HomeMy WebLinkAboutM10-003307 -06 -2010 Inspection Request ReForting Page 26
4:21 pm Vail, CO - City 0
Requested Inspect Date: Wednesday, July 07, 2010
Assigned To: JMONDRAGON
Inspection Type: MECH
Inspection Area: JLE
Site Address: 143 E MEADOW DR VAIL
UNIT 210, ALPINE BANK, SOLARIS
A/P /D Information
Activity: M10 -0033 Type: B -MECH Sub Type: ACOM Status: ISSUED
Const Type: Occupancy: Use: Insp Area: JLE
Owner: SOLARIS PROPERTY OWNER LLC
Contractor: SKYLINE MECHANICAL Phone: 970 - 524 -6809
Description: TENANT IMPROVEMENT (ALPINE BANK): INSTALL HVAC SYSTEM AND FIREPLACE
Requested Inspection(s)
Item: 390 MECH -Final Requested Time: 10:30 AM
Requestor: SKYLINE MECHANICAL Phone: 970 - 524 -6809
Comments: no contact number left
Assigned To: JMONDRAGON Entered By: CGUNION KAction: Time Exp
Comment: INZJULA TTONMAY NOT BE EXPOSE 7N PLENUM CEILING
2 30X30 ACCESS REQURIED FOR FAN COIL UNITSJ3FIREPLACEBENTTERMINATIONBURIEDINRECESSED STONE AREA. TERMINATE 12"
INIMUM ABOVE SNOW LEVEL WITH A LISTED TERMINATION FITTING. WALL CAPS ARE LISTED
FOR WALL TERMINATION ONLY
4) BALANCE REPORT REQUIRED FOR FINAL
5 SMOKE DETECTOR AND UNIT SHUTDOWN REQUIRED FOR FCU -2 OVER 2000 CFM.
Vif fA
3-1
Inspection Histo
Item: 200 MECH -Rough "` Approved ""
04/29/09 Inspector: JRM Action: AP APPROVED
Comment: APPROVED HVAC FAN COILS.
04/29/10 Inspector: JRM Action: AP APPROVED
Comment: FOR FIRE PLACE ONLY
Item: 310 MECH- Heating
Item: 315 PLMB -Gas PipingItem: 320 MECH - Exhaust Hoods
Item: 330 MECH - Supply AirItem: 340 MECH -Misc.
Item: 390 MECH -Final
06/21/10 Inspector: CG Action: CR CORRECTION REQUIRED
Comment: 1 INSULATION MAY NOT BE EXPOSED IN PLENUM CEILING
30X30 ACCESS REQURIED FOR FAN COIL UNITS
3 FIREPLACE BENT TERMINATION BURIED IN RECESSED STONE AREA. TERMINATE 12"
INIMUM ABOVE SNOW LEVEL WITH A LISTED TERMINATION FITTING. WALL CAPS ARE
LISTED FOR WALL TERMINATION ONLY
4 BALANCE REPORT REQUIRED FOR FINAL53SMOKEDETECTORANDUNITSHUTDOWN REQUIRED FOR FCU -2 OVER 2000 CFM.
REPT131 Run Id: 11713