HomeMy WebLinkAboutB17-0340_E-301.75_1507837309.pdfLOAD SUMMARY 'DPA1' DPA1 CAPACITY 1200 A EXISTING LOAD 1085 A NEW PANEL ADDED 'NLEA' 100 A NEW TOTAL LOAD 1185 A LOAD SUMMARY 'EH2B' EH2B CAPACITY 600 A EXISTING LOAD 242 A NEW LOAD ADDED TO PANEL 'EH2D' 194 A NEW TOTAL LOAD 436 A LOAD SUMMARY 'EH2B' EH2B CAPACITY 600 A EXISTING LOAD 242 A NEW LOAD ADDED TO PANEL 'EH2D' 194 A NEW TOTAL LOAD 436 A LOAD SUMMARY 'EH2B' EH2B CAPACITY 600 A EXISTING LOAD 242 A NEW LOAD ADDED TO PANEL 'EH2D' 194 A NEW TOTAL LOAD 436 A 2901 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 Denver 1 A B C D E 2 3 4 5 6 A B C D E 1 2 3 4 5 6 DPA Project: Sheet Number: COPYRIGHT - DAVIS PARTNERSHIP, P.C. Sheet Title: Revisions Date Sheet Information Project Information Issuance Consultant 6/30/2017 2:17:08 PM 15924.00 E-301.75 ELECTRICAL PANEL SCHEDULES 06/30/17 PERMIT EAST WING ADDITION 180 S Frontage Rd W, Vail, CO 81657 O Other 0 VA 0.00% 0 VA E Existing 0 VA 0.00% 0 VA Total Demand Current: 39 A K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 13943 VA G General 0 VA 0.00% 0 VA C Continuous 0 VA 0.00% 0 VA Total Connected Current: 31 A M Motor 11154 VA 125.00% 13943 VA Total Connected Load: 11154 VA R Receptacle 0 VA 0.00% 0 VA L Lighting 0 VA 0.00% 0 VA Power Factor: 1 Load Type Connected Load Demand Factor Demand Load Panel Totals Phase Balance: 0 % A-B 0 % B-C 0 % C-A Total Amps: 31 A 31 A 31 A Total Load: 3718 VA 3718 VA 3718 VA -- 11 Space -- -- -- 0 VA 0 VA -- -- -- Space 12 -- -- 9 Space -- -- -- 0 VA 0 VA -- -- -- Space 10 -- -- 7 Space -- -- -- 0 VA 0 VA -- -- -- Space 8 -- 5 3718 VA 0 VA 1 20 A -- Spare 6 3 3718 VA 0 VA 1 20 A -- Spare 4 1 TRASH COMPACTOR M 20 A 3 3718 VA 0 VA 1 20 A -- Spare 2 Note Circ... Load Type Trip Po... A B C Po... Trip Type Load Circ... Note Circuit Notes: Enclosure: Type 1 MCB Rating: 100 A Mounting: Surface Wire: 4 Bus Rating: 100 A Supply From: Phase: 3 Mains Type: MCB Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000 Panel NLEA General Notes: O Other 0 VA 0.00% 0 VA E Existing 0 VA 0.00% 0 VA Total Demand Current: 725 A K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 602988 VA G General 321000 VA 100.00% 321000 VA C Continuous 0 VA 0.00% 0 VA Total Connected Current: 695 A M Motor 257046 VA 109.70% 281988 VA Total Connected Load: 578046 VA R Receptacle 0 VA 0.00% 0 VA L Lighting 0 VA 0.00% 0 VA Power Factor: Load Type Connected Load Demand Factor Demand Load Switchboard Totals % A-B % B-C % C-A 0 0 0 Refer to one-line diagram for space, spare, and circuit breaker quantities. 696 A 696 A 696 A 192682 VA 192682 VA 192682 VA EXISTING PANEL 'MDP' VIA XFMR G 94200 VA 94200 VA 94200 VA 2 Space -- 0 VA -- CRAC-2 M 388 VA 388 VA 388 VA AC-2 (ON ROOF) M 6623 VA 6623 VA 6623 VA FAN COIL UNIT #2 CT (FCU-2) M 3200 VA 3200 VA 3200 VA 3 EXISTING AMBULANCE BUILDING XFMR G 12800 VA 12800 VA 12800 VA 1 CT SCANNER M 33255 VA 33255 VA 33255 VA 1 AHU-1 M 8960 VA 8960 VA 8960 VA 1 GE XRAY CIRCUIT BREAKER M 33255 VA 33255 VA 33255 VA 1 Load Type A B C Note 1. REFED FROM PANEL 'DHA' 2. REFED FROM PANEL 'DLA' 3. REFED FROM PANEL 'PG-BH2A' Circuit Notes: MCB Rating: 1000 A Mounting: Wires: 4 Bus Rating: 1000 A Supply From: Phases: 3 Mains Type: MCB Location: Volts: 480/277 Wye A.I.C. Rating: 65,000 Switchboard NDH2A O Other 0 VA 0.00% 0 VA E Existing 0 VA 0.00% 0 VA Total Demand Current: 131 A K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 47092 VA G General 30889 VA 100.00% 30889 VA C Continuous 0 VA 0.00% 0 VA Total Connected Current: 147 A M Motor 0 VA 0.00% 0 VA Total Connected Load: 52919 VA R Receptacle 21780 VA 72.96% 15890 VA L Lighting 250 VA 125.00% 313 VA Power Factor: 1 Load Type Connected Load Demand Factor Demand Load Panel Totals Phase Balance: 30 % A-B 12 % B-C 45 % C-A Total Amps: 181 A 139 A 125 A Total Load: 21503 VA 16463 VA 14953 VA 41 3143 VA 0 VA 42 39 3143 VA 0 VA 40 1 37 PANEL 'EC1A' G 100 A 3 3143 VA 0 VA 3 100 A -- Spare 38 35 6820 VA 4990 VA 36 33 6820 VA 6500 VA 34 1 31 PANEL 'CL2A' G 100 A 3 6820 VA 11180... 