Loading...
HomeMy WebLinkAboutF18-0012_303GoreCreekRd-U9-10-CutSheets_1523462049.pdf ° OF1/4 rft FIRE PROTECTION 3QoD lo HYDRAULIC CA L C U L A T I O N S A N D4,,,i,e&Emergency Services MATERIAL CUT SHEETS FROM: 1110 Western States Fire Protection Co. Peedi9 /dV{iez aad proorte,/ 274 CENTER DRIVE GLENWOOD SPRINGS, CO 81601 (720)219-0574 FOR: GALVIN RESIDENCE 303 GORE CREEK DR - #9 & #10 VA I L, CO. 81657 JOB# CH0290 SUBMITTED BY: STEVE ALLEN PROJECT MANAGER MARCH 19, 2018 " OF z•4/ Ctiozqo 4tei' il 040 111 s.t• 0 Vail Fire&Emergency Services western States 04/11 /18 FireProtection Co. Placa/iv 4âe4 a ` proeito Flow Test Information Done By: Steve Allen Address: LOCH cob' (��r-e t ,- eK 66fe C ce 6-K d- tie%,ASt-,,,,ti '.t A,w14. Hydrant Location: Same Date & Time: g- j g--ia @ 11) :3/3 Static: r35--- p.s.i. DErktiieot , --- 131)--- Residual: - l3Residual: 13O p.s.i. @ [1Z'5 g.p.m. 5`i Observers; Signature Print Company -k--) 41/11,1 3Vevt A1(e‘i 03 FP _14:- Ait. L tutA..)1.f, ?\I e CIF I/4 Bulletin 006 ReAOPIIIIIbi A0Reliable111177gr L -311:1131 e.% b Model RFC Series Residential Sprinklers 04/11/18Vail Fire &Emergency Services Flat Cover Plate,Concealed Pendent Sprinkler cULus Listed Product Features • cULus Listed as Residential Sprinklers -'� r, ice. • Push-On cover plate installation - • Low water flow requirements Product Description Model RFC30 Model RFC43 Model RFC Series residential sprinklers are flat cover plate, concealed pendent sprinklers intended for installation in * . accordance with NFPA 13, NFPA 13R, or NFPA 13D. The sprinklers are cULus Listed as Residential Sprinklers in ac- cordance with UL 1626. Model RFC30, RFC43, and RFC49 sprinklers have a 165°F II (74°C) temperature rated fusible-link operating element. Model RFC49 Model RFC58 Model RFC58 sprinklers are offered with either a 165°F (74°C) or 212°F (100°C) temperature rated fusible-link op- erating element.Sprinklers with a 165°F (74°C)temperature rating are ordinary temperature classification and should be used with a 135°F (57°C)temperature rated cover plate. All Sprinklers with a 212°F (100°C) temperature rating are inter- mediate temperature classification and should be used with a 165°F (74°C)temperature rated cover plate. t Model RFC Series sprinklers are installed with a Model RFC cover plate. Model RFC cover plates may be installed by either pushing or threading the cover plate into the sprinkler cup. Model RFC30,RFC43,and RFC49 sprinklers allow 1/2" (13 mm)of cover plate adjustment. Model RFC58 sprinklers allow 3/4°(19 mm)of cover plate adjustment. C.' -- `ten, Model RFC cover plates are available in a variety of finishes Solid Perforated as listed in Table H. In addition, Model RFC cover plates may be ordered as either traditional solid cover plates or Model RFC Cover Plate perforated cover plates. Table A Nominal K-Factor Max.Coverage Area Sprinkler Sprinkler Model gpm/psii2(I/min/bat-1/2) ft x ft(m x m) Identification Number(SIN) RFC30 3.0(43.2) 14 x 14 (4.3 x 4.3) RA0611 RFC43 4.3(62) 20 x 20(6.1 x 6.1) RA0612 RFC49 4.9(70.6) 20 x 20(6.1 x 6.1) RA0616 RFC58 5.8(84) 20 x 20(6.1 x 6.1) RA0613 www.reliablesprinkler.com ll Model RFC30 Residential Sprinkler Z 4 et Te. nicalSpecifications Cover Plate Finishes v Sty ::Flat Concealed Pendent (See Table H) • 4 + tk Threa•s:1/2"NPT or ISO 7-1 R1/2 Nom in. K-Factor:3.0(43.2 metric) Sensitivity • Agin 1 Max.Wo ing Pressure: 175 psi(12 bar) Fast-response Min.Spaci •:8 ft.(2.4 m) Ai, - Vail Fire&Emergency Se ices Temperature Rating 04/11/18 Material Specifi :tions 165°F (74°C)sprinkler ThermalSensor: ickel Alloy Solder Link 135°F (57°C)cover plate Sprinkler Body:Bra,s Alloy Levers:Bronze Alloy Cover Plate Yoke:Brass Alloy Model RFC cover plate •� Sealing Assembly:Nickel 'toy with PTFE Load Screw:Bronze Alloy Sprinkler Wrench Towers:Copper Alloy Model FC Pins:Stainless Steel Deflector:Bronze Alloy Listings and Approvals ' a • Cup:Steel cULus Listed Bottom View 1. •",b Model RFC30 Sprinkler Corn ponentsand Dime ions Figure 1 2-5/16"(58 mm) Threads Dia. Body _ Cup 1 .= W___.= �; = _ Tower 1-3/4"(44 mm)+1-1/4"(6 ,m) i ,' Fusible Link .�� Nominal face of fitting to ceili a ° -` ib�a,' AA.. Deflector(retracted) i' ilik.:.r v—r v—v 3/16"(5 mm) 7////// Pin(extended) - I Deflector(extended) 1/4 I I i -- 7 Model RFC Cover Plate 3-5/16"(84 mm)Dia. - Ceiling Model RFC30 Sprinkler Hydraulic Design Criteria Table B Minim urn Flow and Residual Pressure Max.Coverage Area Flow Pressure ft.x ft. gpm psi (m x m) (I/min) (bar) 12 x 12 9 1.0 (3.6x 3.6) (34) (0.: ) 14 x 14 10 11.0 (4.3x 4.3) (38) (0.76) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of:(1)the flow listed in Table B above and(2)the flow require. o achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above,use the minimum required flow for the next larger max.coverage area liste.. Bulletin 006 Rev.K ��';��'� Page 2 of 7 February 2017 www.reliablesprinkler.com It ki F go , ,. Model RFC43 Residential Sprinkler ! 4 -chnicalSpecifications Cover Plate Finishes S le:Flat Concealed Pendent (See Table H) , 'Milk4 Frs tk Thr=ads:1/2"NPT or ISO 7-1 R1/2 0 SI Nom "al K-Factor:4.3(62 metric) Sensitivity 1QO l Max. rking Pressure: 175 psi(12 bar) Fast-response Min.Spa•'ng:8 ft.(2.4 m) ..",. Vail Fire&Emergency Se ices Temperature Rating 04/11/1.8 Material Spec 'cations 165°F (74°C)sprinkler 4144 Therm alSenso •Nickel Alloy Solder Link 135°F (57°C)cover plate Sprinkler Body: : ass Alloy Levers:BronzeAlloo Cover Plate Yoke:Brass Alloy Model RFC cover plate f k . Sealing Assembly:Nic -I Alloy with PTFE _ Load Screw:Bronze Allo Sprinkler Wrench _ Towers:Copper Alloy Model FC yv" N Pins:Stainless Steela� � Deflector:Bronze Alloy Listings and Approvals Bottom View ° P , Cup:Steel cULus Listed Model RFC43 Sprinkler Com ponents and imensions Figure 2 -2-5/16"(58mm) y Threads Dia. Body - Cup w amt i tri Tower , 1-3/4"(44 mm)+ 1/4"(6 mm) i Fusible Link MM Nominal face of fittin•to ceiling Deflector(retracted) � a+' g .\ ,�. ,,,,, j iiiiiii 3/16"(5 mm) Pin(extended) IIII I • _ • I Lg`� Yi 1-I-1 Deflector(extended) •• } Model RFC Cover Plate 3-5/16"(84 mm)Dia.- Ceiling Model RFC43 Sprinkler Hydraulic Design Criteria Table C Minim urn Flow and Residual Pressure Max.Coverage Area Flow Pressure ft.x ft. gpm psi (m x m) (I/min) (bar) 12 x 12 12 7.8 (3.6 x 3.6) (45) (0.54) 14 x 14 13 9.1 (4.3 x 4.3) (49) (0.63) 16 x 16 13 9.1 (4.9x 4.9) (49) 1.63) 18 x 18 18 17.. (5.5 x 5.5) (68) (1.21 20 x 20 21 23.8 (6.1x 6.1) (79) (1.64) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of:(1)the flow listed in Table C above and(2)the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above,use the minimum required flow for the next larger max.coverage area listed. Bulletin 006 Rev.KReliabl�p Page 3 of- February 2017 ` www.reliablesprinkler.com ° °F I/4 t:rs14E1.14. Model RFC49 Residential Sprinkler Z Technical Specifications Cover Plate Finishes Z Style:Flat Concealed Pendent (See Table H) ft% Threads:1/2"NPT or ISO 7-1 R1/2 .- Nominal K-Factor:4.9(70.6 metric) Sensitivity ^ ilriOD Max.Working Pressure: 175 psi(12 bar) Fast-response -..- Min.Spacing:8 ft.(2.4 m) - !LA/Ail Fire&Emergency Se ice- I Temperature Rating . ;,�, _ i1:1_111/,18 Material Specifications 165°F (74°C)sprinkler .1 Therm alSensor:Nickel Alloy Solder Link 135°F (57°C)cover plate — Sprinkler Body:Brass Alloy Levers:Bronze Alloy Cover Plate Yoke:Brass Alloy Model RFC cover plate Sealing Assem bly:Nickel Alloy with PTFE • Load Screw:Bronze Alloy Sprinkler Wrench Towers:Copper Alloy Model FC � Pins:Stainless Steel - c Deflector:Bronze Alloy Listings and Approvals Bottom View ' t J o Cup:Steel cULus Listed �,r. Model RFC49 Sprinkler Corn ponentsand Dimensions Figure 3 f 2-5/16"(58 mm) Threads Dia. Body Cup�.1 f -_ mmi Tower 1 3/4"(44 mm)+/ 1/4"(6 mm) ,, Fusible Link N6.-_....41111r , Nominal face of fitting to ceiling �� Deflector(retracted) r v=v' 'v=v' 3/16"(5 mm) Pin(extended) ' J1 Deflector(extended) I�' Model RFC Cover Plate 3-5/16"(84 mm)Dia. Ceiling Model RFC49 Sprinkler Hydraulic Design Criteria Table D Minim urn Flow and Residual Pressure Max.Coverage Area Flow Pressure ft.x ft. gpm psi (m x m) (I/min) (bar) 16 x 16 13 7.0 (4.9 x 4.9) (49.0) (0.48) 16 X 16 SPACING @ .1 DENSITY = 25.6 GPM FLOW kJ.J A J.Jf ,VY.JJ 1J.UJ) 20 x 20 20 16.7 (6.1x 6.1) (75.7) (1.15) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of:(1)the flow listed in Table D above and(2)the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above,use the minimum required flow for the next larger max.coverage area listed. Bulletin 006 Rev.K ��';��'� Page 4 of 7 February 2017 www.reliablesprinkler.com Model RFC58 Residential Sprinkler Za 4 T:chnical Specifications Sensitivity i" St e:Flat Concealed Pendent Fast response 4I ft 45. tP Thr-<ds:1/2"NPT or ISO 7-1 R1/2 -r. Nom i :1 K-Factor:5.8(84 metric) Temperature Ratings 'Qin/ Max.W• king Pressure: 175 psi(12 bar) Ordinary: Min.Spac g:8 ft.(2.4 m) 165°F (74°C)sprinkler `,. rf , .-&Emergency Se ices 135°F (57°C)cover plate Material Speci ations Intermediate: ThermalSenso Nickel Alloy Solder Link 212°F (100°C)sprinkler ,!_ ++ Sprinkler Body:B :ss Alloy 165°F (74°C)cover plate Levers:Bronze Allo Yoke:Brass Alloy Cover Plate ri Sealing Assembly:Nick Alloy with PTFE Model RFC Cover Plate j Load Screw:Bronze Alloy Towers:Copper Alloy Sprinkler Wrench Pins:Stainless Steel Model FC Deflector:Chrome Plated Bronz= 'Hoy `� Cup:Steel Listings and Approvals Bottom View •:••,i� cULus Listed Cover Plate Finishes (See Table H) Model RFC58 Sprinkler Com ponents and Dim:nsions Figure 4 2-5/16"(58 mm)___J Dia. Threads Body Cup t .=7 1 - _ tri Tower Fusible Link ������ 1-7/8"(48 mm)+/-3/8" mm) i► ,� �� Nominal face of fitting to c-•ing Deflector(retracted) '— r_`—� i_ 1,.. ...m. .. ir ��\\\��. �� iiiiiiii 3/16"(5mm) Pin(extended) \\\\\\" 4� 7,,,,,,, ��� I I , ` hili,,, Deflector(extended) i H r'— i . . �6 xx3s b Model RFC Cover Plate 3-5/16"(84 mm)Dia. Ceiling Model RFC58 Sprinkler Hydraulic Design Criteria Table E Minimum Flow and Residual Pressure Max.CoverageAred2t Flow Pressure ft.x ft. gpm psi (m x m) (I/min) (bar) 16 x 16 16 7.6 (4.9x 4.9) (60.6) (0.53) 18 x 18 18 •.6 (5.5 x 5.5) (68.1) (0.06) 20 x 20 20 11.9 (6.1 x 6.1) (75.7) (0.82) Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of:(1)the flow listed in Table E above and(2)the flow required achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler. 2. For coverage area dimensions less than those listed above,use the minimum required flow for the next larger max.coverage area liste• Bulletin 006 Rev.K ��';��'� Page 5 of February 2017 www.reliablesprinkler.com ° CIF I/4 Cover Plate Finishesi'ici:40-30 Standard Finishes Special Application Finis White Polyester Off White Paint Black Paint Chrome Plated Bright Brass Finished Bronze B 4112(1310' Stainless Steel o4h"HNrcy Se ices Satin Chrome Clad(3) Paint(2) Notes: 1. Paint or any other coating applied over the factory finish will void all approvals and warranties. 