HomeMy WebLinkAboutB18-0275_Approved Documents_1535756855.pdf 75 South Frontage Road Construction
0West, TOWN OF VAIL B18-0275
TOWN
Vail,CO 81657 Issued: 08/31/2018
TOWN Or VAIL Office:970.479.2139
Inspections:
inspections@vailgov.com
Property Information
Address: 175 FOREST RD(210107113032) (210107113032 )
Unit#:
Parcel Number: 210107113032
LegalDescription: Subdivision:VAILVILLAGE FILING 1 Block:7 Lot:26 PARCEL B BK-0378 PG-0085 DEC 2-8-84
R895487DEC 10-25-04
Contacts
Contact Type:Applicant
Full Name:Joe Stainbrook
Address: 710 West Lionshead Circle Unit A Vail,CO 81657 Phone: 9704772990
Contact Type:Property Owner
Full Name:VENERABLE,C. EDWARD&AMY
Address: Phone: None
Contractor
Contractor Type:General
Company: Paragon Homes Inc.
State License#: Phone: 303-525-7775
Projectinformation
Project Name:Venerable Residence2018
Project Description: Complete demo and New Construction to matchexisting exterior materials of 185 Forest Rd.
Fees Paid
Account#:001-0000.31111.00-Building Permit Fee Fee Amount: $3,718.25
Account#:001-0000.31123.00 Building Plan Review Fee Fee Amount: $2,416.86
Account#: 110-0000.31060.00Construction Use Tax Fee Fee Amount: $11,840.00
Account#:001-0000.31111.00-Mechanical Permit Fee Fee Amount: $1,560.00
Account#:001-0000.31123.00 Mechanical Plan Review Fee Fee Amount: $390.00
Account#:001-0000.31111.00-Plumbing Permit Fee Fee Amount: $765.00
Account#:001-0000.31123.00 Plumbing Plan Review Fee Fee Amount: $191.25
Account#: 111-0000.31127.00-Recreation Fee Fee Amount: $541.50
Account#:001-0000.31128.00 Will Call Fee(Building Scope) Fee Amount: $5.00
Account#:001-0000.31128.00 Will Call Fee(Mechanical Scope) Fee Amount: $5.00
Account#:001-0000.31128.00 Will Call Fee(Plumbing Scope) Fee Amount: $5.00
Total Paid: $21,437.86
Conditions
CONDITIONS UNDER WHICHPERMITS BECOME VOID:
If construction is not begun within 6 months from the date permitwas issued.
If more than 5 months elapses betweeninspections.
If incorrectinformationis given on the application at the time the permitwas issued.
Christopher Jarecki-Town of Vail Building Official
NOTICE:By issuance of this Permitthe applicant agrees to complywith all Titles of the Town of Vail Code and all applicable State and Federal
law.Failure to do so will void this Permit and the applicant shallforfeit all applicablefees.
