HomeMy WebLinkAboutB18-0048_approved documents_1522697777.pdf75 South Frontage Road
West,
Vail, CO 81657
Office: 970.479.2139
Inspection Line: 970.479.2149
Construction
B18-0048
Issued: 04/02/2018
TOWN OF VAIL
Property Information
Address: 660 LIONSHEAD PL (210107203999) ( 210107203999 )
Unit #:
Parcel Number: 210107203999
Legal Description:
Contacts
Contact Type: Applicant
Full Name: matt anderson
Address: 51 Eagle Road 51 Eagle Road Avon, CO 81620 Phone: 9704713459
Contact Type: Property Owner
Full Name: Common Area
Address: Phone: None
Contact Type: Site Superintendent
Full Name: Jeff Rice
Address: CO Phone: 970-309-5974
Contractor
Contractor Type: General
Company: R.A. Nelson & Associates Inc
State License #:Phone: 970-949-5152
Project Information
Project Name: Lion Square Lodge South 2018
Project Description:
THE PROJECT INCLUDES INTERIOR UPGRADES TO EXISTING CONFERENCE ROOMS AT LION
SQUARE LODGE INCLUDING NEW CEILING FINISHES, LIGHTING, INTERIOR TRIM, AND ROOM
DIVIDERS. AREA OF EXISTING COLUMBINE & GORE CREEK ROOMS = 2,350 SF (NO CHANGE TO
EXISTING SF) AREA OF EXISTING WILDWOOD CONFERENCE ROOM AND PREFUNCTION AREA =
2,883 SF (NO CHANGE TO EXISTING SF).
Fees Paid
Account #: 001-0000.31111.00 - Building Permit Fee Fee Amount:$3,514.00
Account #: 001-0000.31123.00 - Building Plan Review Fee Fee Amount:$2,284.10
Account #: 110-0000.31060.00 - Construction Use Tax Fee Fee Amount:$10,978.26
Account #: 001-0000.31111.00 - Mechanical Permit Fee Fee Amount:$1,460.00
Account #: 001-0000.31123.00 - Mechanical Plan Review Fee Fee Amount:$365.00
Account #: 001-0000.31128.00 - Will Call Fee (Building Scope)Fee Amount:$5.00
Account #: 001-0000.31128.00 - Will Call Fee (Mechanical Scope)Fee Amount:$5.00
Total Paid:$18,611.36
Conditions
CONDITIONS UNDER WHICH PERMITS BECOME VOID:
If construction is not begun within 6 months from the date permit was issued.
If more than 5 months elapses between inspections.
If incorrect information is given on the application at the time the permit was issued.
Christopher Jarecki - Town of Vail Building Official
NOTICE: By issuance of this Permit the applicant agrees to comply with all Titles of the Town of Vail Code and all applicable State and Federal
law. Failure to do so will void this Permit and the applicant shall forfeit all applicable fees.
PERMIT FEE RECEIPT
Case # B18-0048
Date Printed: 03/07/2018
TOWN OF VAIL - FEES RECEIPT
Permit Summary
Case Number: B18-0048 Status: Created
Permit Number: Date Started: 02/27/2018
Permit Type: Construction Subcases Multi-Family
Lot Number: 1
Property: 660 LIONSHEAD PL (210107203999) (210107203999)
Contacts
Contact Type: Applicant
Company Name: RA Nelson
Full Name: matt anderson
Address: 51 Eagle Road 51 Eagle Road Avon, CO 81620
Email: manderson@ranelson.com
Contact Type: Property Owner
Full Name: Common Area
Address:
Permit Fees
Fee Information Account Amount
Plan Review 001-0000.31123.00 $2,649.10
Payment Information Date Paid Payment Type Amount
Plan Review 03/07/2018 Check $2,649.10
Paid By: Lion Square Lodge - Notes: ck # 9773
FEE TOTAL $2,649.10
AMOUNT PAID $2,649.10
BALANCE DUE $15,962.26
03/07/2018 - 11:48:53 AM - Generated by: cgodfrey75 South Frontage Road West, Vail, Colorado 81657
1 / 1
PERMIT FEE RECEIPT
Case # B18-0048
Date Printed: 04/02/2018
TOWN OF VAIL - FEES RECEIPT
Permit Summary
Case Number: B18-0048 Status: Approved
Permit Number: Date Started: 02/27/2018
Permit Type: Construction Subcases Multi-Family
Lot Number: 1
Property: 660 LIONSHEAD PL (210107203999) (210107203999)
Contacts
Contact Type: Applicant
Company Name: RA Nelson
