HomeMy WebLinkAboutB17-0340_E-301.75_1507837309.pdfLOAD SUMMARY 'DPA1'
DPA1 CAPACITY 1200 A
EXISTING LOAD 1085 A
NEW PANEL ADDED 'NLEA' 100 A
NEW TOTAL LOAD 1185 A
LOAD SUMMARY 'EH2B'
EH2B CAPACITY 600 A
EXISTING LOAD 242 A
NEW LOAD ADDED TO PANEL 'EH2D' 194 A
NEW TOTAL LOAD 436 A
LOAD SUMMARY 'EH2B'
EH2B CAPACITY 600 A
EXISTING LOAD 242 A
NEW LOAD ADDED TO PANEL 'EH2D' 194 A
NEW TOTAL LOAD 436 A
LOAD SUMMARY 'EH2B'
EH2B CAPACITY 600 A
EXISTING LOAD 242 A
NEW LOAD ADDED TO PANEL 'EH2D' 194 A
NEW TOTAL LOAD 436 A
2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP,
P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
6/30/2017
2:17:08 PM
15924.00
E-301.75
ELECTRICAL PANEL
SCHEDULES
06/30/17
PERMIT
EAST
WING
ADDITION
180 S Frontage Rd W, Vail, CO 81657
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 39 A
K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 13943 VA
G General 0 VA 0.00% 0 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 31 A
M Motor 11154 VA 125.00% 13943 VA Total Connected Load: 11154 VA
R Receptacle 0 VA 0.00% 0 VA
L Lighting 0 VA 0.00% 0 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: 0 % A-B 0 % B-C 0 % C-A
Total Amps: 31 A 31 A 31 A
Total Load: 3718 VA 3718 VA 3718 VA
-- 11 Space -- -- -- 0 VA 0 VA -- -- -- Space 12 --
-- 9 Space -- -- -- 0 VA 0 VA -- -- -- Space 10 --
-- 7 Space -- -- -- 0 VA 0 VA -- -- -- Space 8 --
5 3718 VA 0 VA 1 20 A -- Spare 6
3 3718 VA 0 VA 1 20 A -- Spare 4
1
TRASH COMPACTOR M 20 A 3
3718 VA 0 VA 1 20 A -- Spare 2
Note Circ... Load Type Trip Po... A B C Po... Trip Type Load Circ... Note
Circuit Notes:
Enclosure: Type 1 MCB Rating: 100 A
Mounting: Surface Wire: 4 Bus Rating: 100 A
Supply From: Phase: 3 Mains Type: MCB
Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000
Panel NLEA
General Notes:
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 725 A
K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 602988 VA
G General 321000 VA 100.00% 321000 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 695 A
M Motor 257046 VA 109.70% 281988 VA Total Connected Load: 578046 VA
R Receptacle 0 VA 0.00% 0 VA
L Lighting 0 VA 0.00% 0 VA Power Factor:
Load Type Connected Load Demand Factor Demand Load Switchboard Totals
% A-B % B-C % C-A
0 0 0
Refer to one-line diagram for space, spare, and circuit breaker quantities. 696 A 696 A 696 A
192682 VA 192682 VA 192682 VA
EXISTING PANEL 'MDP' VIA XFMR G 94200 VA 94200 VA 94200 VA 2
Space -- 0 VA --
CRAC-2 M 388 VA 388 VA 388 VA
AC-2 (ON ROOF) M 6623 VA 6623 VA 6623 VA
FAN COIL UNIT #2 CT (FCU-2) M 3200 VA 3200 VA 3200 VA 3
EXISTING AMBULANCE BUILDING XFMR G 12800 VA 12800 VA 12800 VA 1
CT SCANNER M 33255 VA 33255 VA 33255 VA 1
AHU-1 M 8960 VA 8960 VA 8960 VA 1
GE XRAY CIRCUIT BREAKER M 33255 VA 33255 VA 33255 VA 1
Load Type A B C Note
1. REFED FROM PANEL 'DHA'
2. REFED FROM PANEL 'DLA'
3. REFED FROM PANEL 'PG-BH2A'
Circuit Notes:
MCB Rating: 1000 A
Mounting: Wires: 4 Bus Rating: 1000 A
Supply From: Phases: 3 Mains Type: MCB
Location: Volts: 480/277 Wye A.I.C. Rating: 65,000
Switchboard NDH2A
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 131 A
K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 47092 VA
G General 30889 VA 100.00% 30889 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 147 A
M Motor 0 VA 0.00% 0 VA Total Connected Load: 52919 VA
R Receptacle 21780 VA 72.96% 15890 VA
L Lighting 250 VA 125.00% 313 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: 30 % A-B 12 % B-C 45 % C-A