°I1111
PERMIT FEE RECEIPT
TOWN OF VAIL Case # B18-0275
Date Printed: 08/31/2018
TOWN OF VAIL - FEES RECEIPT
Permit Summary
Case Number: B18-0275 Status: Approved
Permit Number: Date Started: 06/27/2018
Permit Type: Construction Subc ases Duplex
Lot Number: 26
Property: 175 FOR EST R D(210107113032)(210107113032)
Contacts
Contact Type: Applicant
Company Name: KH Webb Architects
Full Name: Joe Stainbrook
Address: 710 West Lionshead Circle Unit A Vail, CO 81657
Email: joe@khwebb.com
Contact Type: Property Owner
Full Name: VENERABLE,C. EDWARD&AMY
Address:
Permit Fees
Fee Information Account Amount
Permit Fee 001-0000.31111.00 $6,043.25
Construction Tax 110-0000.31060.00 $11,840.00
Recreation Fee 111-0000.31127.00 $541.50
Will Call Fee 001-0000.31128.00 $15.00
Payment Information Date Paid Payment Type Amount
Recreation Fee 08/31/2018 Check $541.50
Paid By:Amy Wine Venerable-Notes:ck#1096
Permit Fee 08/31/2018 Check $6,043.25
Paid By:Amy Wine Venerable-Notes:ck#1096
Construction Tax 08/31/2018 Check $11,840.00
Paid By:Amy Wine Venerable-Notes:ck#1096
Will Call Fee 08/31/2018 Check $15.00
Paid By:Amy Wine Venerable-Notes:ck#1096
FEE TOTAL $18,439.75
AMOUNT PAID $18,439.75
BALANCE DUE $0.00
75 South Frontage Road West,Vail,Colorado 81657 08/31/2018 -4:44:53 PM-Generated by:cgodfrey
1/1
{ JuL-ed-eum 10:44 From:HP-GEOTECH 9709458454 To: 19708459569 P.2/5
I h-r•N...tlh I'au-I.d. (,t r,�„I,w, tI In,
GeS" teCh
t dr Mt' NI 11•nu ,1 t . L n n l•. ‘I n, 1
070"45 791,
HEPWORTH-PAWLAK GEOTECHNICAL hat .1i,t t145 n4S4
(m•nl ftl•kr, ltl,gt,.tv.l,.-..m
July 22, 2008 .
lop -- o a 73 ,
Ssc2_,
Sunder, Inc.
Attn: John Sunderland
P.O. Box 1393 j
Edwards, Colorado 81632
Job No. 108 400A
Subject: Observation of Excavation, Proposed Western Half of Existing Duplex,
Lot 26, Block 7, Vail Village 1' Filing, 185 Forest Road, Vail, Colorado.
Dear Mr. Sunderland:
As requested, a representative of Hepworth-Pawlak Geotechnical, Inc. observed the
excavation at the subject site on July 17, 2008 to evaluate the soils exposed for foundation
support. The findings of our observations and recommendations for the foundation
design are presented in this report. The services were performed in accordance with our
agreement for professional engineering services to Sunder, Inc., dated July 16, 2008.
The western half of the existing duplex was razed as part of the proposed construction.
The proposed construction will consist of a two story wood frame structure over a
walkout basement level. We understand that due to over-excavation of unsuitable bearing
soils in the building area, a structural basement floor is being planned. The attached
garage floor will be slab-on-grade. Spread footings sized for an allowable soil bearing
pressure of 2,000 psf were assumed in the design.
At the time of our visit to the site, the foundation excavation had been cut in multiple
levels from 3 to 10 feet below the adjacent ground surface. The uphill, southern portion
of the excavation had not been completed. The soils exposed in the bottom of the
excavation consisted of slightly clayey silty sand and gravel in the northern portion of the
excavation and silty sand in the southwest portion of the excavation. The cut depths
extended through the old fill from the previous construction. Results of swell-
consolidation testing performed on a sample of silty sand taken from the site, shown on
Figure 1, indicate the soils have low to moderate compressibility under conditions of
loading and wetting. The results of a gradation analysis performed on a sample of silty
I`ctrkt:r 1014;41-7119 • Coln at.ln Springs 710 01 55(.2 0 •,ikt tllrr,rn, `r7O 4t !kw')
JUL-22-2008 10:44 From:HP-CEOTECH 9709458454 To:19708459569 P.3/5
Sunder, Inc.
July 22, 2008
Page 2
sand and gravel (minus 3 inch fraction) obtained from the site are presented on Figure 2.
No free water was encountered in the excavation and the soils were slightly moist to
moist.
