ASBESTOS INSPECTION REPORT
CLIENT: Ted Steers
ADDRESS: 2905 Booth Creek Drive
Vail,CO, 81657
EMAIL: Accounting@vailvillagerentals.com
PHONE: 970-331-4995
EcoS JOB NUMBER
PROJECT LOCATION: 2905 Booth Creek Drive
DATE OF INSPECTION: 11/23/2018
1
Cr"C rri? ri4
•
ecos
Environmental&Disaster Restoration,Inc.
SUMMARY
ECOS Environmental&Disaster Restoration(ECOS)was retained to conduct a limited asbestos
inspection at the above location in reference to determining if there is asbestos containing material
(ACM),in building materials that are located in a bathroom and adjacent rooms affected by fire/smoke
damage.The inspection was performed in accordance with the Standards of Practice of the Colorado
Regulation 8 Part B in effect at the time of this Inspection.This inspection is not intended to be
technically exhaustive.The inspection included all accessible building materials in the bathroom and
adjacent rooms,however,should any additional building materials be discovered during demolition,
those materials must be sampled and analyzed prior to continuing with the work.Eight(8)samples
were collected of all suspect materials throughout the bathroom and adjacent rooms,as listed in the
Lab Data Table located on Page 9 of this report.
The Inspector has prepared this written asbestos Inspection Report for the sole use and benefit of the
client.The asbestos inspection report shall identify,report,and make recommendations for future
evaluation. Client agrees to read the entire asbestos inspection report when received and shall
promptly call the inspector with questions or concerns regarding the report.The use of this report and
information contained herein by others,in whole or in part,is not authorized without the written
mutual consent of the client and ECOS Environmental.
INSPECTOR QUALIFICATIONS
This inspection was performed by Kris Miller,Colorado State Department of Public Health and
Environment Certification Number 24799.
SAMPLE ANALYSIS PROCEDURF
ECOS collected bulk samples of the homogenous materials in a random and representative manner,as
determined by the Inspector.A minimum of one composite core samples that included all layers within
the suspect material was obtained from each homogenous area.Samples of soft friable materials were
obtained by removing a small portion using wetting techniques.The sampler cleaned equipment
following collection of each sample to minimize cross-contamination between samples.The sampler
assumed that materials in inaccessible locations were similar to those in accessible locations,in order to
limit destruction during the sampling process.All samples were placed in sealed,labeled containers,
and the sample descriptions and locations were recorded.Samples were delivered under a chain of
custody for analysis to Aerobiology Laboratory in Denver,CO. Samples were analyzed by Polarized
Light Microscopy.
Performance of this asbestos inspection is intended to reduce,but not eliminate,uncertainty regarding
the presence of ACBM in connection with the above referenced property. No guarantee is expressed or
implied that all ACBM was identified in the inspection. Therefore,ECOS Environmental cannot be
held accountable for restrictions placed on us by the client,conditions or information that remained
unknown,or areas that were inaccessible at the time of the inspection.
2
ecos
Environmental E.Disaster Restoration,Inc.
TRANSMITTAL OF BUILDING
One(1)copy of the results of the building/structure asbestos survey shall be immediately transmitted
by the building/structure owner as follows:
• One copy of the completed asbestos survey shall be sent by the owner or their agent to the local
government entity charged with issuing a permit for such demolition,renovation,remodeling
or repair work under applicable State or local laws.
• The completed asbestos survey shall be kept on the construction site with the asbestos
notification and variance,if required,throughout the duration of the asbestos project and any
associated demolition,renovation,remodeling or repair project.
BUILDING/STRUCTURE ASBESTOS SURVEY INFORMATION
The asbestos survey shall,at a minimum,identify and assess with due diligence,the locations,
quantities,friability and conditions of all building material types at the affected portion of the
building/structure.The certified asbestos inspector is responsible for identification and assessment of
all type within the affected portion of the building/structure.
All building materials visually assessed shall be assumed to be asbestos containing building material
(ACBM),unless bulk sampling is conducted as per standard EPA and OSHA accepted methodologies.
The subsequent analysis is performed by a laboratory that meets the requirements and the analyses
satisfies both CO STATE ELAP and federal requirements,including multi-layered sample analyses,to
document non-asbestos containing material.
