HomeMy WebLinkAbout14095-Comcheck Report-091217COMcheck Software Version 4.0.7.0
Envelope Compliance Certificate
Project Title:
2015 IECC
Project Type:New Construction
Vertical Glazing / Wall Area:30%
Location:Vail, Colorado
Climate Zone:6b
Construction Site:
598 Vail Valley Drive
Vail, CO 81657
Owner/Agent:Designer/Contractor:
K.H. Webb Architecs, PC
710 West Lionshead Circle
Suite A
Vail, CO 81657
Project Information
Energy Code:
Ski & Snowboard Club of Vail
Building Area Floor Area
1-Office : Nonresidential 43554
Envelope Assemblies
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
Roof: Insulation Entirely Above Deck, [Bldg. Use 1 - Office]6374 ---30.0 0.032 0.032
Roof Deck: Insulation Entirely Above Deck, [Bldg. Use 1 - Office]11052 ---30.0 0.032 0.032
AG Walls: Steel-Framed, 16" o.c., [Bldg. Use 1 - Office]18603 13.0 7.5 0.064 0.064
Windows: Metal Frame:Fixed, Perf. Specs.: Product ID na, SHGC 0.40,
[Bldg. Use 1 - Office] (b)
4813 ------0.290 0.360
Glass Doors: Glass (> 50% glazing):Metal Frame, Non-Entrance Door,
Perf. Specs.: Product ID na, SHGC 0.40, [Bldg. Use 1 - Office] (b)
771 ------0.290 0.770
Solid Doors: Wood, Swinging, [Bldg. Use 1 - Office]518 ------0.290 0.370
BG Walls: Solid Concrete:8" Thickness, Normal Density, Furring: None,
Wall Ht 11.0, Depth B.G. 11.0, [Bldg. Use 1 - Office]
7082 ---7.5 0.113 0.108
Garage Slab: Slab-On-Grade:Unheated, Horizontal without vertical 2 ft.,
[Bldg. Use 1 - Office] (c)
66 ---10.0 0.700 0.540
Floor Above Outside Air: Steel Joist, [Bldg. Use 1 - Office]3324 38.0 0.0 0.032 0.033
Additional Efficiency Package
Reduced interior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations.
(a)Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.
(b)Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
(c)Slab-On-Grade proposed and budget U-factors shown in table are F-factors.
Project Notes
Calcs by: Joey Brenner - Rader Engineering (970)-845-7910
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
281 ofPage
9/12/17
Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed envelope systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.0.7.0 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Envelope PASSES: Design 0.1% better than code
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
282 ofPage
Joey Brenner - Mechanical Engineer 9/12/17
COMcheck Software Version 4.0.7.0
Mechanical Compliance Certificate
Project Title:
2015 IECC
Project Type:New Construction
Location:Vail, Colorado
Climate Zone:6b
Construction Site:
598 Vail Valley Drive
Vail, CO 81657
Owner/Agent:Designer/Contractor:
K.H. Webb Architecs, PC
710 West Lionshead Circle
Suite A
Vail, CO 81657
Project Information
Energy Code:
Ski & Snowboard Club of Vail
Reduced interior lighting power. Requirements are implicitly enforced within interior lighting allowance calculations.
