HomeMy WebLinkAbout395 MILL CREEK TAB.pdf TEST, ADJUST AND BALANCE REPORT
PROJECT
395 MILL CREEK
#1373
PREPARED FOR
SKYLINE MECHANICAL
REPORT ISSUE DATE
10/11/2018
PREPARED BY
HVAC TAB llc
P.O. BOX 1926
VAIL, CO 81658
PHONE: 970-376-5198
E-MAIL: mrichardson@hvactab.co
HVAC TAB llc
DATE: 10/10/2018
INSTRUMENT
CALIBRATION REPORT
PROJECT : 395 MILL CREEK PROJECT ALTITUDE: “HG
INSTRUMENT/ SERIAL # APPLICATION DATE OF USE CALIBRATION DATE CALIBRATION DUE DATE
SHORTRIDGE ADM-870C / #M09211 AIR FLOW READINGS 10/10/2018 6/20/2018 6/20/2019
ANEMOMETER #T57251515001 AIR FLOW READINGS 10/10/2018 6/13/2018 6/13/2019
SHORTRIDGE FLOW HOOD AIF FLOW READINGS NOT USED * *
TH-720 HYGROMETER/ #TH7200950003 AIR TEMP / HUMIDITY NOT USED 6/9/2018 6/9/2019
PITOT TUBE 18” PRES. READINGS 10/10/2018 N/A N/A
PITOT TUBE 24” PRES. READINGS NOT USED N/A N/A
PITOT TUBE 36” PRES. READINGS NOT USED N/A N/A
PITOT TUBE 48” PRES. READINGS NOT USED NA NA
SHIMPO TACHOMETER / #C105B0010 RPM READINGS NOT USED 6/9/2018 6/9/2019
FLUKE 375 / #21290229 VOLT / AMP NOT USED 06/14/2018 6/14/2019
SHORTRIDGE HDM-250/ #W11037 WATER PRES. READINGS NOT USED 6/20/2018 6/20/2019
ASCROFT / 0-100 PSI / #DO68332-06 WATER PRES. READINGS NOT USED * *
FLUKE 52 II THERMOMETER / 99780167 TEMP. READINGS NOT USED 6/21/2018 6/21/2019
REFRACTOMETER RHA-100 / #RHA-
100
GLYCOL % READINGS NOT USED N/A N/A
* CHECKED TO CALIBRATED METER
REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR TEMPERATURE AND ALTITUDE. PAGE:
395 MILL CREEK 10/10/2018
MUA
MANUFACTURER ELECTRO MAKEUP AIR
MODEL EM-MA20-240-1-14
SERIAL #2690,
CFM 613 CFM
KEF
MANUFACTURER JENN AIR
MODEL LIB0057678/W105264131B
SERIAL #NF
CFM 605 CFM