HomeMy WebLinkAboutB17-0340_A-721-1_1507837280.pdf7' - 0"
8' - 6" MAX. 4' - 6" MAX.
PROVIDE BLOCKING AS REQ. TO SUPPORT CABINETS,
SHELVING, EQUIPMENT, AND DECORATIVE PANELING.
PROVIDE FULL HEIGHT CONTROL JOINTS ON
STRIKE SIDE OF DOORS 3'-0" WIDE AND UNDER,
PROVIDE FULL HEIGHT CONTROL JOINTS ON BOTH
SIDES OF DOORS WIDER THAN 3'-0".
DOOR
OPENIN
DOUBLE
DOOR
OPENIN
NOTES:
1. CONTROL JOINTS SHALL BE INSTALLED ON
BOTH SIDES OF ALL PARTITIONS.
2. CONTROL JOINTS SHALL BE INSTALLED EVERY
20'-0" ON BOTH SIDES OF ALL CURVED WALL
PARTITIONS, AND EVERY 30'-0" ON BOTH SIDES OF
STRAIGHT PARTITIONS. ALIGN CONTROL JOINTS
WITH EDGE OF CLOSEST ARCHITECTURAL
FEATURE.
3. PROVIDE FULL HEIGHT HDS STUDS AT ALL
OPENINGS AND DOOR LOCATIONS. ALTERNATE:
STUDS DESIGNATED AS "16 GAUGE PAIR" SHALL
EXTEND FULL HEIGHT FROM FLOOR TRACK TO
TRACK AT STRUCTURE ABOVE AND SHALL BE
STITCH WELDED 1/8" FLARE BEVEL STITCH WELD -
3/4" PER 24", BOTH SIDES.
CONTRACTOR NOTE:
1. IN NO CASE SHALL DOUBLE STUDS OR HDS
STUDS AT SIDES OF OPENING BE CUT FOR
DUCTWORK OR OTHER MECHANICAL, ELECTRICAL,
OR PLUMBING SYSTEMS.
CEILING LINE
BOTTOM TRACK (TYP.) 8' - 6" MAX.
1' - 6" TYP. UNO.
LARGE ABOVE CEILING
OPENING
ABOVE CEILING
OPENING
4' - 6" MAX.
LARGE BELOW CEILING
OPENING
BELOW CEILING
OPENING
8' - 6" MAX. 4' - 6" MAX.
7' - 0"
8' - 6" MAX. 4' - 6" MAX.
PROVIDE FULL HEIGHT CONTROL JOINTS ON
STRIKE SIDE OF DOORS 3'-0" WIDE AND UNDER,
PROVIDE FULL HEIGHT CONTROL JOINTS ON
BOTH SIDES OF DOORS WIDER THAN 3'-0".
DOOR
OPENIN
DOUBLE
DOOR
OPENIN
CEILING LINE
1' - 6" TYP. UNO.
LARGE BELOW CEILING
OPENING
BELOW CEILING
OPENING
8' - 6" MAX. 4' - 6" MAX. 6" TYP.
U.N.O.
3' - 0"
FULL HEIGHT WALL
METAL STUD WITH FULL HEIGHT
GYPSUM WALL BOARD (GWB) BOTH
SIDES.
PARTIAL HEIGHT WALL
01 02
03 03
01
03
02 01 01 03
05
05 05 05
16 GA. DOUBLE STUDS
OR HDS SINGLE STUD
16 GA. DOUBLE STUDS
OR HDS SINGLE STUD
16 GA. DOUBLE STUDS
OR HDS SINGLE STUD
SLIPSLIP
PROVIDE BLOCKING AS REQ.
TO SUPPORT CABINETS,
SHELVING, EQUIPMENT,
AND DECORATIVE
BOTTOM TRACK
NOTE: ALL PARTITIONS NOT EXTENDING TO DECK TO HAVE DIAGONAL
KICKER FRAMING EVERY 48" O.C. MAX. BOTH SIDES OF PARTITION.
