HomeMy WebLinkAboutE10-018611 -09 -2010 Inspection Request Reporting Page 15
7:33 am Veil, C_ O - City Of
Requested Inspect Date: Tuesdayy., November 09, 2010SiteAddress: <None Listed>
WATER STORAGE TANK 3040 BOOTH FALLS
A/P /D Information
Activity: E10 -0186 Type: B -ELEC Sub Type: ACOM Status: ISSUED
Const Type: Occupancy: Use: Insp Area:Owner: TOWN OF VAIL
Contractor: TRIANGLE ELECTRIC Phone: 970 - 453 -5424
Description: ELECTRICAL FOR NEW SERVICE AND NEW IN LINE BOOSTER PUMP STATION
Requested Inspection(s)
Item: 190 ELEC -Final Requested Time: 09:30 AMRequestor: TRIANGLE ELECTRIC Phone: 970 - 453 -5424
Comments: 36 - 0
Assigned To: J ON Entered By: JMONDRAGON K
Action: Time Exp:
Comment: , rovi e r ing per plan. 3/0 to wafer piping and 2 - 5/8" rods 8' apart.
Inspection History
Item: 120 ELEC -Rough *` Approved "
08/12110 Inspector: mdenney Action: AP APPROVED
Comment: underground
08/26/10 Inspector: mdenney Action: AP APPROVED
Comment: service 800ampItem: 190 ELEC -Final
10/26/10 Inspector: mdenney Action: CR CORRECTION REQUIRED
Comment: Provide grounding per plan. 3/0 to water piping and 2 - 5/8" rods 8' apart.
REPT131 Run Id: 12146