2. Custom color paint is semi-gloss,unless specified otherwise. 3. Stainless steel clad cover plates are Type 316 Stainless Steel on the finished side and C102 Copper Allow on the back side.Cover plates are not listed or approved as corrosion resistant.Stainless steel clad cover plates are not available perforated. Installation Dimensions TableJ Recom mended Min.to Min.to Max. Cover Plate Cover Plate Max.Face Dropped Deflector Cover Hole Diameter Cover Plate Sprinkler Diameter Adjustment of Fitting to Distance below Model Plate inch in Ceiling inch Ceilingo) Ceiling Temperature Model (mm) (mm) (mm) inch inch Rating (mm) (mm) RFC30 3-5/16 2-5/8 1/2 1-1/2 to 2 1/2 to 1 135°F RFC43 RFC (84) (67) (13) (38 to 51) (13 to 25) (57°C) RFC49 135°F2 RFC58 RFC 3-5/16 2-5/8 3/4 1-1/2 to 2-1/4 1/4 to 1 (57°C) (84) (67) (19) (38 to 57) (6 to 25) or 165°F3 (74°C) Notes: 1. Face of fitting to ceiling dimensions are based on a nominal thread make up.Verify dimensions based on fitting and thread sealing method prior to installation.A 1/2"x 1/2" brass nipple extension(Reliable P/N 6999991900)is available where necessary for replacement of existing sprinklers. 2. For use with 165°F(74°C)temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 100°F(38°C). 3. For use with 212°F(100°C)temperature rated sprinklers with the Maximum Ceiling Temperature does not exceed 150°F(66°C). Installation Model RFC series sprinklers are intended to be installed in ac- Do not exceed the maximum recommended torque.Exceeding cordance with NFPA 13, NFPA 13R, or NFPA 13D, as well as the the maximum recommended torque may cause leakage or im- requirements of applicable authorities having jurisdiction. Mod- pairment of the sprinkler. Use care when inserting or removing el RFC series sprinklers must not be installed in ceilings with the wrench from the sprinkler to avoid damage to the sprinkler. positive pressure in the space above.Ensure that the 4 slots in the cup are open and unobstructed following installation.Model Install the cover plate by hand by pushing the cover plate into RFC series sprinklers are shipped with a protective cap that the cup and turning the cover in the clockwise direction until it should remain on the sprinkler until installed.The protective cap is tight against the ceiling. should be replaced following installation of the sprinkler and permanently removed only when the cover plate is installed and the sprinkler system is placed in service following construction. A.1. 'lo'location Model RFC series sprinklers are installed with the Model FC Model RFC series sprinklers are intended for installation where wrench.The use of any other wrench to installed Model RFC se- residential sprinklers are permitted or required by NFPA 13, ries sprinklers is not permitted and may damage the sprinkler. NFPA 13R, and NFPA 13D. The sprinklers are concealed pen- Temporarily remove the protective cap during installation of the dent residential sprinklers. sprinkler. Insert the Model FC wrench over the sprinkler until the wrench engages the body.Do not wrench any other part of the Model RFC 30, RFC43, and RFC49 sprinklers are available in sprinkler/cup assembly.The Model FC wrench is designed to ordinary temperature classification for installation where the be turned with a standard 1/2" square drive.Tighten the sprin- Maximum Ceiling Temperature does not exceed 100°F (38°C). kler into the fitting after applying a PTFE based thread sealant Model RFC58 sprinklers are available in either ordinary or in- to the sprinkler's threads.Recommended installation torque is 8 termediate temperature classification for installation where the to 18 ft/lb(11 to 24 N/m). Maximum Ceiling Temperature does not exceed 100°F (38°C) or 150°F (66°C), respectively. Bulletin 006 Rev.K �e';ab'� Page 6 of 7 February 2017 www.reliablesprinkler.com OK° CIF I/4 Wrench tF 41QOD Vail Fire&Emergency Se ices 04/11/18 Model FC Maintenance Guarantee Model RFC series sprinklers should be inspected and the For the Reliable Automatic Sprinkler Co.,Inc. guarantee,terms, sprinkler system maintained in accordance with NFPA 25. Do and conditions, visit www.reliablesprinkler.com. not clean sprinklers with soap and water,ammonia or any other cleaning fluids. Remove dust by gentle vacuuming. Replace Patents any sprinkler cover plate assembly which has been painted (other than factory applied)or damaged in any way.A stock of Model RFC30,RFC43,RFC49,and RFC58 sprinklers are spare sprinklers should be maintained to allow quick replace- covered by U.S.Patent No. 9,248,327 and U.S.Patent No. ment of damaged or operated sprinklers. Prior to installation, 7,275,603. sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to Model RFC30 and RFC43 sprinklers are additionally covered sprinklers that would cause improper operation or non-oper- by U.S.Patent No. 8,776,903. ation. Ordering Information Listings and Approvals Specify the following when ordering. Listed by Underwriters Laboratories, Inc. and UL Certified for Sprinkler Canada(cULus) • Model (RFC30,RFC43,RFC49,RFC58) UL • Temperature Rating Listing Category Cover Plate • Model RFC Residential Automatic Sprinkler • Temperature Rating UL Guide Number • Finish(See Table H) Sprinkler Wrench • Model FC VKKW v z co coco 0 N Bulletin 006 Rev.K �e1i��1e Page 7 of 7 February 2017 www.reliablesprinkler.com rift EP' fP5 Series 2000B-FP A-3120110 ithDouble Check Valve Assemblies 04/11�st . services Sizes: 1" -2" (25- 50mm) - t; g _. Features ; ,/ • Ease of maintenance with only one r �"v cover 1 • Top entry _ 2000B-FP • Replaceable seats and seat discs 11 r • Modular construction . ^"� !L • Compact design • ti. _+� • 1" —2" (25—50mm)Cast bronze f_. — - body construction • • r vr • Low pressure drop • No special tools required • Gear operated, slow close shutoffs • Pre-wired tamper sw itch(2)per Series 2000B-FP Double Check Valve Assemblies shall be installed at referenced cross- shutoff connections to prevent the backflow of polluted waterinto the potable watersupply.Only those cross-corrections identified by local inspection authorities as non-health hazard shall be allow edthe use of an approved double check valve assembly. Pressure — Temperature Check with local authority having jurisdiction regarding vertical orientation,frequency of Temperature Range:33°F—140°F testing or other installation requirements. (0.5°C—60°C) These valves meet the requirements of ASSE Std. 1015 and AWWA Std.C510 and are approved by the Foundation for Cross-Correction Control and Hydraulic Research at the Maximum Working Pressure: 175psi University of Southern California. (12.1 bar) Specifications Standards A Double Check Valve Assembly shall be installed at each noted location.The assembly shall consist of two positive seating check modules with captured springs and rubber seat AWWA Std. C510, IAPMO PS31 discs.The check module seats and seat discs shall be replaceable.Service of all internal components shall be through a single access cover secured with stainless steel bolts.The assembly shall also include two resilient seated gear operated slow close isolation valves and four resilient seated test cocks.The assembly shall meet the requirements of ASSE Std. 1015 and AWWA Std.C510. Approved by the Foundation for Cross-Comection Control and Hydraulic Research at the University of Southern California.Assembly shall be an Ames Company Series 2000B-FP. Approvals NOTICE 0,„ss(F,Fo The information contained herein is not intend- el® O c ® Us ed to replace the full product installation and cus safety information available or the experience 1015 B64.5 1" -2" of a trained product installer.You are required to thoroughly read all installation instructions Approved by the Foundation for Cross-Connection Control and Hydraulic Research at and product safety information before begin- the University of Southern California. ning the installation of this product. Horizontal approval on all sizes. Inh Name Contractor Job Location Approval Engineer Contractor's P.O.No. Approval Representative Ames Fire&Waterworks product specifications in U.S.customary units and metric are appro timate and are provided for reference only.For precise measurements,please contact Ames Fire&Waterworks Technical Service.Ames Fire&Waterworks reserves the right to change or modify prodict design,construction,spedfications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames Fire&Waterworks procbcts previously or subsequently sold. °F I/4 .......0" f, two,' Dimensions - Weights z rift 111111 • E 1 111111 PI z e' l ej%l !Hi II .� , •kii `_ � — i `� �` 'J I 0 01 I����• i '' I��,�I 'a, X07„ �Il��fllllll�l �lll�l��llhll�� II B 101'.�!� •III,liIII�`� �i&i Ih'I IILAIAIII.,e&'mergencyServices :116111111111111111111111rl���, Il� D P • Iii I, G I �� �I „I_ - ,i .—I. A I MODEL SIZE DIMENSIONS WEIGHT A B C D E F G H I in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. 2000B-FP 1 25 131/4 337 4%z 114 3%z 89 1 25 7' 191 5% 146 2'/8 73 2'/e 73 14% 365 12.2 5.5 2000B-FP 114 32 15% 397 53/6 136 33/4 95 1% 41 9' 241 61/6 154 2'/8 73 33/6 81 16% 419 17.3 7.8 2000B-FP 1%z 40 16% 416 5% 143 4 102 1% 41 9% 248 61/4 159 2% 73 33/6 86 17 432 19 8.6 2000B-FP 2 50 191% 486 61 165 41/4 108 21/4 54 13% 340 6%z 165 2%6 73 3% 92 19% 495 26.4 12 Strainer sold separately Capacities As compiled from documented Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California lab tests. *Typical maximum system flow rate(7.5 feet/sec.,2.3 meters/sec.) kPa psi ,, 1” (25mm) kPa psi 1'/s" (40mm) co 110 16 83 12 _i 83 12 Cl) 69 10 y 69 10 0 3 55 8 55 8 J N 41 6 N 41 6 d 28 4 3 28 4 �.-.-'-• 0- 14 2 N 14 2 N 0 0 OP 0 5 10 15 20 25 30 35 40 45 50 55 60 gpm Il AP 10 20 30 40 50 60 70 80 90 100 110 120 gpm 0 19 38 57 76 95 114 133 152 171 190 209 228 Ipm 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps 5 7.5 10 15 fps Flow Rate 1.5 2.3 3.0 4.6 mps Flow Rate 8 PSI LOSE @ 102.4 GPM kPa psi 11/4" (32mm) kPa psi 2"(50mm) 96 14 * 83 12 N 83 12 vi 69 10 Cl) 69 10 1 _1 55 8 y 55 8 2 41 6 41 6 Cl) 28 4 in 28 4 �- Cl) 14 2 O.112 14 2 a 0 0 0 25 50 75 100 125 150 175 200 gpm 0 0 AP 0 95 190 285 380 475 570 665 760 Ipm �P 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm 5 7.5 10 15 fps 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm 1.5 2.3 3.0 4.6 mps 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps Flow Rate Flow Rate NOTICE Inquire with governing authorities for local installation requirements A AMES FIRE&WATERWORKS A Watts Water Technologies Company USA:Backflow Tel:(978)689-6066•Fax:(978)975-8350•AmesFireWater.com USA:Control Valves Tel:(713)943-0688•Fax:(713)944-9445•AmesFireWater.com Canada: Tel:(905)332-4090•Fax:(905)332-7068•AmesFireWater.ca Latin America: Tel:(52)81-1001-8600•Fax:(52)81-8000-7091 •AmesFireWater.com ES-A-2000B-FP 1536 ©2015 Ames Fire&Waterworks *" OFP4, ..