The building/structure asbestos survey shall also include the building/structure name,address,the
building/structure owner's name and address,the name and address of the owner's agent,the name of
the firm performing the asbestos survey and a copy of the firm's current asbestos handling license,the
names of the certified inspector(s)performing the survey and a copy of the current asbestos handling
certificate for each inspector utilized,the dates of the asbestos survey,a listing of homogeneous areas
identifying which ones are ACBM,all laboratory analysis reports for bulk samples collected,and copies
of the appropriate certifications for the laboratory used for analysis of samples taken during the
asbestos survey.
REMOVAL REQUIREMENT
If the building/structure asbestos survey finds that the portion of the building/structure to be
demolished,renovated,remodeled,or have repair work contains asbestos containing building material
(ACBM),which is impacted by the work,the owner or the owner's agent shall conduct,or cause to
have conducted,asbestos removal performed by a licensed asbestos abatement contractor in
conformance with all standards set forth.
All ACBM impacted by the demolition,renovation,remodeling or repair project shall be removed,
prior to access or disturbance by other uncertified trades or personnel.No demolition,renovation,
remodeling or repair work shall be commenced by any owner or the owner's agent prior to the
3
otos
Environmental&Disaster Restoration,Inc.
completion of the asbestos abatement in accordance with the notification requirements.For multi-
phased work,the access restriction for uncertified trades or personnel applies to each intermediate
portion of the entire project.Upon completion of the intermediate portion of the asbestos project,other
trades,or personnel may access that portion of the work site.For demolition projects that are exempt
from asbestos survey requirements due to being structurally unsound,the demolition is considered an
asbestos project.
All building/structure owners and asbestos abatement contractors on a demolition,renovation,
remodeling,or repair project shall inform all trades on the work site about the ACBM at the work site.
UNIDENTIFIED AND UNASSESSED ASBESTOS
When any construction activity,such as demolition,remodeling,renovation or repair work,reveals
suspect ACBM that has not been identified by the asbestos survey,or has not been identified by other
inspections as per current OSHA or EPA requirements,all activities shall cease in the area where the
suspect ACBM is found.Unassessed suspect miscellaneous ACBM shall be treated and handled as
ACBM and assumed to be ACBM,unless proven otherwise by standard EPA and OSHA accepted
methods.To document non-asbestos containing material,analysis must be performed by a laboratory
that meets the requirements of the DOH;and the analysis satisfies both CO STATE ELAP and federal
requirements.
ASBESTOS PROJECT S
An asbestos project is any work that involves the removal,encapsulation,enclosure,repair or
disturbance of friable or non-friable asbestos,or any handling of asbestos material that may result in
the release of asbestos fibers.For the purpose of compliance an asbestos project shall include any
disturbance of asbestos fibers,and the planning,asbestos survey,design,background air sampling,
inspection,air sampling and oversight of abatement work,cleanup,and the handling of all asbestos
material subject to abatement,as well as the supervising of such activities.An asbestos project starts
with Phase I when the planning,asbestos survey,and design work begins or is required to begin.The
project shall not be considered completed until Phase II D is complete.(See Table 1 below).
Phase I Phase II
(Prior to Asbestos Start->Abatement->End
Abatement Contractor)
A B A B C D
Regulated Asbestos Final
Asbestos abatement handling
survey, Background work area(s) including gross cleaning Final waste
planning, air sampling preparation removal or and removal
and design and enclosure abatement,initial clearance from site
construction cleans,and waste air samples
Start->Asbestos Project->Final Clearance
4
ecos
Environmental&Disaster Restoration,Inc.
ASBESTOS RESULTS FLOW CHART
- Non Detect I < 1% >1%
No Action OSHA Reg. 8 dditional Reg_
Required Requirements Requirements Requirements
>3,000 SF
NO Permit Permit Project Design
Required
ECOS provides
clearance (NOT clearance Testing project Manager
required) Oversight
Manifested
Disposal at
ApfrnvNi Landfill
ASBESTOS PROJECT SIZE'
Large asbestos project:An asbestos project involving the removal,disturbance,enclosure,
encapsulation,repair or handling of 160 square feet or more of ACBM,or 260 linear feet or more of
ACBM.
IlSmall asbestos project: An asbestos project involving the removal,encapsulation,enclosure,repair,
disturbance or any handling of more than 10 and less than 160 square feet of ACBM or more than 25
and less than 260 linear feet of ACBM.
