HomeMy WebLinkAboutB17-0340_LS000-1_1507837312.pdfEXISTING FIRE RESISTIVE REQUIREMENTS TO BE MAINTAINED:
STRUCTURAL FRAME
BEAMS
COLUMNS
EXTERIOR BEARING WALLS
INTERIOR BEARING WALLS
EXTERIOR NONBEARING WALLS
FLOOR CONSTRUCTION
ROOF CONSTRUCTION & CANOPY
SHAFT & VERTICAL EXIT ENCLOSURES
EXTERIOR OPENINGS
EDGE OF SLAB
IBC
RATING
TEST
NFPA
RATING
CONSTRUCTION (TYPE I B) (II-222)
UL 263
UL
UL 790
UL
NOTE : REFER TO PARTITION TYPES SCHEDULE ON A-720-1 FOR UL ASSEMBLIES AT ADDITIONAL
INTERIOR PARTITIONS AND WALL RATINGS AND SPECIFICATION SECTION 078413 PENETRATION
FIRESTOPPING FOR USE OF UL ASSEMBLIES AT THROUGH-PENETRATION FIRESTOP CONDITIONS.
REMARKS
2 HR
2 HR
2 HR
2 HR
0 HR
2 HR
1 HR
PER 8.6.5
2 HR
2 HR
2 HR
2 HR
PER 602
2 HR
1 HR
PER 713.4
PER T705.8
NOTE:
WORK TIMES LIMITED BY "VAIL 2016 VAIL VILLAGE AND LIONSHEAD VILLAGE CONSTRUCTION
INFORMATION HANDOUT" IN ADDITION TO OWNER REQUIREMENTS.
PARKING ANALYSIS:
LEVEL 1
- INPATIENT (INCLUDING PHARMACY) = 1,949 SF
- OUTPATIENT 30,035 SF
- REHAB (HHSM) 7,779 SF
LEVEL 2
- INPATIENT 32,606 SF
- OUTPATIENT 0 SF
- REHAB 0 SF
LEVEL 3 AREAS
- INPATIENT 22,883 SF
- OUTPATIENT 13,893 SF
- REHAB 0 SF
LEVEL 4
- INPATIENT 0 SF
- OUTPATIENT 0 SF
- REHAB 0 SF
TOTALS
INPATIENT GSF: 57,438 SF => 52.6% * 75 = 39.5 TOTAL SPOTS => 2 ACCESSIBLE SPOTS
OUTPATIENT GSF: 43,928 SF => 40.2% * 75 = 30.2 TOTAL SPOTS => 3 ACCESSIBLE SPOTS
REHAB GSF: 7,779 SF => 7.1% * 75 = 5.3 TOTAL SPOTS => 1.1 ACCESSIBLE SPOTS
109,145 SF 6.1 ACCESSIBLE SPOTS => 7 ACCESSIBLE SPOTS REQ.
APPLICABLE CODES:
2015 INTERNATIONAL BUILDING CODE
2015 INTERNATIONAL FIRE CODE
2015 INTERNATIONAL MECHANICAL CODE
2015 INTERNATIONAL PLUMBING CODE
2009 ANSI A117.1 ACCESSIBILTY CODE
2012 NFPA 101
NFPA 55, CURRENT EDITION
CGA P-41, CURRENT EDITION
CODES TO BE GOVERNED BY LOCAL AMENDMENTS, STATE, AND FEDERAL REGULATORY ENTITIES.
2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP,
P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
EAST
WING
ENABLING
6/30/2017
4:47:57 PM
15924.00
LS000-1
CODE ANALYSIS
2017
06/30/17
PERMIT
VAIL
VALLEY
MEDICAL
CENTER
180 S. Frontage
Road
West,
Vail, CO 81657
10/12/17