3 100 A R; G; L PANEL 'CL1B' 32 2 29 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 30 27 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 28 25 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 26 23 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 24 21 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 22 19 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 20 17 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 18 15 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 16 13 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 14 11 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 12 9 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 10 7 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 8 5 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 6 3 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 4 1 1 R-1ST FLR HH IT ROOM R 20 A 1 360 VA 0 VA 1 20 A -- Spare 2 Note Circ... Load Type Trip Po... A B C Po... Trip Type Load Circ... Note 1. EXISTING LOAD 2. NEW PANEL 'CL1B' REFED FROM EXISTING FEEDER FOR PANEL 'EC1B' TO BE DEMO'D Circuit Notes: Enclosure: Type 1 MCB Rating: 250 A Mounting: Surface Wire: 4 Bus Rating: 250 A Supply From: Phase: 3 Mains Type: MCB Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000 Panel CDLBA EXISTING General Notes: O Other 0 VA 0.00% 0 VA E Existing 0 VA 0.00% 0 VA Total Demand Current: 47 A K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 17023 VA G General 1000 VA 100.00% 1000 VA C Continuous 0 VA 0.00% 0 VA Total Connected Current: 63 A M Motor 0 VA 0.00% 0 VA Total Connected Load: 22670 VA R Receptacle 21420 VA 73.34% 15710 VA L Lighting 250 VA 125.00% 313 VA Power Factor: 1 Load Type Connected Load Demand Factor Demand Load Panel Totals Phase Balance: 70 % A-B 35 % B-C 129 % C-A Total Amps: 95 A 56 A 42 A Total Load: 11180 VA 6500 VA 4990 VA -- 41 Space -- -- -- 0 VA 0 VA -- -- -- Space 42 -- -- 39 Space -- -- -- 0 VA 0 VA -- -- -- Space 40 -- -- 37 Space -- -- -- 0 VA 0 VA -- -- -- Space 38 -- -- 35 Space -- -- -- 0 VA 0 VA -- -- -- Space 36 -- -- 33 Space -- -- -- 0 VA 0 VA -- -- -- Space 34 -- 31 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 32 29 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 30 27 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 28 25 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 26 23 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 24 21 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 22 19 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 20 17 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 18 15 Spare -- 20 A 1 0 VA 500 VA 1 20 A G R-SHF COMPRESSOR 16 1 2 13 R-CARDIO ABG R 20 A 1 1080 VA 500 VA 1 20 A G R-SPC/ED AUTO DR CTL 14 1 2 11 L-S.H. IT ROOM L 20 A 1 250 VA 900 VA 1 20 A R R-SHF OFFICE 12 1 2 9 R-S.H. COMP. ROOM R 20 A 1 1080 VA 1080 VA 1 20 A R R-CARDIO ABG 10 1 1 7 R-SHF COPIER R 20 A 1 3840 VA 1920 VA 1 20 A R R-SHF COPIER 8 1 1 5 R-SHF IT R 20 A 1 1920 VA 1920 VA 1 20 A R R-SHF IT 6 1 1 3 R-SHF IT R 20 A 1 1920 VA 1920 VA 1 20 A R R-SHF IT 4 1 1 1 R-SHF IT R 20 A 1 1920 VA 1920 VA 1 20 A R R-SHF IT 2 1 Note Circ... Load Type Trip Po... A B C Po... Trip Type Load Circ... Note 1. REFED FROM PANEL 'EC1B' 2. REFED FROM PANEL 'EM1B' Circuit Notes: Enclosure: Type 1 Mounting: Recessed Wire: 4 Bus Rating: 225 A Supply From: CDLBA Phase: 3 Mains Type: MLO Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000 