Loading...
HomeMy WebLinkAboutB17-0340_E-013.75_1507837304.pdf~ TRANSFORMER SCHEDULE KEY HV FLA LV FLA HV PROT HIGH VOLTAGE FEEDER LV PROT LOW VOLTAGE FEEDER GROUNDING DIMENSIONS WEIGHT BTUH NOTE 480 V 208 V CCT BRKR CONDUCTORS "C CCT BRKR CONDUCTORS "C CNDTRS "C HIGH WIDE DEEP OTPT T25 52.1 120.2 70 A 2 P 2 # 4 , 1 # 8 G 1 150 A 2 P 3 # 3/0 AL , 1 # 4 AL G 2 1 # 4 AL 3/4 30.00 17.00 16.00 235 T15 18.0 41.6 25 A 3 P 3 # 10 , 1 # 10 G 3/4 60 A 3 P 4 # 6 , 1 # 10 G 1 1 # 8 3/4 27.00 20.13 16.00 310 2806 T30 36.1 83.3 45 A 3 P 3 # 6 , 1 # 10 G 1 100 A 3 P 4 # 1 , 1 # 8 G 1-1/2 1 # 6 3/4 30.00 20.13 16.00 370 5753 T45 54.1 124.9 70 A 3 P 3 # 4 , 1 # 8 G 1-1/4 150 A 3 P 4 # 3/0 AL , 1 # 4 AL G 2 1 # 4 AL 3/4 39.25 26.13 20.00 480 7425 T75 90.2 208.2 110 A 3 P 3 # 1 , 1 # 6 G 1-1/2 250 A 3 P 4 # 350 AL , 1 # 1/0 AL G 3 1 # 1/0 AL 3/4 39.25 30.00 20.00 675 10549 T150 180.4 416.4 225 A 3 P 3 # 350 AL , 1 # 2 AL G 2-1/2 500 A 3 P 2 [ 4 # 350 AL , 1 # 3/0 AL G 3 ] 1 # 3/0 AL 1 46.63 32.00 27.00 925 16592 NOTES: 1.) PRIMARY AND SECONDARY O.C. PROTECTION PER NEC 450.3. 2.) BONDING AND GROUNDING CONDUCTOR PER NEC 250.66. 3.) CONDUCTORS ARE COPPER UNLESS OTHERWISE NOTED. ALUMINUM CONDUCTORS ARE BASED ON TYPE XHHW-2 COMPACT 600V. 4.) SEE PLANS FOR INCREASED CONDUCTOR SIZES DUE TO VOLTAGE DROP ETC. 5.) DIMENSIONS, WEIGHTS & BTUH OUTPUT SHOWN ARE FOR REFERENCE ONLY. ACTUAL DIMENSIONS MAY VARY FROM MANUFACTURER TO MANUFACTURER. 6.) BRANCH CIRCUITS TO HAVE A DEDICATED NEUTRAL FOR EACH CIRCUIT ON K-RATED TRANSFORMERS. 7.) FOR K-RATED TRANSFORMERS, PROVIDE PARALLEL NEUTRAL CONDUCTORS LUGS AT TRANSFORMERS, LOW VOLTAGE PANELBOARD, DISCONNECTS AND/OR LOAD . FEEDER SCHEDULE KEY CONDUCTORS "C 40.3 G 3 # 8 , 1 # 10 G 1 230.3 G 3 # 300 AL , 1 # 2 AL G 2 1/2 100.4 G 4 # 1/0 AL , 1 # 6 AL G 2 125.4 G 4 # 2/0 AL , 1 # 4 AL G 2 200.4 G 4 # 250 AL , 1 # 4 AL G 2 1/2 225.4 G 4 # 350 AL , 1 # 2 AL G 3 250.4 G 4 # 350 AL , 1 # 2 AL G 3 400.4 G 2 [ 4 # 250 AL , 1 # 1 AL G 2 1/2 ] 800.4 G 3 [ 4 # 500 AL , 1 # 3/0 AL G 3 ] 1000.4 G 4 [ 4 # 350 AL , 1 # 4/0 AL G 3 ] 