HomeMy WebLinkAboutB17-0340_M-001.75_1507837277.pdfHVAC LEGEND
SYMBOL DESCRIPTION ABBR. DESCRIPTION
LOW PRESSURE CONDENSATE RETURN PIPING
HOT WATER SUPPLY PIPING
HOT WATER RETURN PIPING
HIGH TEMPERATURE HOT WATER SUPPLY PIPING
HIGH TEMPERATURE HOT WATER RETURN PIPING
CHILLED WATER SUPPLY PIPING
CHILLED WATER RETURN PIPING
SUPPLY DUCT UP / SUPPLY DUCT DOWN
RETURN DUCT UP / RETURN DUCT DOWN
FLEXIBLE DUCT CONNECTION
BACKDRAFT DAMPER
TEMP. CONTROL DAMPER-OPPOSED BLADE
LOUVER WITH SCREEN
MANUAL VOLUME DAMPER
MOTOR OPERATED DAMPER
SPIN-IN FITTING WITH MVD
CONDENSER WATER SUPPLY PIPING
LOW PRESSURE STEAM SUPPLY PIPING (0 - 15#)
ROUND DUCT UP / ROUND DUCT DOWN
INDICATES FLAT OVAL DUCTWORK
ABBR.
SYMBOL
COOLING COIL DRAIN PAN PIPING
TEMP. CONTROL DAMPER- PARELLEL BLADE
LPS
LPC
MPS
MVD
MPC
BBD
BF
RL
RS
RHG
TT
MEDIUM PRESSURE STEAM SUPPLY PIPING (16# - 60#)
MEDIUM PRESSURE CONDENSATE RETURN
PIPING
HIGH PRESSURE STEAM SUPPLY PIPING (61# - 125#)
HIGH PRESSURE CONDENSATE RETURN PIPING
PUMPED CONDENSATE PIPING
BOILER BLOWDOWN PIPING
REFRIGERANT SUCTION PIPING
BOILER FEED WATER PIPING
FLOAT AND THERMOSTATIC STEAM TRAP
REFRIGERANT LIQUID PIPING
REFRIGERANT HOT GAS PIPING
TCD
FD
FSD
SD
DAD
TEMPERATURE SENSOR
DUCT FIRE DAMPER
COMBINATION DUCT SMOKE & FIRE DAMPER
DUCT SMOKE DAMPER
DUCT SMOKE DETECTOR
DUCT ACCESS DOOR
ELECTRIC-PNEUMATIC CONTROL VALVE
TURNING VANES IN DUCT ELBOW
WALL MOUNTED THERMOSTAT
PNEUMATIC-ELECTRIC CONTROL SWITCH
LOUVER
HUMIDISTAT
DUCT RISE
UNIT MOUNTED THERMOSTAT
UNDERCUT DOOR
THERMOSTATIC STEAM TRAP
DUCT DROP
HWS
HWR
HTWS
HTWR
CWS
CWR
D
C
CR
HPS
HPC
PC
F&T
IBT
TCV
MAV
AAV
FS
EJ
BJ
RSV
DPS
(2 OR 3-WAY) TEMPERATURE CONTROL VALVE
INVERTED BUCKET STEAM TRAP
VENTURI METER
CALIBRATED BALANCING VALVE
REFRIGERANT SERVICE VALVE
AUTOMATIC AIR VENT
DIFFERENTIAL PRESSURE SWITCH
MANUAL AIR VENT
FLOW SWITCH
EXPANSION JOINT
CONDENSER WATER RETURN PIPING
BALL JOINT EXPANSION COMPENSATOR
LPS
LPC
MPS
MPC
BBD
BF
RL
RS
RHG
HWS
HWR
HTWS
HTWR
CWS
CWR
D
C
CR
HPS
HPC
PC
SUPPLY & RETURN BRANCH
PIPING TO TERMINAL UNIT
CWR,HWR
CWS,HWS
CWS,CWR/HWS,HWR
~
~~
ACOUSTICALLY LINED DUCTWORK
TEMPERATURE CONTROL OUTSIDE AIR DAMPER
TEMPERATURE CONTROL RETURN AIR DAMPER
TEMPERATURE CONTROL EXHAUST AIR DAMPER
STATIC PRESSURE IN INCHES WATER COLUMN
SUPPLY AIR DEVICE
RETURN AIR DEVICE
M
TS
F
~~
T
T
~~
H
U
L
R
D
SD
RG
SP IN WC
TCEAD
TCRAD
TCOAD
A.L.