„,0„..._ „. WILKINS Water PressurE ac 47 a ZURN,. company 0 with Inte•ralB -• ,V Ift SPECIFICATION SULUMI I IAL 4o 51 3QO0 IP ti 1 APPLICATION Vail Fire e&Emergency Services '. . Designed for installation on potable water lines to reduce high inlet pressure to a lower outlet pressure.The high flow ,. „ capacity makes this device most suitable for industrial wa- :1°� ,,:413" . �,'!,V, ter lines and commercial irrigationsystems.The directact- ,' ing integral by-pass design prevents buildup of excessive system pressure caused by thermal expansion. The bal- FEATURES anced piston design enables the regulator to react in a Sizes: ❑ 1/2" ❑ 3/4" ❑ 1" ❑ 1 1/4" smooth and responsive manner to changes in system flow ❑ 1 1/2" ❑ 2" ❑ 2 1/2" ❑ 3" demand, while at the same time, providing protection from Maximum workingwater pressure 300 psi inlet pressure changes. Maximum workingwater temperature 180° F STANDARDS COMPLIANCE Reduced pressure range 25 psi to 75 psi • Factorypreset(fieldset 2 1/2" &3") 50 psi ASSE®Listed 1003 (1/2" thru 2 1/2" ) Threaded connections(FNPT) ANSI B1.20.1 • IAP MOO Listed(1/2" thru 3" ) Copperconnections(FC) ANSI B 16.22 • City of Los Angeles Approved(1/2"thru 3") CPVCtailpiece:Max.hotwater temp. 180°F @ 100 psi CSA®Certified(1/2"thru2") Cold water rated temp. 73.4°F @ 400 psi MATERIALS OPTIONS(Suffixescan be combined) Main valve body Cast bronze ASTM B 584 ❑ - standard with single union FNPTinletx FNPT Access covers Cast bronze ASTM B 584 outlet(1/2"thru 2")and less union(21/2" &3") Brass ASTM B 16 ❑ C - copper sweat connection(1/2"thru 2") Fasteners Stainless steel, 300 series ❑ HR - 75 psi to 125 psi spring range, factory set Stem&plunger Cast bronze ASTM B 584 at 85 psi (fieldset 2 1/2" &3") Brass ASTM B 16 ❑ HLR - 10 psi to 125 psi spring range, factory set Elastomers Buna Nitrile(FDA approved) at 50 psi EP DM(FDA approved) ❑ HT - 210°F maximum temp Cap gaskets Natural vulcanized fibre ❑ L - less integral by-passcheck valve(3/4"-2") Acetal(DelrinTM 500), NSF Listed ❑ LPV - 210°F maximum temp with 10 psi to 35 psi Springs Oil temperedwire,ASTMA229 spring range, factory set at 20 psi Seat Stainless steel, 300 series ❑ LPC - 180°F maximum temp with 10 psi to 35 psi spring range, factory set at 20 psi - D ❑ SC - sealed cage bell housing and stainless steel , 11.1 adjustment screw al ❑ SW - made for salt water service ❑ YSBR - with bronze"Y"strainer on inlet ❑ 510 - 400 psi inlet rating and 75 psi to 125 psi it spring range, factory set at 85 psi B = (fieldset 2 1/2" &3") ❑ P - tappedand plugged forgauge1 r , ❑ CP VC - CPVCtailpiececonnection(3/4"-1") I 1 D ,> WILKINS ACCESSORIES �5OO U Repairkit(rubberonly) v DIMENSIONS&WEIGHTS(do not include pkg.) I DIMENSIONS(approximate) SIZE WEIGHT CONNECTIONS A B C D in. mm in. mm in. mm in. mm in. mm lbs. kg. 1/2 15 SINGLE UNION 4 1/2 108 6 152 1 5/8 _ 41 2 3/4 70 3 1.5 3/4 20 SINGLE UNION 4 5/8 118 6 152 _ 1 1/8 _ 29 2 3/4 70 _ 4 2.0 1 25 SINGLE UNION 5 1/8 130 6 7/8 175 1 5/8 41 3 5/16 84 6 3.0 1 1/4 32 SINGLE UNION 6 5/16 160 7 1/4 184 _ 1 3/4 _ 45 4 _ 102 _ 7 3.0 1 1/2 40 SINGLE UNION 8 5/16 211 10 254 1 7/8 48 5 127 14 6.5 2 50 SINGLE UNION 9 1/2 241 10 3/4 273 2 1/8 54 6 1/2 165 20 9.0 2 1/2 65 LESS UNION 10 254 14 1/2 368 3 76 8 203 28 12.5 3 80 LESS UNION 11 1/8 283 16 406 _ 3 1/2 _ 89 8 _ 203 _ 44 20.0 DOCUMENT#: REVISION: REG-500 6/06 Page 1 of 2 .1,. FLOW CHARACTERISTICS a. itli OF .... MODEL 500 1/2"THRU 3" (STANDARD& METRIC) ri,FLOW RATES(Us) 4 •b 3.2 6.3 9.5 12.6 15.8 "' 114#�' 20 - 1/2" _ 3/4" 1" - 1 1/4" 1 1/2" - 2" 2 1/2" 3" AM N CD 15-(15mm (20mm 25mm (32mm 40mm) -(50mm) (65mm 80mm ;,tf. ergen y Services = ,. ..,... ..---...---- 0_ ,.._,� _ CI4 Q d i---- LL 10 69 U- LL //-�I-i: LL 5 _� 35 a /// _ a 0 0 50 100 150 200 250 300 11 PSI LOSE @ 102.4 GPM FLOW RATES(GPM) TYPICAL INSTALLATION Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted in accordance with the manufacturers'instructions and the latest edition of the Uniform Plumbing Code. The assembly shall be installed with sufficient side clearance for testing and maintenance. The Model 500 may be installed in any position. If installed in a pit or vault, specify the "SC" sealed cage option. Multiple installations are recommend for wide demand variations or where the desired pressure reduction is more than 4 to 1 (i.e.: 200 psi inlet reduced to 50 psi outlet). CAUTION: Anytime a reducing valve is adjusted, a pressure gauge must be used downstream to verify correct pressure setting. Do not bottom adjustment bolt on bell housing. i 1. Site o MI II1I=1I=1E MODEL 975XL o I_I II_I I_ 11 RPZ BACKFLOW PREVENTER OPTIONAL PRESSURE , 4 II ■IIIIII I1IIIII IIS III, PROTECTIVE I GAUGE e - ;� g ENCLOSURE ,�. o ■ �loo��l!i�, N IIIMI, SHUT-OFF VALVE 50 SHUT-OFF VALVE ■ it I I117 ` 8 OPTIONAL PRESSURE GAUGE MiEl '�■ .. oiII MODEL DU DIELECTRIC UNION 6�� 12"MIN. 1 ° - 30"MAX. • :ulr lei VERTICAL INSTALLATION =TIEM IE111-1 -1 I I-1 I I I-1 I-1 I f -1 I H 11= 111=111 L MEW =1 1=1 I =111-111 111 -111-1 111=111=' MODEL 500 TO HANDLE LOW =111= 111- -1, -1 =1 DEMANDS(SET @ 65 PSI) - DIRECTION OF FLOW gliplipaillEallimilli TYPICAL INSTALLATION 1 1 A a1 1 s ■.■ MODEL 500FC TO HANDLE DIRECTION OF FLOW HIGH DEMANDS(SET @ 55 PSI) SPECIFICATIONS BATTERY INSTALLATION The Pressure Reducing Valve shall consist of a bronze body and bell housing, a separate access cover for the plunger and a bolt to adjust the downstream pressure.The bronze bell housing and access cap shall be threaded to the body and shall not require the use of ferrousscrews.Theassembly shall be of the balanced piston design and shall reduce pressure in both flow and no-flow conditions. The assembly shall be accessible for maintenance without having to remove the body from the line. The Pressure Reducing Valve shall be a WILKINS Model 500. Page 2 of 2 WILKINS a Zurn company,1747 Commerce Way, Paso Robles,CA 93446 Phone:805/238-7100 Fax:805/238-5766 IN CANADA:ZURN INDUSTRIES LIMITED,3544 Nashua Dr.,Mississauga,Ontario L4V 1L2 Phone:905/405-8272Fax:905/405-1292 Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) - Website: http://www.zurn.com tglo OF P4 t z SYSTEM - . �$ SENSOR . , • j-kin 11:1 Vail Fire&Emergency Services 04/11/18 T-Tap Waterflow Detectors _ • ,r -11 r System SensorT-Tap Waterflow Detectors are designed for primary signaling in residential systems and branch line signaling in larger systems. :..• Features Both the WFDT retard model and the WFDTNR non-retard model fit •Sealed retard mechanism(Model WFDT) any tee that has a 1"NPT branch,including: 1",11/4",1'/"and 2"NPT threaded ferrous and brass tees;1",11/4",1'/z"and 2"copper sweat •Visual switch activation(Model WFDT) tees;Tyco,Spears,Victaulic and NIBO brand 1"CPVC tees;and 11/2" •Twelve different flexible plastic paddles polybutylenetees. •Vertical or horiz ontal mount Design.The design of the WFDTand WFDTNR makes them easy •Durable,tamper-resistant enclosure to install and simple to maintain.Either can be mounted in the •Dual SPDTswitches in durable terminal block vertical or horizontalposition.Twoconduit openings permit easy •Sizes marked on flexible plastic paddles attachment to the local alarm system.The retard mechanism(Model WFDTonly)and switch assemblies are field-replaceable. •100 percent synchronization activates both alarm panel and local bell •Accommodates up to 12 AWG wire Features.Twelve different flexible plastic paddles fit 1",1'/4",1'/"and 2"tees.Sizesare marked clearly on the paddles for ease of installation. Plastic paddles slip over the actuating lever and are securelyfastened with one screw.The handy depth gauge ensures the proper installation depth and clearance of the detector to the tee. Construction.TheWFDTand WFDTNR include a durable,tamper- resistant enclosure and rugged switch assembly.The robust covers completely enclose the electrical components to keep out dust and dirt.Improved self-guiding security screwsand removal tools make the detectors resistant to tampering and simplify field maintenance. Dual SPDT switches are enclosed in a durable terminal block for added strength. Agency Listings U L MEA LISTED �R t approved 5739 .. 7770-1653:114 167-93-E T-Tap Waterflow Detector Specifications "7 II& 6P5 Architectural/Engineering Specifications Model shall be a WFDT or WFDTNR as manufactured by System Sensor.T-tap waterflow detectors shall be installed on a tee that has a 1"NPT br. ° oD 1",114",1Y"or 2"threadedferrous or brass tee;1-2"copper sweattees;Tyco,Spears'Victaulic®and NIBCO brand 1"CPVCtees;or 11/2"polybutylene designated on the drawings and/or as specified herein.Detectors shall mount on any clear pipe span of the appropriate size,either a vertical ocjr on '. : al I e mergency Services least6""from any fittings orvalvesthatmay change waterdirection,flow rate,orpipe diameter ornocloser than 24""from a valve or drain.Detegt41ryslg have a sensitivity in the range of4 to 10 gallons per minute and a static pressure rating of 250 psi.The retardt-tap detector shall be a sealed mechanical pneumatic unit with visual indication of actuation.The actuation mechanism shall include a polyethylene vane insertedthrough the tee fitting and connected by a mechanical linkage to the delay mechanism.The non-retard t-tap detector shall respondwith no time delay to waterflow in the specified direction and range.Outputsshall consist of dual SPDT switches(Form C contacts).Twoconduit entrances(one of which is a knockout type)for standard fittings of commonly used electrical conduit shall be provided on the detectors.A grounding provision is provided.All detectors shall be listed by Underwriters Laboratories for indoor or outdoor use. Physical/Operating Specifications Static Pressure Rating 250 PSI OperatingTemperature Range 32°F to 120°F(0°Cto 49°C) Maximum Surge 18 FPS Enclosure Rating UL indoor/outdoor rated Triggering Threshold 4-10 GPM Cover Tamper Switch UL models:optional P/N546-7000 Bandwidth(Flow Rate) ULC/Canadian models:factory installed Ov erallDimensions, WFDT:4.5"H x 3.75"W x 6.7"L Sery iceUse Automatic Sprinkler:NFPA 13 Installed (11.4cm H x 9.5cm W x 17cm L) One orTwoFamily Dwelling:NFPA 13D WFDTNR:3.75"H x 3.25"W x 4.25"L Residential Occupancies up to 4 Stories:NFPA 13R (9.5cm H x 8.2cm W x 10.8cm L) National FireAlarm Code:NFPA 72 Contact Ratings Two sets of SPDT(Form C) Shipping Weight WFDT:2.6 lbs.(1.2 kg.) 10.0 A @ 125/250 VAC WFDTNR:1.5 lbs.