Minor asbestos project:An asbestos project involving the removal,disturbance,repair,encapsulation,
enclosure or handling of 10 square feet or less of ACBM or 25 linear feet or less of ACBM.
5
ecos
Environmental&Disaster Restoration,Inc.
Homogenous areas sampling requirement:SF=Square Footage.LF=Linear Footage
HOMOGENOUS MATERIAL TYPE QUANTITIES MINIMUM#O -
OTO<1,000 SF 3
SURFACING MATERIAL
1,000 TO 5,000 SF 5
>5,000 SF 7
THERMAL SYSTEM INSULATION EACH MATERIAL 3
PATCH<6 SF,LF 1
MISCELLANEOUS MATERIALS EACH MATERIAL 2
ASBESTOS REMOVAL CATEGiRIES
Category I Non-Friable ACBM:NESHAP classification-Asbestos-containing packings,gaskets,
resilient floor covering,and asphalt roofing products,containing more than one percent(1%)asbestos,
that when dry,cannot be crumbled,pulverized,or reduced to powder by hand pressure.
Category II Non-Friable ACBM:NESHAP classification-Any material,excluding Category I Non-
Friable ACM,containing more than one percent(1%)asbestos that,when dry,cannot be crumbled,
pulverized,or reduced to powder by hand pressure.
Class I Asbestos Work:OSHA term meaning activities involving the abatement of Thermal Systems
Insulation(TSI)and surfacing ACBM and PACM.
Class II Asbestos Work: OSHA term meaning activities involving the abatement of ACBM which is not
TSI or surfacing material.This includes,but is not limited to,the removal of asbestos-containing
wallboard,floor tile and sheeting,roofing and siding shingles,and construction mastics.
Class III Asbestos Work: OSHA term meaning Repair and Maintenance operations,where no more
than a minor quantity of ACM,including TSI and surfacing ACBM and PACM,is likely to be
disturbed.
Class IV Asbestos Work: OSHA term meaning Maintenance and Custodial Activities during which
employees contact but do not disturb ACBM or PACM and activities to clean up non-ACBM dust,
waste and debris resulting from Class I,II and III activities.
6
e LOS
ironni ntal Uisastar Restoration,Inc.
Abatement:Procedures to control fiber release from asbestos material. This includes removal,
encapsulation,enclosure,repair,and disturbance of friable asbestos or any handling of asbestos
material that may result in the release of asbestos fibers.
Amosite:An Asbestiform mineral of the amphibole group containing approximately
50% silicon and 40% Iron(II)Oxide,and is made up of straight brittle fibers, light gray to pale brown in
color.
Amphibole:One of the two major groups of minerals from which the Asbestiform minerals are
derived,distinguished by their chain-like crystal structure and chemical composition.
Asbestos:A generic name given to a number of naturally occurring hydrated mineral silicates that
possess a unique crystalline structure,are incombustible in air,and are separable into fibers. Asbestos
includes the asbesti-form varieties of chrysotile(serpentine);crocidolite
(riebeckite);amosite(cummington-grunerite);anthophyllite;and actinolite.
Asbestos Project:Work undertaken by a contractor which at any time involves any aspect of the
removal,encapsulation,enclosure or disturbance of friable asbestos,or any handling of asbestos
material that may result in the release of asbestos fiber,except work in an owner-occupied single-
family dwelling performed by the owner of such dwelling. An asbestos project shall include the
planning,design,monitoring,inspection,and air sampling of abatement work,as well as the
supervising of such activities.
Building Owner:The person in whom legal title to the premises is vested unless the premises are held
in land trust,in which instance building owner means the person in whom beneficial title is vested.
Electron Microscopy:A method of asbestos sample analysis which utilizes an electron beam to
differentiate between fibers.
Emergency:An unexpected,unanticipated or unforeseen occurrence,including but not limited to,a
steam,chemical,gas or water line rupture,a boiler failure,or a building collapse,which poses(a)an
imminent danger to the health and safety of the public,the response to which will constitute an
asbestos project;or(b) an asbestos-related risk to the health and safety of the public from exposure to
asbestos fibers.
Friable Asbestos:Any materials that contain asbestos and can be crumbled,pulverized,or reduced to
powder by hand pressure.
