HomeMy WebLinkAboutB17-0340_E-302.75_1507837260.pdf 11"ilit
cl-irbj 055.S"
11170J 11
Switchboard MDP Panel NL1 D EXISTING 10/12/17
Location: Volts: 120/208 Wye A.I.C. Rating: 35,000 Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000
Supply From: Phases: 3 Mains Type: MCB Supply From: L1 E Phase: 3 Mains Type: MLO
Mounting: Wires: 4 Bus Rating: 1000 A Mounting: Surface Wire: 4 Bus Rating: 100 A
MCB Rating: 1000 A Enclosure: Type 1
Circuit Notes: Circuit Notes:
1. EXISTING LOAD
1. REFED FROM PANEL'PB' II■ I U
2. REFED FROM 'DHA'
Note Circ... Load Type Trip Po... A B C Po... Trip Type Load Circ... Note 111• 11111
Load Type A B C Note Y Y II
aE 1 R-OFFICE R 20 A 1 720 VA 900 VA 1 20 A R R-NUC. MED 2 E
3 R-OFFICE R 20 A 1 720 VA 720 VA 1 20 A R R-NUC. MED 4
5 R-OFFICE R 20 A 1 720 VA 900 VA 1 20 A R R-NUC. MED-HOT LAB 6 III II
■ 11
7 R-OFFICE R; G 20 A 1 1280 VA 1680 VA 1 20 A G R-NUC. MED-MICRO 8
9 R-OFFICE R 20 A 1 720 VA 180 VA 1 20 A G R-NUC. MED-COMP. 10 111111111
■■
1 11 L-STORAGE L 20 A 1 250 VA 540 VA 1 20 A R R-NUC. MED-CONTROL 12
1 13 L-DR. LOUNGE L 20 A 1 250 VA 200 VA 1 20 A G R-NUC. MED-PRINTER 14
1 15 R-CT R 20 A 1 1080 VA 0 VA 1 20 A -- Spare 16 !i A !"
1 17 R-CT R 20 A 1 1080 VA 0 VA 1 20 A -- Spare 18
19 'SYSCO SWITCH ED 500 VA 0 VA 1 20 A -- Spare 20 `/ _ ' rr
1 21 TELE G 20 A 2 500 VA 0 VA 1 20 A -- Spare 22 PARTNERSHIP
1 23 L-CT L 20 A 1 250 VA 0 VA 1 20 A -- Spare 24
1 25 1L-CT L 20 A 1 250 VA 0 VA 1 20 A -- Spare 26 ARCH I T E C T S
1 27 R-CT R 20 A 1 1080 VA 0 VA 1 20 A -- Spare 28
1 29 R-S.H.VISUAL OFFICE R 20 A 1 900 VA 0 VA 1 20 A -- Spare 30 2901 Blake Street,Site 10C
1 31 R-CT HALL BATH R 20 A 1 180 VA 0 VA 1 20 A -- Spare 32 Demer Denver, ODgpx
33 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 34 303.861.855E
35 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 36Consul
tart
37 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 38
39 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 40
0 VA OVA OVA 41 Spare -- 20 A 1 0 VA OVA 1 20 A -- Spare 42
Refer to one-line diagram for space, spare, and circuit breaker quantities. 0 A 0 A 0 A Total Load: 5960 VA 5000 VA 4640 VA
Total Amps: 50 A 42 A 39 A
%A-B % B-C %C-A Phase Balance: 19 %A-B 9 % B-C 30 % C-A
I Load Type Connected Load Demand Factor Demand Load Switchboard Totals Load Type Connected Load Demand Factor Demand Load Panel Totals CATO R 1 RUM A
L Lighting 0 VA 0.00% 0 VA Power Factor: L Lighting 1000 VA 125.00% 1250 VA Power Factor: 1
kill& ASSOCIATES , CO .
