HomeMy WebLinkAboutB05-0016 _ _ . .
TOWN OF VAIL DEPARTMENT OF COMMUNITY DEVELOPMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2138
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
NEW COMM BUILDING PERMIT Permit # BOS-0016
Job Address: 675 LIONSHEAD PL VAIL Status . . . : COFO
Location.....: LIONSHEAD CORE SITE Applied . . : 02/22/2005
Parcel No...: 210106308007 Issued . . . 10/08/2008
Legal Description: Expires . .: 08/26/2009
OWNER VAIL CORP 02/22/2005
PO BOX 7
VAIL, CO
81658
APPLICANT SHAW CONSTRUCTION COMPANY 02/22/2005 Phone: 970-242-9236
760 HORIZON DR
GRAND JUNCTION CO
81506
License: 108-A
CONTRACTOR SHAW CONSTRUCTION COMPANY 02/22/2005 Phone : 970-242-9236
760 HORIZON DR
GRAND JUNCTION CO
KING COLE 476-0454 X103 81506
License: 108-A
Desciption: Town of Vail Adjusted Valuation: 1,919,438.00
ARRABELLE- CONSTRUCTION OF A NEW HOTEL
Occupancy Type Factor Sq Feet Valuation
Apartment Houses Zone 3 I-FR & II-FR 133 . 11 176, 833$23, 538, 240 . 63
Apartment Houses Zone 3 I-FR & II-FR 133. 11 1, 350 $179, 698 . 50
Auditoriums Zone 3 I-FR & II-FR 155 . 38 26, 722 $4, 152, 064 . 36
Hotels and Motels Zone 3 I-FR & II-FR 149. 60 63, 284 $9, 467, 286. 40
Hotels and Motels Zone 3 I-FR & II-FR 149. 60 18, 469 $2, 762, 962 . 40
Offices Zone 3 I-FR & II-FR 158 . 10 24, 208 $3, 827, 284 . 80
Public Buildings Zone 3 I-FR & II-FR 182 . 75 122, 548$22, 395, 647 . 00
Restaurants Zone 3 Type V-1HR 132 . 26 5, 297 $700, 581 .22
Restaurants Zone 3 Type V-1HR 132 . 26 1, 286 $170, 086. 36
Stores Zone 3 I-FR & II-FR 122 . 06 33, 445 $4, 082, 296. 70
Stores Zone 3 I-FR & II-FR 122 . 06 32, 332 $3, 946, 443 . 92
Warehouses Zone 3 I-FR & II-FR 73. 10 14, 717 $1, 075, 812 .70
Totals . . . 397, 943$111, 919, 438 . 0*
Fireplace Information:Restricted:Y t�of Gas Appliances: 0 #of Gas Logs: 0 #of Wood Pellet: 0
�«*�***�***x�****+�+*****�***r**a**�*�*�++�*��a���*+*****�*��**tr�** FEE S UMMARY +�*+*+*�*+**��****�*�***�***�*+***�++�****►+*�r**�***►***�**
Building------> 910,966.75 Restuarant Plan Review--> $0.00 Total Calculated Fees---> 876,'739.69
Plan Check---> 266,803.39 Recreation Fee--------------> 19B,971.50 Additional Fees-----------> $12,430.27
Investiga[ion-> 50.00 TOTAL FEES-------------> 876,739.64 Total Permit Fee----------> 889,169.91
Will Call-----> $3.00 Payments-------------------> 889,169.91
BALANCE DUE---------> $0.00
*�**�*�*+**.*+*�**++*+�s++**s*�*�*.**�r+***++��**�sa*r*+*********r**r■.***s�.**r�s*■*s***:****s..*�►**�r*�a***t*t*r***►*s*.r*.**.+..*r*r*r******■
Approvals:
Item: 05100 BUILDING DEPARTMENT
04/27/2005 CDAVIS Action: AP
06/20/2005 cdavis Action: AP Addtional revisions recieved showing how
corrections
identified by the Vail Fire Department will be addressed have been approved. Two �
set
of revised drawings are requrired within 120 days of release of this building peri
08/22/2005 cdavis Action: AP Pre-Cast structural drawings reviewed by L]
approved
03/14/2006 cdavis Action: AP Revisions received 12/22/05, routed 1/3/06
and approved by LP2A
05/09/2006 cdavis Action: PA Replacement handrails at Concert Hall Plaz�
See File for detail
06/02/2006 cdavis Action: PA Smoke Management plans approved per LP2A r�
06/13/2006 cdavis Action: NO Issues regarding revised grading plans lis�
below.
I can not approve this design change as drawn.