Panel CL1B O Other 0 VA 0.00% 0 VA E Existing 0 VA 0.00% 0 VA Total Demand Current: 319 A K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 265007 VA G General 183969 VA 100.00% 183969 VA C Continuous 0 VA 0.00% 0 VA Total Connected Current: 312 A M Motor 75278 VA 107.65% 81038 VA Total Connected Load: 259247 VA R Receptacle 0 VA 0.00% 0 VA L Lighting 0 VA 0.00% 0 VA Power Factor: 1 Load Type Connected Load Demand Factor Demand Load Panel Totals Phase Balance: 1 % A-B 1 % B-C 0 % C-A Total Amps: 313 A 310 A 313 A Total Load: 86717 VA 86007 VA 86523 VA 41 21333... 6400 VA 42 39 21333... 6400 VA 40 2 37 X-RAY 2 G 100 A 3 21333... 6400 VA 3 50 A G PANEL 'EL2B' XFMR 38 1 35 10360... 4785 VA 36 33 10360... 4785 VA 34 2 31 STEAM GENERATOR 3RD FLOOR VVSC G 80 A 3 10360... 4785 VA 3 20 A M AC-1 32 2 29 19390... 693 VA 30 27 19390... 693 VA 28 2 25 STEAM GENERATOR 3RD FLOOR VVSC G 100 A 3 19390... 693 VA 3 20 A M ACC-1 CT 26 2 23 3048 VA 831 VA 24 21 3048 VA 831 VA 22 1 19 CU-5 M 25 A 3 3048 VA 831 VA 3 15 A M RCP-1 20 1 17 1920 VA 1330 VA 18 15 1920 VA 1330 VA 16 1 13 AHU-1 G 20 A 3 1920 VA 1330 VA 3 15 A M RF-1 14 1 11 1920 VA 1920 VA 12 9 1920 VA 1920 VA 10 1 7 C-SECTION STERILIZER G 50 A 3 1920 VA 1920 VA 3 15 A M RTU CIRCULATION PUMP 8 1 5 4913 VA 7680 VA 6 3 4397 VA 7680 VA 4 3 1 PANEL 'EL2C' VIA XFMR M 20 A 3 5107 VA 7680 VA 3 60 A M VACUUM PUMP 2 1 Note Circ... Load Type Trip Po... A B C Po... Trip Type Load Circ... Note 1. EXISTING LOAD TO REMAIN 2. EXISTING LOAD REFED FROM PANEL 'PGDHM' 3. NEW LOAD Circuit Notes: Enclosure: Type 1 MCB Rating: 400 A Mounting: Surface Wire: 4 Bus Rating: 400 A Supply From: Phase: 3 Mains Type: MCB Location: Voltage: 480/277 Wye A.I.C. Rating: 35,000 Panel EH2D EXISTING General Notes: O Other 0 VA 0.00% 0 VA E Existing 0 VA 0.00% 0 VA Total Demand Current: 42 A K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 15301 VA G General 0 VA 0.00% 0 VA C Continuous 0 VA 0.00% 0 VA Total Connected Current: 40 A M Motor 14417 VA 106.13% 15301 VA Total Connected Load: 14417 VA R Receptacle 0 VA 0.00% 0 VA L Lighting 0 VA 0.00% 0 VA Power Factor: 1 Load Type Connected Load Demand Factor Demand Load Panel Totals Phase Balance: 18 % A-B 14 % B-C 4 % C-A Total Amps: 43 A 37 A 42 A Total Load: 5107 VA 4397 VA 4913 VA -- 41 Space -- -- -- 0 VA 0 VA -- -- -- Space 42 -- -- 39 Space -- -- -- 0 VA 0 VA -- -- -- Space 40 -- -- 37 Space -- -- -- 0 VA 0 VA -- -- -- Space 38 -- -- 35 Space -- -- -- 0 VA 0 VA -- -- -- Space 36 -- -- 33 Space -- -- -- 0 VA 0 VA -- -- -- Space 34 -- -- 31 Space -- -- -- 0 VA 0 VA -- -- -- Space 32 -- 29 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 30 27 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 28 25 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 26 23 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 24 21 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 22 19 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 20 17 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 18 15 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 16 13 Spare -- 20 A 1 0 VA 1768 VA 14 11 1768 VA 1768 VA 2 20 A M CT A/C CONDENSER ON ROOF BY ELEC RM. 12 2 2 9 IMAGING A/C UNIT M 20 A 2 1768 VA 455 VA 10 7 710 VA 455 VA 2 20 A M AC-3-RF ROOM 8 1 1 5 H-1 - RF ROOM COND M 20 A 2 710 VA 667 VA 1 20 A M ACC-3 6 1 3 1768 VA 406 VA 4 1 1 LAB A/C M 20 A 2 1768 VA 406 VA 2 20 A M SHF-IT ROOM A/C 2 1 Note Circ... Load Type Trip Po... A B C Po... Trip Type Load Circ... Note 1. REFED FROM PANEL 'PGBL1A-1' 2. REFED FROM PANEL 'PB' Circuit Notes: Enclosure: Type 1 Mounting: Surface Wire: 4 Bus Rating: 100 A Supply From: T30 Phase: 3 Mains Type: MLO Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000 Panel EL2C 10/12/17