48F12
TCD
BDD
EP
PE
DOUBLE/SINGLE LINE DUCT LEGEND
45° TEE (ROUND)
FLEX DUCT 90° RADIUS ELBOW
RIGID FLEX
45° TEE (RECTANGULAR) 90° TEE (ROUND) MANUAL VOLUME DAMPER 90° ELBOW
DUCT SPLIT
REDUCER 45° ELBOW
GRD
RUNOUT
90° TEE (RECTANGULAR)
SEE DUCT
TAKE-OFF DETAIL
CONICAL
TEE
VOLUME
DAMPER
PLUMBING LEGEND
SYMBOL DESCRIPTION ABBR. DESCRIPTION
ACID RESISTANT WASTE PIPING (ABOVE FLOOR IN BUILDING)
DOMESTIC COLD WATER PIPING
DOMESTIC HOT WATER PIPING
DOMESTIC HOT WATER CIRC. PIPING
SOFTENED DOMESTIC COLD WATER PIPING
SOFTENED DOMESSTIC HOT WATER PIPING
DOMESTIC HOT WATER PIPING @ TEMPERATURE
SHOWN
SURFACE CLEANOUT
FLOOR CLEANOUT
LINE CLEANOUT
FIXTURE OR DRAIN P-TRAP
AREA DRAIN
FLOOR SINK (SQUARE GRATE)
ROOF DRAIN OR OVERFLOW DRAIN
GAS PRESSURE REDUCING VALVE
ATMOSPHERIC VACUUM BREAKER
ACID RESISTANT VENT PIPING
WASTE PIPING (ABOVE FLOOR IN BUILDING)
WASTE PIPING (BELOW FLOOR IN BUILDING)
WALL CLEANOUT
CLEANOUT TEE
ABBR.
SYMBOL
VENT PIPING
FLOOR DRAIN (ROUND GRATE)
HW
HWC
C-SW
140° HW
V
H-SW
AV
W
W
AW
AW
CW
FS
RD / OD
VB
AV
W
W
AW
AW
GD
IW
S
ST
SSD
SD
SD
OD
OD
A
G G
ACID RESISTANT WASTE PIPING (BELOW FLOOR IN BUILDING)
IW
S
ST
SSD
SD
GD
SD
OD
OD
A COMPRESSED AIR
GREASE DRAIN (WASTE LINE TO GREASE INTERCEPTOR)
INDIRECT WASTE PIPING
SANITARY SEWER PIPING (OUTSIDE BUILDING)
STORM SEWER PIPING (BELOW GRADE OUTSIDE BUILDING)
SUB-SURFACE DRAIN PIPING
OVERFLOW DRAIN PIPING (ABOVE FLOOR IN
BUILDING)
STORM DRAIN PIPING (ABOVE FLOOR IN
BUILDING)
STORM DRAIN PIPING (BELOW FLOOR IN
BUILDING)
OVERFLOW DRAIN PIPING (BELOW FLOOR IN BUILDING)
FCO
WCO
COT
AD
LCO
FD
SCO
BFP
SA
GC
FC
WH
HB
YH
MH
CI
MANHOLE
DOUBLE CHECK BACKFLOW PREVENTER
SHOCK ARRESTOR W / ISOLATION VALVE
GAS SHUT-OFF VALVE
STOP AND DRAIN VALVE
HOSE BIBB
HWC BALANCING VALVE
CAST IRON
WALL HYDRANT
YARD HYDRANT
INVERT ELEVATION
CATCH BASIN
POLYVINYL CHLORIDE
VITRIFIED CLAY PIPE
VENT THRU ROOF
VCP
CB
VTR
IE
PVC
SW
SW
140°
FUEL OIL PIPING LEGEND
SYMBOL DESCRIPTION ABBR. DESCRIPTION
FUEL OIL SUPPLY PIPING
FUEL OIL RETURN PIPING
FUEL OIL FILL PIPING
FUEL OIL VENT PIPING
FUEL OIL OVERFLOW PIPING
DAY TANK PUMP OUT PIPING
PRESSURE RELIEF VALVE
VACUUM GAUGE W/ COCK VALVE
FUEL OIL HAND PUMP
GENERATOR FUEL OIL RETURN PIPING
PRESSURE GAUGE W/ COCK VALVE
FUSIBLE LINK VALVE
ABBR.
