ISSUE LOG KEY:
# DATE
ISSUE LOG
MECHANICAL SHEET INDEX
TITLE
MECHANICAL COVER SHEET
M-000
PERMI T SET
07.25.2017
ISSUED AS PART OF A SET
' ' NOT PART OF SET
' ' ISSUED FOR INFORMATION ONLY
*
√
√
√
√
ROOM 6103 MECHANICAL PLAN
M-101 ROOM 6103 MECHANICAL DEMO PLAN
M-102
NOTES
1. ALL SYMBOLS, ABBREVIATIONS, AND DESIGNATIONS
ON LEGEND SHEET ARE NOT NECESSARILY USED ON
THIS PROJECT.
2. THIS DRAWING SET CONSISTS OF DATA GENERATED, IN
PART, BY OTHER PARTIES. NOT ALL SYMBOLOGIES AND
NOTATION CONVENTIONS OCCURRING IN THIS
DRAWING SET ARE NECESSARILY DEFINED ON THESE
LEGENDS. CONSULT THE ENGINEER IN THE EVENT
SYMBOLOGY OR NOTATION INTERPRETATION IS
REQUIRED.
PLAN SYMBOLS
POINT OF NEW CONNECTION
POINT OF DISCONNECTION
THERMOSTAT
T
PIPING DESIGNATIONS
CHILLED WATER SUPPLY
CHILLED WATER RETURN
DOMESTIC WATER
DOMESTIC HOT WATER
DHW RECIRCULATION
FIRE LINE
PLUMBING VENT PIPE
WASTE PIPE
STORM DRAIN PIPE
STORM DRAIN OVERFLOW
HEATING WATER SUPPLY
HEATING WATER RETURN
DRAIN PIPE
PLUMBING PIPING
CHR
CHS
HWR
HWS
D
CW
HW
HWC
ST
V
W
ST(OF)
F
HYDRONIC PIPING
MECHANICAL LEGEND
ABOVE SEA LEVEL
PROJECT ALTITUDE
8020'
FAN COIL SCHEDULE (HYDRONIC)
MARK SERVICE TYPE
FAN COOLING COIL HEATING COIL
FILTER
MANUFACTURER*
& MODEL #
ACCESSORIES REMARKS
CFM
ELECTRICAL AIR CONDITIONS WATER CONDITIONS AIR CONDITIONS WATER CONDITIONS
@ ALT
(IN WC) HP
VOLT/
PH
E.A.T.
DB/WB
(°F)
L.A.T.
DB/WB
(°F)
TOTAL
MBH
SENSIBLE
MBH
E.W.T.
(°F)
L.W.T.
(°F) GPM MAX.WTR
P.D. (FT.)
E.A.T.
DB (°F)
L.A.T.
DB (°F)
SENSIBLE
MBH
E.W.T.
(°F)
L.W.T.
(°F) GPM MAX.WTR
P.D. (FT.)
FC-1 BEDROOM
HORIZONTAL
CEILING
265 0.4 1/12 120/1 80/60 55/50 4.3 4.0 45.0 55 1.0 3.7 70 106 3.2 160 140 0.6 0.6 MERV8 IEC CPY04 - A, B, C, D
MANUFACTURERS:
* CARRIER, ENVIROTEC, MCQUAY, TRANE
GENERAL NOTES:
A: PROVIDE UNIT WITH REAR RETURN AIR.
B: PROVIDE HONEYWELL THERMOSTAT TO MATCH EXISTING IN UNIT. THERMOSTAT SHALL HAVE 7-DAY PROGRAMMING CAPABILITY, TEMPERATURE ADJUSTMENT, AND MANUAL FAN OVERRIDE.
C: PROVIDE DRAIN PAN FLOAT SWITCH IN LIEU OF SECONDARY DRAIN PAN
D: PROVIDE 3-SPEED FAN THAT RUNS ON MEDIUM SPEED WHILE COOLING AND LOW SPEED WHILE HEATING DURING NORMAL OPERATION.
TYPICAL HANGER DIAGRAM
NO SCALE
ANCHOR,
REFER TO
STRUCTURAL.
THREADED
ROD.
HANGER.
PIPE.
CONCRETE
STRUCTURE.
NOTE:
ALL PIPING WITH
INSULATION TO HAVE
INSULATION RUN FULL
SIZE THROUGH
HANGER WITH SHIELD
AND INSERT.
OFF DIAGRAM
45° DUCT TAKE-
45°
NO SCALE
W
H
1/4 OF "W" OR 6"
MINIMUM.
END
BEARING.
SINGLE BLADE DAMPER
IF H<8" OPPOSED BLADE
DAMPER IF H>=8"
SEAL AIRTIGHT AROUND
ENTIRE TAKE-OFF.
FIRE DAMPER AND FIRE/SMOKE
NO SCALE
1.
2.
NOTES:
DAMPER ASSEMBLY DIAGRAM
FAN COIL UNIT INSTALLATION
NO SCALE
D
SA FAN COIL UNIT
D
FILTER W/ ACCESS
PANEL.
CONDENSATE DRAIN. PIPE
INDIRECT TO APPROVED
RECEPTOR (PROVIDE MIN.
2" DEEP TRAP).
SHEET METAL DRAIN PAN.
3/4" SECONDARY DRAIN TO
APPROVED RECEPTOR. PIPE
INDIRECT TO FLOOR DRAIN
ON SINK TAIL PIECE, TYP.
ROUND HANGER ROD TYP.
WITH EXCEPTION OF FAN
COILS LOCATED IN ATTIC.
SPRING VIBRATION
ISOLATORS, TYP.
DOUBLE LOCKNUT.
CEILING
2-WAY COIL PIPING DIAGRAM
NO SCALE
E
STRAINER WITH
BLOWDOWN
AND CAP.
MANUAL AIR VENT
AT HIGHEST POINT
IN PIPING.
RETURN
SUPPLY
MECHANICAL SPECIFICATIONS
M-001
√
D
C
A
B
ISOLATION
VALVE
BALANCE
VALVE
PROJ. NO.
DRAWN:
CHECKED:
DATE:
SCALE:
SHEET NUMBER
SHEET TITLE:
ISSUED FOR:
APPROVED:
As indicated
FOUR
SEASONS
RESORT AT VAIL
ONE
VAIL
ROAD
VAIL, CO 81657
8203.11
JAC
ARK
2017/08/02
ISSUE FOR BUILDING
PERMIT
FOUR SEASONS RESORT
AT VAIL
BDS
S:\BGPROJECTS\8203.11
VAIL
FOUR
SEASONS
MODEL
ROOM\DRAWINGS\ROOM
6103\8203.11M000.DWG
08.01.17
1:24:19 PM ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. xxxx.xx Copyright 2017
MECHANICAL
COVER SHEET
M-000
3003 Larimer Street
Denver, Colorado 80205
phone 303.861.5704
www.ozarch.com
ARCHITECTURE
®
08/25/17