HEPA Filter Vacuum Equipment:Vacuuming equipment with a high efficiency particulate air
filtration system. This filter is capable of trapping and retaining 99.97 percent of asbestos fibers greater
than 0.3 microns equivalent aerodynamic diameter.
Homogenous:Evenly mixed and similar in appearance and texture throughout.
NESHAP:National Emission Standard for Hazardous Air Pollutants
OSHA:Occupational Safety and Health Administration
7
ecos
F: irnnnu;ntal IlisasU.r Hestoni ion,Inc:.
Operations and Management Plan(OMP): Specific procedures and practices developed for the
interim control of asbestos-containing materials in buildings until it is removed.
Polarized Light Microscopy (PLM):An optical microscopic technique used to distinguish between
different types of asbestos fibers by their shape and unique optical properties.
Repair:Corrective action using required work practices to control fiber release from damaged asbestos
material.
TSI:Thermal Systems Insulation
ACBM: Asbestos containing building material
Surfacing Material - material that is sprayed on, troweled on, or otherwise applied to
surfaces, such as acoustical plaster on ceilings and fireproofing materials on structural
members, or other materials on surfaces for acoustical, fireproofing, or other purposes.
Thermal System Insulation-material applied to pipes,fittings,boilers, breeching, tanks,
ducts, or other interior structural components to prevent heat loss or gain, or water
condensation, or for other purposes.
Miscellaneous Materials-interior building material on structural components, structural
members or fixtures, such as floor and ceiling tiles, and does not include surfacing material or
thermal system insulation.
8
ecos
Environmental Sc Disaster Restoration,Inc.
HOMOGENOUS AREAS SAMPLED DURING INSPECTION
n. q pC cn
LOCATION U 122 iz °p
Material U c . cn O
A
A o w U a. cn
Al Drywall and Bathroom Wall N F D L 3
texture
A2 Drywall and Bathroom Wall N F D L
texture
A3 Drywall and Bathroom Wall N F D L
texture
Bl Drywall and Ceiling N F D L 3
texture
B2 Drywall and Ceiling N F D L
texture
B3 Drywall and Ceiling N F D L
texture
Cl Tile and mastic Tile and mastic in bathroom N NFI D L 2
C2 Tile and mastic Tile and mastic in bathroom N NFI D L
KEY:
CONDITION
G= NO VISIBLE DAMAGE
D= VISIBLE DAMAGE<10%OVER ENTIRE MATERIAL OR 25%LOCALIZED
SD=VISIBLE DAMAGE>10% OVER ENTIRE MATERIAL OR 25% LOCALIZED
FRIABLE CATEGORY
F=FRIABLE MATERIAL;MATERIALS THAT CAN CRUMBLE OR BE REDUCED TO POWDER BY HAND PRESSURE
NFI=CATEGORY I NON-FRIABLE MATERIAL;MATERIALS THAT CANNOT BE CRUMBLED OR REDUCED TO
POWDER BY HAND PRESSURE THAT DO NOT INCLUDE CATEGORY I NON-FRIABLE MATERIALS.
POTENTIAL FOR DISTURBANCE
L= LOw POTENTIAL FOR DAMAGE
D= POTENTIAL FOR DAMAGE
SD=POTENTIAL FOR SIGNIFICANT DAMAGE
INVENTORY
LOCATION/FUNCTIONAL SPACES INCLUDED IN DESCRIPTION
ar HOMOGENOUS AREA
2
cn
A DRYWALL. AND TEXTURE OF ROOM WALLS WALLS
B DRYWALL AND TEXTURE OE ROOM CEILINGS CEILING
C TILE AND MASTIC OE BATHROOM FLOOR FLOOR
9
eros
Environmental&Disaster Restoration,Inc.
CONCLUSION
Visual inspection was completed of building materials in a bathroom and adjacent rooms that were
affected during a limited demolition of building materials in a home due to fire.Eight(8)samples were
collected and sent to Aerobiology Laboratories in Golden,CO,for analysis using Polarized Light
Microscopy (PLM). The samples came back non-detect for asbestos.