Additional Efficiency Package
Mechanical Systems List
Quantity System Type & Description
Heating: 1 each - Radiant Heater, Hot Water, Capacity = 107 kBtu/h
No minimum efficiency requirement applies
Fan System: None
1 PR-1 2 Panel Radiators (Single Zone):
Heating: 1 each - Hydronic or Steam Coil (FC-1), Hot Water, Capacity = 80 kBtu/h
No minimum efficiency requirement applies
Fan System: FC-1 | Club Room -- Compliance (Motor nameplate HP method) : Passes
Fans:
FC 1 Supply, Constant Volume, 2250 CFM, 1.5 motor nameplate hp, 0.0 fan efficiency grade
1 FC-1 Fan Coil (Single Zone):
Heating: 1 each - Hydronic or Steam Coil (FC-2), Hot Water, Capacity = 75 kBtu/h
No minimum efficiency requirement applies
Fan System: FC-2 | Gym -- Compliance (Motor nameplate HP method) : Passes
Fans:
FC 2 Supply, Constant Volume, 1500 CFM, 1.0 motor nameplate hp, 0.0 fan efficiency grade
1 FC-2 Fan Coil (Single Zone):
Heating: 1 each - Hydronic or Steam Coil (FC-3), Hot Water, Capacity = 29 kBtu/h
No minimum efficiency requirement applies
Fan System: FC-3 | Board Room -- Compliance (Motor nameplate HP method) : Passes
Fans:
FC 3 Supply, Constant Volume, 700 CFM, 0.8 motor nameplate hp, 0.0 fan efficiency grade
1 FC-3 Fan Coil (Single Zone):
Heating: 1 each - Hydronic or Steam Coil (MAU-1), Hot Water, Capacity = 190 kBtu/h
No minimum efficiency requirement applies
Fan System: MAU-1 | Ski Tuning Make-Up Air -- Compliance (Motor nameplate HP method) : Passes
Fans:
MAU 1 Supply, Constant Volume, 2200 CFM, 1.5 motor nameplate hp, 0.0 fan efficiency grade
1 MAU-1 Make-Up Air Unit (Single Zone):
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
283 ofPage
Quantity System Type & Description
Heating: 5 each - Unit Heater (GUH-1), Hot Water, Capacity = 52 kBtu/h
No minimum efficiency requirement applies
Fan System: GUH-1 Fan | Garage -- Compliance (Motor nameplate HP method) : Passes
Fans:
GUH 1 Fan Supply, Constant Volume, 2200 CFM, 0.3 motor nameplate hp, 0.9 fan efficiency grade
1 GUH-1 Garage Unit Heater (Unknown):
Heating: 3 each - Unit Heater (UH-1), Hot Water, Capacity = 7 kBtu/h
No minimum efficiency requirement applies
Fan System: UH-1 | Mechanical Rooms, Storage -- Compliance (Motor nameplate HP method) : Passes
Fans:
UH 1 Supply, Constant Volume, 395 CFM, 0.0 motor nameplate hp, 0.0 fan efficiency grade
1 UH-1 Unit Heater (Unknown):
Heating: 4 each - Unit Heater (UH-2), Hot Water, Capacity = 15 kBtu/h
No minimum efficiency requirement applies
Fan System: UH-2 | Mech Shop & Storage -- Compliance (Motor nameplate HP method) : Passes
Fans:
UH 2 Supply, Constant Volume, 550 CFM, 0.0 motor nameplate hp, 0.0 fan efficiency grade
1 UH-2 Unit Heater (Unknown):
Heating: 1 each - Unit Heater (UH-3), Hot Water, Capacity = 64 kBtu/h
No minimum efficiency requirement applies
Fan System: UH-3 | Boiler Room -- Compliance (Motor nameplate HP method) : Passes
Fans:
UH 3 Supply, Constant Volume, 2600 CFM, 0.3 motor nameplate hp, 0.0 fan efficiency grade
1 UH-3 Unit Heater (Unknown):
Heating: 15 each - Unit Heater (CUH-1), Hot Water, Capacity = 9 kBtu/h
No minimum efficiency requirement applies
Fan System: CUH-1 | Club Level -- Compliance (Motor nameplate HP method) : Passes
Fans:
CUH 1 Supply, Constant Volume, 230 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
1 CUH-1 Cabinet Unit Heater (Unknown):
Heating: 1 each - Unit Heater (CUH-2), Hot Water, Capacity = 17 kBtu/h
No minimum efficiency requirement applies
Fan System: CUH-2 | Reception Hall -- Compliance (Motor nameplate HP method) : Passes
Fans:
CUH 2 Supply, Constant Volume, 430 CFM, 0.2 motor nameplate hp, 0.0 fan efficiency grade
1 CUH-2 Cabinet Unit Heater (Unknown):
Heating: Hot Water Boiler, Capacity 2000 kBtu/h, Gas
Proposed Efficiency: 92.00 % Et, Required Efficiency: 80.00 % Et
2 B-1 & B-2 Boilers (Common):
Heating: Hot Water Boiler, Capacity 600 kBtu/h, Gas
Proposed Efficiency: 97.00 % Et, Required Efficiency: 80.00 % Et
2 B-3 & 4 Boilers (Club):
Gas Storage Water Heater, Capacity: 113 gallons, Input Rating: 75 kBtu/h w/ Circulation Pump
Proposed Efficiency: 90.00 EF, Required Efficiency: 0.46 EF
3 WH-1, 2, & 3 Water Heaters:
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
284 ofPage
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.0.7.0 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
285 ofPage
Joey Brenner - Mechanical Engineer 9/12/17
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.0.7.0
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2015 IECC
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR1]1
Plans and/or specifications provide all
information with which compliance
can be determined for the building
envelope and document where
exceptions to the standard are
claimed.