Issues :
1) What is the finish floor elevation of the existing floor in relationship to th�
landing and stairs? The building code will allow a maximum of �" difference IBC sf
1008 . 1 . 4
#4 & 1008 . 1 . 6
2) Is an accessible entrance/exit provided somewhere else? This is not shown
3) The way the handrails are configured does not allow a straight shot or access �
doors . This is now driving the landing width to be sized to not allow the door to
into the required landing width by more than � of the required dimension IBC sec.
#2 . Recommendation: Remove the stair extensions on both sides and install both ha�
parallel to the direction of travel .
4) The stair extension on the east side is not properly sized. These stairs shall
minimum width of 44" . This issue can be corrected as stated in item # 3
Charlie Davis
Chief Building Official
Town of Vail
07/19/2006 cdavis Action: PA Buyer changes for unit 274 approved for '
construction
per LP2A review and approval
08/07/2006 cdavis Action: AP Phased Occupancy Proposal approved, subjec-
field
inspection prior to occupancy
09/18/2006 cdavis Action: PA Unit 282 Buyer Changes approved $750. 00 dut
this
review
10/02/2006 cdavis Action: PA Unit 568 Revisions as reviewed and approvec
LP2A/Buereau Veritias
Addtional fee of $437 . 50 due for this review
10/02/2006 cdavis Action: PA Unit 382 revisions as reviewed and approvec
LP2A/Bureau Veritias additional fee of $437 . 50
10/02/2006 cdavis Action: PA Unit 487 per LP2A review. Addtional fee of
due
10/12/2006 cdavis Action: PA Unit 655 balance due $687 . 50 invoice from :
#32013
10/13/2006 cdavis Action: PA Unit 529 per LP2A review. Addtional fee of
due
per invoice #32018
10/13/2006 cdavis Action: PA Units 217, 255, 372, 414, 472, 482, 514, 572, 582, �
Per LP2A review addtional fee of $875. 00 due Invoice # 32014
10/30/2006 cdavis Action: PA Unit 429 Per LP2A review Total due is $162'
$750 . 00 = $2375. 57
O1/19/2007 cdavis Action: PA Revisions for units 330/332 364/368 Per LP;
approval
dated 1/10/07 Balance due per LP2A invoice #65827 = $875 . 00
01/19/2007 cdavis Action: PA ADA threshold ramps approved No addtional :
assessed
01/30/2007 cdavis Action: AP Boiler Flue and Alternate means approved. ;
and
document dated 1/11/07
02/16/2007 cdavis Action: PA Fire-Stopping Submital Approved
Subject to field inspection
No additional fee assessed
02/16/2007 cdavis Action: PA Kitchen Revisions CCD 115 Aproved
5 hrs of additional plan review time added $275. 00
03/26/2007 cdavis Action: PA Mountain Ops approved Per LP2A Invoice # 1'
addtional fees of $2, 250 . 00 added into Permits Plus
05/24/2007 cdavis Action: PA Request to use a condo space for temporary
construction offices
Approved
06/08/2007 cgunion Action: PA CCD 132, 133, 134, 135, 136, 136R1 revisions
09/17/2007 cdavis Action: PA CCD 155 Approved
Addtional fees due = $993 . 71 per revised valuation total of $165, 000 . 00 added 5/2,
09/24/2007 cdavis Action: PA Repair plan for moment connections of balc�
2 hours of addetional plan review time = $110. 00
09/24/2007 cdavis Action: PA Grease Scrubber Approved
No addtional fees required
11/12/2007 cdavis Action: PA Insulation Details for unit 484/584
11/28/2007 cdavis Action: PA Plaza Level Egress/Special Event staging p:
Field copy hand-delivered to VRDC
12/06/2007 cdavis Action: PA Balcony Fixes Special Inspection Reports a�
Engineering review Approved All Work on balcony framing completed and O.K. to con�
Ol/22/2008 cdavis Action: PA Request to begin additional exterior work <
No
addtional fees assessed
05/02/2008 cgunion Action: PA revisions CCD 155R2 and CCD 180
Handrails required at stairs per IBC, ANSI 117 . 1
Item: 05400 PLANNING DEPARTMENT
04/28/2005 George Action: AP
01/13/2006 George Action: PA Partial approval of revisions dated 12/26/i
set)
05/02/2006 George Action: PA Partial approval of interior changes to Un:
and
530
05/22/2006 George Action: DN A list of teh proposed revisions, incl'udin�
impacts (+/-) to the approved development standards must accompany to the submitt<
06/Ol/2006 George Action: PA Partial approval of revisions to the elect:
plan
for Unit 642, dated May 25, 2006
06/05/2006 George Action: PA Partial approval for interior audio/video �
to
Unit 274
06/13/2006 George Action: PA This partial approval is for minor grading
to
the off-site improvements plan as requested by the Town of Vail Public Works Depa:
Revisions include grading at the stair entries to Kidsport and Bart and Yeti ' s
11/28/2006 George Action: PA This partial approval is for the phased oc�
plan
proposed for the Arrabelle, dated October 27, 2006
12/14/2006 George Action: DN This denial is for the proposed changes to
484/584 . Revised exterior elevations on Sheet A232 must be submitted for review a�
approval
prior to the approval of this revision application. Said changes were discussed w:
applicant on 11/21/06 yet no revised plans have been submitted in response to our
05/04/2007 George Action: PA This partial approval for the Unit 484/584
to
approved plans . All planning issues have been addressed and DRB approval granted :
exterior
changes .