LAB RESULTS AND COC
1.a u.. Page or
ecos '' a 1045(1,0 P"r"
AarabioogyCN.nt IECOS Environmentala�ma... 1.0.,1•1,
Field Contact a Kria Miner er...a gaff w.wr.►mq)°'i"
6690 Ftwy 82 ..wa..a..rom a.an�ti�7 u! t2 5
Adams
Glenwood Springs.CO 81801 _ ,�-- }ePeR .—„
Prom 970-909-4725
"oltbood kmieregecoaenvlronmentai.• .
ea%Yam r b Maur[ Gamy Dar 4 Mor ! , 422. I�lra+..'
SAMPLING LOCATION ZIP CODE \ / sae earmao: a..NM..IOW OWaN GeV ar..nw 1.01)7110.111.1
Sample No. Test Code Sample Location Total Volume/Area
1 f"I 300Z-- 51.,...)44:13,144" 1;4i-1-, Awe
Z- se" Gam- T.
3 if nig" S
4 �1 s0 /z.c 5-
5 SE"
a R3 AM (041/-", 8.w--
T
6,) 1k) cow.- ROW 3
C� IJ� -
a
10
1
•
12
13
14 LAB USE ONLY
15
A 1015 ua-WArGR
10179g -Mae
i0i79q :�1'TEr`.-Pwbr• oowo.l,.
V git f cd7t+ruM€ut�oolMamaa
A063".' „
FIn wa.rve Aa.r n as0aa rc. -PMi1CM as lzadon
71...ram.aw.n..r.l w m1R IM1.a1m ra 111 4s®e•s•Nwm.wr.a
743 1.n.-WWI .¶1.0 SOW..O.*1NOM 01•414011 F.11(RM., Allemmaylm
.ra ta.f..onr.ma4w pagaa.al.a r..lxry maao.tato 0•+..eaea.....o.
uTJ 1r.ryC Mos Fa.14gman VA AIN 0111•1YWI45 pmemceew.a.0 4r..4.ea,45
Snot Eur...r..apa aw..1 U Ort (101 srsl-1=1.25.17-s.mwe.rmmWY ti
/MS..P*9 w.wo•yr 0114 naw.Ay.aot1 We MM.,re/1a02/.1.1.10 w.Mw..ese.MMprM
1111=ftl
10
egos
Environmental&Disaster Restoration,Inc.
Ainobiology� l.aboamoay An el
Noww
arW
Expertise Since 1997 )O01
)40
Certllleale of Analysis vela'„'^'.""
Chao Now ECOS Parilaeorsd Dee Callow& 1313111.
Saw Whom 4NHOBWYMDe .a.
Data X.ocid: 11/36/14
0l>.M. y..
.Z>P rwhy Addy,CO aldal ThITIAa O.I.AWy,.d 13126/19
900 KM Milk, NV)..P LLL.Cad.riWA De.Wowed 110641
Cam holed Now 7905 KWh Caul 1591.•IO. 11}4.50(11
Tea 9.owma ./DM..Geer 1.Balk 9.tylu
laabod. %Woad Li{M Niiamow/D.go.sioa broaba 1193O1.Mubd far lb Detaatealh.a of Moods a 6.l ONION.,M .CPA44*106 Vvl76.Ah'1991
tl,.w. NdoA.I...e. Nrnt.l/lww. MOON
Sample 1001931om Play.ei O..nitalw of S.uapala9.r dd.,. IYr ta„v Ashok,.I1..s.i Ada..Pa.n.Yp. Filo, 6lnnall Mato.CI.. L.h SewaA.N.A. •1.^..., Rawnl..c Noted., 10lar.ta3
10043W-IA WhIro Cult p, d with Tan 9.191 N 2% NI) 1d) C
18045000-IB Whin Tape N 2% NI) 99 I
Al
18045060-10 %Lite Had C.og...ed N 2% ND 100 C
180450604 I) Whila/I an Dryw.11 N 94% ND 15 IS G
16045060-2A Whim C0ep0009 with Te.Paha N 1% ND 100 C
18045090-2D WbildTa0 Drywall N 99% MD 15 85 0
I00d5061L1.9 Whit•Ciniptaind with u
ylatadal Pain) N Taw ND 100 C
Layers
A.1
10114)060-3B White/Top Drywall N 100'. ND 15 85 G
INA SUdY-0A White C'mtpryitd Multi a. 4rood Punt N 1% NO >00 C
LAWDI
I NM3060-40Whll fl...D.yo.11 N 99% ND 15 05 0
AC.Amalie. A1I.A..IeYlfi B-DPW. Q.o-a.m
/). /� -'t J��_ �/ AM.Ami* C..CaM. CatC T.Tar
��,/AJN•R_.O/Is.- Q. TrfuC{.W ajv�'W AN.Aweh.Wryl*a 1G.Pier(Joe D.Dolm. V.Varml.Ai*
_/
CHAT-Cm).9.i. MW.Mra1 WW 0-0)T...
