03A
GENERAL NOTES:
A. THE LUMINAIRE SCHEDULE CAN NOT BE USED INDEPENDENTLY OF THE DRAWINGS AND SPECIFICATIONS TO OBTAIN LUMINAIRE COSTS. THE INDIVIDUAL ESTABLISHING LUMINAIRE COSTS SHALL NOT QUOTE PRICING
WITHOUT FIRST SEEING APPLICABLE ELECTRICAL DRAWINGS AND ELECTRICAL DIVISION SPECIFICATIONS. THE CONTRACTOR IS REPONSIBLE FOR PROVIDING NECESSARY DRAWINGS AND SPECIFICATIONS TO THE
INDIVIDUAL QUOTING LUMINAIRE PRICING.
B. REFER TO DRAWINGS FOR FIXTURES REQUIRING EMERGENCY BATTERY BACKUP OPTION (SHOWN BY HATCH IN/OVER SYMBOL). MINIMUM LIGHT OUTPUT FOR EM BALLAST SHALL BE 600 LUMENS.
C. ALL FLUORESCENT LAMPS ARE TO BE 3500° KELVIN COLOR TEMPERATURE
SPECIFIC NOTES:
(1) PROVIDE LUMINII #PSV-40-24-U2DIM-D POWER SUPPLY UNLESS NOTED OTHERWISE.
(2) PROVIDE LUMINII #PSV-60-24-U2DIM-D POWER SUPPLY UNLESS NOTED OTHERWISE.
(3) PROVIDE LUMINII #PSV-96-24-U2DIM-D POWER SUPPLY UNLESS NOTED OTHERWISE.
(4)
METER PANEL 'PP-RC6.3' FOR 30-DAYS PER NEC 220.87 TO DETERMINE
AVAILABLE LOAD CAPACITY. IT IS ASSUMED AT TIME OF PERMIT, PANEL
'PP-RC6.3' HAS SUFFICIENT CAPACITY FOR ADDED LOADS. ELECTRICAL
CONTRACTOR TO PROVIDE ELECTRICAL ENGINEER WITH METERED DATA
PRIOR TO INSTALLATION OF ELECTRICAL SYSTEMS TO VERIFY
SUFFICIENT CAPACITY IN PANEL.
THE LOAD BEING ADDED TO PANEL 'PP-RC6.3' IS AS FOLLOWS:
1. RECEPTACLES = 5,220 VA
2. DIGITAL SIGNAGE = 50 VA
3. LUTRON CONTROL PANEL = 40 VA
4. MOTORIZED SHADES = 500 VA
5. OVEN = 4,992 VA
6. WARMING DRAWERS (x2) = 3,600 VA
7. COFFEE MAKER = 1,800 VA
8. MIRRORS = 220 VA
9. SAFES (x4) = 200 VA
TOTAL = 16,622 VA
THIS IS A TOTAL ADDED LOAD TO PANEL 'PP-RC6.3' OF 46.2 AMPS AT 208
VOLT, 3-PHASE
PROJ. NO.
DRAWN:
CHECKED:
DATE:
SCALE:
SHEET NUMBER
SHEET TITLE:
ISSUED FOR:
APPROVED:
As indicated
FOUR
SEASONS
RESORT AT VAIL
ONE
VAIL
ROAD
VAIL, CO 81657
8203.11
2017/08/02
ISSUE FOR BUILDING
PERMIT
FOUR SEASONS RESORT
AT VAIL
S:\BGPROJECTS\8203.11
VAIL
FOUR
SEASONS
MODEL
ROOM\DRAWINGS\ROOM
6103\8203.11E002.DWG
08.02.17
10:39:11 AM ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 8203.11 Copyright 2017
ELECTRICAL