05/04/2007 George Action: PA This a partial approval of the proposed re:
revisions per plans dated December 28, 2006 and labeled CCD115 .
05/05/2007 George Action: PA This is a partial approval for revisions s�
to
Level 1 Area A tenant space (CCD 132) dated 5/2/2007
05/05/2007 George Action: PA This is a partial approval for CCD 136 R1 :
1D
for door changes dated 5/2/2007
05/05/2007 George Action: PA This is a partial approval to delete activ:
office
in Area 1D CCD 136 daetd 5/2/2007
05/05/2007 George Action: PA This is a partial approval for revisions tc
1D,
Starbucks, CCD 135.
05/05/2007 George Action: PA This is a partial approval to relocate the
wall at columns 21 ans 22, CCD 134, dated 5/2/2007
05/05/2007 George Action: PA This is a partial approval relocating door:
demising wall in Area 1C, CCD 133, dated 5/2/2007
05/13/2008 George Action: PA This is a partial approval for revisions tc
"beachfront" for the Eagle Bahn
Item: 05600 FIRE DEPARTMENT
06/20/2005 mcgee Action: AP See Bldg comments.
Deferred submittals and shops are required.
03/14/2006 mcgee Action: AP Revisions must addressed in fire alarm and
sprinkler shop drawings and any impacts reflected in the defered submittals
06/07/2006 mcgee Action: AP Buyer changes Uint 642
11/02/2006 mcgee Action: DN Flush test proposal submitted 10 31 06 is c
Obstruction of the Mall is prohibited.
Applicant failed to demonstrate adequate means to address discharge of water.
04/12/2007 mcgee Action: DN Building Commissioning Turnover Plan dated
2007 .
Revise and resubmit per discussion and meeting 04/10/07 .
05/21/2007 mcgee Action: AP ADA revisions dated 5 7 07 , Units 472 and
05/21/2007 mcgee Action: AP Buyer Changes for Units;
274
487
655
282
429
568
643
382
05/21/2007 McGee Action: AP Buyer changes for Units :
330
332
368
364
217
255
372
414
472
482
514
572
582
614
529
08/15/2007 McGee Action: DN 42/40 plans laleled Restaurant Kitchen Gre�
Scrubber, received Aug 14, 2007 and Gaylord plan labeled Arabelle at Vail Square,
Aug 14, 2007, are not approved.
The plans are not stamped.
Gaylord plans are not readable due to too small a scale.
Fire protection system notes are not shown on plan.
02/20/2008 mcgee Action: AP Construction staging plan 1 28 08
02/20/2008 mcgee Action: AP Unit 408, 508, 608 balconies staging.
02/20/2008 mcgee Action: AP Submittal to resume work 01/25/08
02/20/2008 mcgee Action: AP submittal on plastic, wheelbarrow access a�
staging.
03/27/2008 McGee Action: AP Revision to A2, D2 D3 balcony concrete pou:
Item: 05500 PUBLIC WORKS
07/20/2005 tk Action: AP
02/08/2006 tk Action: AP Approved revisions dated 12/26/05 (green sf
05/Ol/2006 tk Action: AP Interior modifications routed 4/14/06 plan;
12/28/05 and 1/06/06.
08/31/2006 tk Action: DN Interior modifications on set received 5/5,
4/17/06 (CCD025) . Comments forwarded on 6/2/06 regarding loading dock change and
turning movements .
08/31/2006 tk Action: DN Revisions dated 5/31/06, received 8/1/06. l
because the plans still show the previously denied revision in the loading dock.
08/31/2006 tk Action: AP Streetscape Plans dated 8/11/06 Approved w:
Conditions . See Memo dated 8/31/06
02/08/2007 tk Action: AP Approved CCD 115 recieved 1/24/07 dated 12,
No
PW issues
05/14/2007 tek Action: AP CCD 132, 133, 134, 135, 136, 136R1 - No Public f
Issues
05/14/2007 tek Action: AP ADA revisions to Units 472&368- No PW issu�
09/14/2007 TK Action: AP Approved CCD 155 - 'Beachfront ' regrading <
01/30/2008 ls Action: AP Approved revised staging plan for crane se
installations of deck railings only.
