HomeMy WebLinkAboutB17-0340_E-302.75_1507837307.pdf2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP,
P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
6/30/2017
2:17:11 PM
15924.00
E-302.75
ELECTRICAL PANEL
SCHEDULES
06/29/17
PERMIT
EAST
WING
ADDITION
180 S Frontage Rd W, Vail, CO 81657
General Notes:
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 42 A
K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 15180 VA
G General 3260 VA 100.00% 3260 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 43 A
M Motor 0 VA 0.00% 0 VA Total Connected Load: 15600 VA
R Receptacle 11340 VA 94.09% 10670 VA
L Lighting 1000 VA 125.00% 1250 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: 19 % A-B 9 % B-C 30 % C-A
Total Amps: 50 A 42 A 39 A
Total Load: 5960 VA 5000 VA 4640 VA
41 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 42
39 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 40
37 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 38
35 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 36
33 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 34
1 31 R-CT HALL BATH R 20 A 1 180 VA 0 VA 1 20 A -- Spare 32
1 29 R-S.H. VISUAL OFFICE R 20 A 1 900 VA 0 VA 1 20 A -- Spare 30
1 27 R-CT R 20 A 1 1080 VA 0 VA 1 20 A -- Spare 28
1 25 L-CT L 20 A 1 250 VA 0 VA 1 20 A -- Spare 26
1 23 L-CT L 20 A 1 250 VA 0 VA 1 20 A -- Spare 24
21 500 VA 0 VA 1 20 A -- Spare 22
1
19 SYSCO SWITCH ED
TELE
G 20 A 2
500 VA 0 VA 1 20 A -- Spare 20
1 17 R-CT R 20 A 1 1080 VA 0 VA 1 20 A -- Spare 18
1 15 R-CT R 20 A 1 1080 VA 0 VA 1 20 A -- Spare 16
1 13 L-DR. LOUNGE L 20 A 1 250 VA 200 VA 1 20 A G R-NUC. MED - PRINTER 14
1 11 L-STORAGE L 20 A 1 250 VA 540 VA 1 20 A R R-NUC. MED - CONTROL 12
9 R-OFFICE R 20 A 1 720 VA 180 VA 1 20 A G R-NUC. MED - COMP. 10
7 R-OFFICE R; G 20 A 1 1280 VA 1680 VA 1 20 A G R-NUC. MED - MICRO 8
5 R-OFFICE R 20 A 1 720 VA 900 VA 1 20 A R R-NUC. MED - HOT LAB 6
3 R-OFFICE R 20 A 1 720 VA 720 VA 1 20 A R R-NUC. MED 4
1 R-OFFICE R 20 A 1 720 VA 900 VA 1 20 A R R-NUC. MED 2
Note Circ... Load Type Trip Po... A B C Po... Trip Type Load Circ... Note
1. REFED FROM PANEL 'PB'
Circuit Notes:
Enclosure: Type 1
Mounting: Surface Wire: 4 Bus Rating: 100 A
Supply From: L1E Phase: 3 Mains Type: MLO
Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000
Panel NL1D
EXISTING
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 122 A
K Kitchen 4320 VA 90.00% 3888 VA Total Demand Load: 44033 VA
G General 7360 VA 100.00% 7360 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 173 A
M Motor 624 VA 125.00% 780 VA Total Connected Load: 62504 VA
R Receptacle 47660 VA 60.49% 28830 VA
L Lighting 2540 VA 125.00% 3175 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: 20 % A-B 17 % B-C 2 % C-A
Total Amps: 188 A 157 A 184 A
Total Load: 22120 VA 18780 VA 21604 VA
83 HEAT TAPE OB GUTTER -- 20 A 1 0 VA 0 VA 1 20 A -- HEAT TAPE OB GUTTER 84
81 HEAT TAPE OB GUTTER -- 20 A 1 0 VA 0 VA 1 20 A -- HEAT TAPE OB GUTTER 82
1 79 FA EXTENDER G 20 A 1 200 VA 0 VA 1 20 A -- Spare 80
1 77 CAMERA POWER R 20 A 1 180 VA 180 VA 1 20 A R L-111,112,113 78 1
1 75 RAY DAMPERS G 20 A 1 200 VA 360 VA 1 20 A R R-SERVER RM 113 76 1
73 Spare -- 20 A 1 0 VA 1080 VA 1 20 A R R-SERV RM 111,112,113 74 1
71 4640 VA 0 VA 1 20 A -- Spare 72
69 5000 VA 500 VA 1 20 A R R-CARDIO STRESS... 70 1
2
67
NEW PANEL 'NL1D' R; G; L 100 A 3