Considering the conditions exposed in the excavation and the nature of the proposed
construction, spread footings placed on the undisturbed natural soil designed for an
allowable soil bearing pressure of 2,000 psf should be adequate for support of the
proposed western half of the duplex. The bearing soils are variable and the silty sand
soils tend to compress when loaded and wetted. There could be some post-construction
settlement of the foundation that could be differential between the different bearing
materials and the eastern half of the duplex. Footings should be a minimum width of 16
inches for continuous walls and 2 feet for columns. Loose disturbed soils and any
remaining fill in footing areas should be removed and the bearing level extended down to
the undisturbed natural soils. Exterior footings should be provided with adequate soil
cover above their bearing elevations for frost protection. Continuous foundation walls
should be reinforced top and bottom to span local anomalies such as by assuming an
unsupported length of at least 12 feet. Foundation walls acting as retaining structures
should also be designed to resist a lateral earth pressure based on an equivalent fluid unit
weight of at least 50 pcf for on-site soil as backfill. A perimeter foundation drain should
be provided to prevent temporary buildup of hydrostatic pressure behind the basement
walls and prevent wetting of the lower level. Structural fill placed within floor slab areas
can consist of the on-site soils compacted to at least 950/0 of standard Proctor density at a
moisture content near optimum. Backfill placed around the structure should be
compacted and the surface graded to prevent ponding within at least 10 feet of the
building.
}
The recommendations submitted in this letter are based on our observation of the soils
exposed within the foundation excavation and do not include subsurface exploration to
evaluate the subsurface conditions within the loaded depth of foundation influence. This
study is based on the assumption that soils beneath the footings have equal or better
support than those exposed. The risk of foundation movement may be greater than
indicated in this report because of possible variations in the subsurface conditions. In
order to reveal the nature and extent of variations in the subsurface conditions below the t1
t
Job No. 108 400A
Cates
JUL-22-2008 10:44 From:HP-C3EOTECH 9709458454 To:19708459569 P.4/5
Sunder, Inc.
July 22, 2008
Page 3
excavation, drilling would be required. It is possible the data obtained by subsurface
exploration could change the recommendations contained in this letter. Our services do
not include determining the presence, prevention or possibility of mold or other biological
contaminants (MOBC) developing in the future. If the client is concerned about MOBC,
then a professional in this special field of practice should be consulted.
If you have any questions or need further assistance, please call our office.
Sincerely,
•
HEPWORTH — PAWLAK GEOTECHNICAL, 114C.
F
}
Jordy Z. Adamson, Jr. P.E ! 297O7i
Rev. by: SLP ,��,I toe's:....,. ,...+C$
k% S/ONAL �t ;
JZA/vam
attachments Figure 1 — Swell-Consolidation Test Results
Figure 2— Gradation Test Results
} Job No. 108 400A 1
Gatech
x
I
JUL-22-2008 10:44 From:HP-GEOTECH 9709458454 To: 19708459569 P.5/5
Moisture Content = 14.8 percent
Dry Density = 110 pcf
Sample of: Silty Sand
From: Bottom of Excavation at Southwest Corner
I
0
c 1 111111
g li
a 2
8 11111
3
tmt11IIIIL___11111111
o moveen110
on
IIIIIII1111111 11111111 111111111111 1111111 1111111 .
i 1111 III 101111
}
1
IIIIIII 1111111 111111110.1 1.0 10 100
APPUED PRESSURE-ksf
_111 ,
108 400A ____ fihh SWELL-CONSOLIDATION TEST RESULTS Figure 1
H.pwrth-Pawlak=n4
‘r' n6 REScheck Software Version 4.6.5
Compliance Certificate
Project VENERABLE RESIDENCE
Energy Code: 2015 IECC
Location: Vail, Colorado
Construction Type: Single-family
Project Type: New Construction
Orientation: Bldg. faces 180 deg. from North
Conditioned Floor Area: 4,432 ft2
Glazing Area 26%
Climate Zone: 6 (9248 HDD)
Permit Date: TBD
Permit Number: TBD
Construction Site: Owner/Agent: Designer/Contractor:
0175 FORESTRD ED VENERABLE SHAYNE MITCHELL
VAIL,CO 81658 LOWDERMILK-MITCHELL
MECHANICAL,LLC
PO BOX 172
WOLCOTT
CO,CO 81622
970.328.6324
SHAYNE@SHAYNEMITCHELL.COM
Compliance:Passes using UA trade-off
Compliance: 0.0% Better Than Code Maximum UA: 670 Your UA: 670
The%Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DO ESNOTprovide an estimate of energy use or cost relative to a minimum-code home.
