Interior Lighting Compliance Certificate
Project Title:
2015 IECC
Project Type:New Construction
Construction Site:
598 Vail Valley Drive
Vail, CO
Owner/Agent:Designer/Contractor:
Architectural Engineering Design
Group, Inc.
1900 Wazee Street, Suite #350
Denver, CO 80202
Project Information
Energy Code:
Ski and Snowboard Club - Vail
High efficiency HVAC. Systems that do not meet the performance requirement will be identified in the mechanical requirements checklist
report.
Additional Efficiency Package
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
1-School/University 38862 0.87 33810
33810Total Allowed Watts =
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
1-School/University
LED 1: C1: 24' LED Cove: Other:1 2 400 800
LED 2: C2: 36' LED Cove: Other:1 2 601 1202
LED 3: C3: 6' LED Cove: Other:1 8 50 400
LED 4: D1/EM: LED Downlight: Other:1 125 26 3250
LED 5: D2: LED Wallwash: Other:1 10 26 260
Linear Fluorescent 1: F1/EM: 4' Strip: 48" T8 32W: Electronic:2 50 70 3500
Linear Fluorescent 2: P3: 4' Fluorescent Pendant: 48" T8 32W: Electronic:2 13 70 910
Linear Fluorescent 3: P4/EM: 8' Fluorescent Pendant: 48" T8 32W: Electronic:4 2 140 280
Linear Fluorescent 4: P5/EM: 12' Fluorescent Pendant: 48" T8 32W: Electronic:8 12 320 3840
Linear Fluorescent 5: P6: 12' Decorative Pendant: 48" T8 32W: Electronic:8 1 320 320
LED 6: P7/EM: Parking Garage Fixture: Other:1 6 130 780
LED 7: P8EM: LED Cylinder: Other:1 2 18 37
Linear Fluorescent 6: R1/EM: 2x4 Troffer: 48" T8 32W: Electronic:3 22 105 2310
Linear Fluorescent 7: R2: 2x2 Troffer: 24" T8 17W: Electronic:2 11 35 385
Linear Fluorescent 8: R3/EM: 2x4 Troffer: 48" T8 32W: Electronic:3 2 105 210
Linear Fluorescent 9: S1/EM: 2x4 Surface Mount: 48" T8 32W: Electronic:3 24 105 2520
Linear Fluorescent 10: S2: 4' Wrap: 48" T8 32W: Electronic:2 36 70 2520
LED 8: S3/EM: Parking Garage Fixture: Other:1 3 130 390
LED 9: S4: Surface Mount Light: Other:1 9 24 216
Linear Fluorescent 11: S5/EM: 8' Wrap: 48" T8 32W: Electronic:4 29 140 4060
Track lighting 1: T1: Track 8': Wattage based on 14 feet of track 0 0 420 420
Project Title:
Data filename:
Ski and Snowboard Club - Vail
J:\2847.00 - Ski and Snowboard Club, Vail\Ltg Calcs\284700LC01 - IECC 2015.cck
09/14/17Report date:
81 ofPage
09-15-17
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Linear Fluorescent 12: W1EM: 4' Wall Mount: 48" T8 32W: Electronic:2 12 70 840
Linear Fluorescent 13: W2: 4' Vanity Fixture: 48" T8 32W: Electronic:1 2 35 70
Linear Fluorescent 14: W3: 12' Vanity Fixture: 48" T8 32W: Electronic:3 2 105 210
Linear Fluorescent 15: W4EM: 16' Wall Mount: 48" T8 32W: Electronic:4 2 140 280
Linear Fluorescent 16: W5: 2' Vanity Fixture: 24" T8 17W: Electronic:1 9 17 153
Linear Fluorescent 17: W6EM: 2' Wall Mount: 24" T8 17W: Electronic:2 1 35 35
30198Total Proposed Watts =
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.0.6.2 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting PASSES: Design 11% better than code
Project Title:
Data filename:
Ski and Snowboard Club - Vail
J:\2847.00 - Ski and Snowboard Club, Vail\Ltg Calcs\284700LC01 - IECC 2015.cck
09/14/17Report date:
82 ofPage
09-15-17
Jeff Mullikin 09-15-17
COMcheck Software Version 4.0.6.2
Exterior Lighting Compliance Certificate
Project Title:
2015 IECC
Project Type:New Construction
Construction Site:
598 Vail Valley Drive
Vail, CO
Owner/Agent:Designer/Contractor:
Architectural Engineering Design
Group, Inc.
