HomeMy WebLinkAboutB17-0340_A-720-1_1507837270.pdfINTERIOR PARTITION TYPES
STRUCTURE
A 7/8" HAT CHANNEL
B 1 5/8" METAL STUD
C 2 1/2" METAL STUD
D 3 5/8" METAL STUD
E 4" METAL STUD
F 6" METAL STUD
G 3 5/8" DOUBLE METAL STUD
J 2 1/2" C-H METAL STUD
K 4" C-H METAL STUD
L 6" C-H METAL STUD
M 2x4 WOOD STUD
N 2x6 WOOD STUD
P 4" CMU
Q 6" CMU
R 8" CMU
S 12" CMU
Z 1 1/2" "Z" FURRING CHANNEL
D1s
X
EXAMPLE
D = 3 5/8" METAL STUD
1 = 1 HOUR FIRE RESISTANCE
RATING
s = SOUND PARTITION
FIRE RESISTANCE RATING*
0 NON-RATED
1 1 HOUR
2 2 HOUR
3 3 HOUR
4 4 HOUR
SUB-TYPE
a 6" ABOVE CEILING
b UNDERSIDE OF STRUCTURE
c UNDER SIDE OF CEILING
f FURRING
l LEAD LINED
k SECURITY MESH
p PARTIAL HEIGHT
s SOUND PARTITION
t THERMAL INSULATION
v SOUND PARTITION WITH (2) LAYERS
GYPSUM BOARD EACH SIDE
w SOUND PARTITION WITH (2) LAYERS
GYPSUM BOARD ONE SIDE
(1) LAYER OTHER SIDE
z TILE BACKER BOARD
SMOKE RATED*
X SMOKE PARTITION,
SMOKE BARRIER OR WALL
RESISTING THE PASSAGE
OF SMOKE
STRUCTURE
FIRE RESISTANCE RATING
SUB-TYPE
SMOKE RATED (OPTIONAL)
* SEE RATED PARTITION NOTE 2
GENERAL CONSTRUCTION AND LAYOUT NOTES
1. THE INTERIOR FRAMING SUBCONTRACTOR SHALL PROVIDE A DELEGATED ENGINEERED STUD DESIGN FOR ALL NON-STRUCTURAL METAL FRAMING FOR
WALLS AND CEILINGS. SUBMIT FRAMING SHOP DRAWINGS WITH DETAILS, PRODUCT SELECTIONS, AND ENGINEERING CALCULATIONS STAMPED BY A
LICENSED ENGINEER IN THE PROJECT JURISDICTION. ENGINEERING SHALL INCLUDE PROVISIONS FOR ELEMENTS ATTACHED TO/SUPPORTED BY THE
FRAMING. FASTENER DESIGN AND SELECTION IS ALSO REQUIRED. SUBMIT ICC ES EVALUATION REPORTS FOR EACH FASTENER. USE OF DIMPLED OR
PERFORMANCE ENHANCED SHAPED STUDS IS ACCEPTABLE. UNLESS OTHERWISE INDICATED DESIGN FOR A MAXIMUM DEFLECTION OF L/240 AT 5 PSF. AT
PARTITIONS TO RECEIVE CERAMIC TILE DESIGN FOR A MAXIMUM DEFLECTION OF L/360 AT 5 PSF. REGARDLESS OF DESIGN, PROVIDE 20 GA STUD AT A
MINIMUM.
2. ALL INTERIOR PARTITIONS ARE DIMENSIONED TO FINISHED FACE OF GYPSUM BOARD UNLESS NOTED OTHERWISE.
3. ALL STUDS SHALL BE FULL HEIGHT TO UNDERSIDE OF STRUCTURE UNLESS INDICATED OTHERWISE BY PARTITION TYPE.
4. BOTTOM OF GYPSUM BOARD SHALL BE 1/4” TO 3/8” ABOVE FINISH FLOOR UNLESS OTHERWISE INDICATED.
5. OFFSET STUDS AS NECESSARY TO ALIGN OUTSIDE FACES OF GYPSUM BOARD AT ADJACENT WALL TYPES WITH VARYING LAYERS OF GYPSUM BOARD.
