HomeMy WebLinkAboutB17-0340_M-107.75_1507837285.pdfPROVIDE MIN. 25 FT SEPERATION FROM OUTSIDE
AIR TO ANY VENT OR EXHAUST
6" G
6" G
(E) VAC PUMP
EXHAUST
(E) NG TO L2 STEAM
BOILER ROOM
(E) NG TO L2
HYDRONIC BOILERS
(N) MULTIZONE AHU
RELIEF
W/GOOSENECK
(N) MULTIZONE AHU
O.A. INTAKE
(E) CONDENSING UNITS
(E) STEAM AND CONDENSATE
RACKED ON WALL TO WEST
WING
(E) CONDENSING UNITS
RELOCATE (E) PLUMBING VENT WEST
TO CLEAR OA CIRCLES
(E) TRANE EXHAUST FAN AND
ENERGY RECOVERY COIL
(E) 8" DOWN TO EF-2-1
(E) 10" DOWN TO HOOD
(E) DX COIL AC-1
(E) AHU FAN AND FURNACE
(E) SA DOWN
OUTSIDE AIR
(E) EF-2-3
(E) FC-3 AND HEATING COIL
(E) 22/22 RA DOWN
(E) DX COIL
(E) 24/22 SA DOWN
22"x24"
(E) 10/10 EXH DOWN
(E) 14/14 EXH DOWN
(E) EXHAUST FAN
(E) 14/14 EXH UP TO
GOOSENECK TERMINATION
(E) RETURN DOWN
(E) 14/14 EXH DOWN
(E) AHU-1 WITH ENERGY
RECOVERY AND DX COILS
14"x14"
22"x16"
22"x16"
(E) 18/18 SA DOWN
(E) FC-2
(E) 20/18 RA DOWN
(E) 20/18 SA DOWN
(E) DX COIL
20"x20" 24"x24"
(E) CONDENSING
UNIT
H1 H1
4
ACC
5
ACC
3
M-107.75
(N) FC-3 AHU O.A.
INTAKE
(N) FC-2 AHU O.A.
INTAKE
(N) LAB AHU O.A.
INTAKE
1
RH
2
RH
4
RH
3
RH
6" G
NATURAL GAS DROP TO NEW METER LOCATION. COORDINATE NEW
METER LOCATION AND REQUIREMENTS WITH UTILITY COMPANY.
2
M-107.75
SUPPORT FROM FACE OF BUILDING
6" G
6" G
6" G
37"x24"
96"x24"
CRAC
CU
OFFSET (E) 6"NG
AROUND ROOF HOOD
H13
H24
H24
H25
H24
H23 21"x37"
6" G
NATURAL GAS DROP TO NEW METER
LOCATION. COORDINATE NEW METER
LOCATION AND REQUIREMENTS WITH
UTILITY COMPANY.
PROVIDE PIPE STAND
SUPPORTS AND BRACING
FOR NATURAL GAS PIPING
ABOVE EXISTING
CONNECTOR ROOF.
EXISTING AMBULANCE
GARAGE BUILDING
PROVIDE UNISTRUT AND PIPE CLAMP
SUPPORTS FOR MOUNTING TO FACE
OF BUILDING EXTERIOR.
NATURAL GAS PIPING INDICATED FOR
THIS ROUTING IS TEMPORARY AND WILL
BE REMOVED AT COMPLETION OF EAST
WING.
37"x21"
1
RH
2
RH
3
RH
4
RH
TURN RELIEF DOWN
AND TERMINATE WITH
SCREEN
37"x21"
6" G
24"x96"
22"x22"
EXISTING AHU
2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP,
P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
EAST
WING
ENABLING
6/30/2017
12:32:57 PM
15924.00
M-107.75
ROOF MECHANICAL PLAN -
ENABLING
06/30/17
PERMIT EAST
WING
ADDITION
180 S Frontage Rd W, Vail, CO 81657
SCALE: 1/8" = 1'-0"
OVERALL MECHANICAL PLAN - ROOF - EAST ENABLING
1/8" = 1'-0"
2 NEW GAS LINE ACROSS AMBI BARN SECTION
1/8" = 1'-0"
3 ROOF SECTION SHOWING OUTSIDE AIR HOODS
KEYNOTES
H1 RELOCATE EXISTING DX SPLIT SYSTEM CONDENSER. INCLUDE
REPLACEMENT OF LINESETS ALL THE WAY BACK TO THE
EVAPORATOR IN STEADMAN IT CENTER.
H13 SPLIT 96/24 OUTSIDE AIR DUCT INTO (4) 20/24 DUCTS TO TRANSITION
THROUGH EXISTING RAFTERS. RECOMBINE AT ENTRY TO RH-1.
H23 ABANDONED BOILER/WATER HEATER FLUE
H24 OFFSET EXISTING WATER HEATER FLUE / BOILER ROOM EXHAUST IF
REQUIRED TO MAINTAIN CODE REQUIRED 25'-0" CLEARANCE FROM
OUTSIDE AIR INTAKE.
H25 EXISTING BOILER ROOM INTAKE HOOD TO REMAIN.
10/12/17