HomeMy WebLinkAboutB17-0340_E-012.75_1507837304.pdfTRANSFORMER SCHEDULE
KEY HV FLA LV FLA HV PROT HIGH VOLTAGE FEEDER LV PROT LOW VOLTAGE FEEDER GROUNDING DIMENSIONS WEIGHT BTUH NOTE
480 V 208 V CCT BRKR CONDUCTORS "C CCT BRKR CONDUCTORS "C CNDTRS "C HIGH WIDE DEEP OTPT
T25 52.1 120.2 70 A 2 P 2 # 4 , 1 # 8 G 1 150 A 2 P 3 # 3/0 AL , 1 # 4 AL G 2 1 # 4 AL 3/4 30.00 17.00 16.00 235
T15 18.0 41.6 25 A 3 P 3 # 10 , 1 # 10 G 3/4 60 A 3 P 4 # 6 , 1 # 10 G 1 1 # 8 3/4 27.00 20.13 16.00 310 2806
T30 36.1 83.3 45 A 3 P 3 # 6 , 1 # 10 G 1 100 A 3 P 4 # 1 , 1 # 8 G 1-1/2 1 # 6 3/4 30.00 20.13 16.00 370 5753
T45 54.1 124.9 70 A 3 P 3 # 4 , 1 # 8 G 1-1/4 150 A 3 P 4 # 3/0 AL , 1 # 4 AL G 2 1 # 4 AL 3/4 39.25 26.13 20.00 480 7425
T75 90.2 208.2 110 A 3 P 3 # 1 , 1 # 6 G 1-1/2 250 A 3 P 4 # 350 AL , 1 # 1/0 AL G 3 1 # 1/0 AL 3/4 39.25 30.00 20.00 675 10549
T150 180.4 416.4 225 A 3 P 3 # 350 AL , 1 # 2 AL G 2-1/2 500 A 3 P 2 [ 4 # 350 AL , 1 # 3/0 AL G 3 ] 1 # 3/0 AL 1 46.63 32.00 27.00 925 16592
NOTES: 1.) PRIMARY AND SECONDARY O.C. PROTECTION PER NEC 450.3.
2.) BONDING AND GROUNDING CONDUCTOR PER NEC 250.66.
3.) CONDUCTORS ARE COPPER UNLESS OTHERWISE NOTED. ALUMINUM CONDUCTORS ARE BASED ON TYPE XHHW-2 COMPACT 600V.
4.) SEE PLANS FOR INCREASED CONDUCTOR SIZES DUE TO VOLTAGE DROP ETC.
5.) DIMENSIONS, WEIGHTS & BTUH OUTPUT SHOWN ARE FOR REFERENCE ONLY. ACTUAL DIMENSIONS MAY VARY FROM MANUFACTURER TO MANUFACTURER.
6.) BRANCH CIRCUITS TO HAVE A DEDICATED NEUTRAL FOR EACH CIRCUIT ON K-RATED TRANSFORMERS.
7.) FOR K-RATED TRANSFORMERS, PROVIDE PARALLEL NEUTRAL CONDUCTORS LUGS AT TRANSFORMERS, LOW VOLTAGE PANELBOARD, DISCONNECTS AND/OR LOAD .
