HomeMy WebLinkAboutB17-0340_E-017.75_1507837301.pdfT
M
SPD
~
~
M
F E E D E R S C H E D U L E
KEY CONDUCTORS "C
1000.4 3 [ 4 # 500 3 1/2 ]
100.4 G 4 # 1 , 1 # 8 G 1 1/2
200.4 G 4 # 3/0 , 1 # 6 G 2 1/2
1000.4 G 3 [ 4 # 500 , 1 # 2/0 G 3 1/2 ]
MEC SEE MECH'L EQUIPMENT SCHEDULE
XFMR SEE TRANSFORMER SCHEDULE
T R A N S F O R M E R S C H E D U L E
KEY PRI FLA SEC FLA PRIMARY SECONDARY GEC DIMENSIONS WEIGHT BTUH NOTE
480 V 208 V CB SWITCH FUSE CONDUCTORS "C CB SWITCH FUSE CONDUCTORS "C CNDTRS "C HIGH WIDE DEEP OTPT
T150 180.4 416.4 225 A 3 P 400 A 3 P FRS-R- 225 3 # 4/0 , 1 # 4 G 2 500 A 3 P 600 A 3 P FRN-R- 500 2 [ 4 # 250 , 1 # 1/0 G 2-1/2 ] 1 # 1/0 3/4 46.63 32.00 27.00 925 16592
NOTES: 1.) OVERCURRENT PROTECTION IS SIZED PER NEC 450.3.
2.) ALL CONDUCTORS ARE COPPER. SEE PLANS FOR INCREASED CONDUCTOR SIZES DUE TO VOLTAGE DROP, ETC.
3.) SECONDARY BONDING AND GROUNDING CONDUCTORS ARE SIZED PER NEC 250.66 AND 250.102.
4.) DIMENSIONS, WEIGHTS & BTUH OUTPUT SHOWN ARE FOR REFERENCE ONLY. ACTUAL DIMENSIONS MAY VARY FROM MANUFACTURER TO MANUFACTURER.
5.) FOR K-RATED TRANSFORMERS, PROVIDE PARALLEL NEUTRAL CONDUCTORS LUGS AT TRANSFORMERS, LOW VOLTAGE PANELBOARD, DISCONNECTS AND/OR LOAD.
6.) CONDUIT 40% FILL RATIO IS BASED ON EMT.
CENTRAL ENABLING ONE-LINE DIAGRAM - NORMAL POWER - NEW
"NDH2A"
BASE
WITH METERING
480/277V XFMR
PAD MOUNTED
1000A3P
400A
1000A3P
"TMDS"
COLD
WATER
PIPE
BLDG.
STEEL
#3/0G
G
N
COLD
WATER
PIPE
BLDG.
STEEL
#3/0G
G
N
(2) SPACE
TO AC-2 (ON
ROOF)
TO CRAC-2 (1ST
FLR CT)
ISCA=33,900
ISCA=32,036
ISCA=26,063
ISCA=5610
ISCA=7847
ISCA=7999
ISCA=25,907
ISCA=4670 ISCA=4670
ISCA=2351
ISCA=20,919 ISCA=21,546
ISCA=7700
NONE
SCALE:
1000A 277/480V, 3PH, 4W
LSIG
XFMR
LSIG
200A3P
LSIG
200A3P
LSIG
100A3P
LSIG
150
GFI GFI
GFI
GFI
GFI
GFI
XFMR
XFMR
1000A 277/480V, 3PH, 4W
LSIGZ
GFI
1000.4 1000.4G
1000.4G BUS DUCT J
LSIGZ
65,000 AIC
NEMA-3R, 65,000 AIC
NEMA-3R
LSIG
25A3P
100.4G
LSIGLSIG
MEC
GFI
LSIGLSIG
100A3P
GFI
MECH MECH
LSIGLSIG
MEC
MECH GFI
200.4G 200.4G
XFMR
LEVEL TWO
LEVEL ONE
TO "MDP"
TO GE
XRAY
TO CT
SCANNER
TO EXISTING
AMBULANCE
BUILDING
EMON DMON
DEMAND METER
TO
FCU
#2 CT
2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP,
P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
EAST WING ENABLING
6/30/2017
2:16:09 PM
15924.00
E-017.75
ELECTRICAL ONE-LINE
DIAGRAM - EAST
TEMPORARY SERVICE
06/30/17
PERMIT EAST
WING
ADDITION
180 S Frontage Rd W, Vail, CO 81657
10/12/17