HomeMy WebLinkAboutB17-0340_S-002-2_1507837284.pdf2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP,
P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
EAST
WING
ENABLING
6/30/2017
2:53:47 PM
16.0188.S.01
S-002-2
QUALITY ASSURANCE
06/30/17
PERMIT VAIL
VALLEY
MEDICAL
CENTER
180 S. Frontage
Road
West,
Vail, CO 81657
- OBSERVE PREPARATION
OF GROUT SPECIMENS,
MORTAR SPECIMENS,
AND/OR PRISMS
P TMS 602, Art. 1.4B ASTM C1019, ASTM C1314
- PREPARATION,
CONSTRUCTION, AND
PROTECTION OF
MASONRY DURING HOT...
P
TMS 602, Art.
1.8C AND 1.8D
REQUIRED WHEN AIR TEMPERATURE IS BELOW
40°F OR ABOVE 90°F
- WELDING OF
REINFORCEMENT C
PER
STRUCTURAL...
-
- TYPE, SIZE, AND
LOCATION OF ANCHORS,
INCLUDING OTHER
DETAILS OF ANCHORAGE
OF MASONRY TO
STRUCTURAL MEMBERS,
FRAMES, OR OTHER...
P - -
- SIZE AND LOCATION OF
STRUCTURAL ELEMENTS P TMS 602, Art. 3.3F -
VERIFY DURING CONSTRUCTION
- CONSTRUCTION OF
MORTAR JOINTS P TMS 602, Art. 3.3B -
- MIX DESIGN FOR
OFF-SITE PREPARED... EACH TRUCK - -
- PROPORTIONS OF SITE
-PREPARED GROUT P TMS 602, Art. 2.6B ASTM C476
- PLACEMENT OF
REINFORCEMENT AND
CONNECTORS (REBAR,
JOINT REINFORCEMENT,
AND TIES)
P
TMS 602, Art. 3.2E
AND 3.34.4
VERIFY TYPE, SIZE, QUANTITY, LOCATION,
SPACING, COVER, SPLICE LENTGH, SPLICE
LOCATION, SURFACE CONDITION, SUPPORT,
AND SECURING. SEE STRUCTURAL CONCRETE
TABLE FOR FIELD BENDING, COATED
REINFORCEMENT, AND MECHANICAL...
- GRADE, TYPE, SIZE OF
REINFORCEMENT AND
ANCHOR BOLTS P
TMS 602 Art. 2.4
AND 3.4
VERIFY TYPE, FINISH, DIAMETER, LENGTH,
QUANTITY, EMBEDMENT LENGTH, SPACING AND
EDGE DISTANCE. VERIFY GROUT SPACE
AROUND ANCHORS IN FACE SHELL
- GROUT SPACE
P
TMS 602, Art.
3.2D AND 3.2F
VERIFY GROUT SPACE IS FREE OF MORTAR
DROPPINGS AND DEBRIS, AND CLEANOUTS
PROVIDED AS REQUIRED
PRIOR TO GROUTING, VERFIY THAT THE FOLLOWING ARE IN COMPLIANCE
- LOCATION OF
REINFORCEMENT AND
CONNECTORS
P TMS 602, Art.3.4 -
- CONSTRUCTION OF
MORTAR JOINTS P TMS 602, Art. 3.3B -
- PROPORTIONS OF
SITE-PREPARED MORTAR P
TMS
602, Art. 2.1
AND 2.6A
-
AS MASONRY CONSTRUCTION BEGINS, VERIFY THAT THE FOLLOWING ARE IN COMPLIANCE
- VERIFY COMPLIANCE
WITH THE APPROVED
SUBMITTALS
P TMS 602, Art 1.5 -
ITEM FREQUENCY STANDARD CRITERIA
STRUCTURAL MASONRY SPECIAL INSPECTIONS (LEVEL B)
- WELDING
REINFORCEMENT,
BOLTS, AND...