6. PROVIDE DEEP LEG TRACKS (3" FLANGE) AT HEAD OF PARTITIONS AT ALL NON-LOAD BEARING PARTITIONS FOR EACH CONDITION THAT ALLOW FOR 1" OF
UPWARD MOVEMENT AND 1" OF DOWNWARD DYNAMIC MOVEMENT CAPABILITIES.
7. AT SLAB-ON-GRADE CONDITIONS PROVIDE DYNAMIC MOVEMENT REQUIREMENTS CALLED FOR IN THE GEOTECHNICAL INVESTIGATION (SOILS REPORT). IF
NO GEOTECHNICAL INVESTIGATION EXISTS CONTACT THE ARCHITECT FOR DEFLECTION CRITERIA.
8. ALL PARTITION TYPES MARKED BY A "t" SUFFIX (IE. D0t) SHALL BE INSTALLED WITH FULL HEIGHT AND WIDTH CONTINUOUS THERMAL INSULATION AND, IF
INDICATED, CONTINUOUS VAPOR RETARDER.
9. PROVIDE GYPSUM BOARD CONTROL JOINTS PER ASTM C 840 UNLESS OTHERWISE INDICATED ON DRAWINGS.
10. PROVIDE FIRE BLOCKING AND DRAFT STOPS PER CODE.
11. AT LOCATIONS ADJACENT TO GLASS SYSTEMS, GC TO VERIFY IN FIELD AND PROVIDE FASTENERS SUCH THAT THE INSTALLATION OF METAL FRAMING
DOES NOT ADVERSELY IMPACT THE GLASS SYSTEM.
RATED PARTITION NOTES
1. FIRE RATED ASSEMBLY CRITERIA TAKE PRECEDENT OVER ANY OTHER CONSTRUCTION CRITERIA.
2. REFERENCE LIFE SAFETY DRAWINGS FOR LOCATIONS OF FIREWALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE PARTITIONS, SMOKE BARRIERS, AND
WALLS RESISTING THE PASSAGE OF SMOKE. COMPLY WITH IBC AND ANY OTHER APPLICABLE CODES FOR CONSTRUCTION REQUIREMENTS FOR EACH
RATED PARTITION TYPE.
3. REFERENCE SPECIFICATION SECTION 07 8413 –‘PENETRATION FIRESTOP’ FOR TREATMENT OF ANY PENETRATIONS THROUGH A FIRE RATED PARTITION.
NEEDS TO MEET UL LISTED TEST REQUIREMENT.
4. REFERENCE SPECIFICATION SECTION 07 8443 –‘JOINT FIRESTOP’ FOR TREATMENT OF TOP AND BOTTOM OF WALL JOINTS AND JOINTS TO ABUTTING
CONSTRUCTION. NEEDS TO MEET UL LISTED TEST REQUIREMENT.
5. PROVIDE AND SUBMIT FOR APPROVAL U.L. RATED HEAD OF WALL ASSEMBLIES FOR EACH RATED PARTITION CONDITION THAT ALLOWS FOR THE DYNAMIC
MOVEMENT INDICATED. IF ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION (AHJ), OBTAIN ENGINEERING JUDGEMENTS FOR JOB SPECIFIC
CONDITIONS NOT ADDRESSED BY TESTED ASSEMBLIES.
6. PROVIDE FIRE-RATED ACCESS DOORS AND FRAMES TO REACH DAMPERS OR CONTROL VALVES IN RATED PARTITIONS OR CEILING AS REQUIRED TO
MAINTAIN RATING. PROVIDE NONRATED ACCESS DOORS AT NON RATED CONSTRUCTION.
7. WHERE DEVICES ARE RECESSED IN A FIRE RATED PARTITION PROVIDE: A.) DEVICE RATED FOR INSTALLATION IN RATED PARTITIONS, OR B.)
CONSTRUCTION SUCH THAT FIRE RATING IS MAINTAINED BEHIND RECESSED DEVICE.
8. WHERE STRUCTURAL ITEMS SUCH AS HANGERS FOR STAIRS ARE EMBEDDED IN A RATED PARTITION CONSTRUCTION SHALL BE SUCH THAT FIRE RATING IS
MAINTAINED BEHIND EMBEDDED ITEM.