(0.7 kg.) 2.5A@24VDC Compatible Tee Threadedferrous and brass tees,copper Warranty 3 years Fittings sweattees,CPVCtees,and polybutylene tees Conduit Entrances Twoopeningsfor l "conduit. U.S.Patent Numbers 5,213,205 Electrical Connections forWFDT Delay AdjustmentDial SSM24-X NOTE:COMMON AND B-NO DELAY /1 I—I r--- UL-LISTED _ UL-LISTED CONNECTIONS WILL CLOSE ADJUSTMENT COMPATIBLE SSV120-X WHEN VANE IS DEFLECTED,I.E., DIAL ON DIAL IS App CONTROL P ANEL WHEN H WATER P IS FLOWING.DUAL ,O0,1 DELAY IN SEC.04, SWP OWER + APPLICATIONS TO BE COMBINED '4J�4S� 0 �S 9TF 24VDC OR ON A SINGLE DETECTOR. 120VDC - I SUGGESTED EOL CONTACT RATINGS { Q INITIATING+ RESISTOR 125/250 VAC 10 AMPS O 7- LOOP _ II,^,,A,11,1I 24VDC 2.5 AMPS �vV — i �OO ' SCHEMATIC OFNO INDIVIDUAL �Ac0,, �O hh HH�� dill SWITCH IN g dill NO DITION LOW L `U Lam" L�`7 `' �' CONDITION ,6,_BN. -V— 45 -- A BM�BI A. BREAKWIRE.Aw 41 SBRaII swag 2 0, SHOWN FOR ,• bads° V SUP ERVISIONOF 3• cwrw CONNECTION.N.DO j i��i NOT STRIP P EDNIRE O........R°) ( we, SWITCH LEADS TO EXTEND NOTE:RETARD TIME MAY EXCEED 90 SECONDS.ADJUST BEYONDAND VERIFY THATTIME DOES NOT EXCEED 90 SECONDS. NUMBER ON DIAL IS APPROXIMATE TIME DELAY IN 0• —.0 HOUSING.HOOPWIR DO NOT SECONDS W!THAN ACCURACY OFN-50%. S. Ordering Information UL Model ULC Model Description WFDT WFDTA Waterflow Detector,Fits 1",11/4",11/2",2"ferrous and brass threaded tees;1",11/4",11/",2"copper sweat tees;1"CPVCtees;and 11/2"polybutylene tees WFDTNR — Waterflow Detector,non-retard,fits same tees as Model WFDT Accessories Description A77-01-02 Replacement terminal block for WFDT A77-01-08 Replacement terminal block for WFDTNR A3008-00 Replacement retard mechanism PRK9 Replacement paddle kit–12 paddles for WFDT and WFDTNR(seeWFDTfor siz es) 546-7000 Covertamper switch kit for WFDT S07-66-02 Replacement tamper screws for covers of WFDT,WFDTNR WFDW Replacement tamper-proof wrenchfor cover of WFDT,WFDTNR WFDN4 NEMA-4 gasket kit C58-164-01 Replacement metal cover C58-195-01 Replacement plastic cover(WFDTNR) Spears°is a registeredtrademark of the Spears Manufacturing Company.Victaulic°is a registered trademark of the Victaulic Company of America. *-Th SYSTEM @2009 System Sensor. 3825 Ohio Avenue•St.Charles,IL 60174 Product specifications subject tochangev,thout notice.Usit sysoemsensoccorn for ....), SENSOR® Phone:800-SENSOR2•Fax:630-377-6495 current product information,including the latest version of this data sheet. A05-0195-013.1/09•#1923 o °F1/4/ N 1 BCD _ AHEAD OF THE FLOW® Z ill 11111 4. 300 lb. WWP Bronze Ball Valvesw, 1:351 fP5 Fire Protection Valve • Threaded or Grooved Body Style • Full Port Design 1" - 2" • De Re " "NOD 111 Standard Port Design 2h/ • Accepts Internal Supervisory Switches Vail Fire&Emergency Services "---- 04/11/18 300 PSI/20.7 Bar Non-Shock Cold Water (cu. A � CONFORMS TO MSS SP-110 • FM APPROVED• ,.....: UL LISTED FOR INDOOR AND OUTDOOR SERVICE • CALIFORNIA STATE FIRE MARSHAL LISTING NO. 7770-1243:103 -� APPROVED BY NEW YORK CITY M.E.A. 218-04-E WITH APPROPRIATE NYC INDICATOR. ' t;.1.14\-, KT-505-W-8 MATERIAL LIST Threaded PART SPECIFICATION 1. Body Bronze ASTM B 584 Alloy C84400 2. Ball Chrome Plated Brass ASTM B 124 Alloy C37700 3. Seat Ring Carbon-filled TFE KG-505-W-8 4. Thrust Washer Reinforced TFE Grooved 5. Stem Bronze ASTM B 371 Alloy C69430 0 6. Stem 0-Ring Nitrile 3a. m 7. Retaining Washer Brass 0 M 8. Retaining Ring Steel 0 9. Ground Wire Screw Steel oo I 10. 505-8 Act Assy. Brass 0 �'O � -.I-n-�1 4 u 11. Body End Bronze ASTM B 584 Alloy C84400 '%AN --„-,- 12. Mounting Screw Steel © l�iiin 1i1I1 i 13. Lock Washer Steel 0 ��I11110111g111 o %--,,,. yp ... 1 14. Handle Pin Brass 15. Hand Wheel Steel/plastisol coated(1174'-2Yz') -B Brass Tee Handle(1") 16. Indicator Flag Painted Steel 2.37 e 6 e, 17. Body Gasket Elastomer 18. Lead Screw 0-Ring Nitrile CNV 7-k w �d- 19. Thrust Washer Anti-friction Polymer 119110NMELFAR 20. Cover Gasket Neoprene • 610.11.9.44- .W11 MAk`11=: 1 - 21. Flag Seal 0-Ring Nitrile •E• I� ir 22. Tamper-Proof Screw Stainless Steel 23. Pipe Plug(-4 units) Stainless Steel(Not shown) ��� ®m m Refer topage 41 for details for TS-2M Sw itchKit. \J KT-505W DIMENSIONS-WEIGHTS-QUANTITIES Dimensions A B Weight Size Threaded Grooved Threaded Grooved C D E F G Cvt Threaded Grooved Box Master In. mm. In. mm. In. mm. In. mm. In. mm. In. mm. In. mm. In. mm. In. mm. In. mm. Value Lbs. Kg. Lbs. Kg.Qty.Ctn.Qty. 1 25 3.33 85 - - 1.66 42 - - 2.11 54 3.81 97 2.31 59 6.14 156 1.75 44 57 6.1 2.77 - - 1 10 11/4 32 4.18 106 - - 2.09 53 - - 2.46 62 4.21 107 2.72 69 6.33 161 3.50 89 103 7.1 3.23 - - 1 8 11/2 40 4.70 119 - - 2.35 60 - - 2.95 74 4.46 113 2.97 75 6.33 161 3.50 89 143 8.1 3.68 - - 1 4 2 50 5.15 131 6.71 170 2.57 65 3.36 85 3.69 94 4.67 119 3.18 81 6.33 161 3.50 89 245 10.7 4.86 9.7 4.40 1 4 2Y2 65 5.65 144 7.28 185 2.92 74 3.64 93 3.75 95 4.67 119 3.18 81 6.33 161 3.50 89 183 13.0 5.91 12.6 5.73 1 4 t Note:Cv is defined as the flow in GPM that a valve w illcarry w itha pressure drop of 1.0 psi w henthe media is w aterat 60°F. 4UL APPROVED NIBCO INC.WORLD HEADQUARTERS•1516 MIDDLEBURY ST.•ELKHART,IN 46516-4740•USA•PH:1.800.234.0227 6 TECH SERVICES PH:1.888.446.4226•FAX:1.888.336.4226•INTERNATIONAL OFFICE PH:+1.574.295.3327•FAX:+1.574.295.3455 www.nibco.com 0400F 1/4, WILKINS 1 � fri. a ZURN. company PRESSURE SPECIFICATION SUBMITTAL °J-kop j Vail Fire&Emergency Services °o ° 04/11/18 nom eo. _ psi • Model HGI-25 Model 92-25 & 92-25A Hose Bibb Pressure Gauge with Pressure Gauge Maximum pressure indicator Application: Application: Designedfor measuring water system pressure within a build- Designed for accurately measuring system pressure down- ing. The 3/4"hose adapter allows for direct connection to a stream of a Pressure Reducing Valve.The Pressure gauge hose bibb or water heater drain valve.The indicator needle can be threadeddirectly to all WI LKI NSPressure Reducing identifies the highest pressure reached within the system. Valves supplied with tapped or plugged option. For water I deal for registering maximum system pressure caused by service only. thermalexpansionor pressure spikes.The maximum pres- sure indicator needle can be reset by turning the external knob counter clockwise.For water service only. • I dentifywater service pressure to determine if a FEATURES pressure regulator is needed. • Troubleshoot pressure problems. Sizes: ❑ 1/8" NPT(Model 92-25A) • I dentifythermal expansion problems. ❑ 1/4" NPT(Model 92-25) FEATURES Dial size: 2" range:0-100 psi; minimum 2 psi graduation Sizes: ❑ 3/4" Hose Connection Dial size: 2" NOTE:APressure Regulator should be installed when sup- Range: 0-200 psi; minimum 2 psi graduation ply pressure exceeds 60psi. 3/4"hose adaptor Knurledfor easy gripping Sold in convenient pegboard packaging p HOSE BIBB "'F• HOSE BIBB HOSE BIBB 1111111iI I :Ip11 .111 PRESSURE GAUGE 4 MODEL BR4 MODEL BR4 — REGULATOR REGULATOR Hill: II PRESSURE SHUT-OFF ' SHUT-OFF ' GAUGE WATER VALVE - I WATER VALVE METER �IF METER Ila w I y DIRECTION OF FLOW DIRECTION OF FLOW 14> TYPICAL INSTALLATION(MODEL HGI-25) TYPICAL INSTALLATION(MODEL 92-25&92-25A) DOCUMENT#: REVISION: MIS-GAUGE 10/02 WILKINS OPERATION OF ZURN INDUSTRIES,1747 CommerceWay,Paso Robles,CA 93446 Phone:805/238-7100 Fax:805/238-5766 IN CANADA:ZURN INDUSTRIES LIMITED,3544 Nashua Dr.,Mississauga,Ontario L4V 1L2 Phone:905/405-8272Fax:905/405-1292 Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Website: http://www.zurn.com � F P4 Mod . /,.....,,40, . WILKINS Swing Aw ,e a ZURN company For Li.uid or Ga. SPECIFICATION SUBMITTAL °Jillopl a Vail Fire&Emergency Services APPLICATION 04/11/18 11147 Designed for installation on liquid or medical gas lines as a ,.� means of positive shut-off. The "swing away" design al- �� ' lows for repair and maintenance without removing the device from the line. MATERIALS FEATURES Main valve body Forged brass ( '/z"-1") Sizes: ❑ '/2" ❑ 3/4" ❑ 1" ❑ 11/2" , Cast bronze ASTM B 584 (1 /2 3 ) ❑ 2" ❑ 2 �/2" ❑ 3" Ball Brass ASTM B 16, chrome plated Seat& packing Teflon Maximum pressure 400 PSI WOG 0-rings Buna Nitrile, NSF Listed Copper connections (FC) ANSI B16.22 SPECIFICATION The three piece swing away ball valve shall consist of a OPTIONS copper alloy body, two tailpieces, a hard-chromed copper alloy ball, two Teflon seats, a stem and coated handle. The ❑ - with female copper inlet x outlet stem shall be blow-out proof and the ball &seats replace- ❑ CL - with copper"L"tube extensions able in-line without the use of special tools. Tailpieces shall be designed to accept sweated copper tube or provided ACCESSORIES with copper tailpiece extensions. The three piece swing away ball valve shall be a WILKINS Model 800C. ❑ Repair kit; o-rings, stem and seats ❑ Bracket for locking ball valve handle in open position I- C (Model BVLCK) ❑ Bracket and padlock (Model BVLCKP) ./..- -i- Ho IIII1 0! t DIMENSIONS &WEIGHTS (do not include pkg.) A DIMENSIONS (approximate) SIZE A B C WEIGHTS in. mm in. mm in. mm in. mm lbs. kg. 1 /2 i 15 2 1/8 54 i 1 5/8 41 3 7/8 i 98 1 0.5 3/4 20 2 3/4 70 1 7/8 48 3 7/8 98 1 0.5 1 25 3 1/2 89 2 51 4 1/2 114 2 1.0 1 1/2 40 4 7/8 124 2 7/8 73 6 152 7 3.0 2 50 5 1/2 140 3 1/8 79 6 152 9 4.0 2 1/2 65 6 3/8 162 3 5/8 92 6 152 17 8.0 3 80 6 3/4 172 4 3/8 111 12 305 22 10.0 DOCUMENT#: REVISION: BV-800C 5/05 WILKINS OPERATION OF ZURN INDUSTRIES,1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766 IN CANADA:ZURN INDUSTRIES LIMITED,3544 Nashua Dr.,Mississauga,Ontario L4V 1L2 Phone:905/405-8272 Fax:905/405-1292 Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Website: http://www.zurn.com saki OF pi.. t � Ipil AIILAD OF NIL FLOW-„f S -4 eC RTF 0 Copper Water Tube continuedVail Fire&Emergency Services 14111: DIMENSIONAL.DATA-COPPER WATER TUBE-.TYPE"M" TYPE"M" Hard Drawn Only: 20-ft.(6.1m)Straight Lengths Usage: Forgeneral purpose plumbing,heating and drainage installations. Tolerances Hard Drawn (Hard Drawn Only) Outside Tubing OD Nominal Wall Weight Bursting Safe Working Nominal Diameter Thickness Per Foot Pressure" Pressures Water Tube Min. Max. Size(In Inches) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Lb (kg) psi (bars) psi (bars) 1/4 0.375 (9.53) 0.373 (9.47) 0.376 (9.55) N/A N/A N/A N/A N/A N/A N/A N/A 3/8 0.500 (12.70) 0.497 (12.62) 0.501 (12.73) 0.025 (0.64) 0.145 (0.07) N/A N/A 855 (59) 1/2 0.625 (15.88) 0.622 (15.80) 0.626 (15.90) 0.028 (0.71) 0.204 (0.09) 6135 (423) 741 (51) 5/8 0.750 (19.05) 0.747 (18.97) 0.751 (19.08) N/A N/A N/A N/A N/A N/A N/A N/A 3/4 0.875 (22.23) 0.872 (22.15) 0.876 (22.25) 0.032 (0.81) 0.328 (0.15) 4717 (325) 611 (42) 1 1.125 (28.58) 1.122 (28.50) 1.127 (28.63) 0.035 (0.89) 0.465 (0.21) 3865 (266) 506 (35) 11/4 1.375 (34.93) 1.372 (34.85) 1.377 (34.98) 0.042 (1.07) 0.682 (0.31) 3875 (267) 507 (35) 11/2 1.625 (41.28) 1.621 (41.17) 1.627 (41.33) 0.049 (1.24) 0.940 (0.43) 3550 (245) 497 (34) 2 2.125 (53.98) 2.121 (53.87) 2.127 (54.03) 0.058 (1.47) 1.460 (0.66) 2935 (202) 448 (31) 21/2 2.625 (66.68) 2.621 (66.57) 2.627 (66.73) 0.065 (1.65) 2.030 (0.92) 2800 (193) 411 (28) 3 3.125 (19.38) 3.121 (79.27) 3.127 (79.43) 0.072 (1.83) f 2.680 (1.22) 2665 (184) 380 (26) 31/2 3.625 (92.08) 3.621 (91.97) 3.627 (92.13) 0.083 (2.11) 3.580 (1.62) N/A N/A 378 (25) 4 4.125 (104.78) 4.121 (104.67) 4.127 (104.83) 0.095 (2.41) 4.660 (2.11) 2215 (153) 377 (26) 5 5.125 (130.18) 5.121 (130.07)1 5.127 (130.23) 0.109 (2.77) 6.660 (3.02) 2490 (172) 349 (24) 6 6.125 (155.58) 6.121 (155.47) 6.127 (155.63) 0.122 (3.10) 8.920 (4.05) 2000 (138) 328 (23) 8 8.125 (206.38) 8.119 (206.22) 8.127 (206.43) 0.170 (4.32) 16.500 (7.48) 2285 (158) 344 (24) 10 10.125 (257.18) 10.119 (257.02)- 10.127 (257.23) 0.212 (5.38) 25.500 (11.61) N/A N/A 344 (24) 12 12.125 (307.98) 12.119 (307.82) 12.127 (308.03) 0.254 (6.45) 36.700 (16.65) WA N/A 345 (24) Note:Information and data contained in these charts,as taken from ASTM Specifications B 88. Rated internal pressure for copper water tube based on the strength of the tube alone and applicable to systems using suitable mechanical joints. "'Based on actual laboratory test data provided by Copper Development Association,Inc. 