6" TYP.
STUD OR CLIP ANGLES
AS REQ'D FOR
SCREW AS
SCREW AS
MTL TRACK AT
HDS MTL STUD
AT BOTH JAMBS ;
ANCHOR TO DECK
OR STRUCTURE
SEE PARTITION SCHEDULE
FOR WIDTH OF
MTL SILL TRACK
TRACK TO BE CUT, BENT
AND THEN SCREWED TO
STUDS
HDS STUD OR DOUBLE
MTL STUDS AT
BOTH JAMBS; JOIN
STUDS WITH 2" LONG
INTERMITTENT WELDS
BOTH SIDES; LOCATE @
TOP AND BOTTOM OF
STUDS, @ ALL DOOR
FRAME HINGE POINT
LOCATIONS AND @
REMAINING PORTION OF
STUDS NOT TO EXCEED
48" O.C.
MTL TRACK AT
MTL.
TRACK TO BE CUT,
BENT AND THEN
SCREWED TO
MTL.
MTL.
TRACK TO BE CUT,
BENT AND THEN
SCREWED TO
MTL.
TRACK TO BE CUT, BENT
AND THEN SCREWED TO
STUDS
DOUBLE 3 5/8" OR
6"
MTL.
TRACK TO BE CUT, BENT
AND THEN SCREWED TO
STUDS
SEE PARTITION SCHEDULE
FOR WIDTH OF
SEE PARTITION SCHEDULE
FOR WIDTH OF
SEE PARTITION SCHEDULE
FOR WIDTH OF
SEE PARTITION SCHEDULE
FOR WIDTH OF
01 DOUBLE DOOR / LARGE OPENING
SCALE: 3" =02 DOOR OPENING
SCALE: 3" = 03 OPENING
SCALE: 3" = 04 LARGE OPENING JAMB
SCALE: 3" = 05 DOOR OPENING JAMB
SCALE: 3" = 06 CORNER
SCALE: 3" = 07 WALL INTERSECTION
SCALE: 3" = 08 HEAD OF WALL
SCALE: 3" =
CONTINUOUS 2" WIDE X 20 GA.
METAL STRAP. ATTACH
GYPSUM BOARD TO STRAP AT
8" O.C. MAXIMUM.
CONTINUOUS 20 GA. 2-1/2" X 2-1/2" METAL
ANGLE WITH 2-1/2" WIDE PIECE OF GYPSUM
BOARD USED FOR THE WALL - ATTACH TO
PLATE OR STEEL DECK AT 12" O.C. MAXIMUM.
NOTE:
DO NOT ATTACH
GYPSUM BOARD TO TOP
SEE PARTITION SCHEDULE
FOR WIDTH OF
SEE PARTITION SCHEDULE
FOR WIDTH OF SEE PARTITION SCHEDULE
FOR WIDTH OF
ROOF OR FLOOR ASSEMBLY ABOVE
(NON-RATED)
SEALANT, TYP. BOTH SIDES
DEFLECTION TRACK TO MATCH WALL
RATING
CONT. HORIZONTAL BRIDGING AS
RECOMMENDED BY MFR. LOCATE 18" FROM
DECK UNLESS NOTED OTHERWISE.
ROOF OR FLOOR ASSEMBLY ABOVE
FLUTE DECK
CONTINUOUS FLUTE COVER
STEEL STUD
FIRE STOP
DEFLECTION TRACK
(1) LAYER OF GYP. BOARD
FOR 1-HOUR FIRE RATING-
ATTACH PER UL DESIGN.
09 HEAD OF WALL
SCALE: 3" =
NOTE:
DO NOT ATTACH
GYPSUM BOARD TO TOP
SEE PARTITION SCHEDULE
FOR WIDTH OF
(RATED - SEE SPECIFICATION 07
8443 FOR MORE INFORMATION)
MINERAL WOOL FLUTE
FILL
CONT. HORIZONTAL BRIDGING AS
RECOMMENDED BY MFR. LOCATE
18" FROM DECK UNLESS NOTED
OTHERWISE.