05/05/2008 tek Action: AP Approved modification to Downspout and Roo:
Plan
CCD 180 dated 4/3/08 received 4/8/08 .
05/09/2008 tk Action: AP Approved CCD 155R2 received 4/9/08 .
«*».*:.�.......*...�*.*.*,*.*.�*.�*..+*...,.*�.*.*...*.*.++.,:.****.*.**.�+**�..*.**�:*:*�..+**::*.�..�,:***.*.*.*.*.*.�.*.,:.....*..*.*.****.�.+.*
See page 2 of this Document for any conditions that may apply to this permit.
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan,to comply with all
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordinances of the Town applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY-FOUR HOURS 1N ADVANCE BY TELEPHONE AT 479-2149 OR AT OUR OFFICE FROM 8:00 AM-4 PM.
SIGNATURE OF OWNER OR CONTRACTOR FOR HIMSELF AND OWNER
;`
PAGE 2
********************************************************************************************************
CONDITIONS OF APPROVAL
Permit# BOS-0016 as of 07-03-2013 Status: COFO
********************************************************************************************************
Permit Type: NEW COMM BUILDING PERMIT Applied: 02/22/2005
Applicant: SHAW CONSTRUCTION COMPANY Issued: 10/08/2008
970-242-9236 To Expire: 08/26/2009
Job Address: 675 LIONSHEAD PL VAIL
Location: LIONSHEAD CORE SITE
Parcel No: 210106308007
Description:
ARRABELLE-CONSTRUCTION OF A NEW HOTEL
Conditions:
Cond: 0
(PLAN): DRB approval does not constitute a permit for building. Please consult with Town of Vail
Building personnel prior to construction activities.
Entry: 09/Ol/2009 By: Martin Action: AP
Cond: 9
(PLAN): Prior to the issuance of a final certificate of occupancy, the applicant shall have
completed all site and landscaping improvements as shown on the approved DRB plans.
Entry: 09/O l/2009 By: Martin Action: AP Per approved inspections
Cond: CON0007083
Prior to the issuance of a temporary certificate of occupancy the applicant shall address the
applicable conditions of approval as noted in teh memorandum to the Planning& Environmental
Commission dated January 24, 2005.
Entry: 09/01/2009 By: Martin Action: AP per approved inspections
********************************************************************************************
TOWN OF VAIL, COLORADOCopy Reprinted on 07-03-2013 at 08:31:04 07/03/2013
Statement
*****************�*******************************************************+******************
Statement Number: R080001897 Amount: $220. 00 10/08/200804 : 11 PM
Payment Method: Check Init: DDG
Notation: Shaw 179045
-----------------------------------------------------------------------------
Permit No: B05-0016 Type: NEW COMM BUILDING PERMIT
Parcel No: 2101-063-0800-7
2101-063-2700-8
2101-063-2700-9
2101-063-2701-0
2101-063-2701-1
2101-063-2701-2
2101-063-2701-3
2101-063-2701-4
2101-063-2701-5
2101-063-2701-6
2101-063-2701-7
2101-063-2701-8
2101-063-2701-9
2101-063-2702-0
2101-063-2702-1
2101-063-2702-2
2101-063-2702-3
2101-063-2702-4
2101-063-2702-5
2101-063-2702-6
2101-063-2702-7
2101-063-2702-8
2101-063-2800-2
2101-063-2800-3
2101-063-2800-4
2101-063-2800-5
2101-063-2800-6
2101-063-2800-7
2101-063-2800-8
2101-063-2800-9
2101-063-2801-0
2101-063-2801-1
2101-063-2801-2
2101-063-2801-3
2101-063-2801-4
2101-063-2801-6
2101-063-2801-7
2101-063-2801-8
2101-063-2801-9
2101-063-2802-1
2101-063-2802-3
2101-063-2802-4
2101-063-2802-5
2101-063-2802-6
2101-063-2802-7
2101-063-2802-8
2101-063-2802-9
2101-063-2803-0
2101-063-2803-1
2101-063-2803-3
2101-063-2803-4
2101-063-2803-6
2101-063-0800-3
2101-063-0800-6
2101-063-0801-0
Site Address: 675 LIONSHEAD PL VAIL
Location: LIONSHEAD CORE SITE
Total Fees: 889, 169. 91
This Payment: $220.00 Total ALL Pmts: 889, 169. 91
Balance: $0. 00
****************************************************************************************+***
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------------- ------------------------------ ------------
PF 00100003112300 PLAN CHECK FEES 220.00
-----------------------------------------------------------------------------
B05-0016: Entries for Item:90 - BLDG-Final 08:31 07/03/2013
Action Comments By Date Unique_
Ke
CR BUILD B-2 ROOMS 212,216,218 APPR 217 GCD 12/18/2007 A000109
REQS SMOKE SEAL AND MAIN ENTRY 568
DOOR REQD TO LATCH.