Envelope Assemblies
Gross Area Cavity Cont.
Assembly or R-Value R-Value U-Factor UA
Perimeter
WALL 1 LOWERLEVELABOVEGRADE:Wood Frame, 16" o.c. 1,636 28.0 0.0 0.050 71
Orientation:Front
Window 1: Wood Frame:Triple Pane with Low-E 96 0.290 28
Orientation:Front
Door 1: Glass 120 0.290 35
Orientation:Front
WALL 2 MAIN LEVEL: Wood Frame, 16" o.c. 1,412 28.0 0.0 0.050 47
Orientation:Back
Window 2: Wood Frame:Triple Pane with Low-E 188 0.290 55
Orientation:Back
Door 2: Glass 281 0.290 81
Orientation:Back
WALL3 UPPER LEVEL: Wood Frame, 16" o.c. 1,461 28.0 0.0 0.050 50
Orientation:Right side
Window 3: Wood Frame:Triple Pane with Low-E 225 0.290 65
Orientation:Right side
Door 3: Glass 243 0.290 70
Orientation:Right side
ROOFASSEMBLY: Cathedral Ceiling 1,508 49.0 0.0 0.022 33
Project Title:VENERABLE RESIDENCE Report date: 08/22/18
Data filename: C:\Users\Shayhe\Documents\REScheck\0175 FORESTRESCHECK.rck Page 1 of10
Gross Area Cavity Cont.
Assembly or R-Value R-Value U-Factor UA
Perimeter
SUBGRADE WALLS: Solid Concrete or Masonry 600 28.0 0.0 0.043 26
Orientation:Left side
Wall height: 10.0'
Depth below grade: 8.0'
Insulation depth: 10.0'
BASEMENT FLOOR:Slab-On-Grade:Heated 124 13.0 0.883 109
Insulation depth: 1.0'
Compliance Statement: The proposed building design described here is consistent with the building plans,specifications,and other
calculations submitted with the permit application.The proposed building has been designed to meet the 2015 IECC requirements in
REScheck Version 4.6.5 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Name -Title Signature Date
Project Title:VENERABLE RESIDENCE Report date: 08/22/18
Data filename: C:\Users\Shayhe\Documents\REScheck\0175 FORESTRESCHECK.rck Page 2 of10
REScheck Software VersionChecklist 4.6.5
Energy Code: 2015 IECC
Requirements: 100.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement,the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section Plans Verified Field Verified
# Pre-Inspection/Plan Review Value Value Complies? Comments/Assumptions
& Req.ID
103.1, Construction drawings and Complies Requirement will be met.
103.2 documentation demonstrate ❑Does Not
[PR1]1 energy code compliance for the
La building envelope.Thermal ❑Not Observable
envelope represented on ❑Not Applicable
construction documents.
103.1, ;Construction drawings and Complies 'Requirement will be met.
103.2, documentation demonstrate ❑Does Not
403.7 energy code compliance for
[PR3]1 lighting and mechanical systems. ❑Not Observable
U.' Systems serving multiple ❑Not Applicable
dwelling units must demonstrate
compliance with the IECC
Commercial Provisions.
AP
302.1, Heating and cooling equipment is Heating: Heating: Complies Requirement will be met.
403.7 sized per ACCA Manual S based Btu/hr Btu/hr ❑Does Not
[PR2]z on loads calculated per ACCA Cooling: Cooling:
y, Manual J or other methods [Not Observable
Btu/hr Btu/hr
approved by the code official. ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title:VENERABLE RESIDENCE Report date: 08/22/18
Data filename: C:\Users\Shayhe\Documents\REScheck\0175 FO RESTRESCHECK.rck Page 3 of10
Section Plans Verified Field Verified
# Foundation Inspection Value Value Complies? Comments/Assumptions
& Req.ID
402.1.2 Slab edge insulation R-value. R- : R- ❑Complies See the Envelope Assemblies
[FO1P ❑ Unheated ; ❑ Unheated ❑Does Not table for values.
