HomeMy WebLinkAboutReview Second - Linhart Petersen Powers AssociatesAPR. 1.2005 4 :OOPM April 1, 2005 LP2A PLEASANTON Charlie Davis Chief Building Official, Building Safety & Inspection Services Town of Vail 75 South Frontage Road Vail, Colorado 81657 Fax; (970) 4792452 Re: Plan Review; ArraBelle At Vail Square Address: Vail, Colorado NO.034 P.2i26 TOWN OF VAIL - SECOND REVIEW L.P Job No.: 2050114.001 Dear Mr, Davis: Linhart Petersen powers Associates (LP has completed a second review of the following documents on behalf of the Town of Vail: 1. Plans: Two (2) copies each: Volume One of Four -cover through sheet A062 (61 sheets), sheets A100.1 through WP8 (283 sheets) dated ( "delta 6 ") February 15, 2005, by Hart / Howerton & 4240 Architecture, Inc. Volume Two of Four -cover through sheet S118D (56 sheets) dated ("deb 6") February 15, 2005, by Monroe & Newell, Engineers, Inc.; sheets M001 through M800.2 (146 sheets) dated ( "delta 6 ") February 15, 2005, by Cator, Ruma & Associates; sheets FS1.1 through LD1.1 (6 sheets) dated ( "delta 6 ") February 15, 2005, by Rloca Newmark Design; sheet IR -01 by Pace Industrial, Inc.; sheets VT01 through VT18 (18 sheets) dated ( "delta 6 ") February 15, 2005: shoots W000 through W604 (31 sheets) dated ( "delta 6 ") February 15, 2005, by STO Design Group, Inc. Volume Three of Four - -cover through E700.10 (146 sheets) dated ("delta 6 ") February 15, 2005, by Cator, Rutna & Associates; sheets LD,151 through LD,867D (57 sheets) dated ( "delta 6 ") February 15, 2005- Volume Pour of 4 -cover through sheet ID 862.90 dated February 15, 2005, for reference. 2, Plan Check Response Documents: A. Various revised sheets of drawings A021 through A534 (it sheets), E700,11. M110.1A through M115,p (18 sheets), S110.1A through S11713 (7 sheets), dated March 24, 2005. 13, Pooklet ASK -1100 through ASK 17 and Plumbing Fixtures and Door Schedules dated March 24, 2005, C, Booklet ESK- E002.1 through MSK12 dated March 24, 2005, D. Architectural Sketches A1Q6A through A041, Mechanical Sketch MSK -13, Food Services Sketches FSK1 through FSK5, Vertical Transportation Sketches VTSK01 and VTSK12, full size architectural sheets A028, A058 and A059, full size food services sheets FS7,1 through 7,9, dated March 24, 2005. E. Booklet SSK - S1,0 through SSK dated March 27, 2005. if - it 11 II 3. P�Qloct_Manuals: Four (4) copies each of Volumes 1, 2, 3, 4, 5, 6, 7 and one (1) additional copy of Volume 5 dated February 15, 2005, by 4240 Architecture, Inc. 4. $trVct Calculations: One (1) bound copy each of Volume #1 and Volume #2 with various dates, by Monroe & Newell, Engineers, Inc. 5, Enemy Gaiculations: Two (2) bound copies (Volume 8) of IECC Compliance Certificates dated February 15, 2005, by 4240 Architecture, Inc. 6. Geotechpical Report: One (1) bound copy dated July 2, 2002, by Koechlein Consulting Engineers, Inc. The 2003 Intematlonal Building Code, 2003 international Mechanical Code, 2003 International Plumbing Code, 2002 National Electrical Code, 2003 International Fire Code, 2003 International Energy Conservation Code and 2003 International Fuel Gns Piping Code were used as the basis of the review. Our re - check comments follow on the attached -list.. LI I\ HART PETKRSF -N POWF-,R5 ASSOCIATES APR 8unol Boulevard, Sulte 100 • Pleasanton, CA 94546 2005 (925) 226 -1370 " FAX(925)218-1970 • Ib Free (800) 34 0 - 4644 LIMtyA{ f PE 04/01/2005 FRI 16:49 [T% /R1 NO 74931 1�1 002 APR. 1.2005 4 :OOPM LP2A PLEASANTON ArmBelle @ Vail Square (N) Hotel Vail Colorado April 1, 2005 NO.034 P.3i26 Second Review - Vail, Colorado LP2A Job No.: 2050914.001 Page 2 Please submit an Itemized response letter and three (3) sets of complete and revised documents with ail revisions clouded, directly to LP Sincerely, LINHART PETERSEN POWERS ASSOC S � Val Dizitser, PE / 6504— Talat Abpasi, PP Orman 9 ICRO /ICC /IRC Plans Examiner ICBOACCARC Plans Examiner Associate Senior Associate nior Plans Examiner N11M O/WIG p:1Va1l200512050114.001 pc2.doc (Sin 400) Enclosures co: Mr. All Charafeddine, 4240 Architecture, Inc.: Fax (303) 292.9113 Mr. Dan Feeney, Vail Resorts Development company: fax (970) 845 -2356 04/01/2005 FRI 16:49 [T% /R% NO 74931 0 003 APR. 1.2005 4 :01PM LP2A PLEASANTON ArraBelle @ Vall square (N) Hotel Volt Colorado April 1, 2005 NO.034 P.4i26 second Revlew - Vail: Colorado LP2A Job No.: 2050114.001 Page 3 Following are comments for the first review of the ArraBelle project. Please note that there are also comments requiring further response from the second review of preliminary documents dated December 7, 2004. The format Includes a restatement of any previous comments followed by the applicant's response, Current