HomeMy WebLinkAboutB10-009811 -19 -2010 Inspection Request Reporting
y
Page 11
4.50 r)m Vail Cn _ riw of
Requested Inspect Date: Monday, November 22, 2010
Inspection Area: JRM
Site Address: 63 WILLOW PL VAIL
UNIT 2, BISHOP PARK
A /P /D Information
Activity:B10 -0098 Type: A -MF Sub Type:AMF Status: ISSUED
Const Type:Occupancy:Use:VA Insp Area: JRMOwner:SNOWSPORTS LLC
7 NAIL PLATE ALL NM CABLE
Contractor:J.L. VIELE CONSTRUCTION Phone:970 - 476 -3082
Architect:K.H. WEBB ARCHITECTS PC Phone:970 - 477 -2990
Description:RENOVATE EXISTING BATHROOMS AND KITCHEN,ADD SMALL BATHROOM AT GARAGE LEVEL AND
Approved **
ADD OFFICE SPACE AT LEVEL 3
Inspector: mdenney Action: AP APPROVED
Comment:
Requested Inspection(s)
Item: 534 PLAN -FINAL C/O
Requestor: J.L. VIELE CONSTRUCTION
Assigned To: BGIBSON
Action: Time Exp:
Requested Time: 08:00 AM
Phone: TONY 970 - 471 -5467
Entered By: SBELLM K
Item: 530 BLDG -Temp C/O
Requestor: J.L. VIELE CONSTRUCTION
Assigned To: CGUNION
Action: Time Exp:
Requested Time: 02:00 PM
Phone: TONY 970 - 471 -5467
Entered By: SBELLM K
Inspection Histo
Item: 226 FIRE DEPT. NOTIFICATION
Item: 410 Special Inspect - progress rept
Item: 30 BLDG - Framing
09/13/10 Inspector: CG
Comment: 1 ILC NOT SIG
Action: CR CORRECTION REQUIRED
REPT131 Run Id: 12196
2 A10 -0066 ROUGH NOT DONE
3 F10 -0055 ROUGH NOT SIGNED OFF
4 E10 -0148 ROUGH NOT DONE
5 M10 -0155 ROUGH NOT DONE
6 MECHANICAL PERMIT ROUGH FOR VENTING NOT DONE
7 NAIL PLATE ALL NM CABLE
8 WELDING SPECIAL INSPECTION REPORT NOT DONE
9 INSTALL BACKING, NAIL PLATES AT CONCRETE AT LOWER LEVEL
1 WINDOWS NOT INSTALLED
11 FIRE DAMPER REQUIRED AT EXHAUST DUCT INTO PARKING GARAGE
12 INSULATE BEHIND WATER PIPE AT SHOWER, OR REMOVE FROM EXTERIOR WALL
Item: 50 BLDG - Insulation Approved **
09/14/10 Inspector: mdenney Action: AP APPROVED
Comment:
Item: 60 BLDG - Sheetrock Nail "" App roved "
09/20/10 Inspector: MDENNY Action: DN DENIED
Comment:1 HR WALL IN BASEMENT - 1 ST LAYER.
PROTECT BEHIND SHOWER VALVE, PROTECT AT DRAIN PIPE PENETRATIONS ABOVE
BATH, INSTALL DAMPER.
09/22/10 Inspector: mdenney Action: AP APPROVED
Comment:2nd layer in basement and garage - fire damper is installed for bath exhaust. Sheetrock through-out unit.
REPT131 Run Id: 12196