FEEDER SCHEDULE
KEY CONDUCTORS "C
40.3 G 3 # 8 , 1 # 10 G 1
100.3 G 3 # 1 , 1 # 8 G 1 1/2
100.4 G 4 # 1/0 AL , 1 # 6 AL G 2
125.4 G 4 # 2/0 AL , 1 # 4 AL G 2
200.4 G 4 # 250 AL , 1 # 4 AL G 2 1/2
225.4 G 4 # 350 AL , 1 # 2 AL G 3
250.4 G 4 # 350 AL , 1 # 2 AL G 3
400.4 G 2 [ 4 # 250 AL , 1 # 1 AL G 2 1/2 ]
800.4 G 3 [ 4 # 500 AL , 1 # 3/0 AL G 3 ]
1000.4 G 4 [ 4 # 350 AL , 1 # 4/0 AL G 3 ]
1200.4 G 4 [ 4 # 500 AL , 1 # 250 AL G 3 ]
2000.4 G 6 [ 4 # 600 AL , 1 # 400 AL G 3 1/2 ]
3000.4 G 8 [ 4 # 750 AL , 1 # 600 AL G 4 ]
MEC SEE MECH'L EQUIPMENT SCHEDULE
XFMR SEE TRANSFORMER SCHEDULE
NOTE: ALUMINUM CONDUCTORS ARE BASED
ON TYPE XHHW-2 COMPACT 600V
OUTSIDE BY
TRASH
COMPACTOR
AREA OF WORK
AREA OF WORK
ISCA=4455
NONE SCALE:
ELECTRICAL ONE-LINE DIAGRAM - WEST NORMAL POWER
NLEA
100FRN-R
100A3P
100.4G
THIRD FLOOR
SECOND FLOOR
FIRST FLOOR
BASEMENT
STEEL
BLDG.
PIPE
WATER
COLD
#1/0G
1000A FUSES (4#500KCMIL,
1#3G, 3 1/2"C.]
DISHWASHER HEATER
(4#3/0,
1#6G)2
1/2"C.
(4#2,
1#2G)2"C.
(4#1/0,
1#6G)2"C.
(4#500KCMIL,
1#3G, 3 1/2"C.]
1000A FUSES
(4#1/0,
1#8G)1
1/2"C.
70A3P
(4#1/0,
1#8G)1
1/2"C.
(4#1/0,
1#8G)1
1/2"C.
(4#1/0,
1#6G)2"C.
DISTRIBUTION PANEL "DPA1"
120/208V, 3PH, 4W 1200A
14,000 AIC
DISTRIBUTION PANEL "DPA"
120/208V, 3PH, 4W 1200A
14,000 AIC
(2)
MECH RM (3#1/0,
1#6G)1
1/2"C.
125A3P
ROOF
FOURTH FLOOR
ISCA = 5,080
ISCA=13,022
ISCA=40,288
ISCA=8,552 ISCA=10,838
ISCA=2,054
ISCA=7,771
ISCA=7,649
ISCA = 4,548
ISCA=11,511
ISCA=12,712
ISCA=5,654
ISCA=7,658
ISCA=7,714
ISCA=10,349
MRI RECEPTION MECH RM
ISCA=3,509
ISCA=2,202
TO DISTRIBUTION
PANEL "MDC"
J
M
J
J
100A3P
X-RAY
100FRN-R
100A3P
100.4G
NL2A
50.3G
150FRN-R
200A3P
90FRN-R
100A3P
LBA1 LBA
150FRN-R
200A3P
L1DC
LBB
100FRN-R
100A3P
200A3P
300
T
L1E
200A3P
A
150FRN-R
200A3P
100FRN-R
100A3P
100FRN-R
100A3P
LBK
200FRN
200A3P
90FRN-R
100A3P
MRI DIST
PANEL
7.5
T
100FRN-R
100A3P
100FRN-R
100A3P
100FRN-R
100A3P
SPACE
200A3P
100A3P
200FRN-R
200A3P
V 400FRN-R
400A3P
50.3G
~
200.4G
45FRN-R
100A3P
125ALPN-RK
200A3P
200FRN-R
200A3P
L3A
100FRN-R
100A3P
L2B
100FRN-R
100A3P
400FRN-R
400A3P
NLBA
SPARE
100.4G
SPARE SPARE
100.4G
NL1D
L1DB
L1D
50.3G
2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP,
P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
EAST WING ENABLING
6/30/2017
2:15:56 PM
15924.00
E-012.75
ELECTRICAL ONE-LINE
DIAGRAM - WEST NORMAL
POWER
06/30/17
PERMIT EAST
WING
ADDITION
180 S Frontage Rd W, Vail, CO 81657
10/12/17