0 ❑ Heated ❑ Heated [Not Observable
ENot Applicable
402.1.2 Slab edge insulation ft ft I❑Complies See the Envelope Assemblies
[F03]' depth/length. ❑Does Not table for values.
til [Not Observable
❑Not Applicable
402.1.1 :Conditioned basement wall R- R- ❑Complies See the Envelope Assemblies
[F04]1 'insulation R-value.Where interior R_ R- ❑Does Not table for values.
0 insulation is used, verification ❑Not O bservable
may need to occur during
Insulation Inspection. Not ❑Not Applicable
required in warm-humid locations
in Climate Zone 3.
303.2 Conditioned basement wall EComplies Requirement will be met.
[F05]1 insulation installed per EDoes Not
manufacturer's instructions.
[Not O bservable
,❑Not Applicable
402.2.9 Conditioned basement wall ft ft ❑Complies See the Envelope Assemblies
[F06]i insulation depth of burial or ❑Does Not table for values.
distance from top of wall.
['Not Observable
❑Not Applicable
303.2.1 'A protective covering is installed ❑Complies Exception: Requirement is
[F01112 to protect exposed exterior ❑Does Not not applicable.
insulation and extends a
,minimum of 6 in. below grade. ['Not O bservable
❑Not Applicable
403.9 Snow-and ice-melting system ❑Complies Requirement will be met.
[FO controls installed. ❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 I High Impact(Tier 1) 12 Medium Impact (Tier 2) 3 Low Impact(Tier 3)
Project Title:VENERABLE RESIDENCE Report date: 08/22/18
Data filename: C:\Users\Shayhe\Documents\REScheck\0175 FORESTRESCHECK.rck Page 4 of10
Section Plans Verified Field Verified
# Framing/ Rough-In Inspection Value Value Complies? Comments/Assumptions
& Req.ID
402.1.1, Glazing U-factor(area-weighted U- U- ❑Complies See the Envelope Assemblies
402.3.1, average). ❑Does Not table for values.
402.3.3,
402.5 ['Not Observable
[FR2]1 ENot Applicable
CO
303.1.3 :U-factors of fenestration products ❑Complies Requirement will be met.
[FR4]1 :are determined in accordance ❑Does Not
a ;with the NFRC test procedure or
[Not Observable
;taken from the default table.
1 ❑Not Applicable
402.4.1.1 'Air barrier and thermal barrier EComplies Requirement will be met.
[FR23]1 installed per manufacturer's ElDoes Not
instructions.
ENot Observable
❑Not Applicable
402.4.3 Fenestration that is not site built i EComplies Requirement will be met.
[FR20]1 is listed and labeled as meeting 1 ❑Does Not
' AAMA/WDMA/CSA 101/I.S.2/A4401
ENot Observable
or has infiltration rates per NFRC
400 that do not exceed code ❑Not Applicable
limits.
402.4. IC-rated recessed lighting fixtures EComplies Requirement will be met.
[FR16 sealed at housing/interior finish ❑Does Not
and labeled to indicate <_2.0 cfm
leakage at 75 Pa. ENot Observable
ENot Applicable
403.3.1 :Supply and return ducts in attics EComplies Requirement will be met.
[FR12]1 insulated >= R-8 where duct is ❑Does Not
>= 3 inches in diameter and >= [Not Observable
R-6 where< 3 inches. Supply and
return ducts in other portions of ENot Applicable
;the building insulated >= R-6 for
;diameter >= 3 inches and R-4.2
for< 3 inches in diameter.