'Based upon 150°F(65.8°C)with an allowable stress of 9500 psi(668 kPa), U.S.customary units in this document are the standard;the metric units are provided for reference only.The values stated in each system are not exact equivalents. II NIOCO INC.WORLD HEADQUARTERS•1516 MIDDLEBURY ST.•ELKHART•IN 46516-4740•USA•PH:1.800.234.6227 TECH SERVICES PH:1.888.446.4226•FAX:1,8002340551•INTERNATIONAL SERVICE PH.+1 574.295.3221 •FAX +1,574295.3455 ! OI 4 ta% Submittal497411:b Package ices 04/11/18 ProPress° System ❑ Potable Water ❑ Low Pressure Steam ❑ Hydronic Heating ❑ F ire Protection ❑ Chilled Water ❑ Vacuum ❑ Compressed Air ❑ Corgon ❑ Nitrogen N2 ❑ Oxygen 02 (non medical) ❑ Argon ❑ System Data Sheet 2 ProPress Product Instructions ProPress for 1/2" to 2" copper tubing 3 ProPress XL for 21/4" to 4" copper tubing 4 ProPress° Dimensional Documentation ProPress for 1/2" to 2" copper tubing 5 ProPress XL for 21/4" to 4" copper tubing 17 Viega Limited Warranty ProPress° FittingsAnd Valves 23 Viega LLC,100 N. Broadway, 6t" Floor• Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 1 of 23 " CIF I/4 :04.14(1140. )411tirle. Submittal Package Va = ices 04/11/18 System Data Sheet ProPress®and ProPress XL(Copper)are safe,reliable and economical copper pipe installation systems that use modern cold press connection technology. Viega®ProPress fittings are for use with type K,L and M hard copper tubing from 1/2" to 4" and soft copper tubing in 1/2"to 11/4" _ _$^ diameters.All tubing must comply with the ASTM B88 standard. ProPress fittings are approved for installations in both above and r,° _r,,,, +� below ground applications. Per code, local inspector approval ' -; must be obtained prior to installation below ground. r / ' ProPress has been used in Europe since the late 1980s and �, t ry ` . ` in the United States since the late 1990s for a variety of 11-'0-• `_ ' _ - • sa applications. Backed by two plumbing leaders with over 175 years of combined excellence. Listings and Certificates • NSF 61G • IAPMO PS117 • UL 213 • FM Class 1920 • ICC LC 1002 Approved Applications: • CSA MSE-13 • Potable Water • ABS • Hydronic Heating (w/Glycol) • Chilled Water International Listings and Certificates • Compressed Air • Deutsch Verein des Gas-und Wasserfachese.V. • Non-medical Gases (DVGW) • Fire Sprinkler(175 PSI maximum) • Lloyd's Register(LR) • Low Pressure Steam(15 PSI maximum) • Det Norske Veritas (DNV) • Vacuum(29.2 in. Hg maximum @ 68°F) • Registro Italiano Navale(RINA) In ProPress 1/2" to 4" dimensions,the Smart Connect Feature • Bureau Veritas (BV) assures leakage of liquids and/or gases from inside the system • KIWA past the sealing element of an unpressed connection.The function of this feature is to provide the installer quick and easy Compliant with: identification of connections which have not been pressed prior • ICC International Plumbing Code to putting the system into operation. • IAPMO Uniform Plumbing Code • PHCC National Standard Plumbing Code Recommended Tools: • Florida Building Code, Volume II Plumbing Code • RIDGID RP 200-B ('/z"to 11/4") • NFPA 13, 13D and 13R • RIDGID RP 210-B ('/z"to 11/4") • ASME B16.51 • RIDGID RP 320-E • U.S. Coast Guard • RIDGID RP 330-B or 330-C Viega ProPress fittings are offered in configurations including: • RIDGID RP 340 Elbows,Couplings, Reducers,Tees, Reducing Tees,Threaded • RIDGID CT 400 Adapters, Unions, Caps and Flanges.All threaded 1/2"to 2" Contact your local Viega representative for details on local fittings are Zero Lead bronze. approvals. Operating Parameters Operating Pressure: 200 PSI maximum Test Pressure: 600 PSI maximum Operating Temperature: 0°F to 250°F Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 2 of 23 " °F I/4 4 47-1 SubmittalV,lei0.:.,.. v„5CS k. Package 1:541120D 1111:1 ices 04/11/18 ProPress Product Instructions Viega ProPress® For Types K, L and M Hard Copper Tubing in 1/2” to 2" and Soft Copper Tubing in 1/2" to 11/411 4,,,, L ,,\ A WARNING Read and understand all instructions for installing Viega ProPress fittings.Failure to follow all //// instructions may result in extensive property damage, ��� serious injury or death. hits 1.Cut copper tubing at right angles using displacement- /d,��' 1 2 3 type cutter or fine-toothed steel saw. 2.Remove burr from inside and outside of tubing to ,� '\ �\ prevent cutting sealing element 3.Check seal for correct fit. Do not use oils or lubricants. op- -a_ 9 Use only Viega ProPress Shiny Black EPDM or Dull \joir la-� Black FKM sealing elements f' ,, ' � �`��,� = J u Note:For applications requiring Viega ProPress with FKM sealing elements,remove the factory-installed EPDM 16.►� sealingelement and replace with FKM sealingelement. 4 5 6 p 4.Mark proper insertion depth as indicated by the Viega ProPress Insertion Depth Chart. Improper insertion ,_� ��� ' depth may result in improper seal. ' �� :411-1Alima � 1,4 % 5.While turning slightly, slide press fitting onto tubing to Ia / ``f' 10 ' `»j' ,; ! the marked depth. --=--i--‘6„---,.— � i% �''M"s0. �r -a Note: End of tubing must contact stop. �' f� 6.Insert appropriate Viega jaw into the pressing tool and yii.�i / push in, holding pin until it locks in place. 8 9 7.Open the jaw and place at right angles on the fitting. Visually check insertion depth using mark on tubing. 8.Start pressing process and hold the trigger until the jaw Viega ProPress Insertion Depth Chart has engaged the fitting. Tube Size 1/2" 3/" 1" 11/4° 11/2° 2" 9.After pressing, the jaw can be opened again. Insertion Depth 3/4" '/s" '/a" 1" 17/16" 19/16" Leak Testing with Smart Connect : �m.._ Unpressed connections are located by = pressurizing the system with air or water. When testing with water the proper pressure range is 15 psi to 85 psi maximum. Leak testing with air can be dangerous at high pressures. When testing with compressed air the proper pressure range is 1/2 psi to 45 psi maximum. Following a successful leak test,the system may be pressure tested up to 200 psi with air,or up to 600 psi with water,if required by local code requirements or project specifications. Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 3 of 23 " °F I/4 Z:pW Ill Submittal '....5OA Package Va = ices 04/11/18 Viega ProPress°XL (Copper) ForTypes K, L and M Hard Copper Tubing in 21/2"to 4" C A WARNING Read,understand and follow all instructions for installing ProPress XL(copper)fittings.F ailure "`I '� ________________ to follow all instructions may result in extensive property .,,, damage,serious injury or death. /�\ �°�� 1. Cut copper tubing at right angles using displacement- ,– type cutter or fine-toothed steel saw. 1 Min. 2 2. Keep end of tubing a minimum of 4" away from the i contact area of the vise to prevent possible damage to the tubing in the press area 3. Remove burr from inside and outside of tubing to prevent 11111';)11 cutting sealing element. • 4. Check seal and grip ring for correctfit.Do not use oils or ,,,,,,c_. �1 ? �E� lubricants.Use only ProPress Shiny Black EPDM sealing ��I _ elements. �� �' 5. Illustration demonstrates proper fit of grip ring, separation 4 6 ring and sealing element. 6. Mark proper insertion depth as indicated by the ProPress XL(copper)Insertion Depth Chart. Improper insertion depth may result in an improper seal. El46 _0 IC!• 7. While turning slightly,slide press fitting onto tubing to the Q r7 marked depth. End of tubing must contact stop. --H)41))14) � • 8. ProPress XL(copper)fitting connections must be x))14) � performed with ProPress XL-C Rings and V2 ACTUATOR. �)tlirN 0.4 `' a�® Use of ProPress XL Rings and/or Actuator(for Bronze 7 8 , 9 fittings)will result in an improper connection. See Ridgid Operator's Manual for proper tool instructions. 9. Open XL-C Ring and place at right angles on the fitting. XL-C Ring must be engaged on the fitting bead.Check insertion �� i� �ra) - -- depth. 10. With V2 ACTUATOR inserted into the tool,open the V2 AL — ,;-,, ACTUATOR as shown and connect V2 ACTUATOR to the 40/ithNit VIS XL-C Ring. g. k��, –./ 11. Place V2 ACTUATOR onto XL-C Ring and start pressing tprocess. Hold the trigger until the Actuator has engaged 10 11 ' N. i 12 the XL-C Ring. Keep extremities and foreign objects away from XL-C Ring and V2 ACTUATOR during pressing operation to prevent injury or incomplete press. ProPress XL(copper)Insertion Depth Chart 12. Release V2 ACTUATOR from XL-C Ring and then remove Tube Size 21/2" 3" 4" the XL-C Ring from the fitting on completion of press. Insertion Depth 111/16" 115/,6" 23/8" Remove tag from fitting,indicating press has been performed. Leak Testing with Smart Connect®:Unpressed connections are located by pressurizing the system with air or water.When testing with water the proper pressure range is 15 psi to 85 psi. Leak testing with air can be dangerous at high pressures.When testing with compressed air the proper pressure range is 1/2 psi to 45 psi. Following a successful leak test,the system may be pressure tested up to 200 psi with air,or up to 600 psi with water,if required by local code requirements or project specifications. Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 4 of 23 " °F I/4 :04111111111114if. ijr*IA Submittal 4.....5Ett_N. (7. Package Va1:541120D10 = _ - ices 04/11/18 ProPress° Dimensional Documentation ProPress for 1/2" to 2" copper tubing Viega ProPress 90°Elbow Copper P x P- Model 2916 L A Part No. Size A(in) L(in) �III. 1 1 ,,�1 �. 