SYMBOL
GENERATOR FUEL OIL SUPPLY PIPING
FOR
FOF
FOV
DPO
GFOS
FOO
GFOR
FOS
FOR
FOF
FOV
DPO
GFOS
FOO
GFOR
FOS
V
F
P
FIRE PROTECTION LEGEND
SYMBOL DESCRIPTION ABBR. DESCRIPTION
FIRE SERVICE PIPING
FIRE SPRINKLER PIPING
WET STANDPIPE
O.S.&Y. VALVE W/ TAMPER SWITCH
FLOW SWITCH
POST INDICATOR VALVE
NEW SPRINKLER HEAD
EXISTING SPRINKLER HEAD
DRY SPRINKLER HEAD (SHAFT)
FIRE HOSE CABINET
FIRE VALVE CABINET
FIRE DEPARTMENT CONNECTION
RELOCATED SPRINKLER HEAD
SIDEWALL SPRINKLER HEAD
ABBR.
F
SYMBOL
FIRE HYDRANT
AUTOMATIC FIRE SPRINKLER
FS
WSP
PIV
FH
FS
FDC
F
FS
N20
FHC
FVC
A/S
D24
LABORATORY / MEDICAL SERVICES LEGEND
SYMBOL DESCRIPTION ABBR. DESCRIPTION
LABORATORY COMPRESSED AIR PIPING
OXYGEN PIPING
VACUUM PIPING
NITROUS OXIDE PIPING
NITROGEN PIPING
MEDICAL AIR PIPING
CARBON DIOXIDE
OXYGEN SERVICE OUTLET
VACUUM SERVICE INLET
NITROGEN SERVICE OUTLET
NATURAL GAS SERVICE OUTLET
LABORATORY/MEDICAL AIR SERVICE OUTLET
ZONE VALVE BOX
MEDICAL GAS OUTLET
AREA ALARM PANEL
MASTER ALARM PANEL
DEIONIZED WATER PIPING
HYDROGEN PIPING
LIQUID NITROGEN PIPING
NATURAL GAS PIPING
WASTE ANESTHESIA GAS DISPOSAL INLET
NITROUS OXIDE SERVICE OUTLET
ABBR.
02
SYMBOL
WASTE ANESTHESIA GAS DISPOSAL
CARBON DIOXIDE SERVICE OUTLET
VAC
N2O
N
CO2
WAGD
MA
DI
H
NL
LA
G
O2
ZVB
MGO
AAP
MAP
VAC
N
WAGD
DI
H
NL
LA
G
N20
MA
CO2
GENERAL LEGEND
SYMBOL DESCRIPTION ABBR. DESCRIPTION
NEW
SECTION DESIGNATION
SECTION DRAWN ON THIS SHEET
SECTION CUT ON THIS SHEET
RISER DIAGRAM NUMBER
SHEET RISER IS DRAWN ON
EQUIPMENT UNIT IDENTIFICATION
CAP END OF PIPE
PITCH DOWN IN DIRECTION OF ARROW
UNION OR FLANGE
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PRESSURE AND/OR TEMPERATURE RELIEF VALVE
PLUG VALVE
GATE VALVE
VERTICAL PIPE VALVE
DIFFUSER IDENTIFICATION
DIFFUSER NECK DIAMETER
DIFFUSER CFM
EXISTING
PIPE ANCHOR
PIPE ALIGNMENT GUIDE
ABBR. SYMBOL
EQUIPMENT UNIT NUMBER
PRESSURE REDUCING VALVE
(E)
(N)
(R)
PTRV
(F)
DIA
WAD
NIC
AFF
GC
MC
EC
RELOCATED
FUTURE
POINT OF CONNECTION, NEW TO EXISTING
DIRECTION OF FLOW IN PIPE
DUCTWORK, PIPING AND EQUIPMENT TO BE REMOVED
DIAMETER
ABOVE FINISHED FLOOR
WALL ACCESS DOOR
ELECTRICAL CONTRACTOR
NOT IN CONTRACT
GENERAL CONTRACTOR
PRV
GLV
BFV
BV
CV
P/T
STRAINER W/ BLOWDOWN
GLOBE VALVE
BUTTERFLY VALVE
BALL VALVE
CHECK VALVE
SOLENOID VALVE
PRESSURE / TEMPERATURE TAP
BUTTERFLY SOLENOID VALVE
FLEXIBLE PIPE CONNECTOR
HOSE END DRAIN VALVE
STRAINER
CEILING ACCESS PANEL
PRESSURE GAUGE
PUMP
THERMOMETER
SIGHT GLASS
C.A.P.