BUILD C-2 ROOMS 220(DOOR UNDERCUT
REQD),222,226,228 229/219,241,243
APPR.
NOTE ALL DECKS ON THIS FLOOR ARE
UN-OCCUPIABLE.
CORRECTIONS FOR TYPE A HOTEL
ROOMS 208,210,224;WATER CLOSETS
REQD TO BE 16 TO 18 INCHES FROM
WALL AS BUILT IS 22", INSTALL GRAB
BARS IN SHOWERS,TRAP GUARDS
REQD,SET ROOM FOR ACCESSABLE
ROUTE.
PENETRATIONS IN ELECTRICAL AND
TELECOM ROOMS REQD FIRE STOPPING
FLOORS AND WALLS.
LEVEL G-1 ROOM G-269 STORAGE ROOM
DOORS REQD TO SELF CLOSE AND
LATCH ie AUTOMATIC FLUSH BOLTS AND
CLOSER.
ELEVATOR G-228 REQS SELF CLOSING
HARDWARE,COORDINATOR AND SMOKE
SEAL.
ROOM G-231 NO LIGHTS DOORS REQD
TO SELF CLOSE AND LATCH. IN BOILER
ROOM F/S DAMPER ACTUATOR ABOVE
DOOR REQD TO BE ACCESSABLE.
FLAMABLE LIQUIDS IN PAINT STORAGE
AREA REQD TO BE IN SEALED ORIGINAL
CONTAINERS NO OPEN BUSKETS.
REMOVE PLASTIC AT HULM OFFICE.
WHAT ABOUT VALET ROOM.
NO COURTESY WALK THRU WITH JD GCD 12/19/2007 A000109
HILLMAN OF SHAW AND STEVE ROBERTS 663
WITH 4240. LEVELS ALL AREAS OF G2
AND G1
SHAW HAS LIST. _
CR FOR CENTRE V, HOTEL LOBBY AND GCD 12/20/2007 A000109
GREAT ROOM 982
1.A-2 OCCUPANCY REQD PANIC
HARDWARE ON EXIT DOORS.
2.IN RESTROOMS BACK GRAB BAR REQD
TO HAVE 12"TO CENTER LINE OF
FIXTURE.
3.STAIR UP TO GREAT ROOM FIRST
FLIGHT OVER MAX 7"RISE,
RUN WELL OVER 3/8"VARIANCE.
4.GUARD AT DECK OF GREAT ROOM
LESS THAN 42".
CR UNITS 342,344: PROVIDE SAFETY cgunion 12/24/2007 A000109
GLAZING AT BATHTUB WINDOW 957
CR BUILD B-2 COMMON JULIETTE BALCONY GCD 01/21/2008 A000110
GUARD<42". UNIT 201 GUARD<42". UNIT 594
205 SMOKE SEAL AT ENTRY DOOR,AND
STONE GUARD<42".
UNIT 219 BOTH SIDE OF ENTRY DOOR
REQD TO SELF CLOSE AND LATCH
(MANUAL FLUSH BOLT PROHIBITED)
SMOEK SEAL REQD AT ASTRIGAL. UNITS
241 AND 243 APPR.
Page 1
B05-0016: Entries for Item:90 - BLDG-Final 08:31 07/03/2013
CR CORRECTIONS FROM 01-21-08 BUILD B-2 GCD 01/23/2008 A000110
UNIT 201,JULIETTE BALCONY APPR. NEW 694
CORRECTIONS UNIT 217 FINISH WALL AT
FIREPLACE CAP,STONE CAP GUARD
REQD TO BE 42".
BUILD B-3 UNIT 319 SMOKE SEAL. UNIT
329 SAFETY GLAZING REQD, MANUAL
FLUSH BOLT PROHIBITED AT ENTRY
DOOR SMOKE SEAL REQD FOR
ASTRIGAL.
BUILD C-3 UNIT 341 DORR UNDER CUT
REQD IN BATH. UNIT 343 WINDOW AT
DOOR TO MASTER BATH REQD TO BE
SAFETY GLAZED.
CR BUILD B AND C 4th FLOOR UNITS GCD 01/24/2008 A000110
732
CR REINSPECTION OF CORRECTIONS GCD 01/25/2008 A000110
BUILD C-4 443 SMOKE SEAL APPR. 773
UNIT 430 SMOKE SEAL APPR.GUARD
DECORATIVE PATTERN OVER 4"MAX.
UNIT 426 SMOKE SEAL NOT APPR
412 SMOKE SEAL APPR
FOURTH FLOOR TELECOM ROOMS REQ
FIRE STOPPING. PATCH HOLE IN BUTLER
PANTRY.