403.3.5 Building cavities are not used as EComplies Requirement will be met.
[FR15]3 ducts or plenums. ❑Does Not
LQ' [Not Observable
❑Not Applicable
403.4 'HVAC piping conveying fluids R- R- EComplies Requirement will be met.
[FR17] above 105°F or chilled fluids ❑Does Not
Le below 55 °F are insulated to >_R-
[Not Observable
3.
❑Not Applicable
403.4.1 Protection of insulation on HVAC ❑Complies Requirement will be met.
[FR24]1 piping. ❑Does Not
' ❑Not Observable
❑Not Applicable
403.5.3 :Hot water pipes are insulated to R- R- ❑Complies Requirement will be met.
[FR18]2 >_R-3. ❑Does Not
['Not Observable
EINot Applicable
403.6 ;Automatic or gravity dampers are ❑Complies Requirement will be met.
[FR19]2 installed on all outdoor air ❑Does Not
intakes and exhausts.
[Not O bservable
E Not Applicable
Additional Comments/Assumptions:
1 I High Impact(Tier 1) 12 Medium Impact (Tier 2) 3 Low Impact(Tier 3)
Project Title:VENERABLE RESIDENCE Report date: 08/22/18
Data filename: C:\Users\Shayhe\Documents\REScheck\0175 FORESTRESCHECK.rck Page 5 of10
U High Impact(Tier 1) 12 Medium Impact (Tier 2) 3 Low Impact(Tier 3)
Project Title:VENERABLE RESIDENCE Report date: 08/22/18
Data filename: C:\Users\Shayhe\Documents\REScheck\0175 FORESTRESCHECK.rck Page 6 of10
Section Plans Verified Field Verified
# Insulation Inspection Value Value Complies? Comments/Assumptions
& Req.ID
303.1 All installed insulation is labeled Complies Requirement will be met.
[IN13]2 'or the installed R-values ElDoes Not
V provided.
[Not Observable
❑Not Applicable
402.1.1, :Wall insulation R-value. If this is a R- R- ❑Complies See the Envelope Assemblies
402.2.5, mass wall with at least 1/2 of the ❑ Wood :❑ Wood ❑Does Not table for values.
402.2.6 ;wall insulation on the wall ❑ Mass ❑ Mass ['Not Observable
[IN3]1 ;exterior,the exterior insulation
�, 'requirementapplies(FR10).
III Steel ❑ Steel Not Applicable
303.2 Wall insulation is installed per EComplies Requirement will be met.
[IN4]1 manufacturer's instructions. ❑Does Not
[Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 I High Impact(Tier 1) 12 Medium Impact (Tier 2) 3 Low Impact(Tier 3)
Project Title:VENERABLE RESIDENCE Report date: 08/22/18
Data filename: C:\Users\Shayhe\Documents\REScheck\0175 FORESTRESCHECK.rck Page 7 of10
Section Plans Verified Field Verified
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
& Req.ID
402.1.1, Ceiling insulation R-value. R- R- ❑Complies See the Envelope Assemblies
402.2.1, ❑ Wood ❑ Wood ❑Does Not table for values.
402.2.2, ❑ Steel ❑ Steel ['Not Observable
402.2.6
[F11]1 ENot Applicable
303.1.1.1,'Ceiling insulation installed per EComplies Requirement will be met.
303.2 manufacturer's instructions. ❑Does Not
[F12]1 Blown insulation marked every
300 ft2. [Not Observable
❑Not Applicable
402.2.3 Vented attics with air permeable EComplies :Exception: Requirement is
[F122] insulation include baffle adjacent ❑Does Not not applicable.
to soffit and eave vents that
extends over insulation.
[Not Observable
ENot Applicable
402.2.4 Attic access hatch and door R- R- EComplies Requirement will be met.
[F13]1 insulation >_R-value of the ❑Does Not
adjacent assembly.