9. MARKING AND IDENTIFICATION: FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
REQUIRED TO HAVE PROTECTED OPENINGS OR PENETRATIONS SHALL BE LABELED PER CODE.
10. PROVIDE SMOKE PARTITIONS TO LIMIT THE TRANSFER OF SMOKE. FILL JOINTS AND THE SPACE AROUND PENETRATING ITEMS SUCH AS DUCTS, PIPES,
CONDUITS, AND SIMILAR BUILDING SERVICE EQUIPMENT WITH AN APPROVED MATERIAL TO LIMIT THE PASSAGE OF SMOKE.
11. SEE A-720.1 FOR TYPICAL FRAMING DETAILS.
SOUND PARTITION NOTES
1. ALL PARTITION TYPES MARKED BY AN "s" SUFFIX (IE. D1s) SHALL BE INSTALLED AS A SOUND PARTITION INCLUDING: FULL HEIGHT AND WIDTH SOUND
ATTENUATION BLANKETS (SAB), ACOUSTICAL JOINT SEALANT AT TOPS AND BOTTOMS OF ALL WALLS AND PENETRATIONS, DRYWALL TO BE FROM FLOOR
TO DECK BOTH SIDES.
2. PROVIDE ELECTRICAL OUTLET BARRIER PADS IN SOUND PARTITIONS.
3. STAGGER DEVICES THAT PENETRATE OPPOSING WALL SURFACES IN ADJACENT STUD CAVITIES.
RATED ASSEMBLY INFORMATION
TOP OF WALL ASSEMBLY:
• STANDARD INTERIOR NON-BEARING WALL ASSEMBLY: UL HW-D-0495 OR EQUAL
• SHAFTWALL FLAT CONCRETE: UL HW-D-0496
• SHAFTWALL PARALLEL TO BEAM: UL HW-D-0497
• SHAFTWALL PAN DECK: UL HW-D-0504
• SHAFTWALL PROTECTED ROOF DECK: UL HW-D-0559
WALL ASSEMBLY:
• STANDARD INTERIOR NON-BEARING WALL ASSEMBLY : UL U419 OR UL U423
• SHAFTWALL ASSEMBLY: UL U415
SILL TRACK OF WALL ASSEMBLY:
• PROVIDE UL LISTED ASSEMBLY COMPLIANT WITH THE UL WALL ASSEMBLY AND THAT MATCHES FIRE RESISTIVITY OF THE WALL.
D0b
4 7/8"
5/8" 3 5/8" 5/8"
D0X
4 7/8" 5/8" 3 5/8" 5/8" D1b
4 7/8" 5/8" 3 5/8" 5/8" DOOR / FRAME MATERIAL:
AL/G - ALUMINUM GLASS
HM - HOLLOW METAL
WD - WOOD
PT - PAINTED
STAIN - STAINED
MFR - MANUFACTURER
DOOR FINISH:
PL# - PLASTIC LAMINATE
ST - STAINED
CA - CLEAR ANODIZED
PT - PAINTED
KF - KYNAR FINISH
GL - GLASS
DOOR NOTES
1. CONTRACTOR TO FIELD COORDINATE ALL ROUGH
OPENINGS.
2. REFER TO SPECIFICATIONS FOR HARDWARE TYPES
AND SCHEDULE.
3. ALL FIRE RATED DOORS SHALL HAVE
UNDERWRITERS LABEL ON DOOR AND FRAME.
4. WHERE EXISTING DOORS TO REMAIN, TOUCH UP
SCUFFING TO MAKE DOOR FINISH LIKE-NEW.
5. AT EXISTING DOORS IN SCOPE: WHERE
SCUFFED,PATCH AND REFINISH TO LIKE-NEW
CONDITION. IN AREA C, REFINISH EXISTING
DAMAGED DOORS AND DOOR FRAMES.
DOOR AND HARDWARE SCHEDULE - ABBREVIATIONS LEGEND/NOTES
FRAME NOTES
1. CONTRACTOR TO FIELD COORDINATE ALL ROUGH
OPENINGS PRIOR TO ORDERING OR FABRICATING
ANY FRAMES.