77317 1/z"x 1/z" 0.75 1.50 A / `tea_I I__- 77322 3/4"x 3/4" 1.04 1.94 L Om__� 77327 1" x 1" 1.32 2.23 � __�, 77332 11/4" x 11/4" 1.65 2.68 �mm( 77337 11/2" x 11/2" 1.98 3.40 1 77342 2"x 2" 2.54 4.13 L Viega ProPress 90°Elbow Copper P x P-Model 2916 Short A w Part No. Size A(in) L(in) ���� 1 1 I 77317 /z"x 1/z" 0.75 1.50 A , , 77022 3/4"x 3/4" 0.76 1.67 L 77027 1" x 1" 1.28 2.19 is 77032 11/4" x 11/4" 1.28 2.31 77037 11/z" x 11/2" 1.29 2.72 1 77042 2"x 2" 2.16 3.74 Viega ProPress 90°Street Elbow Copper P x FTG-Model 2916.1 L A _ Part No. Size A(in) L(in) L1 (in) / 1Ill, 1 2 .11, 1 77347 1/2"x 1/2" 0.75 1.50 1.54 77352 3/4"x 3/4" 1.04 1.94 1.98 L1 i ' 77357 1" x 1" 1.32 2.23 2.27 l77362 11/4" x11/4" 1.65 2.68 2.76 77367 11/2" x 11/2" 1.98 3.40 3.48 2 77372 2"x 2" 2.54 4.13 4.20 L Viega ProPress 90°Street Elbow Copper P x FTG-Model 2916.1 Short A aPart No. Size A(in) L(in) L1 (in) ,=- 1. .1 1 2 Tri �� 77347 %z"x 1/2" 0.75 1.50 1.54 L1 77052 3/4"x 3/4" 0.76 1.67 1.83 ' 77057 1" x 1" 1.28 2.19 2.27 77062 11/4" x11/4" 1.28 2.31 2.48 14- -*1 77067 11/2" x 11/2" 1.29 2.72 2.80 77072 2"x 2" 2.16 3.74 3.78 Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 5 of 23 " CIF I/4 SubmittalVII.....-.cr.,... ..7....,, Package ices 04/11/18 . 1 Viega ProPress 90°Reducing Elbow Copper P x P-Model 2916.3 MML Part No. Size A(in) Al (in) L(in) Li(in) L imir1 2 \;s 77325 3/4"x 1/" 0.91 0.94 1.81 1.69 A \_III 2 77330 1" x 3/4" 1.20 1.30 2.11 2.21 Al L, i.- Viega ProPress 90°Extended Street Elbow Copper P x FTG-Model 2947 • M Part No. Size A(in) L(in) L1(in) 1 2 ' 77353 3/4"x 3/4" 1.02 1.93 5.98 L Viega ProPress 45°Elbow Copper P x P-Model 2926 APart No. Size A(in) L(in) L A/, 1.11 , 1 1 J Ell 77607 1/"x 1/2" 0.30 1.04 ,-f/ 77612 3/4"x 3/4" 0.43 1.34 77617 1' x 1" 0.55 1.46 77622 11/4" x11/4" 0.68 1.71 77627 11/" x 11/" 0.81 2.24 77632 2"x 2" 1.05 2.63 L 1 Viega ProPress 45°Elbow Copper P x P-Model 2926 Short A A � Part No. Size A(in) L(in) L �I _ 1 77607 1/2"x 1/21 0.30 1.04 �® J 77023 3/4"x 3/4" 0.36 1.26 77028 1" x 1" 0.47 1.38 1./ 77033 11/4" x11/4" 0.58 1.61 77038 11/2" x 11/2" 0.65 2.08 77043 2"x 2" 0.86 2.44 Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 6 of 23 " OF I/4 ..6P4011111114if. ijr*IA Submittal ...„, (7...,„, ,. Package Va = _ - ices 04/11/18 L Viega ProPress 45°Street Elbow Copper P x FTG-Model 2926.1 A Part No. Size A(in) L(in) L, (in) 1*It 1 1 2 .11 77637 1/2"x 1/2" 0.31 1.06 1.10 77642 3/4"x 3/a" 0.43 1.34 1.37 77647 1" x 1" 0.55 1.46 M1.49 77652 11/4" x 11/4" 0.68 1.71 1.79 77657 111/2" x 11" 0.81 2.24 U 2.32 77662 2"x 2" 1.05 2.63 2.71 L 1 Viega ProPress 45°Street Elbow Copper P x F TG-Model 2926.1 Short A 4- Part No. Size A(in) L(in) L1(in) 1 2 filial L1 - 77637 /z"x /z" 0.31 1.06 , 77053 3/a"x 3/a" 0.36 1.26 1.30 77058 0.47 1.38 •111.49 2 77063 11/4" x 11/4" 0.58 1.61 1.67 77068 11/2" x 11/2" 0.65 2.08 12.04 77073 2"x 2" 0.86 2.44 2.54 �__ Viega ProPress Coupling with Stop Copper P x P-Model 2915 1 11.1111011 1 Part No. Size A(in) L(in) ��■ .11 1 1 A 78047 1/2"x 1/" 0.12 1.61 L 78052 3/4"x 3/4" 0.20 2.01 78057 1" x 1" 0.16 1.97 78062 11/4" x 11/4" 0.14 2.20 78067 11/2" x 11/" 0.14 2.99 78072 2"x 2" 0.14 3.31 Viega ProPress Coupling No Stop Copper P x P- Model 2915.3 Part No. Size L(in) 1 II I 1 1 1 78172 1/2"x 1/2" 1.61 78177 3/4"x 3/4" 2.01 L 78182 M 1" x 1" 1.97 78187 11/4" x 11/4" 2.20 78192 MI=11/2" x 11/2" 2.99 78197 2"x 2" 3.31 Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 7 of 23 " CIF I/4 ii:4 ,11 Submittal 40,-.cr.,ip (7...,5 0 ,3QQD10% Package Va = _ - ices 04/11/18 1 �Il , Viega ProPress Extended Coupling Copper P x P-Model 2915.5 1 Part No. SizeL(in) 1 1 v r 79005 1/2"x 1/2" 2.99 L 79010 3/4"x 3/4" 3.50 79015 1" x 1" 3.74 79020 114" x 11/4" 4.13 79025 11/2" x 11/2" 4.72 79030 2"x 2" 5.31 ��---�__;I_-_ Viega ProPress Reducer Copper P x P-Model 2915.2 1 1I .111 2 - Part No. Size A(in) L(in) 1 2 A~ 78147 3/4"x'/2" 0.42 2.07 L 15603 1" x 1/2" 0.71 2.36 78152 1" x 3/4" 0.48 2.29 15593 1t/4" x 3/4" 0.70 2.64 78157 11/4" x 1" 0.55 2.48 18473 11/2" x 3/4" 0.98 3.33 15588 11/2" x 1" 0.74 3.07 78162 11" x 1t/4" 0.50 2.96 18468 2" x 3/4" 1.54 4.02 15608 2" x 1" 1.29 3.78 22328 2"x 1t/4" 0.81 3.43 78167 2" x 11/2" 0.74 3.75 Viega ProPress Reducer Copper FTGx P-Model 2915.1 Part No. Size A(in) L(in) 1iti 2 1 2 A 78077 3/4"x'/2" 1.42 2.17 L 78082 1" x 1/2" 1.69 2.44 78087 1" x 3/4" 1.42 2.32 22333 11/4" x 1/2" 1.91 2.74 78092 11/4" x 3/4" 1.85 2.76 78097 VA" x 1" 1.57 2.48 14543 11/2" x 3/4" 2.56 3.46 78102 11/2" x 1" 2.28 3.19 78107 11/2" x 11/4" 2.04 3.07 78112 2" x 1" 3.03 3.94 78117 2" x 11/4" 2.79 3.82 78122 2" x 1'/" 2.63 4.06 Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 8 of 23 " CIF I/4 SubmittalAr lit,i,.....-.cr.,ic. (7...,5 Package ices 04/11/18 L2 Viega ProPress Tee Copper P x P x P-Model 2918 - A2 Part No. Size A(in) Al (in) A2(in) L(in) Ll (in) L2(in) 1 1 2 3 ==[, 77377 1/2"x 1/2"x 1/2" 0.75 0.75 0.50 1.50 1.50 1.25 L I■■II 77382 1/2"x 1/2"x 3/4" 0.91 0.91 0.59 1.65 1.65 1.50 A 1111 15493t/2"x t/2"x 1" 1.10 1.10 0.55 1.85 1.85 1.46 3 773873/a"x 3/a"x 3/a" 0.85 0.85 0.59 1.75 1.75 1.50 At _4! 77392 3/a"x 1/2"x 1/2" 0.69 0.98 0.63 1.59 1.73 1.38 Li I 77397 3/a"x 1"x 3A" 0.85 1.14 0.59 1.75 1.89 1.50 =i 77402 3/"x 3/4"x 1/2" 0.69 0.69 0.63 1.59 1.59 1.38 2 77407 3/4"x 3/4"x 1" 0.97 0.97 0.63 1.87 1.87 1.54 77412 1" x 1"x 1" 0.97 0.97 0.79 1.87 1.87 1.69 22263 1" x 1/2"x 3/4" 0.85 1.24 0.75 1.76 1.99 1.66 94767 1"x 1/2"x 1" 0.97 1.52 0.79 1.87 2.26 1.69 77417 1" x 3A"x 1/2" 0.69 0.89 0.79 1.59 1.79 1.54 77422 1" x 3/a"x 3/4" 0.85 1.04 0.75 1.75 1.95 1.65 77427 1"x 3/4"x 1" 0.97 1.18 0.78 1.87 2.07 1.69 77432 1" x 1" x'/" 0.69 0.69 0.79 1.59 1.59 1.54 77437 1" x 1" x 3A" 0.85 0.85 0.75 1.75 1.75 1.65 15488 1" x 1" x 1 1/4" 1.16 1.16 0.84 2.07 2.07 1.87 77442 11/4" x 11/4 x 11/4" 1.02 1.02 0.86 2.05 2.05 1.89 22253 11" x 1/2"x 11A" 1.02 11.77 0.87 2.05 2.5211 1.89 22243 11/4" x 3/4"x 1/2" 0.64 1.13 0.93 1.68 2.03 1.68 22258 11/a" x 3/a"x 3A" 0.76 1 1.30 0.87 1.80 2.21 11 1.78 22268 11/4" x 3/a"x 1" 0.88 1.40 0.91 1.91 2.31 1.82 22248 11" x 3/4"x 11/4" 1.02 1.54 J.86 2.05 2.4511 1.89 22238 11/4" x 1" x 1/2" 0.64 0.91 0.93 1.68 1.82 1.68 94762 11/4"x 1"x 3/4" 0.76 1 1.14 1.87 1.79 2.05 1.77 14568 11/4"x 1" x 1" 0.88 1.28 0.91 1.91 2.19 1.81 94757 11/4"x 11/a"x 1/2" 0.65 1 0.65 1.93 1.67 1.67 1.67 77452 11" x 11/4"x 3/4" 0.77 0.77 0.89 1.79 1.79 1.77 77447 _1/a"x 11A" x 1" 0.88 1 0.88 1190 1.91 1.91 1.81 77457 11/2"x 11"x 11" 1.13 1.13 1.13 2.56 2.56 2.56 79660 11/2"x 1" x 3/a" 0.67 1 1.39 1.16 2.17 2.44 II 2.05 15458 11/2"x 1" x 1" 0.74 1.54 1.06 2.17 2.44 1.97 -15463 11/2"x 1" x 11/2" 1.13 1 1.83 '1.13 2.56 2.74 2.56 22233 11/2"x 11/4"x 3/a" 0.67 1.08 1.15 2.09 2.11 2.05 15453 1'/2"x 11" x 1" 0.74 1.29 1.18 2.17 2.32 2.09 15483 11/2"x 114"x VA" 0.86 1.33 1.13 2.28 2.36 2.17 15448 11/2"x 11"x 1/2" 0.47 1 0.47 1.10 1.89 1.89 1.85 77462 11/2"x 11"x 3/4" 0.66 0.66 1.14 2.09 2.09 2.05 77467 1t/2"x 1t1/2"x 1" 0.74 .0.74 1.18 2.17 2.17 II 2.09 77472 11/2"x 11/2"x 11/4" 0.86 0.86 1.13 2.28 2.28 2.17 77477 2" x 2"x 2" 1.37 1 1.37 1.37 2.95 2.95 II 2.95 15518 2" x 11/4" x 11/4" 0.94 1.84 1.33 2.52 2.87 2.36 15513 2"x 11/2" x 3/4" 0.70 1 1.25 1.38 2.28 2.68 2.28 15498 2" x 1t/2" x 1" 0.82 1.45 1.38 2.40 2.87 2.28 15508 2"x 11/2" x 11A" 0.94 1 1.55 1.49 2.52 2.97 2.52 Continued on next page Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 9 of 23 " CIF I/4 :0411111111114if. ijr IA Submittal iree......, (7... 0�3QQ� ,b Package Va = _ - ices 04/11/18 L2 Copper Tee P x P x P-Model 2918(continued) - Az Part No. Size A(in) Al(in) A2(in) L(in) Ll(in) L2(in) 1 1 2 3 1=MI, 15503 2"x 11/2" x 11/2" 1.13 1.65 1.37 2.72 3.07 2.80 L c"i■:�I 22228 2"x 11/2" x 2" 1.38 II 1.89 1.38 2.95 3.33 I 2.95 MI 15538 2"x 2"x t/2" 0.54 0.54 1.30 2.13 2.13 2.05 A 3 94777 2"x 2"x 3/a" 0.79 1.26 2.37 2.37 2.17 AlII 94772 2"x 2" x 1" 0.91 0.91 1.30 2.49 2.49 2.21 Li CMI 77487 2"x 2"x 11/4" 1.04 IMF 1.37 2.62 2.62 2.40 1 )Mai77482 2"x 2" x 11" 1.13 1.13 1.37 2.72 2.72 2.80 2 Viega ProPress Cap Copper P-Model 2956 Part No. Size L(in) D(in) 1 77712 '/2" 0.92 0.79 77717 34" 1.07 0.94 < D > 77722 1" 1.11 0.99 < 77727 11/4" 1.32 1.20 77732 11/2" 1.62 1.49 77737 2" 1.81 1.69 Viega ProPress Cross-Over Copper P x P- Model 2928 Part No. Size A(in) L(in) H(in) I nor -EliA 77742 1/2"x'/2" 3.62 5.12 0.77 77747 3A"x 3A" 4.49 6.30 0.90 Viega ProPress Cross-Over Copper P x FTG-Model 2927 E ' Part No. Size A(in) L(in) H(in) � _ 1 2 A 2 78137 1/2"x 1/2" 3.83 4.58 1.10 78142 3/4"x 3/4" 4.64 5.54 1.54 Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 10 of 23 " OF I/4 V%, IA ..7. Submittal j3QQ 0 Package Va = _ - ices 04/11/18 Viega ProPress Adapter Zero Lead Bronze P x MPT-Model 2911ZL Part No. Size A(in) L(in) 1 2 1111 `li I- 2 79210 '/z"x3/8" MPT 0.77 1.59 79215 1/2"x 1/2" MPT 0.89 1.71 ` ii.® 79220 1/2"x 3/4" MPT 1.00 1.83 A 79225 3/4"x 1/2" MPT 1.02 1.93 . L 79230 3/4"x 3/4" MPT 1.02 1.93 79235 3/4"x 1" MPT 1.18 2.09 79240 1" x 3/"MPT 1.18 2.09 79245 1" x 1" MPT 1.26 2.17 79250 x 11/a" MPT 1.54 2.44 79255 11/4" x 1" MPT 1.22 2.24 79260 11A" x 11A" MPT 1.34 2.36 79265 11/4" x 11/2" MPT 1.48 2.50 79270 11" x 11A" MPT 1.34 2.76 79275 11/2" x 11/2" MPT 1.28 2.70 79280 11/2" x 2" MPT 1.65 3.07 79285 2"x 11/2" MPT 1.54 3.11 79290 2"x 2" MPT 1.50 3.07 Viega ProPress Adapter Zero Lead Bronze P x FPT-Model 2912ZL Part No. Size A(in) L(in) 1 1 2 1 lit 279295t/2"x%" FPT0.191.42 1 111111 79300 t/2"x 1/2" FPT 0.25 1.61 79305 t/2"x 3/a" FPT 0.27 1.65 \f 79310 3/4"x 1/2"FPT 0.33 1.77 A j 79315 3A"x 3A"FPT 0.35 1.81 L 79320 1" x t/2" FPT 0.41 1.85 79325 1" x 3/4" FPT 0.39 1.85 79330 1" x 1" FPT 0.44 2.01 79335 1" x 11/4" FPT 0.50 2.09 79340 11/4" x 1/2" FPT 0.37 1.93 79345 11/4" x 1" FPT 0.24 1.93 79350 11/4" x 11A" FPT 0.34 2.05 79355 11" x 11" FPT 0.42 2.13 79360 11/2" x 11/4" FPT 0.26 2.36 79365 11/2" x 11" FPT 0.34 2.44 79370 2"x 2" FPT 0.41 2.68 Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 11 of 23 ° CIF I/4 ‘JFIVIrlI Submittal 4IS0044 117 Package Va : ices 04/11/18 Viega ProPress Adapter Zero Lead Bronze FTGx MPT- Model 2911.1ZL / dv-,”% I Part No. Size L(in) 1 2 1 2 79375 1/"x 3/s"MPT 1.75 79380 1/"x 1/"MPT 1.95 79385 1/2"x 3/a"MPT 2.05 L 79390 3/a"x 1/2" MPT 1.93 79395 3/a"x 3/a"MPT 2.05 79400 1" x 3/4" MPT 2.05 79405 1" x 1" MPT 2.22 79410 11/4" x 11/4" MPT 2.54 79415 11/2" x 11" MPT 2.89 79420 2"x 2" MPT 3.33 Viega ProPress Adapter Zero Lead Bronze FTGx FPT- Model 2912.1ZL ����� Part No. Size A(in) L(in) 1 2 T 1 II 2 79425 /z"x 3/a" FPT 1.10 1.54 j 79430 /z"x'/z" FPT 1.22 1.75 ®�1 79435 1/2"x 3/a"FPT 1.30 1.83 A , 79440 3/a"x 1/2" FPT 1.26 1.79 L 79445 3/a"x 3/a"FPT 1.28 1.83 79455 1" x'/2" FPT 1.35 1.99 79450 1" x 1" FPT 1.33 1.99 79460 11/a" x 1/2" FPT 1.65 2.19 79465 11/4" x 11/4" FPT 1.50 2.19 79470 11/2" x 11/" FPT 1.88 2.56 79475 2"x 2" FPT 2.13 2.95 Viega ProPress 90°Elbow Zero Lead Bronze P x F PT-Model 2914.2ZL L1-1 Part No. Size A(in) Al (in) L(in) Ll (in) Al 1 2 �_� 79520 1/z"x%" FPT 0.94 0.42 1.77 0.83 4II 79525 1/2"x 1/2" FPT 0.94 0.57 1.77 1.10 A �/ I� 2 79530 1/z"x 3/4" FPT 1.06 0.51 1.89 1.06 11 79535 3/a x 1/z FPT 1.06 0.65 1.97 1.18 �Mm 4 L (_! 