BUILD B-3 UNIT 301 GUARD OVER 4"MAX
AT BOTTOM. SMOKE SEAL REQD AT
CLOSET ENTRY DOOR TO CORRIDOR.
UNDER CUT POCKET DOOR.
UNIT 305 PATCH WALL AT VANITY BOTH
SIDES,SHOWER NOT COMPLETE
CR POOL,SPAAND RESTROOMS NUMEROUS GCD 01/29/2008 A000110
CORRECTIONS 849
CR BUILD C-1 FITNESS CENTER GCD 02/01/2008 A000110
CORRECTIONS 942
1.PROVIDE EXIT SIGH AT WEST DOOR
2.SAFETY GLAZING REQD AT EAST DOOR
SIDE LITE
3.PROVIDE BALANCE REPORT
3.DURABLE WASHABLE SURFACE REQD
AT TOILET
5.PROVIDE PLAN FOR OCCUPANCY OF
PARTIAL AREAS
BUILD A-1 CHILDRENS SIK SCHOOL
TICKETS APPR FOR OCCUPANCY
CR SKI VALET GCD 02/07/2008 A000111
1.ADD HAND RAIL AT EAST SIDE STAIR 051
2.EAST SIDE STAIR RUN OVER 3/8"
3.BALNK OFF EXIT SIGN
4.EMERGENCE EGRESS LIGHT NOT
WORKING CHECK ALL
5.PROVIDE BALANCE REPORT
6.REMOVE ALL CONSTRUCTION DEBRIS
6.COMPLETE FRONT ENTRY FOR TCO _
PA FITNESS CENTER APPR TO OCCUPY GCD 02/08/2008 A000111
1.RECEIVED A PURCHASE ORDER FROM 075
PLATTE VALLEY LUMBER REGARDING
SAFETY GLAZING AT SIDE LITE AT EAST
DOOR.
PROVIDE AFFIDAVIT FROM SUPPLIER.
2.PROVIDE SPECIFIC BALANCE REPORT
FOR FITNESS CENTER FAN COIL AND
EXHAUST
Page 2
B05-0016: Entries for Item:90 - BLDG-Final 08:31 07/03/2013
CR SKI VALET GCD 02/12/2008 A000111
ENTRY PLATFORM ALL LAYER OF 117
PLYWOOD FOR 7"MAX RISE.
RETURN HANDRAILS TO WALL OR
SAFETY NEWELL.
ITMES 1,2,3,4,6APPR.
SKATE RENTAL APPROVED FOR
OCCUPANCY.
PA SKI VALET CORRECTIONS MADE GCD 02l13/2008 A000111
APPROVED FOR OCCUPANCY 156
CR BUILD B AND C 5th FLOOR CORRIDOR GCD 02/13/2008 A000111
AND UNITS 157
1.ELEVATOR 16 LOBBY PROVIDE VACUUM
BREAKER ON HOSE BIB
2.DOOR FRAME FROM ELEVATOR 16
LOBBY TO CORRIDOR NOT LABELED.
3.FIRESTOP CLEAN OUT IN BUTLER
PANTRY
4.LERNER UNIT(541,543,538,544)
COMPLETE ALL FIRESTOPPING IN WALLS
AND FLOORS
5.TELECOM REQS HEAD OF WALL JOINT.
UNITS INSPECTED
580,512,514,522,526,529,530,536. DRYER
BOOSTER FAN IN UNITS 508,514,529 NOT
WORKING. _ __
PA BUILD B AND C 5th FLOOR UNITS GCD 02/14/2008 A000111
508,512,514,522,526,530,536 APPROVED 187
FOR OCCUPANCY. ITEMS 1,3,4,5 FROM 02-
13-08 APPR. DRYER BOOSTER FANS IN
508,514,529 OPERATIONAL.
_ ITEM 2 REQS REINSPECTION. ____ _
CR POOL DECK CORRECTIONS GCD 02/14/2008 A000111
1.ELECTRICAL FINAL REQUIRED. 189
2.PROVIDE LETTER FROM 4240 RE POOL
BARRIER AND DOOR CONFIGURATION.
4.PROVIDE HARDWARE PER LETTER
FROM 4240.
NO MEETING WITH SHAW,4240 AND VRDC GCD 02/15/2008 A000111
REGARDING 4th FLOOR POOL. RVIEWED 203
PLAN SUBMITTED FROM 4240 WITH
CHRIS GUNION. CARD READER AND
LOCK REQD TO BE 54"ABOVE FLOOR.