2. ALL ELEVATIONS ARE DRAWN FACING THE
EXTERIOR OF THE WINDOW FRAME.
3. STOREFRONT FABRICATOR TO PROVIDE
REINFORCING AS REQUIRED
4. ALL DIMENSIONS ARE TO MASONRY OR ROUGH
OPENING UNLESS NOTED OTHERWISE, PROVIDE
PROPER SHIM CLEARANCE AS REQUIRED.
5. AT EXISTING FRAMES IN SCOPE: WHERE SCUFFED,
PATCH AND REFINISH TO LIKE-NEW CONDITION
GLAZING TYPES
S = PROVIDE TEMPERED
GLASS IN NON-RATED
DOORS WHERE INDICATED.
F = PROVIDE FIRE-
PROTECTION-RATED GLASS
MEETING OR EXCEEDING
THE RATING OF THE DOOR
ASSEMBLY WHERE
INDICATED
SEE SPECIFICATION FOR
ACCEPTABLE GLASS
TYPES.
SINGLE FLUSH
F1
RE: SCHEDULERE: SCHED.
SINGLE NARROW LITE
(TEMPERED OR FIRE
RATED GLASS)
N1
RE: SCHEDULE
RE SCHED.
3' - 4" 8"
8"
8"
DOUBLE FLUSH
F3
RE: SCHEDULE
RE: SCHEDULE
EQ EQ
SINGLE NARROW LITE
(TEMPERED OR FIRE
RATED GLASS)
N2
RE: SCHED.
EQ EQ
8"
3' - 4" 8" 8" 8" 8"
RE: SCHEDULE
UNO
6" TYP.
TYPE
RE: PARTITION
SECTION 09 2900 -
GYPSUM BOARD
08 1416 - FLUSH WOOD
DOOR
08 1113 - INTERIOR
HOLLOW-METAL FRAME
05 4000 - COLD-FORMED
METAL FRAMING
07 9200 - JOINT SEALANT07 9200 - JOINT SEALANT
TYPE
RE: PARTITION
SECTION 09 2900 -
GYPSUM BOARD
08 1113 - INTERIOR
HOLLOW-METAL FRAME
08 1416 - FLUSH WOOD
DOOR
07 9200 - JOINT SEALANT
05 4000 - COLD-FORMED METAL FRAMING
SINGLE OR
DOUBLE DOOR
FRAME
HM1
RE: SCHEDULE 2"
2" RE: SCHED. 2"
/ C2A-720-1
/C1
A-720-1
2 1/2" 4"
1 1/2" MIN
MECH
SEE
1 1/2" MIN
4 1/4"
MECH
SEE
WALL BUMPER
SECURED TO VISUALLY
CONCEALED METAL FRAMING
16 GA GALV BRAKE
METAL; EASE EDGES
COUNTERSUNK FASTENER,
TYP 24" OC MAX
SNOW MELT PIPE AND PIPE CLAMP;
SEE MECHANICAL FOR MORE
INFORMATION
EXISTING WALL
EXISTING DOOR
8" EXISTING
DOOR
SWING
COORD
WITH
EXISTING FLOOR
7' - 2" EXISTING CEILING;
CUT BACK PANELS TO PREVENT
PIPE FROM DAMAGING
CEILING PANEL, PROVIDE
FLANGE, AND SEAL THE OPENING
CONCRETE HOUSEKEEPING PAD
B1
A-720-1
SIM
FLOORING TO MATCH EXISTING
HEAT WELD ALL SEAMS, TYP BOTH SIDES
EXISTING FLOORING OVER EXISTING
CONCRETE SLAB ON GRADE
STEGO 'CRETECLAW' TAPE OR SIM
STEGO 'WRAP' 25 MIL VAPOR BARRIER
NEW ELEC DUCT; SEAL ALL JOINTS; SEE ELECTRICAL
NEW CONCRETE INFILL AT TRENCH;
FORM FOR DUCT INSTALLATION
2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP,
P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
EAST
WING
ENABLING
6/30/2017
4:47:33 PM
15924.00
A-720-1
DOOR SCHEDULE,
PARTITION TYPES, AND
DETAILS
2017
06/30/17
PERMIT
VAIL
VALLEY
MEDICAL
CENTER
180 S. Frontage
Road
West,
Vail, CO 81657
DOOR SCHEDULE
ROOM LEAF FRAME
Hardware
Set Fire Rating
Wall
Widt
h Remarks REV
NAME
Door
Type
Door
Material Finish Width Height Thickness
Door
Glass
Type
Frame
Type
Frame
Material
Frame
Finish
LEVEL 1
101 STORAGE F3 WD PT 6' - 0" 7' - 0" 1 3/4" - HM01 HM PT 23 - 5 1/4"
110X (E) CORRIDOR N1 WD PT 4' - 0" 7' - 0" 1 3/4" - PT 1 20 4 7/8" RESISTS PASSAGE OF SMOKE
120X (E) CORRIDOR N2 PT 7' - 0" 7' - 0" 1 3/4" F HM 22 PER LS101-1 4 7/8" REUSE EXISTING FRAME. REFINISH FRAME.