Full Name: matt anderson
Address: 51 Eagle Road 51 Eagle Road Avon, CO 81620
Email: manderson@ranelson.com
Contact Type: Property Owner
Full Name: Common Area
Address:
Contact Type: Site Superintendent
Company Name: Ra Nelson
Full Name: Jeff Rice
Address: CO
Email: jrice@ranelson.com
Permit Fees
Fee Information Account Amount
Permit Fee 001-0000.31111.00 $4,974.00
Construction Tax 110-0000.31060.00 $10,978.26
Will Call Fee 001-0000.31128.00 $10.00
Payment Information Date Paid Payment Type Amount
Will Call Fee 04/02/2018 Check $10.00
Paid By: Lion Square Lodge and Conference Center - Notes: 9800 - Lion Square Lodge and Conference Center
Permit Fee 04/02/2018 Check $4,974.00
Paid By: Lion Square Lodge and Conference Center - Notes: 9800 - Lion Square Lodge and Conference Center
Construction Tax 04/02/2018 Check $10,978.26
Paid By: Lion Square Lodge and Conference Center - Notes: 9800 - Lion Square Lodge and Conference Center
FEE TOTAL $15,962.26
AMOUNT PAID $15,962.26
BALANCE DUE $0.00
04/02/2018 - 1:32:08 PM - Generated by: dcouch75 South Frontage Road West, Vail, Colorado 81657
1 / 1
COMcheck Software Version 4.0.6.1
Interior Lighting Compliance Certificate
Project Title:
2015 IECC
Project Type:Alteration
Construction Site:
660 W. Lionshead Pl
Vail, CO
Owner/Agent:
Lionshead Lodge
660 W. Lionshead Pl
Vail, CO
Designer/Contractor:
Andrew Wilder
Wilder Engineering LLC
1170 Blue Sage Drive
Steamboat Springs, CO 80487
970-819-7848
Project Information
Energy Code:
Lion Square Lodge
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
1-Gore Creek (Common Space Types:Conference/Meeting/Multipurpose) 2492 1.23 3065
1.00 130(b)Allowance: Decorative Appearance / Fix. ID: FB 800(a)
1.00 800(b)Allowance: Decorative Appearance / Fix. ID: FC 800(a)
3995Total Allowed Watts =
(a)Area claimed must not exceed the illuminated area permitted for this allowance type.
(b)Allowance is (B x C) or the actual wattage of the fixtures given in Proposed Power section, whichever is less.
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Gore Creek ( Common Space Types:Conference/Meeting/Multipurpose 2492 sq.ft.)
LED 1: FB: Sconce: LED PAR 13W: 1 10 13 130
LED 2: FC: Chandelier: LED Other Fixture Unit 46W: 1 6 300 1800
LED 3: FE: Linear: LED Linear 33W: 1 34 33 1122
LED 4: FF: Wallwash: Other: 1 5 50 250
3302Total Proposed Watts =
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the
building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting
systems have been designed to meet the 2015 IECC requirements in COMcheck Version 4.0.6.1 and to comply with any
applicable mandatory requirements listed in the Inspection Checklist.
Andrew Wilder - PE
Name - Title Signature Date
Interior Lighting PASSES
Project Title:
Data filename:
Lion Square Lodge
C:\_Wilder Engineering\_Projects\Kohler Design\201772 - Lion Square Lodge\Calculations\Gore
Room.cck
02/10/18Report date:
51 of Page
2-12-18
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.0.6.1
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2015 IECC
Section
#
& Req.ID
Plan Review Complies? Comments/Assumptions
C103.2
[PR4]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the interior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
Lion Square Lodge
C:\_Wilder Engineering\_Projects\Kohler Design\201772 - Lion Square Lodge\Calculations\Gore
Room.cck
02/10/18Report date:
52 of Page
Section
#
& Req.ID
Rough-In Electrical Inspection Complies? Comments/Assumptions
C405.2.1
[EL15]1
Lighting controls installed to uniformly
reduce the lighting load by at least
50%.