Complies
Does Not
Not Observable
Not Applicable
C103.2
[PR2]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the mechanical
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
Complies
Does Not
Not Observable
Not Applicable
C103.2
[PR3]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the service water
heating systems and equipment and
document where exceptions to the
standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
Complies
Does Not
Not Observable
Not Applicable
C402.4.1
[PR10]1
The vertical fenestration area <= 30
percent of the gross above-grade wall
area.
Complies
Does Not
Not Observable
Not Applicable
C402.4.1
[PR11]1
The skylight area <= 3 percent of the
gross roof area.
Complies
Does Not
Not Observable
Not Applicable
C406
[PR9]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
efficiency package options.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
286 ofPage
Section
#
& Req.ID
Footing / Foundation Inspection Complies?Comments/Assumptions
C303.2
[FO2]2
Below-grade wall insulation installed
per manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
C303.2
[FO4]2
Slab edge insulation installed per
manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
C303.2.1
[FO6]1
Exterior insulation protected against
damage, sunlight, moisture, wind,
landscaping and equipment
maintenance activities.
Complies
Does Not
Not Observable
Not Applicable
C402.1.4
[FO1]2
Below-grade wall insulation R-value.Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.5
[FO3]2
Slab edge insulation R-value.Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.6
[FO12]3
Radiant heating systems panels
insulated to >=R-3.5 on face opposite
space being heated.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C403.2.4.
5,
C403.2.4.
6
[FO9]3
Snow/ice melting system sensors for
future connection to controls. Freeze
protection systems have automatic
controls installed.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
287 ofPage
Section
#
& Req.ID
Framing / Rough-In Inspection Complies?Comments/Assumptions
C303.1.3
[FR12]2
Fenestration products rated in
accordance with NFRC.
Complies
Does Not
Not Observable
Not Applicable
C303.1.3
[FR13]1
Fenestration products are certified as
to performance labels or certificates
provided.
Complies
Does Not
Not Observable
Not Applicable
C402.4.3
[FR10]1
Vertical fenestration SHGC value.Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.4.3,
C402.4.3.
4
[FR8]1
Vertical fenestration U-Factor.Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.4.4
[FR14]2
U-factor of opaque doors associated
with the building thermal envelope
meets requirements.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.5.1.
2.2
[FR20]1
The building envelope contains a
continuous air barrier that is sealed in
an approved manner and average
assembly air leakage <= 0.04 cfm/ft2.
Air barrier penetrations are sealed in
an approved manner.
Complies
Does Not
Not Observable
Not Applicable
C402.5.2,
C402.5.4
[FR18]3
Factory-built fenestration and doors
are labeled as meeting air leakage
requirements.
Complies
Does Not
Not Observable
Not Applicable
C402.5.7
[FR17]3
Vestibules are installed on all building
entrances. Doors have self-closing
devices.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
288 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
289 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.6.1,
C404.6.2
[PL3]1
Automatic time switches installed to
automatically switch off the
recirculating hot-water system or heat
trace.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2810 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2811 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2812 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2813 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2814 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C402.2.6
[ME41]3
Thermally ineffective panel surfaces of
sensible heating panels have
insulation >= R-3.5.
Complies
Does Not
Not Observable
Not Applicable
C402.5.5,
C403.2.4.
3
[ME3]3
Stair and elevator shaft vents have
motorized dampers that automatically
close.
Complies
Does Not
Not Observable
Not Applicable
C402.5.5,
C403.2.4.
3
[ME58]3
Outdoor air and exhaust systems have
motorized dampers that automatically
shut when not in use and meet
maximum leakage rates. Check
gravity dampers where allowed.
Complies
Does Not
Not Observable
Not Applicable
C403.2.12
.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.2.12
.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
C403.2.13
[ME71]2
Unenclosed spaces that are heated
use only radiant heat.
Complies
Does Not
Not Observable
Not Applicable
C403.2.3
[ME55]2
HVAC equipment efficiency verified.Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.2.5.
1
[ME114]2
Hot water boilers supplying heat via
one- or two-pipe systems include
outdoor setback control.
Complies
Does Not
Not Observable
Not Applicable
C403.2.5.
1
[ME114]2
Hot water boilers supplying heat via
one- or two-pipe systems include
outdoor setback control.
Complies
Does Not
Not Observable
Not Applicable
C403.2.6.
