12 -15 -2009 Inspection Request Reporting Page 24
4:05 pm Vail, CO - City Of
Requested Inspect Date: Wednesday, December 16, 2009
Inspection Area: JRM
Site Address: 190 GORE CREEK DR VAIL
CHECKPOINT CHARLIE
A/P /D Information
Activity: M09 -0210 Type: B -MECH Sub Type: NCOM Status: ISSUED
Const Type: Occupancy: Use: Insp Area: JRMOwner: VAIL COLORADO MUNICIPAL BLDG
AUTHORITY
Contractor: R & H MECHANICAL LLC Phone: (970) 328 -2699
Description: NEW COMMERCIAL BUILDING (CHECKPOINT CHARLIE): INSTALL BOILERS, EXHAUST FANS, MAINLINES, TUBING FOR SNOW MELT SYSTEM
Reauested Inspections
Item: 390 MECH -Final Requested Time: 11:30 AM
Requestor: R & H MECHANICAL LLC Phone: (970) 328 -2699Comments: 471 -5679
Assigned To: JMQNDRAGON . ,y. ,sly Entered By: JMONDRAGON K
eAction: _ Time Exp: '•
Comment:
J kL-
Inspection History
Item:200 MECH -Rough Approved*
11/03/09 Inspector: Martin Action: PA PARTIAL APPROVAL
Co and at floor joist
1/2/Inspector: tG Action: CR CORRECTION REQUIRED
Comment:100 PSI AIR TEST ON HYDRONIC
CORRECTIONS:
1 MOVE EQUIPMENT FROM FRONT OF BOILERS TO MAINTAIN 30" WORKING CLEARANCE
2 LABEL BOILER DISCONNECT SWITCH
3 EXPANSION TANK TO BE COMPLETE FOR FINAL
4 CONCENTRIC BOILER VENTS AT ROOF SHALL TERMINATE MINIMUM 12" ABOVE ROOF
SNOW LEVEL
5 DECORATIVE SHROUD AT BOILER VENTS DOES NOT APPEAR TO BE LISTED.
6 PLUMBING VENT NEXT TO INTAKE FOR BOILER
Item:310 MECH - Heating ** Approved **
11/02/09 Fnspector: NSC Action: AP APPROVED
Comment:100# test on snowmelt mains 2 gauges
11/05/09 Inspector: Martin Action: PA PARTIAL APPROVAL
Comment:Curbs only
Item:340 MECH -Misc.
Item:390 MECH -Final
12/08/09 Inspector: cg Action: NR NOT READY FOR INSPECTION
Comment:
REPT131 Run Id: 10760