Loading...
HomeMy WebLinkAboutB16-0490_E1_1501275565.pdf1 of 1 12/29/16 Row House 12 Load Calculation Lighting Demand Load line neutral Square Footage 2926 8778 8778 Small Appliance 2 1500 3000 3000 Laundry Circuit 1 1500 1500 1500 Total Load 13278 13278 First 3000w @ 100% 3000 3000 Next 3001 to 120000 @ 35% 3597 3597.3 Remainder @ 25% 0 0 Total Lighting Demand =======> 6597 6597.3 A/C and Heat Demand Air Conditioning Load 240V Qua KVA Total 3hp 2.5 ton 2 10 20 0 Air Conditioning Total 20 Electric Heat Load 240V 0 0 0 0 0 0 Electric Heat Total 0 Air Conditioning Larger Total Heat vs. Air Conditioning=> 20000 omit electric heat Appliance Fastened in Place Voltage Qua Watts Line Neutral Humidifiers 208 4 1600 6400 0 Air Handlers 208 4 1000 4000 0 Boilers 120 2 500 1000 1000 Steamers 208 2 12000 24000 0 Exhaust fans 120 4 800 3200 3200 AV Equipment 120 2 1600 3200 3200 120 0 0 0 0 120 0 0 0 0 120 0 0 0 0 120 0 0 0 0 240 0 0 0 0 120 0 0 0 0 120 0 0 0 0 120 0 0 0 0 120 0 0 0 0 240 0 0 0 0 120 0 0 0 0 240 0 0 0 0 240 0 0 0 0 240 0 0 0 0 240 0 0 0 0 0 0 0 0 0 0 Total Appliance (75% for 4 or more) 41800 7400 31350 5550 Elec.Clothes Dryer (5Kw min) 1 5000 Demand Factor % (220-18) 100% 5000 3500 Electric Cooking Equipment Demand Factor Kw (220-19) 0 0 0 Largest Motor * 25% volts , watts 240 4500 1125 0 Total Demand line 64072 Total Demand Neutral 15647 Line Amperage Demand 267 Neutral Amperage 65 220-22 First 200 at 100% 65 Remainder at 70% 0 Neutral Amperage Demand 65 System Voltage H,L 240 120 Service Size ====>> 300 07/28/17