Complies
Does Not
Not Observable
Not Applicable
C405.2.1
[EL18]1
Occupancy sensors installed in
required spaces.
Complies
Does Not
Not Observable
Not Applicable
C405.2.1,
C405.2.2.
3
[EL23]2
Independent lighting controls installed
per approved lighting plans and all
manual controls readily accessible and
visible to occupants.
Complies
Does Not
Not Observable
Not Applicable
C405.2.2.
1
[EL22]2
Automatic controls to shut off all
building lighting installed in all
buildings.
Complies
Does Not
Not Observable
Not Applicable
C405.2.3
[EL16]2
Daylight zones provided with
individual controls that control the
lights independent of general area
lighting.
Complies
Does Not
Not Observable
Not Applicable
C405.2.3,
C405.2.3.
1,
C405.2.3.
2
[EL20]1
Primary sidelighted areas are
equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
C405.2.3,
C405.2.3.
1,
C405.2.3.
3
[EL21]1
Enclosed spaces with daylight area
under skylights and rooftop monitors
are equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
C405.2.4
[EL4]1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
Complies
Does Not
Not Observable
Not Applicable
C405.2.4
[EL8]1
Additional interior lighting power
allowed for special functions per the
approved lighting plans and is
automatically controlled and
separated from general lighting.
Complies
Does Not
Not Observable
Not Applicable
C405.3
[EL6]1
Exit signs do not exceed 5 watts per
face.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
Lion Square Lodge
C:\_Wilder Engineering\_Projects\Kohler Design\201772 - Lion Square Lodge\Calculations\Gore
Room.cck
02/10/18Report date:
53 of Page
Section
#
& Req.ID
Final Inspection Complies? Comments/Assumptions
C303.3,
C408.2.5.
2
[FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
Complies
Does Not
Not Observable
Not Applicable
C405.4.1
[FI18]1
Interior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
Complies
Does Not
Not Observable
Not Applicable
See the Interior Lighting fixture schedule for values.
C408.2.5.
1
[FI16]3
Furnished as-built drawings for
electric power systems within 90 days
of system acceptance.
Complies
Does Not
Not Observable
Not Applicable
C408.3
[FI33]1
Lighting systems have been tested to
ensure proper calibration, adjustment,
programming, and operation.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
Lion Square Lodge
C:\_Wilder Engineering\_Projects\Kohler Design\201772 - Lion Square Lodge\Calculations\Gore
Room.cck
02/10/18Report date:
54 of Page
Project Title:
Data filename:
Lion Square Lodge
C:\_Wilder Engineering\_Projects\Kohler Design\201772 - Lion Square Lodge\Calculations\Gore
Room.cck
02/10/18Report date:
55 of Page
COMcheck Software Version 4.0.6.1
Interior Lighting Compliance Certificate
Project Title:
2015 IECC
Project Type:Alteration
Construction Site:
660 W. Lionshead Pl
Vail, CO
Owner/Agent:
Lionshead Lodge
660 W. Lionshead Pl
Vail, CO
Designer/Contractor:
Andrew Wilder
Wilder Engineering LLC
1170 Blue Sage Drive
Steamboat Springs, CO 80487
970-819-7848
Project Information
Energy Code:
Lion Square Lodge
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
1-Wildwood Room (Common Space Types:Conference/Meeting/Multipurpose) 3019 1.23 3713
1.00 2400 (b)Allowance: Decorative Appearance / Fix. ID: FC 2400 (a)
1.00 52 (b)Allowance: Decorative Appearance / Fix. ID: FB 2400 (a)
6165Total Allowed Watts =
(a) Area claimed must not exceed the illuminated area permitted for this allowance type.
(b) Allowance is (B x C) or the actual wattage of the fixtures given in Proposed Power section, whichever is less.
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Wildwood Room ( Common Space Types:Conference/Meeting/Multipurpose 3019 sq.ft.)