PA ZAMBONI GARAGE APPR. GCD 02/15/2008 A000111
204
CR BUILD A-2 ALL UNITS HAVE GCD 02/21/2008 A000111
CORRECTIONS REMOVE CONSTRUCTION 326
DEBRIS FROM DECKS,CHECK ALL DOOR
SEALS. UNIT 276 NO GLASS AT SHOWER,
PASSAGE DOOR LOCKED. UNIT 278
PASSAGE DOOR FRAME NOT LABELED.
UNIT 282 NO MEP INSPECTIONS. UNIT 284
FINISH SHEATHING ON DECK,WATER
DRIPPING THROUGH FROM DECKABOVE,
GUARD INCOMPLETE. UNIT 285 LOAD
DOOR HINGES. UNIT 287 GUARD NOT
COMPLETE, MASTER BATH WINDOW AT
SHOWER REQD TO BE SAFETY GLAZED.
CR UNITS 284 AND 287 MISSING BALCONIES. SHAHN 03/20/2008 A000111
976
PA CHECKED CORRIDOR DOORS FOR SHAHN 03/20/2008 A000111
CLOSING AND GASKETS BUILDING A2 977
274,276,278,282,284,285,287,275.
APPROVED.
PA VICHY ROOM OK FOR TCO. GCD 03/26/2008 A000112
085
PA FINAL CONDOS 387,375,376,378,385. shahn 04/04/2008 A000112
320
Page 3
B05-0016: Entries for Item:90 - BLDG-Final 08:31 07/03/2013
PA BUILD D-3 UNIT 353,355(1)SAFETY GCD 04/11/2008 A000112
GLAZING REQD IN MASTER BATH,(2) 482
GUARD NOT INSTALLED ON DECK
ACCESS PROHIBITED BY PLYWOOD AT
DOORS,364,368,372.
BUILD A-3 UNITS 374,382,384.
APPROVED FOR TCO.
CR BUILD B-6 RANGES REQD FOR TCO GCD 04/18/2008 A000112
653
PA BUILD B-6 UNITS 608,612,614,617,619 GCD 04/21/2008 A000112
C-6 UNITS 622,630,636 APPROVED FPR 710
TCO __
PA BUILD B AND C 6th FLOOR UNITS GCD 05/02/2008 A000113
643 GUARD REQD TO BE 42 AT STAIRS. 199
DOOR REQD TO BE LABELED.
UNIT 330 ACCESSABLE TYPE A UNIT
REACH RANGE REQD FOR DRYER,
KITCHEN RANGE REQD TO BE
ACCESSABLE,SEAT REQD FOR TUB.
642 UPPER DOOR NOT LABELED INSTALL
COORDINATOR ON MAIN ENTRY DOOR.
GASPIPE ON DECK REQS SHUTOFF
VALVE.
629 INSTALL COORDINATOR ON MAIN
ENTRY DOOR. DOOR LABELS REQD.
UPPER DECK NOT FINISHED. ELECT
FINAL REQD.
UNIT 626 APPR.
UNIT 429 INSTALL COORDINATOR ON
MAIN ENTRY DOOR. DRYER EXHAUST
FAN NOT INSTALLED.
CR UNIT 330 TYPE A DWELLING UNIT GCD 05/06/2008 A000113
1.SHARP CORNERS UNDER KITCHEN 241
SINK COUNTER.
2.KITCHEN HOOD CONTROLS EXCEED
REACH RANGE.
3.KITCHEN SINK COMPLETE TRAP
GAU R D.
4.KITCHEN RECEPTACLE AT OVEN
COUNTER PER 308?
5.TOWEL BARS REQD TO BE 48"AFF MAX.
PA BUILD A-4 UNITS 476(SWEEP REQD ON GCD 05/16/2008 A000113
2nd DOOR),478,482, 687
487 NO DOOR SEAL.
BUILD D-4 UNITS 455(MASTER BATH
WINDOW REQS SAFETY GLAZING AT
DOORS,WEST DECK GUARD LESS THAN
42",SOUTH DECK GUARD OVER 4"AT
WALL.452(INTER CONNECT DOOR NOT
LABELED,SPRINKLER LEAK/
460,461,462,463,464,468(DECK GUARD
OVER 4"AT WALL.
CORRIDOR TELECOM AND ELECT
! CLOSETS REQ FIRESTOPPING AND WALL
PATCHING.ALL ITEMS REQ
REINSPECTION.
Page 4
B05-0016: Entries for Item:90 - BLDG-Final 08:31 07/03/2013
PA BUILD FINAL REINSPECTION GCD 06/11/2008 A000114
UNIT 343 SAFETY GLASING NOT REQD AT 579
WINDOW INTO BATHROOM.
UNITS 342,344 SAFETY GLAZING IS REQD
AT TUBS.
UNIT 643 DOOR AND FRAME IS LABELED,
AND GUARD IS NOT 42"MIN.
UNIT 642 DOOR AND FRAME IS LABELED.