R Receptacle 0 VA 0.00% 0 VA R Receptacle 11340 VA 94.09% 10670 VA
M Motor 0 VA 0.00% 0 VA Total Connected Load: 0 VA M Motor 0 VA 0.00% 0 VA Total Connected Load: 15600 VA
896 Tabor Street 420 W.Lincolnway
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 0 A C Continuous 0 VA 0.00% 0 VA Total Connected Current: 43 A Lakewood,C080401 Cheyenne,W'82001
303.232.6200(P) 307.274.3830(P)
G General 0 VA 0.00% 0 VA G General 3260 VA 100.000/0 3260 VA 303.233.3701(F) 303.233.3701(F)
K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 0 VA K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 15180 VA www.catorruma.com
C E Existing 0 VA 0.00% 0 VA Total Demand Current: 0 A E Existing 0 VA 0.00% 0 VA Total Demand Current: 42 A C
O Other 0 VA 0.00% 0 VA 0 Other 0 VA 0.00% 0 VA
General Notes: General Notes:
�,�\ M�` �v�aDO L� ■A. 'fes!
Panel L1 E EXISTING 4 •'',1, .'.ir �f l .,,C+4
Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000 ;ti 0;
Supply From: Phase: 3 Mains Type: MLO77-: ;d 418 i I a; rz
E
Mounting: Surface Wire: 4 Bus Rating: 200 A
Enclosure: Type 1 MCB Rating: 200 A A' a Iga it?‘"
r A�
0
Circuit Notes: ffr,
<',..w,-.NAl o ����k��yh�
1. EXISTING LOAD
n101111111 it10
2. NEW LOAD
Note Circ... Load Type Trip Po... A B C Po... Trip Type Load Circ... Note
1 1 R-SHF RECEPTION R 20 A 1 540 VA 1080 VA 1 20 A R R-OFFICE 2 2
1 3 R-SHF OFFICE, RR R 20 A 1 540 VA 540 VA 1 20 A R R-SHF OFFICES 4 1 Issuance
1 5 I R-SHF OFFICE,VISITOR R 20 A 1 1440 VA 540 VA 1 20 A R R-SHF OFFICES 6 1
1 7 R-SHF OFFICES R 20 A 1 720 VA 720 VA 1 20 A R R-SHF OFFICES 8 1 PERMIT 06/29/17
1 9 R-SHF OFFICES R 20 A 1 900 VA 180 VA 1 20 A R R-SHF BIOMECH... 10 1
1 11 L-MRI L 20 A 1 1540 VA 900 VA 1 20 A R R-OFFICE 12 2
13 1360 VA 920 VA 1 20 A R; G R-SHF BIOMECH... 14 1 Revisions Date
1 15 PANEL'MRI' R; G 50 A 2 0 VA 900 VA 1 20 A R R-OFFICE 16 2
1 17 R-SHF OFFICES R 20 A 1 900 VA 1080 VA 1 20 A R R-OFFICE 18 2
2 19 R-CONFERENCE ROOM R; G 20 A 1 560 VA 1440 VA 1 20 A R R-CARDIO CONTROL 20 1
1 21 R-SHF CORRDIOR R 20 A 1 900 VA 720 VA 1 20 A R R-STORAGE 22 2
C 1 23 R-MRI MECH ROOM R 20 A 1 1080 VA 0 VA 1 20 A -- Spare 24 C
1 25 R-PRE-OP CHECK IN R 20 A 1 720 VA 0 VA 1 20 A -- Spare 26
1 27 R-PRE-OP CHECK IN R 20 A 1 720 VA 360 VA 1 20 A R CARDIO CNTL CHG 28 1
2 29 R-OFFICE/COPY R 20 A 1 540 VA 360 VA 1 20 A R CARDIO CNTL CHG 30 1
2 31 R-COPIER G 20 A 1 1000 VA 180 VA 1 20 A R R-CARDIO CONTROL RR 32 1
2 33 R-CONF ROOM -NV R 20 A 1 360 VA 540 VA 1 20 A R R-ULTRASOUND 34 2