TB
MECHANICAL CONTRACTOR
#
UNIT
M-X
X
X.X X.X
X
GV
THRUST BLOCK
XX
P/T
DETAIL SHEETS PLAN SHEETS
XX
NATURAL GAS
PIPING
(Not all symbols listed below are used on these drawings) (Not all symbols listed below are used on these drawings)
(Not all symbols listed below are used on these drawings)
(Not all symbols listed below are used on these drawings)
(Not all symbols listed below are used on these drawings)
(Not all symbols listed below are used on these drawings)
NECK
CFM
X
EXHAUST DUCT UP / EXHAUST DUCT DOWN
WALL MOUNTED CARBON DIOXIDE SENSOR
C
EXHAUST AIR DEVICE
EG
KEYNOTE
SINGLE LINE
DOUBLE LINE
DOUBLE LINE
SINGLE LINE
SINGLE LINE
FLEX RIGID
SINGLE LINE DOUBLE LINE
DOUBLE LINE
(Not all symbols listed below are used on these drawings)
DP
T
IBT
F&T
TT RND
REC
45° TAKEOFF
SPIN IN
X
RETURN AIR DEVICE WITH SOUND BOOT
RG
~~
POINT OF DISCONNECTION (DEMO)
2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP,
P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
EAST
WING
ENABLING
6/30/2017
12:31:55 PM
15924.00
M-001.75
MECHANICAL LEGENDS &
NOTES
06/30/17
PERMIT
EAST
WING
ADDITION
180 S Frontage Rd W, Vail, CO 81657
1.
2.
3.
4.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
1.
2.
3.
4.
GENERAL NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
WORK INCLUDED IN THE CONTRACT IS DENOTED IN BOLD. EXISTING
CONDITIONS TO REMAIN ARE DENOTED LIGHTLY.
A DETAILED METHOD OF PROCEDURE IS REQUIRED WHEN A CONSTRUCTION
ACTIVITY AFFECTS THE SAFETY OF THE OCCUPANTS, OWNER'S EQUIPMENT
OR VALUABLE CONTENTS OR ANY SYSTEM WHICH SUPPORTS THESE
SYSTEMS; OR ESSENTIALLY AFFECTS THE BUILDING MANAGEMENT,
OPERATIONS OR SECURITY.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTING
CONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY
THE ENGINEER/ARCHITECT OF ANY DISCREPANCIES FOR RESOLUTION.
COORDINATE WORK WITH ALL TRADES.
CONTRACTOR IS RESPONSIBLE FOR SECURING AND WEATHERPROOFING ANY
ROOF OPENING NOT COMPLETED DURING WORKING HOURS.
COORDINATE ALL DUCTWORK AND PIPING WITH EQUIPMENT, STRUCTURE,
ETC.
CONTRACTOR SHALL BE RESPONSIBLE FOR DEACTIVATION OF ROOF-
MOUNTED EQUIPMENT AND ASSOCIATED INDOOR EQUIPMENT. ONLY ONE
UNIT SHALL BE TAKEN OUT OF SERVICE AT ANY TIME, WITH REMAINDER OF
UNITS LEFT OPERATIONAL.