UNIT 629 DOOR AND FRAME IS LABELED
AND COORDINATOR IS INSPTALLED
APPR.
UNITS 229,329,429,529 COORDINATOR
INSTALLED ON ENTRY DOORS AND
APPROVED.
PA REINSPECTION OF CORRECTIONS FROM GCD 06/12/2008 A000114
05-16-08. UNIT 455 HAS SOME TYPE OF 644
FILM APPLIED TO THE WINDOW IN THE
MASTER BATH,WITHOUT APPROVAL.
DECK GUARD CORRECTIONS APPROVED.
DOORS TO UNITS 476,478,482,487
CORRECTIONS APPROVED
452,SPRINKLER LEAK FIXED.
PA BUILD A UNITS 576,582,587 OK FOR TCO, GCD 06/13/2008 A000114
WITH CORRECTIONS; 697
DOOR SEALS ARE INSTALLED BUT DON'T
SEAL.
AP T.C.O.CORRECTIONS HAVE BEEN MADE NC 06/18/2008 A000114
ON UNITS#655,672,682,582,587,576 788
NO INSPECTION CANCELED BY GCD 06/20/2008 A000114
CONTRACTOR 897
__ REVIEWED TCO UNITS.
CR HANDRAILS SHALL CONTINUE 1 TREAD GCD 06/23/2008 A000114
DEPTH PLUS 12"AT BOTTOM OF FLIGHT 943
_ PER IBC SEC 1009.11.5
NO HANDRAILS IN STAIRS MEET CODE FOR GCD 07/03/2008 A000115
EXTENSION 322
CR BARON UNIT 484,584 1.ENTRY DOOR GCD 07/07/2008 A000115
FRAME UNLABELED CHECKALL DOORS. 382
2.PROVIDE SAFETY GLAZING IN ALL
DOORS AND WINDOWS AS REQD BY IBC
3.PROVIDE SMOKE SEAL AT SECOND
ENTRY DOOR.
4.LANDING RUN REQD TO BE EQUAL TO
WIDTH OF STAIRS AT TOP OF FLIGHT.
5.UPPER ENTRY DOOR REQD TO LATCH.
6.GUARD AT LOFT REQD TO MEET 42"
HEIGHT AND 4"SPACING.
UNIT 342 SAFETY GLAZING APPR. UNIT
355 SAFETY GLAZING APPR.455 AND 555
3M SCLARL 150 SAFETY FILM IS
INSTALLED.
UNIT 655 MASTER SAFETY GLAZING APPR
JR MASTER REQS SAFETY GLAZING.
CR STAIR 7 CHECK ALL FLIGHTS AND GCD 08/O8/2008 A000116
LANDINGS FOR RISE ALL HAVE 468
CORRECTIONS,OVER 7"MAX OR 3/8"
VARIENCE. ___
CR STAIR 5 STARTING FROM THE TOP; GCD 08/21/2008 A000116
GUARD AT ROOF ACCESS DOOR<42". 870
TOP RUN IS 10 3/4"MIN IS 11". MID FLIGHT
L-5 OVER 3/8"VARIANCE AND OVER 7"
MAX RISE. FLIGHT AT L-4 OVER 3/8"
VARIANCE THIS CONDITION REPEATS AT
LANDINGS L-3,MID FLIGHT L-2 ON DOWN
INSPECTION STOPPED CHECK ALL.
Page 5
B05-0016: Entries for Item:90 - BLDG-Final 08:31 07/03/2013
NO MET WITH GARY STARR AND PETER GCD 10/22/2008 A000119
FRANK RE: FLOOR 100
COVERING IN STAIRS,CARPET IS REQD
TO BE CLASS II.
THERE ARE SPRINKLER PIPES THAT
ENCROACH INTO THE ACTUAL WIDTH OF
THE LANDING IN THE STAIRS. __
PA UNIT 543/544 OK FOR TCO GCD 12/04/2008 A000120
681
CR FIRE CAULK THE DRYWALL PATCH AT shahn 05/04/2009 A000124
G203. 194
G1 PARKING NEAR BALLROOM PATCH
THE RATED WALL.
BALL ROOM STAIRS MISSING EGRESS
LIGHTING DURING OCCUPIED HOURS.
GENERAL NOTE: FIRECAULK ALL NEW
PENETRATIONS IN RATED WALLS
THROUGHOUT THE GARAGE LEVELS..
EXERCISE ROOM OPERATING HOURS
HAVE CHANGED TO 24/7, SO THE KEYED
ENTRANCE NEEDS TO BE REPLACED
WITH PANIC HARDWARE.
REPAIR BROKEN FROGEYE OUTSIDE
G 102.06.
REPLACE MISSING STAIR BARRICADE
1/G1 AND 9/L1
Total Rows:43
Page 6