HomeMy WebLinkAboutB17-0293_E-105_1507140025.pdfMASTER BEDROOM
BEDROOM 2
LAUNDRY
KITCHEN
BEDROOM 3
BEDROOM 4
ENTRY
TV
SCALE:
ROOM 6103 ELECTRICAL PLAN
1/4" = 1'-0"
J
J
J
+44"
T
J +12" +50"
J
T +60"
+12"
J
+50"
+12"
T
+60"
J
J +65"
+52"
J +65"
+52"
J
+65"
+52"
J
+50"
J
+12"
J
J
+65"
+52"
T
+12"
+60"
T
+60"
CK
CK
TV
TV
TV
CH
+12"
+24"
+12"
+12"
+12"
+12"
+12"
+12"
+12"
+12"
+12"
+12"
+12"
TV
TV
(E)DISP
J
(E) STEAM
GENERATOR
FLAG NOTES:
1 PROVIDE 20A, 120V ELECTRICAL FEED TO JUNCTION
BOX FOR ELECTRIC MIRROR WITH INTEGRAL TV.
COORDINATE EXACT LOCATION WITH ARCHITECT
PRIOR TO ROUGH-IN. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER SUBMITTAL
PRIOR TO ROUGH-IN.
PROVIDE 20A, 120V ELECTRICAL FEED TO JUNCTION
BOX FOR MIRROR. COORDINATE EXACT LOCATION
WITH ARCHITECT PRIOR TO ROUGH-IN.
COORDINATE EXACT POWER REQUIREMENTS WITH
MANUFACTURER SUBMITTAL PRIOR TO ROUGH-IN.
PROVIDE 20A, 120V ELECTRICAL FEED TO JUNCTION
BOX FOR NIGHTLIGHT LOCATED BELOW VANITY
LIGHT. COORDINATE EXACT LOCATION WITH
ARCHITECT PRIOR TO ROUGH-IN. COORDINATE
EXACT POWER REQUIREMENTS WITH
MANUFACTURER SUBMITTAL PRIOR TO ROUGH-IN.
PROVIDE 20A, 120V ELECTRICAL FEED FOR
MOTORIZED DRAPERY. COORDINATE EXACT
LOCATION WITH ARCHITECT PRIOR TO ROUGH-IN.
COORDINATE EXACT POWER REQUIREMENTS WITH
MANUFACTURER SUBMITTAL PRIOR TO ROUGH-IN.
PROVIDE 20A, 120V ELECTRICAL FEED FOR SAFE.
COORDINATE EXACT LOCATION WITH ARCHITECT
PRIOR TO ROUGH-IN. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER SUBMITTAL
PRIOR TO ROUGH-IN.
PROVIDE PNUEMATIC PUSH BUTTON TO OPERATE
GARBAGE DISPOSAL. COORDINATE EXACT
LOCATION AND INSTALLATION WITH ARCHITECT
AND MECHANICAL CONTRACTOR PRIOR TO
ROUGH-IN.
PROVIDE 30A, 208V RECEPTACLE FOR OVEN.
REUSE EXISTING ELECTRICAL CIRCUIT SERVING
THIS AREA TO SERVE NEW RECEPTACLE.
REPLACE EXISTING 42-SPACE PANEL WITH NEW
54-SPACE PANEL. REFER TO ELECTRICAL ONE-LINE
DIAGRAM ON SHEET E-001 FOR MORE
INFORMATION.
NOT USED.
PROVIDE DUPLEX RECEPTACLE WITH (2) USB
CHARGING PORTS. RECEPTACLE SHALL BE
MOUNTED HORIZONTALLY ADJACENT TO LIGHTING
CONTROL KEYPAD SHOWN ON EL-105.
1. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER
(AFCI) CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS SERVING OUTLETS OR DEVICES IN
RESIDENCE, EXCEPT FOR GARAGE AND
BATHROOMS, PER NEC 210.12.
2. PROVIDE TAMPER-RESISTANT TYPE
RECEPTACLES IN ALL AREAS REQUIRED IN NEC
406.12.
3. VERIFY ALL EQUIPMENT AND APPLIANCE
ELECTRICAL POWER CONNECTION
REQUIREMENTS WITH GC PRIOR TO ROUGH-IN,
FOR THE EXACT MODELS MAY HAVE CHANGED
SINCE DESIGN.
4. REFER TO LIGHTING DESIGN PLANS AND
SPECIFICATIONS FOR WORK ASSOCIATED WITH
THE LIGHTING AND LIGHTING CONTROL SYSTEMS.
5. REFER TO ARCHITECTURAL PLANS AND INTERIOR
ELEVATIONS FOR RECEPTACLE AND DEVICE
PLACEMENT. COORDINATE ALL RECEPTACLE
MOUNTING LOCATIONS WITH FIXTURES,
APPLIANCES, CABINETRY, AND OTHER
EQUIPMENT.
