December 20, 2018
Mike Vaughan
Fire Marshall —Town of Vail
2399 North Frontage Road West
Vail, CO 81657
RE: Marriott—Vail, CO
Fire Protection System —Colorado Ballroom/Pre-function/Conference Rooms
Mr. Vaughn:
Rondinelli Life Safety was on-site on December 20, 2018, to perform pre-testing of the fire
protection systems in the renovation of the Colorado Ballroom/Pre-function/Conference
Rooms. Testing began with Alarm Specialists at approximately 1:00pm and ended at 2:30pm.
Below you find my comments and observations from today.
1. All smoke detectors located in the ballrooms, conference, pre-function, and corridor
were activated using aerosol smoke. Each device successfully reported an alarm
condition at the FACP as well as verified that the device address and location matched
the location in the FACP.
2. Manual pull station located in the main corridor were activated and the location of the
pull station was confirmed at the FACP. All horns and strobes successfully activated, and
all strobes were in sync with each other.
Fire Protection and Code Consulting
15272 West Warren Drive-Lakewood, Colorado, 80228
Phone: 303.807.3321
Steve@RondinelliLifeSafety.corn
RondinelliLifeSafety.corn
le2 k PId«ell
LIFE SAFE T Y
3. Other observations noted during pre-testing:
• The electrical breaker panel doors located in the Mountain View Conference Room
were removed: 1`
li is
II1
• Some of the magnetic hold open devices still need to be installed on doors.
IP
V
i` 1
\
Fire Protection and Code Consulting
15272 West Warren Drive-Lakewood, Colorado, 80228
Phone: 303.807.3321
Steve@RondinelliLifeSafety.corn
RondinelliLifeSafety.corn
Q��d«ell
LIFE SAFE T Y
Based upon Rondinelli Life Safety's testing and observations, it is our belief the fire protection
system is installed and properly working as designed and that final testing of the 5th floor can
proceed as scheduled. If you have any questions or concerns, please feel free to contact me at
303.748.5846.
Report Prepared By:
Shaun Rondinelli
Life Safety Specialist
Rondinelli Life Safety
Reviewed By:
c;i C040,
co 4,TEPHEN 0
-.wet TON 4
rte►
A 47
r ACV
p r4
a MA Pier
Stephen Rondinelli, AIA
Rondinelli Life Safety