Loading...
HomeMy WebLinkAboutB17-0340_E-014.75_1507837304.pdf~ ~~ ~ TRANSFORMER SCHEDULE KEY HV FLA LV FLA HV PROT HIGH VOLTAGE FEEDER LV PROT LOW VOLTAGE FEEDER GROUNDING DIMENSIONS WEIGHT BTUH NOTE 480 V 208 V CCT BRKR CONDUCTORS "C CCT BRKR CONDUCTORS "C CNDTRS "C HIGH WIDE DEEP OTPT T25 52.1 120.2 70 A 2 P 2 # 4 , 1 # 8 G 1 150 A 2 P 3 # 3/0 AL , 1 # 4 AL G 2 1 # 4 AL 3/4 30.00 17.00 16.00 235 T15 18.0 41.6 25 A 3 P 3 # 10 , 1 # 10 G 3/4 60 A 3 P 4 # 6 , 1 # 10 G 1 1 # 8 3/4 27.00 20.13 16.00 310 2806 T30 36.1 83.3 45 A 3 P 3 # 6 , 1 # 10 G 1 100 A 3 P 4 # 1 , 1 # 8 G 1-1/2 1 # 6 3/4 30.00 20.13 16.00 370 5753 T45 54.1 124.9 70 A 3 P 3 # 4 , 1 # 8 G 1-1/4 150 A 3 P 4 # 3/0 AL , 1 # 4 AL G 2 1 # 4 AL 3/4 39.25 26.13 20.00 480 7425 T75 90.2 208.2 110 A 3 P 3 # 1 , 1 # 6 G 1-1/2 250 A 3 P 4 # 350 AL , 1 # 1/0 AL G 3 1 # 1/0 AL 3/4 39.25 30.00 20.00 675 10549 T150 180.4 416.4 225 A 3 P 3 # 350 AL , 1 # 2 AL G 2-1/2 500 A 3 P 2 [ 4 # 350 AL , 1 # 3/0 AL G 3 ] 1 # 3/0 AL 1 46.63 32.00 27.00 925 16592 NOTES: 1.) PRIMARY AND SECONDARY O.C. PROTECTION PER NEC 450.3. 2.) BONDING AND GROUNDING CONDUCTOR PER NEC 250.66. 3.) CONDUCTORS ARE COPPER UNLESS OTHERWISE NOTED. ALUMINUM CONDUCTORS ARE BASED ON TYPE XHHW-2 COMPACT 600V. 4.) SEE PLANS FOR INCREASED CONDUCTOR SIZES DUE TO VOLTAGE DROP ETC. 5.) DIMENSIONS, WEIGHTS & BTUH OUTPUT SHOWN ARE FOR REFERENCE ONLY. ACTUAL DIMENSIONS MAY VARY FROM MANUFACTURER TO MANUFACTURER. 6.) BRANCH CIRCUITS TO HAVE A DEDICATED NEUTRAL FOR EACH CIRCUIT ON K-RATED TRANSFORMERS. 7.) FOR K-RATED TRANSFORMERS, PROVIDE PARALLEL NEUTRAL CONDUCTORS LUGS AT TRANSFORMERS, LOW VOLTAGE PANELBOARD, DISCONNECTS AND/OR LOAD . FEEDER SCHEDULE KEY CONDUCTORS "C 40.3 G 3 # 8 , 1 # 10 G 1 100.3 G 3 # 1 , 1 # 8 G 1 1/2 230.3 G 3 # 300 AL , 1 # 2 AL G 2 1/2 100.4 G 4 # 1/0 AL , 1 # 6 AL G 2 125.4 G 4 # 2/0 AL , 1 # 4 AL G 2 200.4 G 4 # 250 AL , 1 # 4 AL G 2 1/2 225.4 G 4 # 350 AL , 1 # 2 AL G 3 250.4 G 4 # 350 AL , 1 # 2 AL G 3 400.4 G 2 [ 4 # 250 AL , 1 # 1 AL G 2 1/2 ] 800.4 G 3 [ 4 # 500 AL , 1 # 3/0 AL G 3 ] 1000.4 G 4 [ 4 # 350 AL , 1 # 4/0 AL G 3 ] 1200.4 G 4 [ 4 # 500 AL , 1 # 250 AL G 3 ] 2000.4 G 6 [ 4 # 600 AL , 1 # 400 AL G 3 1/2 ] 3000.4 G 8 [ 4 # 750 AL , 1 # 600 AL G 4 ] MEC SEE MECH'L EQUIPMENT SCHEDULE XFMR SEE TRANSFORMER SCHEDULE NOTE: ALUMINUM CONDUCTORS ARE BASED ON TYPE XHHW-2 COMPACT 600V ~ EXTEND EXISTING FEEDER FROM PANEL 'EC1B' TO NEW PANEL 'CL1B' ISCA=2296 NONE SCALE: ELECTRICAL ONE-LINE DIAGRAM - WEST CRITICAL AND EQUIPMENT CL1B TO "MDC" TO "MDC" ATS-11-EQ 400A3P CRITICAL BRANCH SUB-DISTRIBUTION PANEL "CDHBA" 277/480V, 3PH, 4W, 400A BUS 35,000 AIC ISCA=20,318 ISCA = 34,497 ISCA = 30,946 ISCA = 5,056 ISCA = 30,946 ISCA = 34,497 ISCA = 5,147 VACUUM PUMP 4 VACUUM PUMP 3 MED. AIR COMP. EL-3 EQUIPMENT