- - PER STRUCTURAL STEEL TESTING
- SELF-CONSOLIDATING
GROUT SLUMP FLOW EACH TRUCK ASTM C1611
VERIFY SLUMP FLOW AND VISUAL STABILTY
INDEX
ITEM FREQUENCY STANDARD CRITERIA
STRUCTURAL MASONRY TESTING (LEVEL B)
- AFTER INSTALLATION
100% VISUAL -
VERIFY MATERIALS HAVE BEEN DRAWN
TOGETHER AND FASTENER HEAD STAND-OFF IS
ACCEPTABLE (FULLY DRIVEN)
- DURING INSTALLATION P ICC-ES REPORT -
- PRIOR TO INSTALLATION FIRST OF EACH
FASTENER TYPE
AND BASE
MATERIAL
ICC-ES
REPORT
VERIFY TYPE, DIAMETER,
LENGTH, FINISH, AND
BASE MATERIAL
POWER-ACTUATED FASTENERS
- COLD FORMED STEEL
ASSEMBLIES P ICC-ES REPORT
VERIFY TYPE, NUMBER OF FASTENERS, AND
INSTALLATION IN CONFORMANCE WITH ICC-ES
REPORT
- DAMAGED SCREWS
P -
NO POPPED SCREW HEADS OR STRIPPED
SCREWS ARE PERMITTED. ALL DAMAGED
SCREWS SHALL BE REPLACED
- SCREW PENETRATION
P -
VERIFY MATERIALS HAVE BEEN DRAWN
TOGETHER
AND SCREWS ARE FULLY DRIVEN
WITH A MINIMUM PENETRATION OF 3 THREADS
THROUGH THE LAST MATERIAL JOINED
- FASTENER
P -VERIFY TYPE, DIAMETER, LENGTH, SPACING
AND EDGE DISTANCES
SCREWED ATTACHMENTS
- CORROSION RESISTANCE
TREATMENT P -
WELDED AREAS ARE TO BE TREATED WITH
APPROVED TREATMENT TO MATCH CORROSION
RESISTANCE OF AFFECTED AREA
- AFTER WELDING 100% VISUAL AWS D1.3 -
- DURING WELDING P AWS D1.3 -
- PRIOR TO WELDING
- AWS D1.1/D1.3
VERIFY FILLER MATERIALS, WELDING
PROCEDURES, WELDER QUALIFICATIONS, AND
MANUFACTURER'S CERTIFICATE OF...
WELDED ATTACHMENTS
- PUNCHOUTS
P -
VERIFY SPACING REQUIREMENTS FROM
BEARINGS AND CONNECTIONS AND
REINFORCING IS USED WHERE REQUIRED
- SPLICING
P -
NO SPLICING OF STRUCTURAL MEMBERS
PERMITTED UNLESS SPECIFIED ON THE
CONSTRUCTION DOCUMENTS
- FIELD CUTS AND
NOTCHES P -NO CUTS OR NOTCHES THROUGH SECTION
FLANGES PERMITTED
- BRIDGING AND BLOCKING P - VERIFY TYPE, LOCATION, AND ATTACHMENT
- MEMBERS AND
CONNECTIONS P - VERIFY TYPE, SIZE, LOCATION, SPACING
FRAMING
ITEM FREQUENCY STANDARD CRITERIA
STRUCTURAL COLD FORMED STEEL SPECIAL INSPECTIONS(2)
OBSERVE - OBSERVE THESE ITEMS ON A RANDOM BASIS
PERFORM - THESE INSPECTIONS SHALL BE PERFORMED FOR EACH WELDED CONNECTION, EACH BOLTED
CONNECTION, AND EACH ITEM, PRIOR TO ACCEPTANCE
- DOCUMENT ACCEPTANCE OR
REJECTION OF BOLTED
CONNECTIONS
PERFORM
DOCUMENT
ACCEPTANCE
OR REJECTION
OF WELDED
MEMBER OR
JOINT
-
AFTER BOLTING
- PRETENSIONED AND
SLIP-CRITICAL JOINTS USING
CALIBRATED WRENCH OR
TURN-OF-NUT METHOD
WITHOUT MATCHMARKING
PERFORM
AISC 360,
CHAPTER N AND
RCSC
SPECIFICATION
JOINT BROUGHT IN SNUG-TIGHT
CONDITION PRIOR TO PRETENSIONING,
FASTENER PREVENTED FROM
ROTATING, PRETENSIONED IN PROPER
SEQUENCE. INSPECTOR SHALL BE
RESENT DURING INSTALLATION OF...
