HomeMy WebLinkAboutM10-000706 -02 -2010 Inspection Request Reporting Page 26
4:34 pm Val CO - City Of
Requested Inspect Date: Thursday, June 03, 2010
Inspection Area: JRM
Site Address: 143 E MEADOW DR VAIL
UNIT 101, VAIL T -SHIRT CO, SOLARIS
A /P /D Information
Activity: M10 -0007 Type: B -MECH Sub Type: NCOM Status: ISSUED
Const Type: Occupancy: Use: Insp Area: JRM
Owner: SOLARIS PROPERTY OWNER LLC
Contractor: SKYLINE MECHANICAL Phone: 970 - 524 -6809
Description: TENANT IMPROVEMENT (VAIL T -SHIRT CO & GENERATION VAIL): INSTALL FAN COIL, DUCT & HEAT
SYSTEM
Reauested Inspection(s
Item: 390 MECH -Final Requested Time: 10:30 AM
Requestor: SKYLINE MECHANICAL Phone: 970 - 524 -6809
Comments: 331 -4774
Assigned To: JMONDRAGON Entered By: JMONDRAGON K
Action: Time Exp
Comment: PPLY REGISTER nTSTDR - GE ROOMMHECONDARYCONDENSATEDRAINNOTRUNSEPERATE. INSTALL WATER SENSOR IN PAN
SHUT -OFF PER CODE
3 FAN COIL INSTALLATION MANUAL TO BE ON SITE FOR INSPECTION
4 COMPLETE DUCT DETECTOR IN RETURN AIR
5 BALANCE REPORT NEEDED FOR FINAL
ep(20 uc
I 3 (,o
Inspection Histo
Item: 200 MECH - Rough "" Approved ""
03/22/10 Inspector: JRM Action: AP APPROVED
Comment: ROUGH HVAC APPROVED
Item: 310 MECH - Heating "" Approved "'
04/22/10 Inspector: JRM Action: AP APPROVED
Comment: IN FLOOR HEAT APPROVED ONLY SOUTH HALF OF THE RETAIL SPACE
Item: 315 PLMB -Gas Piping
Item: 320 MECH - Exhaust Hoods
Item: 330 MECH - Supply AirItem: 340 MECH -Misc.
Item: 390 MECH -Final
05/27/10 Inspector: cg Action: CR CORRECTION REQUIRED
Comment: 1 ) COMPLETE SUPPLY REGISTER IN STORAGE ROOM
SECONDARY CONDENSATE DRAIN NOT RUN SEPERATE. INSTALL WATER SENSOR IN
PAN WITH SHUT -OFF PER CODE
3 FAN COIL INSTALLATION MANUAL TO BE ON SITE FOR INSPECTION43COMPLETEDUCTDETECTORINRETURNAIR
5 BALANCE REPORT NEEDED FOR FINAL
REPT131 Run Id: 11471