79540 3/a"x 3/a" FPT 1.06 0.57 1.97 1.12 79545 1" x 1/2"FPT 1.06 0.72 1.97 1.26 J_Ep 79550 1" x 1" FPT 1.34 0.76 1 2.24 1.42 =1 79560 11/4" x 11/4" FPT 1.54 0.89 2.56 1.57 N-1 79565 11/2" x 11/2" FPT 1.69 1.05 1 3.11 1.73 79570 2"x 2" FPT 2.17 1.35 3.74 2.05 Viega LLC,100 N. Broadway, 6th Floor• Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 12 of 23 e klCIFI/4 tr4.41.1,14. Submittal 4Is0...„"IP 497N. Ltk 01 Package Va : _ - ices 04/11/18 rL3 " L2-1 Viega ProPress 90°Drop Ear Elbow Zero Lead Bronze P X FPT-Model 2925.5ZL T L1 ` � Part No. Size A(in) L(in) L1 (in) L2(in) L3(in) I�� A � � 1 2 y 79185 /z"x 3/a" FPT 0.94 1.77 0.74 0.83 0.67 + 79190 /2"x'/2" FPT 0.94 1.77 0.74 1.10 0.67 L == 79195 3/4"x 3/4" FPT 1.06 1.97 0.83 1.12 0.83 1 14-1 -*I < L1 .1 Viega ProPress 90°Hi Ear Elbow Zero Lead Bronze P x F PT-Model 2925.2ZL Al \ t Part No. Size A(in) Al (in) L(in) Li (in) L2(in) � � L2 1 2 ;� !I '-- 2 I 79205 1/2"x'/z" FPT 0.94 0.57 1.77 1.10 1.07 L 1 , Na> 1-1-'1 rL4 1 -,• L3 I�-L2- Viega ProPress Double Drop Elbow Zero Lead Bronze P x P x F PT-Model 2928.7ZL #/ 1 I -o Part No. Size A(in) L(in) Li (in) L2(in) L3(in) L4(in) I T ,��.'�I�\# '//�I �� l 1 2 3 L A airiP\ __ ' 78800 Y2"x'/2"x'/2"FNPT 1.34 2.17 1.97 1.10 0.67 1.57 1 Mkt 11 1 lT 78802 3/4"x 3/4"x 1"FNPT 1.54 2.44 1.97 1.10 0.83 2.05 1 i 78801 3/4"x 3/4"x 3/4"FNPT 1.54 2.44 1.97 1.12 0.83 1.89 1 2 78803 1" x 1" x 1/2"FNPT 1.77 2.68 2.36 1.10 0.87 2.52 F.-L1 i• _ Viega ProPress Reducer Zero Lead Bronze FTGx P-Model 2915.1ZL 1 MOM2Part No. Size 1 2 A(in) L(in) A 79850 11/2" x'/2" 1.95 2.78 L 79855 2" x'/2" 2.38 3.21 79860 2"x 3/4" 2.42 3.33 Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 13 of 23 ItticiFk4 :timplii, ?, tre% z ,d Submittal 4IS'90 497gr Package Va : ices 04/11/18 Viega ProPress Tee Zero Lead Bronze P x P x F PT-Model 2917.2ZL 4-L1-0. Part No. Size A(in) Al(in) L(in) Ll (in) -► Al 1 2 3 h 1-1 79580 1/2"x Y2"x Yz"FPT 0.79 0.69 1.61 1.30 ir= 1 79585 3/4"x 3/4"x 1/4" FPT 0.67 0.79 1.57 1.18 (ii: , 79590 3A"x 3/a"x 1/2" FPT 0.79 0.88 1.69 1.42 a' L =J 79595 3A"x 3A"x 3A"FPT 0.91 0.59 1.81 1.14 #r 79760 1" x 1" x Y2" FPT 0.79 1.04 1.69 1.57 A II 1 03 79765 1" x 1" x 3/a"FPT 0.91 1.06 1.81 1.61 79770 11"x 11"x Y2"FPT 0.83 1.16 1.85 1.69 A 1 1 � 79775 11"x 11" x 3A"FPT 0.95 1.18 1.97 1.73 L -=� 79780 11/2"x 11/2"x 1/2"FPT 0.87 1.24 2.28 1.77 J=Ms_. 79785 1Y"x 1t "x 3A"FPT 0.94 1.30 2.36 1.85 t , 79790 2"x 2" x Y2" FPT 0.98 1.59 2.56 2.13 2 79795 2"x 2"x 3/a"FPT 1.06 1.65 2.64 2.20 r3.1 Viega ProPress Vent Tee Zero Lead Bronze P x F PTx P-Model 2917.3ZL 1 ! ( \ Part No. Size A(in) Al(in) A2(in) L(in) Ll (in) L2(in) L1 a 1 2 3 Al ._ ,=-=,%� 79635 Y2"x 1/s" FPT x Y2" 0.67 0.67 0.44 1.50 1.50 0.71 1 T-1111111 ,/ lif 2 _ 79640 3/4"x I/8" FPT x 3/4" 0.83 0.83 0.54 1.73 1.73 0.81 111 �llllll__rU-f . A A2 L 0• L2-+ Viega ProPress Union Zero Lead Bronze P x P-Model 2960ZL ' 11111111111r11 Part No. Size A(in) L(in) -tr-\^Ts-`-v-' 79125 '/" 1.19 2.84 79130 3%" 1.34 3.15 A 79135 1" 1.83 3.65 L 79140 VC 1.64 3.69 79145 11/2" 2.13 4.96 79150 2" 2.07 5.22 Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 14 of 23 0CIF I/4 ......0,104..(*()Submittal Package ices 04/11/18 Viega ProPress Union Zero Lead Bronze P x F PT-Model 2962ZL ._,1-‘,__ !! ■I f 1 Part No. Size 2 A(in) L(in) --/- `= � 2 1 79700 1/2"x Y2" FPT 0.91 2.27 79705 3/4"x 3/a" FPT 0.96 2.42 A 79710 1" x 1" FPT 1.31 2.88 L 79715 11/4" x 11/4" FPT 1.27 2.97 79720 11/2" x 11/2" FPT 1.77 3.87 79725 2"x 2" FPT 1.65 3.92 Viega ProPress Union Zero Lead Bronze P x MPT-Model 2965ZL 1 �i. I 2_ Part No. Size A(in) L(in) 111 1 1 2 it ���1.��� 79730 1"x 1" MPT 1.86 2.69 A 79735 3/4"x 3/4" MPT 2.00 2.90 79740 1" x 1" MPT 2.54 3.45 L 79745 1A" x 11/4" MPT 2.49 3.52 79750 11/2" x 11/2" MPT 3.05 4.47 79755 2"x 2" MPT 2.99 4.57 Viega ProPress Dielectric Union Zero Lead Bronze P x F PT-Model 2967ZL ` Part No. Size A(in) L(in) -1%----' ill.1 II IIIIII III' 2 79155 Y2"x Y2" FPT 0.88 2.24 I�IIIIILJII'`\. NM 79160 3/4"x 3/4" FPT 1.11 2.57 is�__ro 79165 1" x 1" FPT 1.00 2.57 � 79170 11/4" x 11/4" FPT 0.97 2.68 A 79175 11/2" x 11" FPT 1.01 3.11 L 79180 2"x 2" FPT 1.26 3.53 ..W, Viega ProPress Tailpiece Zero Lead Bronze P x F BSP- Model 2957ZL I Part No. 1 Size A(in) L(in) 1 I I- 2 2 1 L 79800 YZ"x 1" BSP 0.39 1.57 N' - 79805 3/4"x 1" BSP 0.63 1.87 A 79810 1" x 1" BSP 0.91 2.14 L 79815 1" x 11/4" BSP 0.73 2.04 Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 15 of 23 " CIF I/4 :041111111114if. it:*IA Submittal RetOfkno Package Va = _ - ices 04/11/18 Viega ProPress Adapter F lange Zero Lead Bronze P x Flange-Model 2959.5ZL A� 0- _ Part No. Size L(in) A(in) b(in) D(in) k(in) d(in) 4 1 _0 iv _ d 79680 1" 2.76 1.85 0.84 4.33 3.11 0.63 1111111- 1 79685 11/4" 2.76 1.73 0.84 4.53 3.50 0.63 I `'\7 I 79690 1Y2" 3.07 1.65 0.84 4.92 3.86 0.63 � 79695 2" 3.66 2.09 0.84 5.91 4.76 0.75 < k->- - b� FLS < D > Viega PEX Press Adapter Zero Lead Bronze P x P-Model 2813PZL hep. T1 I I Part No. Size A(in) L(in) 1 � 2 1 2 99620 '/2"x'/2" 0.29 1.61 -111111111r I I 99626 1/2"x 34 0.43 1.83 99630 3/4"x'/2" 0.23 1.56 A 99640 3/4"X 3/4" 0.33 1.73 99660 i 1" x 1" 0.45 1.97 99670 11/4" x 1t/4" 0.49 2.38 99680 .11/2" x 11" 0.59 2.87 99690 2"x 2" 0.58 3.21 Viega ProPress Venturi Insert Zero Lead Bronze-Model 2911.5ZL • L ► 4-A ► A2 ► Part No. Size A(in) A2(in) L(in) ? 1 2 l' Flow 1 78810 1t/4" x 1Y4" 1.02 1.60 3.07 1 - 2 78811 1'h" x 1Y2" 1.43 2.10 3.98 i II 78812 2" x 2" 1.58 2.45 4.48 Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 16 of 23 tvioFk4 .....94040.11,. . ...-old Submittal iz (T..., .,, If Package ices 04/11/18 ProPress XL for 21/4" to 4" copper tubing L Viega ProPress XL-C 90°Elbow P x P-Model 0916XL .-A� _I III 1 Part Number 1Siz 1 A(in) L(in) A Ari„,„ 1 20623 21/2"x 21/2" 3.19 4.88 20628 3"x 3" 3.76 5.73 L20633 4"x 4" 4.90 7.26 1 _ L Viega ProPress XL-C 90°Street Elbow P x FTG-Model 0916.1XL .-A Part Number Size A( in) L( in) L1 ( in) . 111110 1 1 2 :' illift 20638 21/2"x 21/2" 3.19 4.88 4.80 / 20643 3"x 3" 3.76 5.73 5.63 Li i 20648 4"x 4" 4.90 7.26 7.13 l - 2 L Viega ProPress XL-C 45°P x P- Model 0926XL A Part Number Size A(in) L(in) 11 1 1 1 '''' o 20653 21/"x 21/2" 1.48 3.18 �,• I ^I'I 20658 3"x 3" 1.73 3.70 1 ,-' 20663 4"x 4" 1.96 4.63 L-► Viega ProPress XL-C 45°Street Elbow P x FTG- Model 0926.1XL fA Part Number Size A(in) L(in) L1 (in) LiI II 1 1 2 I 20668 21/"x 21 1.48 3.18 3.10 0 Ile 20673 3"x 3" 1.73 3.70 3.60 20678 4"x 4" 2.23 4.59 4.45 Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 17 of 23 " CIF I/4 ii:4 ,11 Submittal0,-.cr.,... ...,, 0 j3QQ 0Package Va = _ - ices 04/11/18 Viega ProPress XL-C Coupling with Stop P x P-Model 0915XL Him.ii-iiJ , Part Number SizeA(in) L(in) 20728 2'/z"x 2'/z" 0.95 4.33 . 20733 3"x 3" 0.98 4.92 -10 A r 20738 4"x 4" 1.06 5.79 L Viega ProPress XL-C Coupling No Stop P x P-Model 0915.5XL 1 III I I I Part Number 1Size1 L(in) 111111111E i 20743 20748 21/2 3"x 3'/z 4.33 4.92 20753 4"x 4" 5.79 L-1.- Viega ProPress XL-C Reducer P x P-Model 0915.2XL 7.---t--_____ ___, - Part Number Size A(in) L(in) JI 1 2 1 20685 21/z"x 1" 1.76 4.36 20690 2�/z x 11/4" 1.61 4.34 111 I 20695 21/2"x 11/2" 1.52 4.64 20700 21/2"x 2" 1.41 4.69 1, .II-A-I. 20705 3"x 11/2" 1.78 5.17 L-o- 20710 3"x 2" 1.53 5.08 20715 3"x 21/2" 1.41 5.07 20720 4"x 2" 2.06 6.00 20725 4"x 21" l3 5.99 20730 4"x 3" 1.70 6.03 Viega ProPress XL-C Reducer FTGx P-Model 0915.1XL 1 1.1 I'II 2 Part Number Size 1 2 A(in) L(in) 1 I,I III + 20814 2081521/2" 08152' "Ix 11/4" 3.61 3.47 4.52 4.51 A; 20813 21/2"x11/2" 3.41 4.84 L 20758 21/2"x 2" 2.35 3.94 20817 3"x 11/4" 3.96 5.00 20818 3"x 11/2" 3.91 5.34 20763 3"x 2" 2.98 4.57 20768 3"x 21/2" 2.76 4.45 20773 4"x 2" 4.58 6.17 20778 4"x 21/2" 4.45 6.15 20783 4"x 3" 4.17 6.14 Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 18 of 23 ItticiFk4 .......0,14.. ,41.1,. . .4 Submittal 4....L,... .Rai Package ices 04/11/18 Viega ProPress XL-C Adapter P x MPT-Model 0911XL ---.mu, Part Number Size A(in) L(in) 1I1 t 1 2 Ii1I•iIJ � 20823 2t/2x 2�/zMPT 2.76 4.45 20828 3x 3" MPT 2.84 4.80 / 20838 4"x 4" MPT 3.10 5.46 A-0- L Viega ProPress XL-C Adapter P x F PT-Model 0912XL L A Part Number Size A(in) L(in) 1 2 ra-im._1.._5"'��---- 20819 21/2"x 21/2" FPT 1.53 4.15 20829 3"x 3" FPT 1.84 4.82 2 20839 4"x 4" FPT 2.09 5.55 Viega ProPress XL-C Tee P x P x P-Model 0918XL AL1 Part Number Size A(in) Al(in) A2(in) L(in) L1(in) L2(in) -A1 1 2 3 .i-l-ri 20684 21/2"x 3/a"x 21/2" 1.83 1.91 3.23 1152 3.60 4.13 } _.._ 20689 21/2"x 1"x 21/2" 1.83 1.91 3.25 3.52 3.60 4.15 j= 20694 2Yz"x 1Y4"x 21/2" 1.83 1.91 3.20 13.52 3.60 4.23 L i A B III;I 20699 21/2"x 11/2" x 21/2" 1.83 1.91 3.14 3.52 3.60 4.57 20704 21/2"x 2"x 3/4" 1.04 1.61 1.59 12.74 2.52 3.17 A2 ,I 111 I�� 20709 21/2"x 2"x 1" 1.04 1.77 1.65 2.74 2.67 3.24 L2 ,_;®!) -``!" 22283 21/2"x 2"x 11/2" 1.30 1.78 2!112.99 3.20 3.66 MSI ) ! 22278 21"x 2"x 2" 1.50 1.78 2.25 3.19 3.36 3.83 ,.-as-., 1-4-2-r-120714 21"x 2"x 21/2" 1.83 1.91 2.41 13.52 3.60 4.00 22303 21/2"x 21/2"x 1/2" 0.91 1.52 0.91 2.60 2.27 2.60 22298 21/2"x 21/2"x 3/4" 0.911 1.58 0.91 12.60 2.48 2.60 22293 21/2"x 21/2"x 1" 1.04 1.77 1.04 2.74 2.68 2.74 22288 21"x 21/2"x 11/4" .!9511 1.76 1.16 12.85 2.79 2.85 20803 21/2"x 21/2"x 11/2" 1.30 1.78 1.30 2.99 3.21 2.99 20688 21/2"x 21/2"x 2" 1.5ii 1.75 1.54 3.23 3.34. 3.23 20683 21"x 21/2"x 21/2" 1.83 1.94 1.83 3.52 3.63 3.52 20719 3"x 3/4"x 3" .N7 2.15 3.82 4.04 4.111 4.72 20724 3"x 1"x 3" 2.07 2.15 3.96 4.04 4.11 4.86 20729 3"x 114"x 3" 2.07 2.15 3.83 4.04 4.11 4.86 Continued on next page Viega LLC,100 N. Broadway, 6th Floor• Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 19 of 23 0CIF I/4 ...s:4•14. . ,40.1„,. z .4 Submittal ....L _..„,... Package Va _ : _ ices 04/11/18 Viega ProPress XL-C Tee P x P x P-Model 0918XL (continued from previous page) ~L1~ Part Number Size A(in) Al(in) A2(in) L(in) Li(in) L2(in) ..-Al-i. 1 2 3 ~1-1 20727 3"x 11/2"x 3" 2.07 2.15 3.71 4.04 4.11 5.14 [._..,1moi 20732 3"x 2"x 2" 1.56 2.03 2.33 3.52 3.61 3.92 ��i 20734 3"x 2"x 21/2" 1.85 2.15 2.63 3.82 3.85 4.21 A w1p1111 20739 3"x 2"x 3" 2.07 2.15 2.84 4.04 4.11 4.43 20744 3"x 21/2"x 2" +� 2.03 2.07 1 3.52 3.61 3.76 A2 \1 20749 3"x 21/2"x 21/2" 1.85 2.15 2.56 3.82 3.85 4.25 __i 20754 3"x 21/2"x 3"'E& 2.15 2.78 1 4.04 4.11 4.47 20759 3"x 3"x 1/2" 0.93 1.76 0.93 2.89 2.50 2.89 I.-2-.