ENot Observable
E Not Applicable
402.4.1.2 Blower door test @ 50 Pa. <=5 ACH 50 = ACH 50 = EComplies Requirement will be met.
[F117]1 ach in Climate Zones 1-2, and ❑Does Not
<=3 ach in Climate Zones 3-8.
['Not Observable
❑Not Applicable
403.3.4 :Duct tightness test result of<=4 cfm/100 cfm/100 EComplies Requirement will be met.
[F14]1 1 cfm/100 ft2 across the system or ft2 ft2 ❑Does Not
<=3 cfm/100ft2 without air
:handler @ 25 Pa. For rough-in [Not O bservable
:tests,verification may need to ENot Applicable
occur during Framing Inspection.
403.3.3 :Ducts are pressure tested to cfm/100 cfm/100 EComplies Requirement will be met.
[F127]1 determine air leakage with ft2 ft2 ❑Does Not
:either:Rough-in test:Total
:leakage measured with a [Not O bservable
pressure differential of 0.1 inch:pressure Applicable
w.g. across the system including
the manufacturer's air handler
enclosure if installed at time of
test. Postconstruction test:Total
leakage measured with a
pressure differential of 0.1 inch
w.g. across the entire system
including the manufacturer's air
handler enclosure.
I
403.3.2.1 :Air handler leakage designated EComplies 'Requirementwill be met.
[F124]1 :by manufacturer at <=2% of ❑Does Not
design air flow.
[Not Observable
❑Not Applicable
403.1. Programmable thermostats EComplies Requirement will be met.
[F19]2 installed for control of primary ❑Does Not
heating and cooling systems and
initially set by manufacturer to ['Not O bservable
:code specifications. ENot Applicable
403.1.2 Heat pump thermostat installed ❑Complies Exception: Requirement is
[F110]2 on heat pumps. ❑Does Not not applicable.
E Not O bservable
❑Not Applicable
11403.5. Circulating service hot water ❑Complies Requirement will be met.
systems have automatic or ❑Does Not
accessible manual controls.
[Not Observable
❑Not Applicable
1 I High Impact(Tier 1) 12 Medium Impact (Tier 2) 3 Low Impact(Tier 3)
Project Title:VENERABLE RESIDENCE Report date: 08/22/18
Data filename: C:\Users\Shayhe\Documents\REScheck\0175 FORESTRESCHECK.rck Page 8 of10
Section Plans Verified Field Verified
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
& Req.ID
403.6.1 All mechanical ventilation system' Complies Requirement will be met.
[F125]2 fnot d •EDoes Not
HVACans equipmentpart of meettestedanefficacylistedand air flow limits. ❑Not Observable
❑Not Applicable
403.2 ;Hot water boilers supplying heat ❑Complies Requirement will be met.
[F126]2 through one-or two-pipe heating ❑Does Not
systems have outdoor setback
control to lower boiler water ['Not Observable
temperature based on outdoor ❑Not Applicable
;temperature.
403.5.1.1 I Heated water circulation systems ❑Complies Requirement will be met.
[FI28]2 have a circulation pump.The ❑Does Not
system return pipe is a dedicated
return pipe or a cold water supply [Not Observable
pipe.Gravity and thermos- ❑Not Applicable
syphon circulation systems are
not present.Controls for
circulating hot water system
pumps start the pump with signal ,
for hot water demand within the
occupancy. Controls
automatically turn off the pump
when water is in circulation loop
is at set-point temperature and
no demand for hot water exists.
403.5.1.2 :Electric heat trace systems ❑Complies Exception: Requirement is
[F129]2 comply with IEEE 515.1 or UL ❑Does Not not applicable.
515. Controls automatically
adjust the energy input to the ❑Not O bservable
heat tracing to maintain the ENot Applicable
desired water temperature in the
piping. ,
403.5. Water distribution systems that ' ❑Complies Requirement will be met.
[F130]2 have recirculation pumps that ❑Does Not
pump water from a heated water
supply pipe back to the heated ['Not Observable
water source through a cold ❑Not Applicable
water supply pipe have a
demand recirculation water
:system. Pumps have controls
IIIthat manage operation of the
pump and limit the temperature
of the water entering the cold
water piping to 104°F.