CAM.Wad Wawasaw Ca-- " OT.OILS M-ABm
Lina q Asthal A.YW.Lb ame.11e TIL.T.olis a1N-f4a.Lds OIL.d^a
T.0)% TL.TY1a OP.OPtwa
ND.)3s..D.l.alal W.Wo4aemila P-Padia
Paw loll
\�AEnob+otogy� LAboRATotty ....ow tsar
AILS. H wad IN
�` al.laa c0.anal
E7fperdse Since INCOMPOWAI1997 CtrwleaaofAnay.I. �•++w�
mina Nem vcon r.Mnn....al noacl,a...1L. 1117v1a
9r...Wiea OA90 HWY82 Dam 9.4.6.0 I I/M'Il
Cay.IS.2.11. 0.m.owlape6 o CC)31001 vata0 sea.%Sts& II/73070
NW Km Miler NV..?la.Deb aemalto Dea llwataa1 I 026/11
MAW P. Nara 2905 Boa Cloak Padau 11): 13015000
Tao ILwP.a.4. 7p®.A90500 ie*Ds
%W oa Pidd1yl/d1sowcw/Dspe..a.e. $113000>1 DANS WON D.ewleaa.aAeeaa.OWalk WitlauMnme.mPA,i.O1RA/71La AM 1995.
ee.ya.NaetacN.n Nano- L... .l..Aaboad Nmiltn,. Moria
MOWN D.rcelab of 10.131.146sma Asteis M.e1 Pw.Ymlit
tar e . Ir Na el° Maw°
5719111 1d19$9lnoloNuII o- (991 P.m..** remnant, NNa.daB, ,C.mSVa).e
18045060-5A Whits Ga.1p:..wl1.
Impart/ {1.14 N Dow ND 000C
R]
1804 5060-5D WhitdT0 Drywall N 100% ND 15 85 G
18045060-6A WMI.CPwp.ed,l6M .o,I oated e N 1% ND 100 C
Loola
133
18045060-6R WhiVM Drywdl N 99.. ND 15 95 Cl
18045060.7A (hay(30.t N 2% ND 104 Q
CI
18045060-10 Tea Carman Ns N 98% ND 100
11104.5060-IA Gary Grant N 2% ND 100 Q
c=
18043060-RN Tel C..a..c Tito N 99% ND 100
I/ AC.Aer80. AR-Aaimoll4ir B.1l0.tYr Q-Qrb
f] /JI_ wM.Aw..e. PO+Maf.m t-Diatoms T-114
V`f `,�L{.{,�„v AN.A„ahapb7gya. 9G.fasmfidN D.Dlr.r V..V
.baa ,. .6Ow
/- nsionisiini
CTIIY.6a.y.w1* CT -AY.si Woe O.OoPe
lww)m+pn TapecAev CIL.C...wl.ttla Qr.Odd, M-lois
Tatar/Ey A.rlye Aeaeml.biperde TR.T.e.mh. BTN-L)elLatia OIL.07som.e
Tor .041% TL.Tea OP.D.. OilO.
ND.Now ar0ad W.W.11mladt. P.~id
Paso 2 Ma
11
'
ecos
Environmental =x Disaster Restoration,Inc.
AERObioLogy LabORATORy lauseams Street
ASSOCIATES,:� INCCNo'ORAIiD State 104
(.ddat,(3).81)401
Expertise Since 1997 313.232.3740
Certificate of Analysis www aernhhanga nal
Client Name 0_('00 linvironmenlaIMf��J7 late Celleeled. 1123.14
Street address ((Mt HR'Y 112 LIV�J A? Dine Reeeivcd 11 2(..14
City.Stoicin' (ilcnward Springs.CO 81411 I 1IS71S( IIIiii Date Analayed: II 2(18
Attn. Kris Miller XVI APIA),rode 200860-0 Date Reported: I12(,1N
Client Project Name: 29415 Booth Creel Project Ill. l t(iM5(K t)
General Plates
• ND indicates no asbestos was detected:the method detection limit is 111.