- PRETENSIONED AND
SLIP-CRITICAL JOINTS
OBSERVE
AISC 360,
CHAPTER N AND
RCSC
SPECIFICATION
JOINT BROUGHT IN SNUG-TIGHT
CONDITION PRIOR TO PRETENSIONING,
FASTENER PREVENTED FROM
ROTATING, PRETENSIONED IN PROPER...
- FASTENERS PLACED IN ALL
HOLES AND POSITIONED AS
REQUIRED
OBSERVE
AISC 360,
CHAPTER N
-
DURING BOLTING
- PROPER STORAGE FOR
FASTENER COMPONENTS OBSERVE
AISC
360,
CHAPTER N
-
- PRE-INSTALLATION
VERIFICATION TESTING OBSERVE
AISC 360,
CHAPTER
N
NOT APPLICABLE FOR SNUG TIGHT
JOINTS
- CONNECTING ELEMENTS MEET
REQUIREMENTS, INCLUDING
HOLE REPARATION AND FAYING
SURFACE
OBSERVE
AISC
360,
CHAPTER N
-
- PROPER FASTENERS AND
BOLTING PROCEDURE
SELECTED FOR JOINT DETAIL
OBSERVE
AISC 360,
CHAPTER N
-
- FASTENERS MARKS IN
ACCORDANCE WITH ASTM
REQUIREMENTS
OBSERVE
AISC 360,
CHAPTER N
-
- REVIEW MANUFACTURER
CERTIFICATIONS FOR
FASTENER MATERIALS
PERFORM
AISC 360,
CHAPTER N
-
PRIOR TO BOLTING
- DOCUMENT ACCEPTANCE OR
REJECTION OF WELDED
MEMBER OR JOINT
PERFORM
AISC 360,
CHAPTER N
-
- PLACEMENT AND INSTALLATION
OF HEADED STUD ANCHORS PERFORM
AISC 360,
CHAPTER N
-
- REPAIR ACTIVITIES
PERFORM
AISC 360,
CHAPTER N
-
- K-AREA
PERFORM
AISC 360,
CHAPTER N
-
- ARC STRIKES
PERFORM
AISC 360,
CHAPTER N
-
- WELDS MEET VISUAL
ACCEPTANCE CRITERIA PERFORM
AISC 360,
CHAPTER N,
AWS D1.1
WHERE
INSPECTOR OBSERVES
QUESTIONABLE WELDS,
NON-DESTRUCTIVE TESTING SHALL BE
PERFORMED
- SIZE, LENGTH, AND LOCATION
OF WELDS PERFORM
AISC 360,
CHAPTER N
-
- WELDS CLEANED
OBSERVE
AISC 360,
CHAPTER N
-
AFTER WELDING
- WELDING TECHNIQUES -
MULTI-PASS WELDS OBSERVE
AISC 360,
CHAPTER N
-
- WELDING TECHNIQUES - SINGLE
PASS WELDS OBSERVE
AISC 360,
CHAPTER N
-
- ENVIRONMENTAL CONDITIONS,
AND WPS FOLLOWED OBSERVE
AISC 360,
CHAPTER N
-
- NO WELDING OVER CRACKED
TACK WELDS OBSERVE
AISC 360,
CHAPTER N
-
- CONTROL AND HANDLING OF
WELDING CONSUMABLES OBSERVE
AISC
360,
CHAPTER N
-
- USE OF QUALIFIED WELDERS
OBSERVE
AISC 360,
CHAPTER N
-
DURING WELDING
- WELDER IDENTIFICATION
SYSTEM OBSERVE
AISC 360,
CHAPTER N
-
- MATERIAL IDENTIFICATION
OBSERVE
AISC 360,
CHAPTER N
-
- FIT UP OF WELDS, INCLUDING
JOINT GEOMETRY, AND
CONFIGURATIONS AND FINISH
OF ACCESS HOLES
OBSERVE
AISC 360,
CHAPTER N
-
- REVIEW MANUFACTURER
CERTIFICATIONS FOR WELDING
CONSUMABLES AND WELDING
PROCEDURE SPECIFICATIONS
PERFORM
AISC 360,
CHAPTER N
-
PRIOR TO WELDING
- PRIOR TO FABRICATION OR
ERECTION
PERFORM
AISC 360,
CHAPTER
N
REVIEW MATERIAL TEST REPORTS AND
CERTIFICATIONS FOR STRUCTURAL
STEEL, FASTENERS, ANCHOR RODS,
HEADED STUD ANCHORS
ITEM
INSPECTION
TASK
STANDARD CRITERIA/REMARKS
STRUCTURAL STEEL INSPECTIONS
UT - ULTRASONIC TESTING
MT - MAGNETIC PARTICLE TESTING
PT - PENETRANT TESTING
SFRS - SEISMIC FORCE RESISTING SYSTEM...