DEFLECTION
1" ALLOWABLE
HIGHER PRIORITY
PARTITIONS TO
RUN
CONTINUOUS
PAST A LOWER
PRIORITY
LOWER PRIORITY
PARTITIONS TO
TERMINATE INTO
HIGHER PRIORITY
PARTITIONS
LOWER PRIORITY
PARTITIONS TO TERMINATE
INTO HIGHER PRIORITY
PARTITIONS
ALIGN
ALIGN
HIGHER PRIORITY
PARTITIONS TO RUN
CONTINUOUS PAST A LOWER
PRIORITY PARTITION
NOTES:
1. REFER TO PARTITION PLANS FOR
PARTITION TYPES, NUMBER OF LAYERS OF
GYP, STUD SIZE, UL LISTING ETC.
2. THE HIGHER PRIORITY PARTITION MUST
PASS THROUGH THE LESSER PRIORITY
PARTITION. THE COMPLETE WALL
ASSEMBLY MUST BE CONTINOUS THROUGH
INTERSECTION.
3. TAPE AND SEAL JOINTS IN GYP. BOARD IN
PARTITION BEHIND INTERSECTING
PARTITIONS.
LOWER
PRIORITY
PARTITIONS
TO
TERMINATE
INTO HIGHER
PRIORITY
PARTITIONS
HIGHER PRIORITY
PARTITIONS TO
RUN CONTINUOUS
PAST A LOWER
PRIORITY
PARTITION
PLAN PLAN
HIGHER PRIORITY
PARTITIONS TO RUN
CONTINUOUS PAST A LOWER
PRIORITY PARTITION
LOWER PRIORITY
PARTITIONS TO TERMINATE
INTO HIGHER PRIORITY
PARTITIONS
HIGHER PRIORITY
PARTITIONS TO RUN
CONTINUOUS PAST A LOWER
PRIORITY PARTITION
LOWER PRIORITY
PARTITIONS TO TERMINATE
INTO HIGHER PRIORITY
PARTITIONS
ALIGN
PLAN
PLAN
PARTITION PRIORITY LEGEND
DISCRIPTION PRIORITY RANKING
3 HOUR FIRE RATED WALLS PRIORITY 1 - HIGHEST
2 HOUR FIRE RATED SHAFTWALLS PRIORITY 2
2 HOUR FIRE RATED PARTITIONS PRIORITY 3
1 HOUR FIRE RATED SHAFTWALLS PRIORITY 4
1 HOUR FIRE RATED PARTITIONS PRIORITY 5
SMOKE PARTITIONS PRIORITY 6
SOUND PARTITIONS PRIORITY 7
NON-FIRE RATED; NON-SOUND
RATED
PRIORITY 8 - LOWEST
MTL. WALL
STUDS
REFER
TYPICAL
MOUNTING3 5/8" MIN,
DEEPER IF18 GA. METAL RUNNER TRACK
LEG NOTCHED AROUND STUD,
EXTEND TO ONE
STUD BEYOND ATTACHMENT
POINT
MAX.1/4"
PARTITIO
SEALAN
"LC"
INTERIOR PARTITION
NON-EXPOSED EDGE
CJ 1
2 3/4" GYPSUM BOARD SUSPENDED
CEILING SYSTEM
CONTROL
CONTROL JOINT FOR GYPSUM BOARD
CJ
24'-0"
MAX.
24'-0"
MAX.