LED 1: FA: Downlight: LED PAR 20W: 1 82 21 1722
LED 2: FC: Chandelier: Other: 1 12 300 3600
LED 5: FB: Sconce: LED PAR 13W: 1 4 13 52
LED 6: FD: Wallwas: LED PAR 20W: 1 5 21 105
5479Total Proposed Watts =
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the
building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting
systems have been designed to meet the 2015 IECC requirements in COMcheck Version 4.0.6.1 and to comply with any
applicable mandatory requirements listed in the Inspection Checklist.
Andrew Wilder - PE
Name - Title Signature Date
Interior Lighting PASSES
Project Title:
Data filename:
Lion Square Lodge
C:\_Wilder Engineering\_Projects\Kohler Design\201772 - Lion Square
Lodge\Calculations\Wildwood Room.cck
02/10/18Report date:
51 of Page
2-12-18
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.0.6.1
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2015 IECC
Section
#
& Req.ID
Plan Review Complies? Comments/Assumptions
C103.2
[PR4]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the interior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
Lion Square Lodge
C:\_Wilder Engineering\_Projects\Kohler Design\201772 - Lion Square
Lodge\Calculations\Wildwood Room.cck
02/10/18Report date:
52 of Page
Section
#
& Req.ID
Rough-In Electrical Inspection Complies? Comments/Assumptions
C405.2.1
[EL15]1
Lighting controls installed to uniformly
reduce the lighting load by at least
50%.
Complies
Does Not
Not Observable
Not Applicable
C405.2.1
[EL18]1
Occupancy sensors installed in
required spaces.
Complies
Does Not
Not Observable
Not Applicable
C405.2.1,
C405.2.2.
3
[EL23]2
Independent lighting controls installed
per approved lighting plans and all
manual controls readily accessible and
visible to occupants.
Complies
Does Not
Not Observable
Not Applicable
C405.2.2.
1
[EL22]2
Automatic controls to shut off all
building lighting installed in all
buildings.
Complies
Does Not
Not Observable
Not Applicable
C405.2.3
[EL16]2
Daylight zones provided with
individual controls that control the
lights independent of general area
lighting.
Complies
Does Not
Not Observable
Not Applicable
C405.2.3,
C405.2.3.
1,
C405.2.3.
2
[EL20]1
Primary sidelighted areas are
equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
C405.2.3,
C405.2.3.
1,
C405.2.3.
3
[EL21]1
Enclosed spaces with daylight area
under skylights and rooftop monitors
are equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
C405.2.4
[EL4]1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
Complies
Does Not
Not Observable
Not Applicable
C405.2.4
[EL8]1
Additional interior lighting power
allowed for special functions per the
approved lighting plans and is
automatically controlled and
separated from general lighting.
Complies
Does Not
Not Observable
Not Applicable
C405.3
[EL6]1
Exit signs do not exceed 5 watts per
face.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
Lion Square Lodge
C:\_Wilder Engineering\_Projects\Kohler Design\201772 - Lion Square
Lodge\Calculations\Wildwood Room.cck
02/10/18Report date:
53 of Page
Section
#
& Req.ID
Final Inspection Complies? Comments/Assumptions
C303.3,
C408.2.5.
2
[FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
Complies
Does Not
Not Observable
Not Applicable
C405.4.1
[FI18]1
Interior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
Complies
Does Not
Not Observable
Not Applicable
See the Interior Lighting fixture schedule for values.
C408.2.5.
1
[FI16]3
Furnished as-built drawings for
electric power systems within 90 days
of system acceptance.
Complies
Does Not
Not Observable
Not Applicable
C408.3
[FI33]1
Lighting systems have been tested to
ensure proper calibration, adjustment,
programming, and operation.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)
Project Title:
Data filename:
Lion Square Lodge
C:\_Wilder Engineering\_Projects\Kohler Design\201772 - Lion Square
Lodge\Calculations\Wildwood Room.cck
02/10/18Report date:
54 of Page
Project Title:
Data filename:
Lion Square Lodge
C:\_Wilder Engineering\_Projects\Kohler Design\201772 - Lion Square
Lodge\Calculations\Wildwood Room.cck
02/10/18Report date:
55 of Page