Loading...
HomeMy WebLinkAboutB17-0340_E-016.75_1507837303.pdfFEEDER SCHEDULE KEY CONDUCTORS "C 40.3 G 3 # 8 , 1 # 10 G 1 100.3 G 3 # 1 , 1 # 8 G 1 1/2 100.4 G 4 # 1/0 AL , 1 # 6 AL G 2 125.4 G 4 # 2/0 AL , 1 # 4 AL G 2 200.4 G 4 # 250 AL , 1 # 4 AL G 2 1/2 225.4 G 4 # 350 AL , 1 # 2 AL G 3 250.4 G 4 # 350 AL , 1 # 2 AL G 3 400.4 G 2 [ 4 # 250 AL , 1 # 1 AL G 2 1/2 ] 800.4 G 3 [ 4 # 500 AL , 1 # 3/0 AL G 3 ] 1000.4 G 4 [ 4 # 350 AL , 1 # 4/0 AL G 3 ] 1200.4 G 4 [ 4 # 500 AL , 1 # 250 AL G 3 ] 2000.4 G 6 [ 4 # 600 AL , 1 # 400 AL G 3 1/2 ] 3000.4 G 8 [ 4 # 750 AL , 1 # 600 AL G 4 ] MEC SEE MECH'L EQUIPMENT SCHEDULE XFMR SEE TRANSFORMER SCHEDULE NOTE: ALUMINUM CONDUCTORS ARE BASED ON TYPE XHHW-2 COMPACT 600V TRANSFORMER SCHEDULE KEY HV FLA LV FLA HV PROT HIGH VOLTAGE FEEDER LV PROT LOW VOLTAGE FEEDER GROUNDING DIMENSIONS WEIGHT BTUH NOTE 480 V 208 V CCT BRKR CONDUCTORS "C CCT BRKR CONDUCTORS "C CNDTRS "C HIGH WIDE DEEP OTPT T25 52.1 120.2 70 A 2 P 2 # 4 , 1 # 8 G 1 150 A 2 P 3 # 3/0 AL , 1 # 4 AL G 2 1 # 4 AL 3/4 30.00 17.00 16.00 235 T15 18.0 41.6 25 A 3 P 3 # 10 , 1 # 10 G 3/4 60 A 3 P 4 # 6 , 1 # 10 G 1 1 # 8 3/4 27.00 20.13 16.00 310 2806 T30 36.1 83.3 45 A 3 P 3 # 6 , 1 # 10 G 1 100 A 3 P 4 # 1 , 1 # 8 G 1-1/2 1 # 6 3/4 30.00 20.13 16.00 370 5753 T45 54.1 124.9 70 A 3 P 3 # 4 , 1 # 8 G 1-1/4 150 A 3 P 4 # 3/0 AL , 1 # 4 AL G 2 1 # 4 AL 3/4 39.25 26.13 20.00 480 7425 T75 90.2 208.2 110 A 3 P 3 # 1 , 1 # 6 G 1-1/2 250 A 3 P 4 # 350 AL , 1 # 1/0 AL G 3 1 # 1/0 AL 3/4 39.25 30.00 20.00 675 10549 T150 180.4 416.4 225 A 3 P 3 # 350 AL , 1 # 2 AL G 2-1/2 500 A 3 P 2 [ 4 # 350 AL , 1 # 3/0 AL G 3 ] 1 # 3/0 AL 1 46.63 32.00 27.00 925 16592 NOTES: 1.) PRIMARY AND SECONDARY O.C. PROTECTION PER NEC 450.3. 2.) BONDING AND GROUNDING CONDUCTOR PER NEC 250.66. 3.) CONDUCTORS ARE COPPER UNLESS OTHERWISE NOTED. ALUMINUM CONDUCTORS ARE BASED ON TYPE XHHW-2 COMPACT 600V. 4.) SEE PLANS FOR INCREASED CONDUCTOR SIZES DUE TO VOLTAGE DROP ETC. 5.) DIMENSIONS, WEIGHTS & BTUH OUTPUT SHOWN ARE FOR REFERENCE ONLY. ACTUAL DIMENSIONS MAY VARY FROM MANUFACTURER TO MANUFACTURER. 6.) BRANCH CIRCUITS TO HAVE A DEDICATED NEUTRAL FOR EACH CIRCUIT ON K-RATED TRANSFORMERS. 7.) FOR K-RATED TRANSFORMERS, PROVIDE PARALLEL NEUTRAL CONDUCTORS LUGS AT TRANSFORMERS, LOW VOLTAGE PANELBOARD, DISCONNECTS AND/OR LOAD . ALTERNATE TO REPLACE THIS BOARD NONE SCALE: PARTIAL ELECTRICAL ONE-LINE DIAGRAM - EAST -EMERGENCY POWER - EXISTING BOILER ROOM 2nd FLOOR TO PANEL "EH2E" VIA 15KVA XFMR SEE SHEET E3.3 TO PANEL "EDLBA" TO PANEL "CDLBA" SEE SHEET E3.4 ISCA=2,139 2ND FLR ELEC ROOM J M M ~ ~ ~ ~ ~~~~~~~ 4#4,#8G THHN-1"C. 1 2 3 4 5 6 7 8 9 10 11 12 DUPLEX VACUUM PUMPS P-1 P-2 AHU-5 EF-20 P-4 AHU-1 LIFE SAFETY PANEL 4#4,#8G THHN-1"C. BASEMENT STORAGE BASEMENT STORAGE NURSES STATION COND. UNIT (ON ROOF) AHU-4 IN BSMT. BASEMENT BOILER ROOM "EMCC" (SQUARE D QMB - SAFELEX) 120/208V, 3PH, 4W 50% NEUTRAL 400A EC1B 225.4G1 225.4G1 150.4G1 50.4G 50.4G EM1CA 100 100A3P 100.4G EM1C 60.4G EPB 30 30A3P 30.3 20.3 15 30A3P 7 30A3P 20.3 30A3P 20.3 30.3 25 30A3P 30.3 25 30A3P 30.3 30 30A3P SPARE 30A3P 60.3 40 60A3P 40 60A3P 100 100A3P 100.4 EM1B EM1A EC1C 225.4G EC1B EC1A 225.4G E1A 2901 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 Denver 1 A B C D E 2 3 4 5 6 A B C D E 1 2 3 4 5 6 DPA Project: Sheet Number: COPYRIGHT - DAVIS PARTNERSHIP, P.C. Sheet Title: Revisions Date Sheet Information Project Information Issuance Consultant EAST WING ENABLING 6/30/2017 2:16:05 PM 15924.00 E-016.75 ELECTRICAL ONE-LINE DIAGRAM - EAST EMERGENCY POWER 06/30/17 PERMIT EAST WING ADDITION 180 S Frontage Rd W, Vail, CO 81657 10/12/17