1
[ME59]1
Demand control ventilation provided
for spaces >500 ft2 and >25
people/1000 ft2 occupant density and
served by systems with air side
economizer, auto modulating outside
air damper control, or design airflow
>3,000 cfm.
Complies
Does Not
Not Observable
Not Applicable
C403.2.6.
2
[ME115]3
Enclosed parking garage ventilation
has automatic contaminant detection
and capacity to stage or modulate
fans to 50% or less of design capacity.
Complies
Does Not
Not Observable
Not Applicable
C403.2.7
[ME57]1
Exhaust air energy recovery on
systems meeting Table C403.2.7(1)
and C403.2.7(2).
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2815 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.2.8
[ME116]3
Kitchen exhaust systems comply with
replacement air and conditioned
supply air limitations, and satisfy hood
rating requirements and maximum
exhaust rate criteria.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9
[ME60]2
HVAC ducts and plenums insulated.
Where ducts or plenums are installed
in or under a slab, verification may
need to occur during Foundation
Inspection.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9
[ME10]2
Ducts and plenums sealed based on
static pressure and location.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2816 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2
[ME69]3
Temperature reset by representative
building loads in pumping systems for
chiller and boiler systems >500,000
Btu/h.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2
[ME69]3
Temperature reset by representative
building loads in pumping systems for
chiller and boiler systems >500,000
Btu/h.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2817 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.4.2.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
2
[ME64]2
Two-pipe hydronic systems using a
common distribution system have
controls to allow a deadband >=15 ºF,
allow operation in one mode for at
least 4 hrs before changeover, and
have rest controls to limit heating and
cooling supply temperature to <=30
ºF.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
2
[ME64]2
Two-pipe hydronic systems using a
common distribution system have
controls to allow a deadband >=15 ºF,
allow operation in one mode for at
least 4 hrs before changeover, and
have rest controls to limit heating and
cooling supply temperature to <=30
ºF.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
4
[ME68]3
Hydronic systems greater than
500,000 Btu/h designed for variable
fluid flow.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
4
[ME68]3
Hydronic systems greater than
500,000 Btu/h designed for variable
fluid flow.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
5
[ME107]3
System turndown requirement met
through multiple single-input boilers,
one or more modulating boilers, or a
combination of single-input and
modulating boilers. Boiler input
between 1.0 MBtu/h and 5 MBtu/h has
3:1 turndown ratio, boiler input
between 5.0 MBtu/h and 10 MBtu/h
has 4:1 turndown ratio, boiler input >
10.0 MBtu/h has 5:1 turndown ratio.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.4.2.
6
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
6
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
6
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2818 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.4.2.
6
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
6
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
6
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
6
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
6
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
6
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
6
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
C403.4.2.
6
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2819 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.4.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
C403.4.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2820 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.4.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
C403.4.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
C403.4.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
C403.4.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
C403.4.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
C403.4.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
C403.4.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
C403.4.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
C403.4.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
C404.2.1
[ME111]2
Gas-fired water-heating equipment
installed in new buildings: where a
singular piece of water-heating
equipment >= 1,000 kBtu/h serves
the entire building, thermal efficiency
>= 90 Et. Where multiple pieces of
water-heating equipment serve the
building with combined rating >=
1,000 kBtu/h, the combined input-
capacity-weighted-average thermal
efficiency >= 90 Et. Exclude input
rating of equipment in individual
dwelling units and equipment <= 100
kBtu/h.
Complies
Does Not
Not Observable
Not Applicable
C408.2.2.
1
[ME53]3
Air outlets and zone terminal devices
have means for air balancing.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2821 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2822 ofPage
Section
#
& Req.ID
Insulation Inspection Complies?Comments/Assumptions
C303.1
[IN3]1
Roof insulation installed per
manufacturer’s instructions. Blown or
poured loose-fill insulation is installed
only where the roof slope is <=3 in
12.
Complies
Does Not
Not Observable
Not Applicable
C303.1
[IN10]2
Building envelope insulation is labeled
with R-value or insulation certificate
providing R-value and other relevant
data.
Complies
Does Not
Not Observable
Not Applicable
C303.2
[IN7]1
Above-grade wall insulation installed
per manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
C303.2,
C402.2.4
[IN9]2
Floor insulation installed per
manufacturer’s instructions. Cavity or
structural slab insulation installed in
permanent contact with underside of
decking or structural slabs.