6. COORDINATE EXACT POWER CONNECTION AND
DEVICE REQUIREMENTS FOR TELECOM, AV, DATA,
AND SECURITY EQUIPMENT WITH LOW VOLTAGE
SYSTEMS PLANS. OR WITH ARCHITECT AND LOW
VOLTAGE CONTRACTOR IF NO LOW VOLTAGE
SYSTEMS PLANS ARE AVAILABLE.
7. COORDINATE 120 VOLT POWER CONNECTIONS
FOR FIRE ALARM SYSTEM AND DEVICES, AND
CARBON MONOXIDE DEVICES.
8. ALL EQUIPMENT, DEVICES AND CONDUCTORS
SHALL BE IN NEW CONDITION AND RATED FOR
THE APPLICATION.
9. COORDINATE POWER CONNECTIONS FOR
MECHANICAL EQUIPMENT, OWNER PROVIDED
EQUIPMENT AND APPLIANCES, AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD COORDINATE EXACT
LOCATIONS OF EQUIPMENT AND POWER
CONNECTIONS WITH GC AND OTHER
DIVISIONS/CONTRACTORS.
10. CONTRACTOR SHALL PROVIDE A “BOX
WALK” WITH ARCHITECT AND/OR OWNER'S
REPRESENTATIVE AFTER ELECTRICAL DEVICE
BOXES HAVE BEEN ROUGHED-IN OR INSTALLED
AND PRIOR TO WIRING AND INSTALLATION OF
DEVICES. CONTRACTOR SHALL INCLUDE IN THEIR
PRICE THE RELOCATION AND ADJUSTMENTS OF
ELECTRICAL DEVICE BOXES TO MEET THE
ARCHITECT'S/OWNER'S REQUIREMENTS.
11. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
12. ALL EXISTING DEVICES ARE NOTED WITH (E).
RESIDENTIAL DWELLING
UNIT NOTES:
C
(E)W/D
(E)'PP-RC6.3'
+38"
+38"
+60"
+38"
J SAFE
2
2
J
3
3
4
+60"
4
4
2
J
5
5
5
4
J
5
J
3
3
2
J
4
5
+12"
+12"
+44"
SAFE
SAFE
+44"
J
3
2
4
REF/FRZR
OVEN
40,42
WARMING DRWR
COFFEE MAKER
MW
DW
6
+44"
6
COOKTOP
7
7
SAFE
(E)
(E)
(E)
(E)
C
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
C
(E)
(E)
(E)
FC
1
1. ALL DEVICES IN UNIT 6103 SHALL BE CIRCUITED TO
PANEL 'PP-RC6.3'
2. METER PANEL 'PP-RC6.3' FOR 30-DAYS PER NEC
220.87 TO DETERMINE AVAILABLE LOAD CAPACITY. IT
IS ASSUMED AT TIME OF PERMIT, PANEL 'PP-RC6.3'
HAS SUFFICIENT CAPACITY FOR ADDED LOADS.
ELECTRICAL CONTRACTOR TO PROVIDE ELECTRICAL
ENGINEER WITH METERED DATA PRIOR TO
INSTALLATION OF ELECTRICAL SYSTEMS TO VERIFY
SUFFICIENT CAPACITY IN PANEL.
3. FIRE ALARM SCOPE LIMITED TO REMODEL PORTION
OF BUILDING ONLY. FIRE ALARM SYSTEM SHALL BE
DESIGN/BUILD BY CONTRACTOR. FIRE ALARM
DEVICES SHOWN ON PLAN ARE FOR DESIGN INTENT.
FINAL DESIGN RESPONSIBILITY BY DESIGN/BUILD
CONTRACTOR.
NOTES:
(E)
8
8
(E)
8
+38"
8
8
8
8
(E)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
20
20
20
20
1 3
5
7
7
9
7
9
7
7
7
20
20
20
20
20
7
7
9
9
9
9
9
11
11
11
11
27
27
27
27
27 33 33
35
37
37
37
37
37
37
37
39
39
39
39
41
41
41
41
9
9
20
H
H
H
H
H
F
CO
CO
CO
CO
(E)
(E)
(E)
(E)
(E)
(E)
H
10
11
11
8
11
8
11
8
11
8
11
8
11
8 11 8 11
1
1
1
1
1
1
1
1
1
1
1
PROJ. NO.
DRAWN:
CHECKED:
DATE:
SCALE:
SHEET NUMBER
SHEET TITLE:
ISSUED FOR:
APPROVED:
As indicated
FOUR
SEASONS
RESORT AT VAIL
ONE
VAIL
ROAD
VAIL, CO 81657
8203.11
2017/09/05
ISSUE FOR BUILDING
PERMIT
FOUR SEASONS RESORT
AT VAIL
S:\BGPROJECTS\8203.11
VAIL
FOUR
SEASONS
MODEL
ROOM\DRAWINGS\ROOM
6103\8203.11E105.DWG
09.19.17
9:41:08 AM ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 8203.11 Copyright 2017
1
REVISION 1
ROOM 6103
ELECTRICAL PLAN
E-105
BAS
MAS
MAS
3003 Larimer Street
Denver, Colorado 80205
phone 303.861.5704
www.ozarch.com
ARCHITECTURE
®
10/04/17