BRANCH SUB-DISTRIBUTION PANEL "EDHBA" 277/480V, 3PH, 4W, 400A BUS 35,000 AIC ISCA=26,141 ISCA=5,567 ISCA=5,579 ISCA=25,028 TO "EMCC" TO "EC1A" GDCA GDCA DISTRIBUTION PANEL "CDHBB" 277/480V, 3PH, 4W 600A 35,000 AIC ISCA = 33,196 ISCA = 9,775 ISCA = 5,189 ISCA = 17,342 ISCA = 16,346 ISCA = 13,285 ISCA = 1,777 T-EL2D ISCA = 2,759 BASEMENT ROOF THIRD FLOOR SECOND FLOOR FIRST FLOOR FOURTH FLOOR TO "CL3A" ISCA = 13,495 TO "ATS-12-CR" DISTRIBUTION PANEL "QDHBA" 277/480V, 3PH, 4W 800A 42,000 AIC ISCA = 36,814 TO "ATS-13-EQ" DISTRIBUTION PANEL "UCLBB" 120/208V, 3PH, 4W 225A 10,000 AIC ATS-10-CR 260A3P RENAME PANEL 'EL2D' TO 'QL2A' RENAME PANEL 'EH2F' TO 'QH2A' ISCA=9,164 ISCA = 10,882 ISCA = 1,766 ISCA=3,014 ISCA=6,068 ISCA=18,484 ISCA=1,767 ISCA=12,126 ISCA=1,756 ISCA=7,755 ISCA=3,057 ISCA=6,836 ISCA=2,917 ISCA=9,364 ISCA=1,733 ISCA=7,292 ISCA=1,696 ISCA=6,371 ISCA=1,709 ISCA=5,484 ISCA=1,652 ISCA=16,613 ISCA=1,796 ISCA=12,095 ISCA=1,776 ISCA=17,422 ISCA=1,798 ISCA=12,544 ISCA=1,780 ISCA=11,834 ISCA=1,771 ISCA=9,61 ISCA=1,741 ISCA=3,200 ISCA=3,259 ISCA=2,573 ISCA=2,675 ISCA=2,469 ISCA=1,914 ISCA=4,610 ISCA=7,582 ISCA=7,823 ISCA= 14,344 ISCA=5,906 ISCA= 5,906 ISCA=5,076 ISCA=26,827 ISCA=3,014 ISCA=6,068 EX FAN #10 KIT. HOOD TO 'CL2C' 150A3P F F F J F J M J M ST M M J M M M M M M M M M M M M M ~ ~ ~ ~ ~~ ~ PDU CATH1 UPS CATH1 100.4G CL2A QL2A XFMR 10 T ST 250A3P CH2A 250.4G1 ST 30.2G CATH1 60.3G1 125.3G1 30 T XFMR QH2A 225.4G 150.4G1 225.4G XFMR EDLBA 110A3P 80.3G XFMR XFMR 100A3P 15A3P XFMR XFMR SPACE 100A 250A3P 110A3P 30A3P 75 T 110A3P 15A3P 110A3P SPARE 70A3P 15.3G 15.3G 75 T 30.3G 250.4G 400A3P 400.4G2 SPACE 20A CDLBA CL4A 30 T XFMR CL3C XFMR 45 T XFMR CH3A MEC MEC CH4A 100.4G 100A3P XFMR 225.4G 225A3P CL2B XFMR 45 T XFMR CL1A XFMR 30 T XFMR CH1A 100.4G 100A3P 250A3P 200.4G 200A3P 100.4G 100A3P 100.4G 100A3P SPACE QL4A 30 T XFMR QL3A XFMR 30 T XFMR QH3A QH4A XFMR QL1A XFMR 30 T XFMR QH1A AHU-1R A QLRA 30 T XFMR QHRA XFMR AHU 4 230.3G 250A3P UPS 160KVA UCLBA 150 T XFMR UCL4A UCL3A 100.4G 100.4G UCL2A UCL1A 100.4G 100.4G 100A3P 100A3P 100A3P 100A3P XFMR 75 T 225.4G XFMR XFMR MEC AHU-1R B MEC MEC EL 7 EL 8 MEC MEC MEC MEC 200.4G 200A3P ST ST RELOCATED 80KVA UPS SPARE 100A MEC MEC CHWP 1 MEC MEC CHWP 2 XFMR MEC MEC LVAC 2 AHU-1S C AHU-1S D MEC MEC MEC MEC MEC HCP 1 15A3P MEC DI 1 MEC MEC MEC 150.4G 2901 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 Denver 1 A B C D E 2 3 4 5 6 A B C D E 1 2 3 4 5 6 DPA Project: Sheet Number: COPYRIGHT - DAVIS PARTNERSHIP, P.C. Sheet Title: Revisions Date Sheet Information Project Information Issuance Consultant EAST WING ENABLING 6/30/2017 2:16:00 PM 15924.00 E-014.75 ELECTRICAL ONE-LINE DIAGRAM - WEST CRITICAL AND EQUIPMENT 06/30/17 PERMIT EAST WING ADDITION 180 S Frontage Rd W, Vail, CO 81657 10/12/17