Naperville Address : 4937 Juniper Lane
2016 Dwelling Unit Electric Service & Feeder Load Calculator
220.12 General Lighting Load
3 va/ft2 of floor area,including unused space adaptable for future use.
Floor Area= 5785 ft2 17,355 va
Basement Floor Area= o ft2 - va
220.52(A) Small Appliance Load
1500 va for each 20 amp branch circuit required per 210.1(C)(1)in EACH kitchen,
pantry, breakfast room,dining room,or similar areas.
#of Small Appliance Branch Circuits= 2 "1500 va= 3,000 va
220.52(B) Laundry Load
#of Laundry Branch Circuits= 1 "1500 va= 1,500 va
Total General Lighting&Appliance Load= 21,855 va
220.42 Lighting Load Feeder Demand Factors
First 3000 or less at i00%o 3,000 va
From 3001 to 120,000 at 35°x6 6,599 va
Remainder over 120,000 at 25% - va
Total Lighting Demand Load= 9,599 va
220.54 Electric Clothes Dryers
Qty 1 Electric Dryer#1 5.00 kw 5,000 w
Qty 0 Electric Dryer#2 - kw - w
220.55 Electric Cooking-Ranges,Stove Tops and Wall Ovens
Qty 0 Wall Oven Nameplate - kw
Qty 1 Electric Range Nameplate 11,99. kw
Qty 0 Wall Oven Nameplate kw
Electric Cooking Demand Load= 8,000 w
220.51 Fixed Electric Space Heating Loads or Air Conditioning Load:
Fixed Electric Space Heat#1 - kw AC#1/Geo - kva
Fixed Electric Space Heat#2 - kw AC#2/Geo - kva
Fixed Electric Space Heat#3 - kw AC#3/Geo - kva
Fixed Electric Space Heat#4 - kw AC#4/Geo - kva
Fixed Electric Space Heat#5 - kw AC#5/Geo - kva
Total Heat&AC Load= - va
220.14 Appliance load--Dwelling Units
Qty Description va(watts) Qty Description va(watts)
1 Central Furnace 1,200 0 -
1 Dishwasher 1,200 0
1 Refrigerator 1,440 0
1;Microwave 1,580 0
1 Range Hood 240 0
4 Vent Fan 400 0
0 - 0 -
Total Connected Appliance Load= 6,060 va
220.53 Appliance load—Dwelling Units Total Appliance Demand Load= 4,545 va
220.50 Motor Loads @ 120 Volts
Qty Description va(watts) Qty Description va(watts)
11/2hpSump/EjectPump 375 0 0
1/2hpGarbage Disposa 375 0
2 1/2hpGar/DoorOpener 375 0 -
0 0
Total Motor Load= 1,500 va
430.24 Several Motors or a Motor(s)and Other Load(s) 25%of Largest Motor Load= 94 va
Total Motor Demand Load= 1,594 va
TOTAL CALCULATED DEMAND LOAD in Volt-amperes= 28,738 va
TOTAL CALCULATED DEMAND LOAD in AMPS @1201240V 1ph3W= 120 amps
EXISTING SERVICE SIZE 200 AMPS
MINIMUM SERVICE SIZE 200 AMPS SERVICE SIZE REQUESTED= 200 amps