• Trace or"-I"indicates asbestos sans identified in the sample.but the rx neentration is Icss than
• All regulated asbestos minerals p.c.chits while.untasite.crocidolite,anlhophyllite.iremeli Ie.and actinolite i were sought in in cry laver of each sample,bur only boa asbestos
minerals detected arc listed.Amesite is the common name for the astastiform varies of the minerals eunmmnglomte and gruttcrite.Crocidolite is the common time used for ibe
aslteslifitrm Carrels id'tlte mineral nebeclne
• Tile.vinyl.foam.plastic.and tine powder samples may contain asbestos titters of such small diameter P 0 25 nneron,in diameter)that these tilers cannot he detected he Pi.M
For such samples.more sensitive analytical methods leg.!Llai SIM-and YRD)are recommended if greater certainty about asbestos content is required. Semi-quantitative hull ILM
Iiesar tile analysis is accepted under NFS1IAP regulations
• These results are submitted pursuant to Aetobmlagy Laboraton Associates,Inc.s current tam and conditions clinic.including the company s standard warrants and limitation
of liability provisions No responsibility of liability is assumed lir the manner in which the results are used or inregarded.
• Itnless soothed in venting to return the samples covered hs this report.Aerobiology I shot:Nis Associates.hie will store the samples fora minimum period of thirds/301 days
before discarding.A shipping and handling charge will be assessed for the return oltun samples
• Aerolaology does not guarantee the results of ape lilts.microvaa,sage.and'or skins samples Accurate analysis cannot he perforated due to particle sloe,medm used.and-or
amount of material given.Analysis of thea materials should he preformed by a T12d. A result of Nh does not indicate that the sample area docs not contain iubesto. It means the
analyst could not identify asbestos in the specific sample for the reasons listed abort.
Rotes Required ba NV LAP
• This report must not he used by the client to claim product certification.appt,sal or endorsement In-NVf.AP,NIST,or am agency of the Federal Government
• This test retain relates only to the items tested or calibrated
• This report is not valid unless it bears the name of a N VLAP-appto sed signature.
• Any reproduction of this document must include the entire document in ander for the report to be solid.
Page 3 of 3
12
• ecos
Environmental&Disaster Restoration,Inc.
CERTIFICATIONS
,.......... .. ?01114: ..9.-, : '�' '.
7 4.' Colorado p � }: .
of Publicflalth L.
k ' and Environment
ASBESTOS
CERTIFICATION* I'''',: =.
•
1 This certifies that I J. Y.
}
..i
Kristopher Miller
N.
Certification Nat 24799 y
• ham mer the requirerma4 of 2S-7-S07,C.R.S.and Air Quality Control - •
k
Commission Regulation N.8,Part B.and is hereby certified by the • 4 '
• state of Colorado in the mowing discipline: '% V;
}
., Building Ii
nspector*
: : .M11
* • ' Tomer Jay m.2018 .>�
: ' Expires: fay GS.2019 t
a ,
} r.
«..,.n.-...+.•Neap ;r:':' C:�r.-.
o.t
- . .. ''0
t ,. a * 400, * T'0: . •
� %
' + .f Y+
'
:` Colonido t l i
of Pub&Health
' and Environment
' :: ! ASBESTOS CONSULTING FIRM l..,x','
` This certifies that
Eeos Environmental and Disaster Restoration,Incl swy
. Registration No.:ACP-t80 44 .1I's .'
has mot the registration requirements of 25-7.507,C.R.S.and the Air Quality Centcoi '
Cotttmissitn Regulation No.8,Pan B,and is hereby aitthee rad le Rohm'Abeam tumult/nig 'j,' •4'
.I activities as required under Regulation No R,Part B,in the state of Colorado. -.t<
Issued: September 09,2018 • -. - ' r t .
Expires: September 09,2019 _ ,1W,e.[1 '(d I''.' <
f. r .+.-eros A.4:•vw.l.r .. ..
•
•
;: .
13
ecos
Environmental s Disaster Restoration,Inc.
This report represents the opinion of the reporting asbestos inspector at the time of the asbestos
assessment survey. If you have any further questions,or if additional information is needed please do
not hesitate to call.