Total Amps: 181 A 139 A 125 A
Total Load: 21503 VA 16463 VA 14953 VA
41 3143 VA 0 VA 42
39 3143 VA 0 VA 40
1
37
PANEL 'EC1A' G 100 A 3
3143 VA 0 VA
3 100 A -- Spare
38
35 6820 VA 4990 VA 36
33 6820 VA 6500 VA 34
1
31
PANEL 'CL2A' G 100 A 3
6820 VA 11180...
3 100 A R; G; L PANEL 'CL1B'
32
2
29 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 30
27 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 28
25 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 26
23 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 24
21 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 22
19 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 20
17 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 18
15 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 16
13 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 14
11 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 12
9 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 10
7 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 8
5 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 6
3 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 4
1 1 R-1ST FLR HH IT ROOM R 20 A 1 360 VA 0 VA 1 20 A -- Spare 2
Note Circ... Load Type Trip Po... A B C Po... Trip Type Load Circ... Note
1. EXISTING LOAD
2. NEW PANEL 'CL1B' REFED FROM EXISTING FEEDER FOR PANEL 'EC1B' TO BE DEMO'D
Circuit Notes:
Enclosure: Type 1 MCB Rating: 250 A
Mounting: Surface Wire: 4 Bus Rating: 250 A
Supply From: Phase: 3 Mains Type: MCB
Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000
Panel CDLBA
EXISTING
General Notes:
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 47 A
K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 17023 VA
G General 1000 VA 100.00% 1000 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 63 A
M Motor 0 VA 0.00% 0 VA Total Connected Load: 22670 VA
R Receptacle 21420 VA 73.34% 15710 VA
L Lighting 250 VA 125.00% 313 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: 70 % A-B 35 % B-C 129 % C-A
Total Amps: 95 A 56 A 42 A
Total Load: 11180 VA 6500 VA 4990 VA
-- 41 Space -- -- -- 0 VA 0 VA -- -- -- Space 42 --
-- 39 Space -- -- -- 0 VA 0 VA -- -- -- Space 40 --
-- 37 Space -- -- -- 0 VA 0 VA -- -- -- Space 38 --
-- 35 Space -- -- -- 0 VA 0 VA -- -- -- Space 36 --
-- 33 Space -- -- -- 0 VA 0 VA -- -- -- Space 34 --
31 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 32
29 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 30
27 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 28
25 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 26
23 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 24
21 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 22
19 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 20
17 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 18
15 Spare -- 20 A 1 0 VA 500 VA 1 20 A G R-SHF COMPRESSOR 16 1
2 13 R-CARDIO ABG R 20 A 1 1080 VA 500 VA 1 20 A G R-SPC/ED AUTO DR CTL 14 1
2 11 L-S.H. IT ROOM L 20 A 1 250 VA 900 VA 1 20 A R R-SHF OFFICE 12 1
2 9 R-S.H. COMP. ROOM R 20 A 1 1080 VA 1080 VA 1 20 A R R-CARDIO ABG 10 1
1 7 R-SHF COPIER R 20 A 1 3840 VA 1920 VA 1 20 A R R-SHF COPIER 8 1
1 5 R-SHF IT R 20 A 1 1920 VA 1920 VA 1 20 A R R-SHF IT 6 1
1 3 R-SHF IT R 20 A 1 1920 VA 1920 VA 1 20 A R R-SHF IT 4 1
1 1 R-SHF IT R 20 A 1 1920 VA 1920 VA 1 20 A R R-SHF IT 2 1
Note Circ... Load Type Trip Po... A B C Po... Trip Type Load Circ... Note
1. REFED FROM PANEL 'EC1B'
2. REFED FROM PANEL 'EM1B'
Circuit Notes:
Enclosure: Type 1
Mounting: Recessed Wire: 4 Bus Rating: 225 A
Supply From: CDLBA Phase: 3 Mains Type: MLO
Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000