1200.4 G 4 [ 4 # 500 AL , 1 # 250 AL G 3 ] 2000.4 G 6 [ 4 # 600 AL , 1 # 400 AL G 3 1/2 ] 3000.4 G 8 [ 4 # 750 AL , 1 # 600 AL G 4 ] MEC SEE MECH'L EQUIPMENT SCHEDULE XFMR SEE TRANSFORMER SCHEDULE NOTE: ALUMINUM CONDUCTORS ARE BASED ON TYPE XHHW-2 COMPACT 600V G ~ AREA OF WORK AREA OF WORK TO BE DEMO'D REFEED TO NEW PANEL NONE SCALE: ELECTRICAL ONE-LINE DIAGRAM - WEST EMERGENCY POWER EL2C J 80.4G BASEMENT ROOF THIRD FLOOR SECOND FLOOR FIRST FLOOR TO "MDC" DISTRIBUTION PANEL "EDPA" 277/480V, 3PH, 4W 1200A 35,000 AIC SHUNT ELEV ISCA=23,639 ATS-9-EQ 400A3P ATS-8-CR 150A3P TO "H2A" TO "H2A" ISCA=18,506 ISCA=2,002 ISCA=7,961 75 HP ISCA=37,924 XFMR AHU-1 "TCL2LAB" XFMR EL-4 ISCA=23,794 "T1B" TRACTION ISCA=3,524 ISCA=8,321 ISCA=3,609 ISCA=35,011 200A3P 110AF TO "E1A" XFMR ISCA=14,880 DISTRIBUTION PANEL "EH2B" 277/480V, 3PH, 4W 600A ISCA=3,367 ISCA= 18,376 ISCA=1,787 ISCA=21,617 ISCA=17,779 ISCA= 19,190 ISCA=19,607 100A3P ISCA=1,903 ISCA=3,050 RTU-1 ISCA=4,903 ISCA=26,523 7 HP ISCA=6,218 2000A3P DIESEL DRIVEN ENGINE/GENERATOR 277/480V 1350KW AT SITE ATS-10-CR ATS-11-EQ FOURTH FLOOR ATS-12-CR 600A4P (NEUT. BONDED NOT SWITCHED) TO MDC DISTRIBUTION PANEL "EDPB" 277/480V, 3PH, 4W 1200A 35,000 AIC ISCA = 40,288 ISCA = 13,809 DISTRIBUTION PANEL "EHDP" 277/480V, 3PH, 4W 800A 35,000 AIC ATS-6-EQ 600A3P ATS-5-LS 125A4P (NEUT. BONDED NOT SWITCHED) ATS-4-CR 125A4P (NEUT. BONDED NOT SWITCHED) "GDCA" 2000A 277/480V, 3PH, 4W 35,000 AIC TO "CDHBA" TO "CDHBB" ATS-14-EQ 1200A4P (NEUT. BONDED NOT SWITCHED) TO MDC "QDHRA" 1200A 277/480V, 3PH, 4W ATS-13-EQ 800A4P (NEUT. BONDED NOT SWITCHED) TO MDC TO QDHBA #1/0G G N FUTURE NEUTRAL TO GROUND BOND WHEN TRANSFER SWITCHES ARE ALL 4 POLE TO TEMP GENERATOR PANEL EL-5 20 HP EXTEND FEEDER TO NEW ELEVATOR MACHINE ROOM ISCA=16,071 ISCA=3,012 ISCA=1,531 ISCA=1,469 ISCA=6,770 ISCA=1,198 ISCA=4,340 ISCA=1,195 ISCA=5,208 ISCA=1,240 ISCA=4,138 ISCA=1,221 ISCA=13,355 ISCA=25,368 ISCA=5,923 ISCA=4,258 ISCA=4,725 ISCA=5,599 ISCA=6,297 ISCA=4,885 ISCA=4,445 ISCA=4,022 ISCA=32,119 ISCA=27,573 ISCA=33,551 ISCA=19,651 ISCA=28,591 