Complies
Does Not
Not Observable
Not Applicable
C303.2.1
[IN14]2
Exterior insulation is protected from
damage with a protective material.
Verification for exposed foundation
insulation may need to occur during
Foundation Inspection.
Complies
Does Not
Not Observable
Not Applicable
C402.2.1
[IN17]3
Insulation intended to meet the roof
insulation requirements cannot be
installed on top of a suspended
ceiling. Mark this requirement
compliant if insulation is installed
accordingly.
Complies
Does Not
Not Observable
Not Applicable
C402.2.3
[IN6]1
Above-grade wall insulation R-value.Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.5
[IN8]2
Floor insulation R-value.Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.6
[IN18]3
Radiant panels and associated
components, designed for heat
transfer from the panel surfaces to the
occupants or indoor space are
insulated with a minimum of R-3.5.
Complies
Does Not
Not Observable
Not Applicable
C402.4.2.
2
[IN2]1
Roof R-value. For some ceiling
systems, verification may need to
occur during Framing Inspection.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.5.1.
1
[IN1]1
All sources of air leakage in the
building thermal envelope are sealed,
caulked, gasketed, weather stripped
or wrapped with moisture vapor-
permeable wrapping material to
minimize air leakage.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2823 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C303.3,
C408.2.5.
3
[FI8]3
Furnished O&M manuals for HVAC
systems within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
C402.5.3
[FI51]3
Where open combustion air ducts
provide combustion air to open
combustion fuel burning appliances,
the appliances and combustion air
opening are located outside the
building thermal envelope or enclosed
in a room, isolated from inside the
thermal envelope. Such rooms are
sealed and insulated.
Complies
Does Not
Not Observable
Not Applicable
C402.5.6
[FI37]1
Weatherseals installed on all loading
dock cargo doors.
Complies
Does Not
Not Observable
Not Applicable
C402.5.8
[FI26]3
Recessed luminaires in thermal
envelope to limit infiltration and be IC
rated and labeled. Seal between
interior finish and luminaire housing.
Complies
Does Not
Not Observable
Not Applicable
C403.2.2
[FI27]3
HVAC systems and equipment
capacity does not exceed calculated
loads.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2824 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1.2
[FI38]3
Thermostatic controls have a 5 °F
deadband.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1.3
[FI20]3
Temperature controls have setpoint
overlap restrictions.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2
[FI39]3
Each zone equipped with setback
controls using automatic time clock or
programmable control system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.1,
C403.2.4.
2.2
[FI40]3
Automatic Controls: Setback to 55°F
(heat) and 85°F (cool); 7-day clock, 2-
hour occupant override, 10-hour
backup
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2825 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.3
[FI41]3
Systems include optimum start
controls.
Complies
Does Not
Not Observable
Not Applicable
C404.3
[FI11]3
Heat traps installed on supply and
discharge piping of non-circulating
systems.
Complies
Does Not
Not Observable
Not Applicable
C404.4
[FI25]2
All piping insulated in accordance with
section details and Table C403.2.10.
Complies
Does Not
Not Observable
Not Applicable
C404.6.1
[FI12]3
Controls are installed that limit the
operation of a recirculation pump
installed to maintain temperature of a
storage tank. System return pipe is a
dedicated return pipe or a cold water
supply pipe.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2826 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C408.2.1
[FI28]1
Commissioning plan developed by
registered design professional or
approved agency.
Complies
Does Not
Not Observable
Not Applicable
C408.2.3.
1
[FI31]1
HVAC equipment has been tested to
ensure proper operation.
Complies
Does Not
Not Observable
Not Applicable
C408.2.3.
2
[FI10]1
HVAC control systems have been
tested to ensure proper operation,
calibration and adjustment of controls.
Complies
Does Not
Not Observable
Not Applicable
C408.2.4
[FI29]1
Preliminary commissioning report
completed and certified by registered
design professional or approved
agency.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
1
[FI7]3
Furnished HVAC as-built drawings
submitted within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
3
[FI43]1
An air and/or hydronic system
balancing report is provided for HVAC
systems.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
4
[FI30]1
Final commissioning report due to
building owner within 90 days of
receipt of certificate of occupancy.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2827 ofPage
Project Title:
Data filename:
Ski & Snowboard Club of Vail
J:\Jobs\2014 - Jobs\14095.00 - SS Club Vail\Mechanical\Calculations\COMCheck\14095-Comcheck-
JCB.cck
09/12/17Report date:
2828 ofPage