1900 Wazee Street, Suite #350
Denver, CO 80202
Project Information
Energy Code:
Ski and Snowboard Club - Vail
2 (Residential mixed use area)Exterior Lighting Zone
Allowed Exterior Lighting Power
A
Area/Surface Category
B
Quantity
C
Allowed
Watts / Unit
D
Tradable
Wattage
E
Allowed Watts
(B X C)
Other door (not main entry)54 ft of door 20 Yes 1080
Total Tradable Watts (a) =
Total Allowed Watts =
Total Allowed Supplemental Watts (b) =
1080
1080
600
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Other door (not main entry) (54 ft of door width): Tradable Wattage
LED 1: EG1: Monument Sign: Other:1 2 2 5
LED 2: EG2: In-Grade Building Light: Other:1 2 14 28
LED 3: EST1: Step Light: Other:1 59 6 354
LED 4: EW1/EM: Wall Sconce: Other:1 15 19 285
LED 5: EW3: Wall Sconce: Other:1 7 3 21
693Total Tradable Proposed Watts =
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.0.6.2 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Exterior Lighting PASSES: Design 59% better than code
Project Title:
Data filename:
Ski and Snowboard Club - Vail
J:\2847.00 - Ski and Snowboard Club, Vail\Ltg Calcs\284700LC01 - IECC 2015.cck
09/14/17Report date:
83 ofPage
09-15-17
Jeff Mullikin 09-15-17
Inspection Checklist
Requirements: 52.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.0.6.2
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2015 IECC
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR4]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the interior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
C103.2
[PR8]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the exterior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
C406
[PR9]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
efficiency package options.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski and Snowboard Club - Vail
J:\2847.00 - Ski and Snowboard Club, Vail\Ltg Calcs\284700LC01 - IECC 2015.cck
09/14/17Report date:
84 ofPage
09-15-17
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
C405.2.1
[EL15]1
Lighting controls installed to uniformly
reduce the lighting load by at least
50%.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.1
[EL18]1
Occupancy sensors installed in
required spaces.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.1,
C405.2.2.
3
[EL23]2
Independent lighting controls installed
per approved lighting plans and all
manual controls readily accessible and
visible to occupants.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.2.
1
[EL22]2
Automatic controls to shut off all
building lighting installed in all
buildings.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.3
[EL16]2
Daylight zones provided with
individual controls that control the
lights independent of general area
lighting.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.3,
C405.2.3.
1,
C405.2.3.
2
[EL20]1
Primary sidelighted areas are
equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.3,
C405.2.3.
1,
C405.2.3.
3
[EL21]1
Enclosed spaces with daylight area
under skylights and rooftop monitors
are equipped with required lighting
controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.4
[EL4]1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.2.4
[EL8]1
Additional interior lighting power
allowed for special functions per the
approved lighting plans and is
automatically controlled and
separated from general lighting.
Complies
Does Not
Not Observable
Not Applicable
C405.2.5
[EL25]null
Automatic lighting controls for exterior
lighting installed. Controls will be
daylight controlled, set based on
business operation time-of-day, or
reduce connected lighting > 30%.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C405.3
[EL6]1
Exit signs do not exceed 5 watts per
face.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski and Snowboard Club - Vail
J:\2847.00 - Ski and Snowboard Club, Vail\Ltg Calcs\284700LC01 - IECC 2015.cck
09/14/17Report date:
85 ofPage
09-15-17
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski and Snowboard Club - Vail
J:\2847.00 - Ski and Snowboard Club, Vail\Ltg Calcs\284700LC01 - IECC 2015.cck
09/14/17Report date:
86 ofPage
09-15-17
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C303.3,
C408.2.5.
2
[FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
Complies
Does Not
Not Observable
Not Applicable
C405.4.1
[FI18]1
Interior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
Complies
Does Not
Not Observable
Not Applicable
See the Interior Lighting fixture schedule for values.
C405.5.1
[FI19]1
Exterior lighting power is consistent
with what is shown on the approved
lighting plans, demonstrating
proposed watts are less than or equal
to allowed watts.
Complies
Does Not
Not Observable
Not Applicable
See the Exterior Lighting fixture schedule for values.
C408.2.5.
1
[FI16]3
Furnished as-built drawings for
electric power systems within 90 days
of system acceptance.
Complies
Does Not
Not Observable
Not Applicable
C408.3
[FI33]1
Lighting systems have been tested to
ensure proper calibration, adjustment,
programming, and operation.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Ski and Snowboard Club - Vail
J:\2847.00 - Ski and Snowboard Club, Vail\Ltg Calcs\284700LC01 - IECC 2015.cck
09/14/17Report date:
87 ofPage
09-15-17
Project Title:
Data filename:
Ski and Snowboard Club - Vail
J:\2847.00 - Ski and Snowboard Club, Vail\Ltg Calcs\284700LC01 - IECC 2015.cck
09/14/17Report date:
88 ofPage
09-15-17