--1 22323 3"x 3"x 3/4" r'bT 1.80 0.93 2.89 2.71 2.89 22308 3"x 3"x 1" 1.06 2.02 1.06 3.03 2.92 3.03 22313 3"x 3"x 114" m1= 2.01 1.18 1 3.15 3.04 3.15 20798 3"x 3"x 11/2" 1.32 2.03 1.32 3.29 3.45 3.29 20698 3"x 3"x 2" 1 r 2.00 1.56 '3.52 3.59 3.52 20703 3"x 3"x 21/2" 1.85 2.15 1.85 3.82 3.85 3.82 20693 3"x 3"x 3" -MI..07 2.21 2.07 1 4.04 4.18 4.04 20774 4"x 3"x 2" 1.59 2.57 3.33 3.96 4.15 5.22 20784 4"x 3"x 3" 1.11 2.66 3.84 4.47 4.63 5.81 ' 20788 4"x 4"x�/z" 1.08 2.24 1.08 3.45 2.99 3.45 20793 4"x 4"x 3/4" 11116 2.32 1.08 '3.45 3.22 3.45 20794 4"x 4"x 1" 1.36 2.52 1.36 3.72 3.42 3.72 20795 4"x 4"x 11/4" 1.36 2.50 1.36 3.72 3.54 3.72 20808 4"x 4"x 11/2" 1.36 2.52 1.36 3.72 3.95 3.72 20713 4"x 4"x 2" Br 2.53 1.59 3.96 4.11 3.96 20718 4"x 4"x 21/2" 1.89 2.65 1.89 4.25 4.35 4.25 20723 4"x 4"x 3" 2.69 2.11 ■4.47 4.65 4.47 20708 4"x 4"x 4" 2.60 2.72 2.60 4.96 5.09 4.96 Ll Viega ProPress XL-C Tee P x P x FPT-Model 0917.2XL Al 1 Part Number Size A(in) Al (in) L(in) Li(in) ;s 1 2 3 L MM20883 21/2"x 21/2"x 3/4"FPT 1.02 1.78 2.72 2.34 _ 20878 2Y2"x 2t/2"x 2"FPT 1.54 1.90 3.23 2.60 A I�all�l 20893 3"x 3"x3/4"FPT 1.04 2.03 3.01 2.59 A iMW-L l 3 20888 3"x 3"x 2"FPT 1.56 2.16 3.52 2.85 L i 20873 4"x 4"x 3/4"FPT 1.08 2.53 3.34 3.09 ) 20868 4"x 4"x 2"FPT 1.59 2.69 3.96 3.38 -4-2-... Viega LLC,100 N. Broadway, 6th Floor• Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 20 of 23 " CIF I/4 :04111111114if. ijr IA Submittal 4.....5Et, (7. 0, 17 b Package Va = _ - ices 04/11/18 Viega ProPress XL-C Cap P-Model 0956XL I.I I'I" 1 Part Number Size A(in) L(in) al II� 1 20833 20843 3" 0.39 0.39 2.11 2.36 tA-. 20848 4" 0.39 2.76 L- L A ''/Oi S 4d01Viega ProPress XL-C Adapter Flange P x Flange-Model 0959.5XL Part Number Size Ain Lin binkin Din d in ) 2'/2 lilt 1 1V � I 20853 " 1.09 2.79 0.70 5.51 7.09 0.75 � 20858 3" 1.20 3.17 0.79 5.98 7.48 0.75 k D L A Vii, �i Viega ProPress XL-C Adapter Flange P x Flange-Model 0959.5XL 11111A fil �, Part Number Size A(in) L(in) b(in) k(in) D(in) d(in) �.. d 1 1 11 �� 20863 4" 1.29 3.66 0.86 7.52 9.06 0.75 l -41 I k D Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 21 of 23 " OF I/4 Z:pV ..11.1. Submittal ,i,.....50.. (7.„,4,0,... _„ Package ] ices 04/11/18 -A A ■_,_■... . I. GIII B mis I I �■■_1 i� �1�r\ r r ih. _ `` r lU CN I- , n F 1-1111- 1 . � -D }J <-E-• H Butterfly Valve-Model 2873.81 Part No. Size A(in) B(in) C(in) D(M1E(in) F(in) G(in) H(in) I(in) 22074 2'/2” 6.50 7.40 2.1'Im� M•111 2.64 5.35 5.20 5.51 22075 3" 7.28 7.64 2.80 0.67 1.81 2.82 5.59 7.01 5.98 < A • ■__i iai ..'.LI.. B ,.I�Ls, G /�, , ":air' I I,'-� iii ill t l ��i� Tit!D H . Butterfly Valve-Model 2873.81 Part No. Size A(in) B(in) C(in) D(in) E(in) F(in) G(in) H(in) I(in) 22076 4" 9.06 8.47 3.54 0.91 2.05 3.62 6.42 8.27 7.48 Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 22 of 23 " CIF I/4 SubmittalCPA 0 17 b Package Va = = ices 04/11/18 Viega Limited Warranty ProPress° FittingsAnd Valves Subject to the conditions and limitations in this Limited warranty. The part or parts which you claim failed should Warranty, Viega LLC(VIEGA)warrants to wholesalers be kept and Viega contacted by writing to the address and licensed plumbing and mechanical contractors below or telephoning 1-800-976-9819 within thirty(30) in the United States and Canada that its PROPRESS days after the leak or other failure and identifying yourself fittings, when properly installed in non industrial and as having a warranty claim. You should be prepared to non marine applications and under normal conditions ship, at your expense,the product which you claim failed of use, will be free of failure from manufacturing defect due to a manufacturing defect and document the date of for a period of fifty(50)yearsfrom date of installation installation. Within a reasonable time after receiving the and that its PROPRESS valves,when properly installed product,Viega will investigate the reasons for the failure, in non industrial and non marine applications and under which includes the right to inspect the product at Viega. normal conditions of use, will be free of failure from Viega will notify you in writing of the results of its review. manufacturing defect for a period of two(2)years from date of installation. In the event that Viega determines that the failure or leak was the result of a manufacturing defect in the part Under this Limited Warranty, you only have a right to a covered by this warranty and that this warranty applies, remedy if the failure or leak resulted from a manufacturing the EXCLUSIVE AND ONLY REMEDY under this warranty defect in the products covered by this warranty and the shall be the reimbursement for repair and/or replacement failure or leak occurred during the warranty period. You do of the part. VIEGA SHALL NOT BE LIABLE FOR ANY not have a remedy under this warranty and the warranty CONSEQUENTIAL OR OTHER DAMAGE(FOR EXAMPLE, does not apply if the failure or any resulting damage is WATER OR PROPERTY OR MOLD REMEDIATION) caused by(1)components other than those manufactured UNDER ANY LEGAL THEORYAND WHETHER or sold by Viega;(2)not designing, installing, inspecting, ASSERTED BY DIRECT ACTION,FOR CONTRIBUTION or testing the ProPress fittings or valves in accordance OR INDEMNITY OR OTHERWISE. with Viega's installation instructions in effect at the time of the installation;applicable code requirements; and THE ABOVE WARRANTY IS IN LIEU OF ALL OTHER accepted industry practice; (3)improper handling and WARRANTIES, EXPRESS OR IMPLIED,INCLUDING protection of the product prior to and during installation, BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF inadequate freeze protection, exposure to water pressures MERCHANTABILITY AND FITNESS FOR A PARTICULAR or temperatures or in applications outside acceptable PURPOSE. If a limited warranty shall be found to apply, operating conditions;(4)acts of nature such as, but not such warranty is limited to four years. Other than this limited to, earthquakes, fire,flood, or lightning, or(5) Limited Warranty, Viega does not authorize any person external environmental causes,such as water quality or firm to create for it any other obligation or liability in variations, aggressive water, or other external chemical or connection with its products. physical conditions. This Limited Warranty gives you specific legal rights and In the event of a leak or other failure of the parts covered you also may have other rights which may vary from state by this warranty, it is the responsibility of the property to state. This warranty shall be interpreted and applied owner to obtain and pay for repairs Only if the warranty under the law of the state in which the product is installed applies will Viega be responsible for the remedy under this and is intended as a Commercial Warranty. "Zero Lead identifies Viega®products meeting the lead free requirements of NSF 61-G through testing under NSF/ANSI 372(Q25% or less maximum weighted average lead content). Viega products are designed to be installed by licensed and trained plumbing and mechanical professionals who are familiar with our products'proper use and installation.Installation by non-professionals may void Viega LLC's warranty. This document subject to updates. For the most current Viega technical literature please visit www.viega.us. Click Services->Click Electronic Literature Downloads->Select Product Line->Select Desired Document Viega LLC,100 N. Broadway, 6th Floor•Wichita,KS 67202• P h:800-976-9819• Fax:316-425-7618 SM-PP 1116 23 of 23 kl °F I/4 111; '61 ,11 lit J � low"' i .1 ji A:I In 111)111b S, perior Products from a I ire&Emergency Services Trusted Source /18 r r. f lifilgIF e . imi �'�� POLYETHYLENE 6 ., ., PURE-COREi . ` # 9 - - i .Oh.... Siii: I: _.- - IF- 10111)41 , - k . . ilk , ii._ , . . . • . • . 4, .,, -.re. r{,f+ la.I r - 4 .11 „ill I i POLYETHYLENE PURE-CORE BLUE • . Eau le Pure-Core and Pure-axe 3 lue are relied upon by municipalities and + lir independent contractors iiitio. alike for water service distributiiu. Laclh is available in a variety of diameter and spool Maine. lengths. Irrigation & Plumbing Products www . pwpipe . com N tit F I/4 Eagle Pure-Core' Blue Pure-Core®Blue HDPE Pipe Pipe and Tubing P.R.200 psi,SIDR 7,Mandarin Tag Color + • Pipe meets the requirements of Nominal Approximate Average Minimum Appro .r ASTM D2239and AWWAC901. Pipe Size Outside Diameter Inside Diameter Wall Thickness Wei •Tubing meets the requirements of (inches) (inches) (inches) (inches) (lbs/1le ASTM D 2737 and AWWA C901 3/4 1.07 0.824 0.118 15 f..} Q°7 with Copper Tube Size(CTS) 1 1.37 1.049 0.150 25 - - outside diameters. Vail I-,e&C.i. ryel c1 Services • Material is high-density PE 3408, 11/4 1.80 1.380 0.197 43 04/11/ 8 100-300 meeting cell class 345444 or 11/2 2.10 1.610 0.230 59 100-250 335444. • Listed for potability to ANSI/NSF Standard 61. Pure-Core®Blue HDPE Tubing P.R.200 psi,SDR 9,White Tag Color • Natural core with blue exterior. Nominal Average Approximate Minimum Approximate Standard •Color-coded tags denote product Pipe Size Outside Diameter Inside Diameter Wall Thickness Weight Coil Lengths and pressure rating for improved (inches) (inches) (inches) (inches) (lbs/100') (feet) warehouse control. 1/2 0.625 0.47 0.069 5 100-400 •50 year warranty 3/4 0.875 0.66 0.097 10 100-400 1 1.125 0.85 0.125 17 100-300 Eagle Pure-Core®Pipe 11/4 1.375 1.04 0.153 26 100-300 • Meets the requirements of ASTM D 2239. 11/2 1.625 1.23 0.181 36 100-250 • Material is medium-density PE 2 2.125 1.62 0.236 62 100-200 2406,meeting cell class 224343. • Listed for potability to ANSI/NSF Standard 61. Pure-Core®MDPE Pipe-ASTM D2239 Premium Grade Flexible NSF Listed • Natural core with carbon black Nominal PressureTag Approx. Average Min.Wall Approx. Coil exterior. Pipe Size SIDR Rating Color O.D. I.D. Thickness Weight Lengths •Color-coded tags denote product (inches) (psi) (inches) (inches) (inches) (lbs/100') (feet) and pressure rating for improved 9 100 Blue 0.77 0.622 0.069 7 100-400 warehouse control. 1/2 7 125/160 Green 0.81 0.622 0.089 9 100-400 •50 year warranty 11.5 80 Goldenrod 0.98 0.824 0.072 9 100-400 PWPipe is the largest producer of 3 9 100 Blue 1.02 0.824 0.092 12 100-400 PVC pipe in western North America 7 125/160 Green 1.08 0.824 0.118 15 100-400 and our products are available from distributors throughout this 11.5 80 Goldenrod 1.24 1.049 0.091 14 100-300 geographic area.PWPipe products 1 9 100 Blue 1.30 1.049 0.117 19 100-300 include PVC and polyethylene pipe and tubing for a variety 7 125/160 Green 1.37 1.049 0.150 25 100-300 of applications servicing the potable water,well casing, 11.5 80 Goldenrod 1.64 1.380 0.120 25 100-300 sewer,turf,agriculture, plumbing, 11/4 9 100 Blue 1.71 1.380 0.153 32 100-300 communications,and electrical markets. Our manufacturing facilities 7 125/160 Green 1.80 1.380 0.197 43 100-300 in Oregon,Washington,California, Utah,and Nebraska assure 1'/2 9 100 Blue 1.99 1.610 0.179 44 100-250 on-time delivery. 2 9 100 Blue 2.56 2.067 0.230 7 100-200 I PPFA MEMBER Note e y u PLASTIC PIPE PWPipe product specifications and warranties are continual) dated. AND FITTINGS p p p p ASSOCIATION If more than 12 months have passed since the date of this brochure, call your PWPipe representative and ask about changes. PivEgic P.O.Box 10049, Eugene,OR 97440 • (800)347-0200 •(541)343-0200•FAX(541)686-9247•www.pwpipe.com