403.5.4 Drain water heat recovery units EComplies Exception: Requirement is
[F131]2 tested in accordance with CSA ❑Does Not not applicable.
B55.1. Potable water-side
pressure loss of drain water heat [Not O bservable
Irecovery units< 3 psi for ❑Not Applicable
individual units connected to one
or two showers.Potable water-
side pressure loss of drain water
j heat recovery units< 2 psi for
-1 individual units connected to
three or more showers.
404.1 75% of lamps in permanent ❑Complies Requirement will be met.
[F16]1 fixtures or 75%of permanent ❑Does Not
fixtures have high efficacy lamps.
Does not apply to low-voltage ['Not Observable
lighting. ,❑Not Applicable
404.1.1 Fuel gas lighting systems have ❑Complies Exception: Requirement is
[F123]3 no continuous pilot light. ❑Does Not not applicable.
' ['Not Observable
❑Not Applicable
1 I High Impact(Tier 1) 12 Medium Impact (Tier 2) 3 Low Impact(Tier 3)
Project Title:VENERABLE RESIDENCE Report date: 08/22/18
Data filename: C:\Users\Shayhe\Documents\REScheck\0175 FORESTRESCHECK.rck Page 9 of10
Section Plans Verified Field Verified
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
& Req.ID
401.3 ;Compliance certificate posted. ❑Complies Requirement will be met.
[F17]2 : ElDoes Not
, [Not Observable
❑Not Applicable
303.3 Manufacturer manuals for ❑Complies Requirement will be met.
[F118]3 i mechanical and water heating ❑Does Not
systems have been provided. •
[Not Observable
, ,❑Not Applicable
Additional Comments/Assumptions:
1 I High Impact(Tier 1) 12 Medium Impact (Tier 2) 3 Low Impact(Tier 3)
Project Title:VENERABLE RESIDENCE Report date: 08/22/18
Data filename: C:\Users\Shayhe\Documents\REScheck\0175 FORESTRESCHECK.rck Page 10 of10
2015 IECC Energy
Efficiency Certificate
Insulation Rating R-Value
Above-Grade Wall 28.00
Below-Grade Wall 28.00
Floor 13.00
Ceiling / Roof 49.00
Ductwork(unconditioned spaces):
Glass &Door Rating U-Factor SHGC
Window 0.29 0.20
Door 0.29 0.20
Heating&Cooling Equipment Efficiency
Heating System:
Cooling System:
Water Heater:
1111 11=1
Name: Date:
Comments
1
„ ,/
Boulder Environmental Inc.
2400 Broadway St.,Unit B,Boulder,CO 80304
Phone:(303)382-1175 Fax: 1 (866)699-4121
March 29, 2018
Paragon Homes
Ed Venerable
Ed@paragonhomesdenver.com
SUBJECT: Asbestos Survey and Bulk Sampling for Building Demolition
175 Forest Road,Vail,Colorado
Dear Mr.Venerable:
Attached is the report for the bulk sampling of suspected asbestos-containing materials at
175 Forest Road,Vail,Colorado. This report must be used for complete building
demolition purposes only.
This investigation was conducted on behalf of and for the exclusive use of Paragon
Homes(client). This report and the findings herein shall not,in whole or in part,be
disseminated or conveyed to any other party,nor used by any other party,in whole or in
part,without prior written consent of Boulder Environmental Inc.
Personnel knowledgeable of asbestos containing materials should always oversee
demolition activities. Demolition work should be halted and sampling performed by a
state of Colorado licensed building inspector if additional materials, which are suspected
of containing asbestos, are encountered.
If you have any questions regarding the contents of this report,please do not hesitate to
contact us.
Sincerely,
V l
Chris Maron
Project Manager
CO Building Inspector#615
1 iPage