5960 VA 0 VA 1 20 A -- Spare 68
2 65 R-OFFICE R 20 A 1 1260 VA 360 VA 1 20 A R R-PT TREADMILL 66 1
1 63 R-BREAK ROOM DISP K 20 A 1 1620 VA 300 VA 1 20 A G R-CARDIO TECH WORK 64 1
61 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 62
1 59 PRE-ACTION COMP. M 20 A 1 624 VA 0 VA 1 20 A -- Spare 60
2 57 R-OFFICE R 20 A 1 900 VA 0 VA 1 20 A -- Spare 58
1 55 R-MRI CONTROL ROOM R 20 A 1 900 VA 360 VA 1 20 A R R-STORAGE 56 2
2 53 R-OFFICE COPIER G 20 A 1 1000 VA 540 VA 1 20 A R R-STORAGE 54 2
2 51 R-OFFICE R 20 A 1 1080 VA 720 VA 1 20 A R R-CARDIO CLEAN CHG 52 1
2 49 R-OFFICE R 20 A 1 1260 VA 720 VA 1 20 A R R-CARDIO CLEAN CHG 50 1
2 47 R-OFFICE R 20 A 1 540 VA 1080 VA 1 20 A R R-CARDIO TECH WORK 48 1
1 45 R-BREAK ROOM R 20 A 1 540 VA 540 VA 1 20 A R R-CARDIO CORRIDOR 46 1
1 43 R-BRK MICROWAVE K 20 A 1 1500 VA 360 VA 1 20 A R R-CARDIO ABG ROOM 44 1
1 41 R-BRK REF K 20 A 1 1200 VA 720 VA 1 20 A R R-CARDIO RECEPTION 42 1
1 39 MAG DOOR HOLDERS G 20 A 1 0 VA 360 VA 1 20 A R R-CORR/STAFF RECESS 40 2
1 37 R-SHF WORK ROOM R 20 A 1 540 VA 0 VA 1 20 A -- Spare 38
1 35 R-SHF OFFICE NORTH R 20 A 1 360 VA 540 VA 1 20 A R R-CARDIO OFFICE 36 1
2 33 R-CONF ROOM - A/V R 20 A 1 360 VA 540 VA 1 20 A R R-ULTRASOUND 34 2
2 31 R-COPIER G 20 A 1 1000 VA 180 VA 1 20 A R R-CARDIO CONTROL RR 32 1
2 29 R-OFFICE/COPY R 20 A 1 540 VA 360 VA 1 20 A R CARDIO CNTL CHG 30 1
1 27 R-PRE-OP CHECK IN R 20 A 1 720 VA 360 VA 1 20 A R CARDIO CNTL CHG 28 1
1 25 R-PRE-OP CHECK IN R 20 A 1 720 VA 0 VA 1 20 A -- Spare 26
1 23 R-MRI MECH ROOM R 20 A 1 1080 VA 0 VA 1 20 A -- Spare 24
1 21 R-SHF CORRDIOR R 20 A 1 900 VA 720 VA 1 20 A R R-STORAGE 22 2
2 19 R-CONFERENCE ROOM R; G 20 A 1 560 VA 1440 VA 1 20 A R R-CARDIO CONTROL 20 1
1 17 R-SHF OFFICES R 20 A 1 900 VA 1080 VA 1 20 A R R-OFFICE 18 2
15 0 VA 900 VA 1 20 A R R-OFFICE 16 2
1 13
PANEL 'MRI' R; G 50 A 2
1360 VA 920 VA 1 20 A R; G R-SHF BIOMECH... 14 1
1 11 L-MRI L 20 A 1 1540 VA 900 VA 1 20 A R R-OFFICE 12 2
1 9 R-SHF OFFICES R 20 A 1 900 VA 180 VA 1 20 A R R-SHF BIOMECH... 10 1
1 7 R-SHF OFFICES R 20 A 1 720 VA 720 VA 1 20 A R R-SHF OFFICES 8 1
1 5 R-SHF OFFICE, VISITOR R 20 A 1 1440 VA 540 VA 1 20 A R R-SHF OFFICES 6 1
1 3 R-SHF OFFICE, RR R 20 A 1 540 VA 540 VA 1 20 A R R-SHF OFFICES 4 1
1 1 R-SHF RECEPTION R 20 A 1 540 VA 1080 VA 1 20 A R R-OFFICE 2 2
Note Circ... Load Type Trip Po... A B C Po... Trip Type Load Circ... Note
1. EXISTING LOAD
2. NEW LOAD
Circuit Notes:
Enclosure: Type 1 MCB Rating: 200 A
Mounting: Surface Wire: 4 Bus Rating: 200 A
Supply From: Phase: 3 Mains Type: MLO
Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000
Panel L1E
EXISTING
General Notes:
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 0 A
K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 0 VA
G General 0 VA 0.00% 0 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 0 A
M Motor 0 VA 0.00% 0 VA Total Connected Load: 0 VA
R Receptacle 0 VA 0.00% 0 VA
L Lighting 0 VA 0.00% 0 VA Power Factor:
Load Type Connected Load Demand Factor Demand Load Switchboard Totals
% A-B % B-C % C-A
Refer to one-line diagram for space, spare, and circuit breaker quantities. 0 A 0 A 0 A
0 VA 0 VA 0 VA
Load Type A B C Note
1. EXISTING LOAD
2. REFED FROM 'DHA'
Circuit Notes:
MCB Rating: 1000 A
Mounting: Wires: 4 Bus Rating: 1000 A
Supply From: Phases: 3 Mains Type: MCB
Location: Volts: 120/208 Wye A.I.C. Rating: 35,000
Switchboard MDP
10/12/17