ISCA = 38,789 ISCA = 37,389 ISCA=10,168 ISCA=9,988 ISCA=9,614 ISCA=20,033 ISCA=17,391 ISCA=21,142 ISCA=1,887 ISCA= 1,756 ISCA=2,603 ISCA=2,280 ISCA=17,162 ISCA=2,151 ISCA=3,110 ISCA=2,992 ISCA=2,255 ISCA=2,191 ISCA=2,089 ISCA=1,944 ISCA=1,994 ISCA=2,199 ISCA=2,264 ISCA=2,608 ISCA=13,836 ISCA=1,186 ISCA=1,783 ISCA=14,011 ISCA= 24,437 ISCA=12,928 ISCA=13,469 TO 'CL2B' M VFD M M M M M M VFD M M M ~ ~ ~~ ~ EL1C ~ ~~ ~ ~ ~ 150.3G 20.2G OR1B XFMR 60A3P 40.2G GFI 100A3P 70.4G 4004.GX XFMR 100.4G OR3A 112.5 T XFMR EHBA OR2A OR2B GFI 150A3P OR4B EH3A ST 30 T 60.4G 150.4G 40.2G 125.4G 20.2G 150A3P 500.4GX 125.4G ELBA1 70.4G 75 4 TK EL2A 100.4G 80.3G 100A3P 20.2G CL2LAB 500A3P 60.3G 200.3GN1 XFRM 600.4G 600A3P CL2C 125A3P EL3D 450.4G MCB 1200A3P XFMR SPACE OR3B 20.2G OR4A EL2B1 50.3G EH2C 20.2G XFMR 100A3P 400.4GX 60.4G 20.2G 60.4G 200.4GX1 EHBC 45 T-K4 50.4G ELBA 150A3P 15 T 60A3P 60.3G 125.4G 100A3P 450.4G GFI 600.4G XFMR GFI 450.4G 450A3P 110.4GX 100.4G EH2A 20.2G 150.4G 45 T 450A3P 30 T EHBB SPD EH2D SPACE OR4A OR4B 40.2G OR2A CL3A 45 T 125.4G 100A3P OR2B 600.4G 40.2G 70.3G 20.2G EL2B 150A3P 30 T XFMR 350A3P XFMR 20.2G 20.2G CL3B OR1A OR3A OR3B C-SECT XFMR EH2E XFMR 175A3P OR1A OR1B 100.4G XFMR GFI LSIA LSIA LSIA 400.4G2 250.4G SPACE (4) XFMR 15 T XFMR SH3A SL3A MEC SPARE (4) 100A3P MEC MEC MEC 1200.4G 250A3P 2000.4G GFI GFI GFI 400A3P 1200A3P SH1A 100.4G 100.4G XFMR 15 T XFMR SL1A LSIA 1200.4G GFI 1200A3P 1200.4G CH 1 AHU 2 AHU 3 CU 4 LSIA 800.4G GFI 800A3P 800.4G 1200.4G 800.4G SPD SPD SPD SPD 40.2G 40.2G 40.2G 40.2G 25 T XFMR XFMR XFMR ELDP MEC MEC MEC MEC MEC MEC SHBA PH 3 SP 2 100.4G 125.4G 2901 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 Denver 1 A B C D E 2 3 4 5 6 A B C D E 1 2 3 4 5 6 DPA Project: Sheet Number: COPYRIGHT - DAVIS PARTNERSHIP, P.C. Sheet Title: Revisions Date Sheet Information Project Information Issuance Consultant EAST WING ENABLING 6/30/2017 2:15:57 PM 15924.00 E-013.75 ELECTRICAL ONE-LINE DIAGRAM - WEST EMERGENCY POWER 06/30/17 PERMIT EAST WING ADDITION 180 S Frontage Rd W, Vail, CO 81657 10/12/17