CONTRACTOR SHALL NOT SHUT DOWN / TAKE OUT OF SERVICE ANY SYSTEMS
WITHOUT FIRST COORDINATING WITH OWNER AND PREPARING M.O.P.
DEMOLITION GENERAL NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
EXISTING ITEMS TO REMAIN ARE DENOTED LIGHTLY UNLESS OTHERWISE
NOTED. ALL ITEMS SHOWN HATCHED SHALL BE REMOVED UNLESS
OTHERWISE NOTED.
CONTRACTOR SHALL NOT SHUT-OFF OR PUT-OUT OF SERVICE ANY SYSTEMS
OR SERVICE WITHOUT FIRST COORDINATING WITH THE OWNER.
IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VISIT THE SITE AND
UNDERSTAND THE EXTENT OF THE REMODEL WORK REQUIRED PRIOR TO
BID. NO EXTRAS WILL BE ALLOWED FOR WORK REQUIRED TO ACHIEVE THE
END RESULT AS INDICATED BY THE CONTRACT DOCUMENT.
CONTRACTOR SHALL DETERMINE AND COORDINATE THE EXACT EXTENT OF
DEMOLITION TO FACILITATE ALL WORK INDICATED BY THE CONTRACT
DOCUMENT.
PRIOR TO COMMENCEMENT OF ANY DEMOLITION WORK, VERIFY EXISTING
CONDITIONS AND NOTIFY ENGINEER OF ANY DISCREPANCIES FOR
RESOLUTION.
ALL ITEMS IDENTIFIED TO BE REMOVED SHALL BE REMOVED IN THEIR
ENTIRETY UNLESS OTHERWISE NOTED. REMOVED ITEMS SHALL BE TURNED
OVER TO THE OWNER UNLESS OTHERWISE NOTED AND STORED IN THE AREA
DESIGNATED BY THE OWNER. REMOVE FROM SITE AND LEGALLY DISPOSE OF
ALL ITEMS THE OWNER CHOOSES NOT TO ACCEPT.
WHERE EXISTING PIPING, T.C. TUBING/WIRING ETC. ARE TO BE REMOVED
FROM WALLS WHICH ARE REMAINING, THE WALLS SHALL BE REPAIRED TO
MATCH ORIGINAL CONDITIONS.
WHERE EXISTING PIPING TO BE REMOVED PASSES THROUGH FLOORS, THEY
SHALL BE CUT BACK TO WITHIN CONCRETE AND FILLED WITH GROUT TO
ACHIEVE A SMOOTH AND EVEN FINISH WITH CONCRETE SURFACE.
HVAC PLAN NOTES:
1.
2.
3.
4.
DUCT SIZE OF BRANCH DUCT TO AIR DEVICE SHALL BE THE SAME SIZE AS
NECK SIZE OF AIR DEVICE UNLESS NOTED OTHERWISE.
UNLESS OTHERWISE NOTED, ALL SUPPLY AIR DUCTWORK SHALL BE
EXTERNALLY WRAPPED TO THICKNESS AS STATED IN SPECIFICATIONS.
RETURN AND EXHAUST DUCTWORK IS NEITHER LINED NOR WRAPPED.
PROVIDE ROOM AIR BALANCE TO ACHIEVE POSITIVE (+) OR NEGATIVE (-) AT
THE DIFFERENTIAL PRESSURE INDICATED ON THE DRAWINGS.
PROVIDE MANUAL VOLUME DAMPER FOR ALL AIR DEVICES. SPIN-IN DAMPERS
ARE REQUIRED FOR LOW PRESSURE SUPPLY TAKEOFFS. REFER TO DETAILS.
PLUMBING NOTES:
CONTRACTOR SHALL NOT SHUT-OFF/PUT OUT OF SERVICE ANY
SYSTEMS/SERVICES WITHOUT FIRST COORDINATING WITH OWNER.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTING
CONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY
THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES FOR RESOLUTIONS.
THIS CONTRACTOR SHALL COORDINATE LOCATIONS OF PIPING WITH OTHER
TRADES AND ADVISE ARCHITECT/ENGINEER OF ANY POSSIBLE CONFLICTS.
