HomeMy WebLinkAboutB17-0340_E-012.75_1507837304.pdfTRANSFORMER SCHEDULE KEY HV FLA LV FLA HV PROT HIGH VOLTAGE FEEDER LV PROT LOW VOLTAGE FEEDER GROUNDING DIMENSIONS WEIGHT BTUH NOTE 480 V 208 V CCT BRKR CONDUCTORS "C CCT BRKR CONDUCTORS "C CNDTRS "C HIGH WIDE DEEP OTPT T25 52.1 120.2 70 A 2 P 2 # 4 , 1 # 8 G 1 150 A 2 P 3 # 3/0 AL , 1 # 4 AL G 2 1 # 4 AL 3/4 30.00 17.00 16.00 235 T15 18.0 41.6 25 A 3 P 3 # 10 , 1 # 10 G 3/4 60 A 3 P 4 # 6 , 1 # 10 G 1 1 # 8 3/4 27.00 20.13 16.00 310 2806 T30 36.1 83.3 45 A 3 P 3 # 6 , 1 # 10 G 1 100 A 3 P 4 # 1 , 1 # 8 G 1-1/2 1 # 6 3/4 30.00 20.13 16.00 370 5753 T45 54.1 124.9 70 A 3 P 3 # 4 , 1 # 8 G 1-1/4 150 A 3 P 4 # 3/0 AL , 1 # 4 AL G 2 1 # 4 AL 3/4 39.25 26.13 20.00 480 7425 T75 90.2 208.2 110 A 3 P 3 # 1 , 1 # 6 G 1-1/2 250 A 3 P 4 # 350 AL , 1 # 1/0 AL G 3 1 # 1/0 AL 3/4 39.25 30.00 20.00 675 10549 T150 180.4 416.4 225 A 3 P 3 # 350 AL , 1 # 2 AL G 2-1/2 500 A 3 P 2 [ 4 # 350 AL , 1 # 3/0 AL G 3 ] 1 # 3/0 AL 1 46.63 32.00 27.00 925 16592 NOTES: 1.) PRIMARY AND SECONDARY O.C. PROTECTION PER NEC 450.3. 2.) BONDING AND GROUNDING CONDUCTOR PER NEC 250.66. 3.) CONDUCTORS ARE COPPER UNLESS OTHERWISE NOTED. ALUMINUM CONDUCTORS ARE BASED ON TYPE XHHW-2 COMPACT 600V. 4.) SEE PLANS FOR INCREASED CONDUCTOR SIZES DUE TO VOLTAGE DROP ETC. 5.) DIMENSIONS, WEIGHTS & BTUH OUTPUT SHOWN ARE FOR REFERENCE ONLY. ACTUAL DIMENSIONS MAY VARY FROM MANUFACTURER TO MANUFACTURER. 6.) BRANCH CIRCUITS TO HAVE A DEDICATED NEUTRAL FOR EACH CIRCUIT ON K-RATED TRANSFORMERS. 7.) FOR K-RATED TRANSFORMERS, PROVIDE PARALLEL NEUTRAL CONDUCTORS LUGS AT TRANSFORMERS, LOW VOLTAGE PANELBOARD, DISCONNECTS AND/OR LOAD . FEEDER SCHEDULE KEY CONDUCTORS "C 40.3 G 3 # 8 , 1 # 10 G 1 100.3 G 3 # 1 , 1 # 8 G 1 1/2 100.4 G 4 # 1/0 AL , 1 # 6 AL G 2 125.4 G 4 # 2/0 AL , 1 # 4 AL G 2 200.4 G 4 # 250 AL , 1 # 4 AL G 2 1/2 225.4 G 4 # 350 AL , 1 # 2 AL G 3 250.4 G 4 # 350 AL , 1 # 2 AL G 3 400.4 G 2 [ 4 # 250 AL , 1 # 1 AL G 2 1/2 ] 800.4 G 3 [ 4 # 500 AL , 1 # 3/0 AL G 3 ] 1000.4 G 4 [ 4 # 350 AL , 1 # 4/0 AL G 3 ] 1200.4 G 4 [ 4 # 500 AL , 1 # 250 AL G 3 ] 2000.4 G 6 [ 4 # 600 AL , 1 # 400 AL G 3 1/2 ] 3000.4 G 8 [ 4 # 750 AL , 1 # 600 AL G 4 ] MEC SEE MECH'L EQUIPMENT SCHEDULE XFMR SEE TRANSFORMER SCHEDULE NOTE: ALUMINUM CONDUCTORS ARE BASED ON TYPE XHHW-2 COMPACT 600V OUTSIDE BY TRASH COMPACTOR AREA OF WORK AREA OF WORK ISCA=4455 NONE SCALE: ELECTRICAL ONE-LINE DIAGRAM - WEST NORMAL POWER NLEA 100FRN-R 100A3P 100.4G THIRD FLOOR SECOND FLOOR FIRST FLOOR BASEMENT STEEL BLDG. PIPE WATER COLD #1/0G 1000A FUSES (4#500KCMIL, 1#3G, 3 1/2"C.] DISHWASHER HEATER (4#3/0, 1#6G)2 1/2"C. (4#2, 1#2G)2"C. (4#1/0, 1#6G)2"C. (4#500KCMIL, 1#3G, 3 1/2"C.] 1000A FUSES (4#1/0, 1#8G)1 1/2"C. 70A3P (4#1/0, 1#8G)1 1/2"C. (4#1/0, 1#8G)1 1/2"C. (4#1/0, 1#6G)2"C. DISTRIBUTION PANEL "DPA1" 120/208V, 3PH, 4W 1200A 14,000 AIC DISTRIBUTION PANEL "DPA" 120/208V, 3PH, 4W 1200A 14,000 AIC (2) MECH RM (3#1/0, 1#6G)1 1/2"C. 125A3P ROOF FOURTH FLOOR ISCA = 5,080 ISCA=13,022 ISCA=40,288 ISCA=8,552 ISCA=10,838 ISCA=2,054 ISCA=7,771 ISCA=7,649 ISCA = 4,548 ISCA=11,511 ISCA=12,712 ISCA=5,654 ISCA=7,658 ISCA=7,714 ISCA=10,349 MRI RECEPTION MECH RM ISCA=3,509 ISCA=2,202 TO DISTRIBUTION PANEL "MDC" J M J J 100A3P X-RAY 100FRN-R 100A3P 100.4G NL2A 50.3G 150FRN-R 200A3P 90FRN-R 100A3P LBA1 LBA 150FRN-R 200A3P L1DC LBB 100FRN-R 100A3P 200A3P 300 T L1E 200A3P A 150FRN-R 200A3P 100FRN-R 100A3P 100FRN-R 100A3P LBK 200FRN 200A3P 90FRN-R 100A3P MRI DIST PANEL 7.5 T 100FRN-R 100A3P 100FRN-R 100A3P 100FRN-R 100A3P SPACE 200A3P 100A3P 200FRN-R 200A3P V 400FRN-R 400A3P 50.3G ~ 200.4G 45FRN-R 100A3P 125ALPN-RK 200A3P 200FRN-R 200A3P L3A 100FRN-R 100A3P L2B 100FRN-R 100A3P 400FRN-R 400A3P NLBA SPARE 100.4G SPARE SPARE 100.4G NL1D L1DB L1D 50.3G 2901 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 Denver 1 A B C D E 2 3 4 5 6 A B C D E 1 2 3 4 5 6 DPA Project: Sheet Number: COPYRIGHT - DAVIS PARTNERSHIP, P.C. Sheet Title: Revisions Date Sheet Information Project Information Issuance Consultant EAST WING ENABLING 6/30/2017 2:15:56 PM 15924.00 E-012.75 ELECTRICAL ONE-LINE DIAGRAM - WEST NORMAL POWER 06/30/17 PERMIT EAST WING ADDITION 180 S Frontage Rd W, Vail, CO 81657 10/12/17