1 35 R-SHF OFFICE NORTH R 20 A 1 360 VA 540 VA 1 20 A R R-CARDIO OFFICE 36 1
1 37 R-SHF WORK ROOM R 20 A 1 540 VA 0 VA 1 20 A -- Spare 38
1 39 MAG DOOR HOLDERS G 20 A 1 0 VA 360 VA 1 20 A R R-CORR/STAFF RECESS 40 2
1 41 R-BRK REF K 20 A 1 1200 VA 720 VA 1 20 A R R-CARDIO RECEPTION 42 1
1 43 R-BRK MICROWAVE K 20 A 1 1500 VA 360 VA 1 20 A R R-CARDIO ABG ROOM 44 1
1 45 R-BREAK ROOM R 20 A 1 540 VA 540 VA 1 20 A R R-CARDIO CORRIDOR 46 1
2 47 R-OFFICE R 20 A 1 540 VA 1080 VA 1 20 A R R-CARDIO TECH WORK 48 1
2 49 R-OFFICE R 20 A 1 1260 VA 720 VA 1 20 A R R-CARDIO CLEAN CHG 50 1
2 51 R-OFFICE R 20 A 1 1080 VA 720 VA 1 20 A R R-CARDIO CLEAN CHG 52 1 Project Information
2 53 R-OFFICE COPIER G 20 A 1 1000 VA 540 VA 1 20 A R R-STORAGE 54 2
1 55 R-MRI CONTROL ROOM R 20 A 1 900 VA 360 VA 1 20 A R R-STORAGE 56 2
2 57 1R-OFFICE R 20 A 1 900 VA 0 VA 1 20 A -- Spare 58
1 59 PRE-ACTION COMP. M 20 A 1 624 VA 0 VA 1 20 A -- Spare 60
61 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 62
1 63 R-BREAK ROOM DISP K 20 A 1 1620 VA 300 VA 1 20 A G R-CARDIO TECH WORK 64 1
2 65 R-OFFICE R 20 A 1 1260 VA 360 VA 1 20 A R R-PT TREADMILL 66 1
67 5960 VA 0 VA 1 20 A -- Spare 68
2 69 NEW PANEL'NL1 D' R; G; L 100 A 3 5000 VA 500 VA 1 20 A R R-CARDIO STRESS... 70 1
71 4640 VA 0 VA 1 20 A -- Spare 72
73 1 Spare -- 20 A 1 OVA 1080 VA 1 20 A R R-SERV RM 111,112,113 74 1 h-
1
1 75 RAY DAMPERS G 20 A 1 200 VA 360 VA 1 20 A R R-SERVER RM 113 76 1 It)
1 77 CAMERA POWER R 20 A 1 180 VA 180 VA 1 20 A R L-111,112,113 78 1 CO
1 79 FA EXTENDER G 20 A 1 200 VA 0 VA 1 20 A -- Spare 80
81 HEAT TAPE OB GUTTER -- 20 A 1 0 VA 0 VA 1 20 A -- HEAT TAPE OB GUTTER 82 O co
83 HEAT TAPE OB GUTTER -- 20 A 1 0 VA 0 VA 1 20 A -- HEAT TAPE OB GUTTER 84 0
E Total Load: 22120 VA 18780 VA 21604 VA E l' 0
Total Amps: 188 A 157 A 184 A Q
Phase Balance: 20 %A-B 17 % B-C 2 %C-A CO
Load Type Connected Load Demand Factor Demand Load Panel Totals 0
L Lighting 2540 VA 125.00% 3175 VA Power Factor: 1
R Receptacle 47660 VA 60.49% 28830 VA
M Motor 624 VA 125.00% 780 VA Total Connected Load: 62504 VA -o
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 173 A
Z Et
G General 7360 VA 100.00% 7360 VA
CD
K 'Kitchen 4320 VA 90.00% 3888 VA Total Demand Load: 44033 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 122 A CO
O Other 0 VA 0.00% 0 VA C
CO O
Q LL
W u)
O
Co
Sheet Information
A p Sheet Title:
ELECTRICAL PANEL
SCHEDULES
Sheet NJ-rber:
2
o_ E _ 3 0 2,,,
E - 302 . 75
7 5
,,:
(V
r
O
M DPA Project: 15924.00
CCPYFddii -D'OAS PARTNEFEHP,
1 1 2 1 3 1 4 1 5 6