EMBEDDED PLATE
ASSEMBLIES WITH
PLATES EXCEEDING 3/4
INCH
100% UT
NOT REQUIRED FOR STEEL PRODUCED IN USA.
TEST ALONG CENTERLINE OF PLATE WIDTH
AFTER WELDING
- PLATES EXCEEDING 3/4
INCH, LOADED IN
TENSION IN THE
THROUGH-THICKNESS
DIRECTION IN TEE AND
CORNER JOINTS
100% ASTM A435
NOT REQUIRED FOR STEEL PRODUCED IN USA.
ANY DISCONTINUITY CAUSING A TOTAL LOSS OF
BACK REFLECTION THAT CANNOT BE
CONTAINED WITHIN A CIRCLE 3 INCHES IN
DIAMETER SHALL BE REJECTED. REQUIRED
WHERE NOTED AS 'TTT' IN DRAWINGS
- SHAPES EXCEEDING 1 1/2
INCHES THICK, LOADED
IN TENSION IN THE
THROUGH- THICKNESS
100%
ASTM A898
(LEVEL 1
CRITERIA)
NOT REQUIRED FOR STEEL PRODUCED IN USA.
CRITERIA TO BE MET
6 INCHES ABOVE AND
BELOW EACH WELD. REQUIRED WHERE NOTED
AS 'TTT' IN DRAWINGS
FRAMING
- SHEAR CONNECTOR,
HEADED ANCHOR STUDS,
DEFORMED ANCHOR
STUDS, THREADED...
2 BEND TESTS
AT START OF
EACH SHIFT, 1%
BEND TEST,...
AWS D1.1
SECTION 7
BEND TEST: PER AWS D1.1 BENT STUD (TORQUE
TEST FOR THREADED STUDS) ACCEPTANCE
CRITERIA. RING TEST: STRIKE WITH HAMMER.
IF THE STUD RINGS, STUD IS ACCEPTABLE. IF...
- THERMALLY CUT
SURFACES OF BEAM
COPES AND ACCESS
HOLES WHEN MATERIAL
THICKNESS EXCEEDS 2
INCHES
100% MT OR PT -
- COMPLETE JOINT
PENETRATION GROOVE
WELDS FOR MATERIAL
5/16" THICK AND...
100% UT
FREQUENCY MAY BE REDUCED IN
ACCORDANCE WITH AISC 360, CHAPTER N
- COMPLETE JOINT
PENETRATION GROOVE
WELDS FOR MATERIAL
5/16" THICK AND...
10% UT
FREQUENCY SHALL BE INCREASED SHOULD
THE REJECT RATE EXCEED 5% FOR AN
INDIVIDUAL WELDER, IN ACCORDANCE WITH
AISC 360, CHAPTER N. [DESIGNER NOTE - FOR...
WELDING
ITEM FREQUENCY STANDARD CRITERIA/REMARKS
STRUCTURAL STEEL TESTING
6/30/17
10/12/17