HomeMy WebLinkAboutB17-0340_S-204-D_1507837293.pdfA
A
A
A
1'-7" 10" 1'-7" 1'-0"
1/2" BASE PLATE
1" NON-SHRINK GROUT
(4) 3/4" A.B. (HD6)
#4 @ 12" OC VERT EF
#4 @ 12" HORIZ EF
(5) #5xCONT
3" CLR
#5 @ 12" OC
TYP
3/4" CLR
1'-0"
T/WALL
SEE PLAN
-
2" CLR
3 1/2"
3 1/2"6"
6" 1 1/2"
1 1/2"3 1/2"3 1/2"
9" 4" 1 1/2" TYP
1 1/2" 3" @ DOOR & CORNER
S-200-1
3
TYPICAL
CONCRETE CURB
SEE ARCH
10" 4'-2"
SLAB ON GRADE
MASONRY DOWELS
#5 @ 12" OC VERT EF
#5 @ 12" HORIZ EF
#5x @ 12" OC
2" CLR
B LTS #5 @ 12" OC 4'-0" MIN
'MLS'
PERIMETER
DRAIN PER CIVIL
FREE DRAINING
BACKFILL PER
GEOTECH
S-200-1
3
1'-0"
-
NOTES:
1. FOR ADDITIONAL INFORMATION SEE 2/S-204-D
DOWELS TO MATCH
WALL REINF
'MLS'
WALL REINF
4'-0" MIN
SEE PLAN
10"
CONCRETE CURB
SEE ARCH
10" CMU BOND BEAM
W/ (2) #4 @ 4'-0 VERT
10" CMU BOND BEAM
W/ (2) #5
3/8" MORTAR JOINT
ALL SIDES
REMOVE MASONRY FACE SHELL
AND WEBS AT EMBED PL
SET OUTSIDE FACE OF EMBED
FLUSH W/ FACE OF MASONRY
PL 1/4x3x9 EA SIDE
EMBED PL 1/2x8x1'-4 W/
(4) 3/4"Ø x 5" HAS @ 4" GA
HSS BEAM W/
1/4" CAP PL TYP
PL 1/4x3x4 EA SIDE
EMBED PL 1/2x8x8 W/
(4) 3/4"Ø x 5" HAS @ 4" GA
2" 4" 2" 4" 8" 4"
3/16
TYP
3/16
3 SIDES TYP
4"
(2)- #5 EA FACE FULLY GROUTED
#4 @ EMBED PL
AT COURSE BELOW
PL
'MLS' HSS COLUMN W/
1/4" CAP PL
SEAL WELD
SEAL WELD
1/4
3/16
SEAL WELD
1/4
HSS GIRT W/ 1/4"
CAP PL SEAL WELD
1/4
HSS COLUMN W/
1/4" CAP PL
SEAL WELD
3/16
REMOVE MASONRY FACE SHELL
AND WEBS AT EMBED PL
SET OUTSIDE FACE OF EMBED
FLUSH W/ FACE OF MASONRY
EMBED PL 1/2x8x1'-2" W/
(4) 3/4"Ø x 5" HAS @ 4" GA
PL 1/2x12
SEE ARCH FOR SPACING
1/4" CAP PL
SEAL WELD TYP
3/16
3/16
3/16 TYP
GROUT SOLID 24" BELOW
& 12" EA SIDE OF EMBED PL
BOND BEAM
(2) #5
3/4" = 1'-0" 2 FOUNDATION @ COLUMN
3/4" = 1'-0" 4 NORTH FOUNDATION WALL
3/4" = 1'-0" 3 TYP FOUNDATION WALL
2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP,
P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
EAST
WING
ENABLING
6/30/2017
2:54:03 PM
16.0188.S.01
S-204-D
O2 ENCLOSURE DETAILS
06/30/17
PERMIT VAIL
VALLEY
MEDICAL
CENTER
180 S. Frontage
Road
West,
Vail, CO 81657
3/4" = 1'-0" 5 TOP OF MASONRY WALL
3/4" = 1'-0" 6 EMBED CONNECTION TO CMU WALL
3/4" = 1'-0" 7 CORNER COLUMN CONNECTION
1" = 1'-0" 8 COLUMN CONNECTION
3/4" = 1'-0" 9 TRELLIS FRAMING
6/30/17
10/12/17