VERIFY EXACT LOCATIONS, ELEVATIONS AND DIMENSIONS OF STRUCTURAL
MEMBERS AND OPENINGS.
SEE SPECIFICATIONS FOR WATER HAMMER ARRESTOR SIZING. ALL FLUSH
VALVES AND SOLENOID OPERATED EQUIPMENT SHALL HAVE A WATER
HAMMER ARRESTOR.
SEE PLUMBING FIXTURE SCHEDULE FOR PIPE SIZING TO INDIVIDUAL
PLUMBING FIXTURES.
ALL EXISTING FIXTURES AND EQUIPMENT TO BE REMOVED SHALL HAVE ALL
ASSOCIATED PIPING CONTROLS, HANGERS, SUPPORTS AND ANY
MISCELLANEOUS ASSOCIATED SERVICE OR PART REMOVED COMPLETELY.
REFER TO ARCHITECTURAL DRAWINGS FOR ROOF PENETRATION DETAILS.
REFER TO ARCHITECTURAL DRAWINGS FOR FIXTURE ELEVATIONS AND
LOCATIONS.
SEE ARCHITECTURAL CONSTRUCTION DOCUMENTS FOR DIMENSIONED
LOCATION OF PLUMBING FIXTURES AND WALLS.
PROVIDE CLEANOUTS IN ACCESSIBLE LOCATIONS PER THE PROJECT
SPECIFICATIONS AND LOCAL PLUMBING CODES.
FIRE PROTECTION PLAN NOTES:
FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES
NECESSARY FOR THE INSTALLATION OF A COMPLETE AND PROPERLY
FUNCTIONING FIRE PROTECTION SYSTEM.
THE FIRE PROTECTION WORK INVOLVES ENGINEERING AND DESIGN BY
THE CONTRACTOR TO DETERMINE THE EXTENT OF NEW WORK AND
THE MODIFICATION AND EXTENSION OF EXISTING SYSTEMS TO
PROVIDE FULL COVERAGE TO THE PROJECT AREA SHOWN ON THESE
AND THE ARCHITECTURAL PLANS.
THE INFORMATION PRESENTED ON THESE DRAWINGS IS
DIAGRAMMATIC. IT DOES NOT NECESSARILY REPRESENT ALL ELBOWS,
OFFSETS, HANGERS, ETC., REQUIRED FOR A COMPLETE WORKING
SYSTEM.
ALL FIRE PROTECTION SYSTEMS INSTALLED SHALL BE IN ACCORDANCE
WITH NFPA-13, 14, 20, ETC. AND LOCAL BUILDING CODES AND
ORDINANCES.
FIRE PROTECTION CONTRACTOR SHALL COORDINATE THE LOCATION
OF ALL NEW FIRE PROTECTION EQUIPMENT AND PIPING WITH ALL
OTHER TRADES PRIOR TO SUBMITTAL OF SHOP DRAWINGS AND
SYSTEM INSTALLATION, SO AS NOT TO INTERFERE WITH THE ROUTING
OF NEW DUCTWORK, PLUMBING PIPING, ETC.
PROVIDE ALL FITTINGS, RISER NIPPLES, ARM-OVERS, HANGERS, ETC.
TO MAINTAIN CONFORMANCE WITH APPLICABLE STANDARDS AND TO
POSITION THE SPRINKLERS IN THE PROPER LOCATIONS.
SEAL ALL PIPE PENETRATIONS THROUGH FIRE RATED WALLS AND
CEILINGS WITH FIRE STOPPING MATERIALS AS REQUIRED.
FOR REMODEL AREAS NEW SPRINKLERS SHALL MATCH EXISTING
SPRINKLERS.
PROVIDE WORKING DRAWINGS AND HYDRAULICALLY CALCULATE THIS
FIRE SPRINKLER SYSTEM PER NFPA-13 WHERE REQUIRED BY THE
LOCAL AUTHORITY HAVING JURISDICTION.
PROVIDE FIELD COORDINATION OF PIPING AND SPRINKLER
INSTALLATIONS WITH DUCTWORK, LIGHTS, SMOKE DETECTORS,
DIFFUSERS, ETC.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
10/12/17