Panel CL1B
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 319 A
K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 265007 VA
G General 183969 VA 100.00% 183969 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 312 A
M Motor 75278 VA 107.65% 81038 VA Total Connected Load: 259247 VA
R Receptacle 0 VA 0.00% 0 VA
L Lighting 0 VA 0.00% 0 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: 1 % A-B 1 % B-C 0 % C-A
Total Amps: 313 A 310 A 313 A
Total Load: 86717 VA 86007 VA 86523 VA
41 21333... 6400 VA 42
39 21333... 6400 VA 40
2
37
X-RAY 2 G 100 A 3
21333... 6400 VA
3 50 A G PANEL 'EL2B' XFMR
38
1
35 10360... 4785 VA 36
33
10360... 4785 VA 34
2
31 STEAM
GENERATOR
3RD FLOOR VVSC
G 80 A 3
10360... 4785 VA
3 20 A M AC-1
32
2
29 19390... 693 VA 30
27
19390... 693 VA 28
2
25 STEAM
GENERATOR
3RD FLOOR VVSC
G 100 A 3
19390... 693 VA
3 20 A M ACC-1 CT
26
2
23 3048 VA 831 VA 24
21 3048 VA 831 VA 22
1
19
CU-5 M 25 A 3
3048 VA 831 VA
3 15 A M RCP-1
20
1
17 1920 VA 1330 VA 18
15 1920 VA 1330 VA
16
1
13
AHU-1 G 20 A 3
1920 VA 1330 VA
3 15 A M RF-1
14
1
11 1920 VA 1920 VA 12
9 1920 VA 1920 VA
10
1
7
C-SECTION STERILIZER G 50 A 3
1920 VA 1920 VA
3 15 A M
RTU CIRCULATION
PUMP
8
1
5 4913 VA 7680 VA 6
3 4397 VA 7680 VA
4
3
1
PANEL 'EL2C' VIA XFMR M 20 A 3
5107 VA 7680 VA
3 60 A M VACUUM PUMP
2
1
Note Circ... Load Type Trip Po... A B C Po... Trip Type Load Circ... Note
1. EXISTING LOAD TO REMAIN
2. EXISTING LOAD REFED FROM PANEL 'PGDHM'
3. NEW LOAD
Circuit Notes:
Enclosure: Type 1 MCB Rating: 400 A
Mounting: Surface Wire: 4 Bus Rating: 400 A
Supply From: Phase: 3 Mains Type: MCB
Location: Voltage: 480/277 Wye A.I.C. Rating: 35,000
Panel EH2D
EXISTING
General Notes:
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 42 A
K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 15301 VA
G General 0 VA 0.00% 0 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 40 A
M Motor 14417 VA 106.13% 15301 VA Total Connected Load: 14417 VA
R Receptacle 0 VA 0.00% 0 VA
L Lighting 0 VA 0.00% 0 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: 18 % A-B 14 % B-C 4 % C-A
Total Amps: 43 A 37 A 42 A
Total Load: 5107 VA 4397 VA 4913 VA
-- 41 Space -- -- -- 0 VA 0 VA -- -- -- Space 42 --
-- 39 Space -- -- -- 0 VA 0 VA -- -- -- Space 40 --
-- 37 Space -- -- -- 0 VA 0 VA -- -- -- Space 38 --
-- 35 Space -- -- -- 0 VA 0 VA -- -- -- Space 36 --
-- 33 Space -- -- -- 0 VA 0 VA -- -- -- Space 34 --
-- 31 Space -- -- -- 0 VA 0 VA -- -- -- Space 32 --
29 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 30
27 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 28
25 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 26
23 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 24
21 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 22
19 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 20
17 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 18
15 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 16
13 Spare -- 20 A 1 0 VA 1768 VA 14
11 1768 VA 1768 VA
2 20 A M
CT A/C CONDENSER ON
ROOF BY ELEC RM.
12
2
2
9
IMAGING A/C UNIT M 20 A 2
1768 VA 455 VA 10
7 710 VA 455 VA
2 20 A M AC-3-RF ROOM
8
1
1
5
H-1 - RF ROOM COND M 20 A 2
710 VA 667 VA 1 20 A M ACC-3 6 1
3 1768 VA 406 VA 4
1 1 LAB A/C M 20 A 2 1768 VA 406 VA
2 20 A M SHF-IT ROOM A/C 2
1
Note Circ... Load Type Trip Po... A B C Po... Trip Type Load Circ... Note
1. REFED FROM PANEL 'PGBL1A-1'
2. REFED FROM PANEL 'PB'
Circuit Notes:
Enclosure: Type 1
Mounting: Surface Wire: 4 Bus Rating: 100 A
Supply From: T30 Phase: 3 Mains Type: MLO
Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000
Panel EL2C
10/12/17