RECERTIFY ASSEMBLY.
1200A EQUIPMENT F1 WD PT 3' - 6" 7' - 0" 1 3/4" - HM01 HM PT 21 PER LS101-1 4 7/8"
PARTITION TYPES SCHEDULE
PARTITION
TYPE USE DESCRIPTION
PARTITION
WIDTH STRUCTURE CONSTRUCTION DESCRIPTION TOP OF WALL TO FIRE RATING
DESIGN
NUMBER
(FIRE)
D0b PARTITION WALL 4 7/8" 3-5/8" STEEL STUDS (1) LAYER 5/8" GYPSUM BOARD EACH SIDE UNDER SIDE OF STRUCTURE NON-RATED N/A
D0s PARTITION WALL, SOUND BATTS 4 7/8" 3-5/8" STEEL STUDS (1) LAYER 5/8" GYPSUM BOARD EACH SIDE UNDER SIDE OF STRUCTURE NON-RATED N/A
D0X SMOKE PARTITION WALL 4 7/8" 3-5/8" STEEL STUDS (1) LAYER 5/8" GYPSUM BOARD EACH SIDE UNDER SIDE OF STRUCTURE NON-RATED N/A
D1b 1-HR PARTITION WALL 4 7/8" 3-5/8" STEEL STUDS (1) LAYER 5/8" TYPE "X" GYPSUM BOARD EACH SIDE UNDER SIDE OF STRUCTURE 1 HR UL U419
W1
1/4" = 1'-0"
DOOR TYPES
3" = 1'-0"
C1
HM INTERIOR DOOR FRAME JAMB
3" = 1'-0"
C2
HM
INTERIOR DOOR FRAME HEAD
1/4" = 1'-0"
FRAME TYPES
<02 - 600 - FINISH SCHEDULE>
Room
Number Room Name
Floor
Finish
Base
Finish
Wall Finish
Casework Ceiling Finish Remarks
N E S W
LEVEL 1
FUEL TANK ENCLOSURE SEE A101B-1 AND A200B-1 FOR SPECIFIC FINISH INFORMATION
101 STORAGE EXISTING FINISHES TO REMAIN. EXTEND EXISTING FINISHES TO NEW INFILL WALL.
102 O2 ENCLOSURE
110 (E) CORRIDOR EXISTING FINISHES TO REMAIN. PROVIDE MATCHING FINISHES AT CEILING, WALLS,
AND DOORS TO EXISTING FACILITY AT THIS LOCATION.
120 (E) CORRIDOR EXISTING FINISHES TO REMAIN. PROVIDE MATCHING FINISHES AT CEILING, WALLS,
AND DOORS TO EXISTING FACILITY AT THIS LOCATION.
1200B EQUIPMENT EXISTING EXISTING EXISTING PT EXISTING PT - MATCH BLDG STANDARD EXTEND EXISTING WALL BASE AESTHETIC TO NEW WALLS. WALL PAINT TO MATCH
EXISTING ADJACENT FINISHES, BOTH SIDES OF WALL.
1 1/2" = 1'-0"
B1
PIPE WRAP
1/2" = 1'-0"
B2
PIPE WRAP ELEVATION
1 1/2" = 1'-0"
A1
FLOOR TRENCH SECTION
10/12/17