CEILING GRID
SUSPENSION SYSTEM
CASTING
1/8" EACH
CONTINUOUS 2" WIDE
NEOPRENE FILLER
PARTITIO
PARTITION ATTACHMENT TO CEILING
CJ
PARTITION
SOLID ATTENUATION
BLANKET
COMPRESSED TO FILL
OPENING AT
L-
SEALANT AND BACKER
LINE OF
CONTROL JOINT AT
CJ
INTERSECTION / CHANGE IN
CJ
DOUBLE 20 GAUGE METAL STUDS
WITH 1"X226A METAL STRAP
PLATES AT 3'-6" O.C. EACH SIDE
5/8" TYPE "X" GYPSUM
5/8" MAX.
TYPICAL CONTROL
JOINT FOR PARTITION
TYPE REQUIRING (1)
LAYER OF GYPSUM
BOARD
VINYL OR METAL CONTROL
BACKER ROD & FIRE STOP SEALANT,
CONTINUOUS AT RATED CONSTRUCTION.
1/2" GAP MAX.
5/8" TYPE "X"
GYPSUM
BACKER ROD AND FIRE
STOP SEALANT
CONTINUOUS AT RATED
CONSTRUCTION
1/2" GAP MAX.
METAL GYPSUM
BOARD CONTROL
DOOR CONTROL JOINT
(PROVIDE MINIMUN ONE JOINT
AT ALL DOORS AND
CJ
TYPICAL CONTROL
JOINT FOR PARTITION
TYPE REQUIRING (1)
LAYER OF GYPSUM
BOARD
VINYL OR METAL CONTROL
BACKER ROD & FIRE STOP SEALANT,
CONTINUOUS.
1/2" GAP MAX.
5/8" TYPE "X" GYPSUM
5/8" TYPE "X" GYPSUM
VINYL OR METAL CONTROL
BACKER ROD & FIRE STOP SEALANT,
CONTINUOUS.
NOTE: LOCATE CONTROL JOINTS IN
UNINTERRUPTED WALL SPANNING
MORE THAN 30"-0" & WHERE
INDICATED ON DRAWINGS, OR AT A
CHANGE IN MATERIALS, FINISH,
BACKING, OR INSIDE
FACE OF
BRICK EXPANSION JOINT.
ASSEMBLY GA-WH1651-0318.1
5/8" GAP
1 HOUR PARTITION
CONTROL JOINT
CJ
TYPICAL CONTROL
JOINT FOR PARTITION
TYPE REQUIRING (1)
LAYER OF GYPSUM
BOARD
VINYL OR METAL CONTROL
BACKER ROD & FIRE STOP SEALANT,
CONTINUOUS.
1/2" GAP MAX.
5/8" TYPE "X" GYPSUM
5/8" TYPE "X" GYPSUM
VINYL OR METAL CONTROL
BACKER ROD & FIRE STOP SEALANT,
CONTINUOUS.
NOTE: LOCATE CONTROL JOINTS IN
UNINTERRUPTED WALL SPANNING
MORE THAN 30"-0" & WHERE
INDICATED ON DRAWINGS, OR AT A
CHANGE IN MATERIALS, FINISH,
BACKING, OR INSIDE FACE OF
BRICK EXPANSION JOINT.
ASSEMBLY GA-WH1651-0318.1
5/8" GAP
1
HOUR PARTITION
CONTROL JOINT
CJ
2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP,
P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
EAST
WING
ENABLING
6/30/2017
4:47:38 PM
15924.00
A-721-1
FRAMING DETAILS
2017
06/30/17
PERMIT VAIL
VALLEY
MEDICAL
CENTER
180 S. Frontage
Road
West,
Vail, CO 81657
1/4" = 1'-0"
TYPICAL PARTITION FRAMING ELEVATIONS
3" = 1'-0"
C1
PARTITION FRAMING - PHASE 1.75
1 1/2" = 1'-0"
D1
PARTITION PRIORITY
3" = 1'-0"
D4
EQUIPMENT / ACCESSORIES MOUNTING
1 1/2" = 1'-0"
B1
CONTROL JOINTS - PHASE 1.75
10/12/17