new or recheck comments are sho In a separate bold italicized paragraph,. Re: Occupancy Groups: R -1, R -2, S -1, S -2, A A-3, B, M Type of Construction: is Stories: Seven and two garage levels Sprinklers: Yes Building Area (sq. ft.): 538,663 GENERAL COMMENTS: A. The following plan review comments are based on the 2003 Intemational Building Code, 2003 international Mechanical Code, 2003 Intemational Plumbing Code, 2002 National Electrical Code, 2003 International Fire Code, 2003 International Energy Conservation Code and 2003 International Fuel Gas Piping Code. B, Please respond in writing to each comment by marking the attached comment list or creating a response letter, Indicate which detail, spec cation, or calculation shows the requested information. Further, amendments to plans shall be identified by "clouding" and "delta symbol ", Your complete and clear responses will expedite the recheck process and eventual approval of this project. Thank you for your assistance. C. For the final set of drawings, please be sure to have designer's "wet" stamp and signature on all sheets of plans and on covers of specifications and calculations. D. The following code comments reflect a review of building plans only. If site - related comments are applicable to this project, they will be generated by others (e.g, City Engineering, Public Works, Fire Department, Health, etc.). E. The review of the automatic fire alarm and sprinkler system is not included in LP2Xs scope of review. ARCHITECT COMMENTS: 15. Ut Diagrams, Sheets A020.1 through A023 G. On these exit diagrams, dearly show complete exit discharge. a. Show that exit discharge Is at grade or provide direct access to grade. Show conformance with IBC 1023.2 exit discharge capacity, 1023.3 exit discharge location, IBC 1023A exit discharge components, IBC 1023.5 egress courts, IBC 1023.5.1 widths, 1023,5.2 construction and openings and 1023.6 access to public way, b, Please show the exit discharge from termination of an exit to the public way per IBC 1002. The site drawings shows a road around the project. Please describe this road as a component of the exit discharge and show the exit r.A APR. 1.2005 4:01PM LP2A PLEASANTON NO.034 P.5i26 ArraBelle @ Vall Sgpare (N) Hotel Second Reylew - Vall, Colorado Vail Colorado LP2A Job No.; 2050194,001 APd l 1. 2005 Page 4 discharge extending to the pubic way, Identify the public ways on the site plan, Applicant's Response: Please see sheet A031, Plaza and Building Egress at Plaza Level. The roadway on three sides of the project is a pedestrian mall and public way (as noted on sheet A011, Site Plan) and fire lane (as noted on Sheet L400, Fire Department Site access Plan). March 15, 2005 Comment Sheet A031, Plaza and Building Egress at Plaza level and Sheet 1.400; At the south and south portion of east side of the site, please show e)at discharge to the public way and that exit discharge conformance with the above requirements, Sheet A031 does not provide adequate information on exit discharge from these areas. Applicant's Response (3- 24 -05): The public way on the south side of the property is an open ski yard with gondola and chairfih' access to the mountain. On the south side of the yard is a new bridge (replacing an existing bridge) that connects to public streets and US. forestland. An existing bike & pedestrian path crossing the skl yard leads to Lionshead Place to the west and continues east to public streets. No one site plan shows the entire context of the current bridge and current bike & pedestrian path alignment Please see sheet C13 for overall site context with the new bridge, but with the bike & pedestrian path (in dashed lines) prior to construction of the bridge. Please see sheet 3C for a clearer view of the path (dashed lines) prior to construction of the new bridge, and sheets C9A, C9B and COC for existing alignment of the path since construction of the bridge. Current Comment: I. Sheet A050 east yard shows several flights of steps which are not accessible. Review for accessible exit discharge to public way. 2. On revised Sheet A050, for clarity, please show the bike & pedestrian paths and bridge to clarify their location and how they prove exit discharge to public way. Indicate whether bikepaths, pedestrian paths and bridge are new. Indicate how they meet accessibility requirements. 3. Show how am south of Zone 7 provides accessible discharge to public way. 21. Sheet A021, Exit Diagram — Level 1: A. Amend plans to include occupant load for outdoor area per IBC 1004.8. Include outdoor area occupant load in providing means of egress. Please specify the Intended use of the common area and provide the designed exiting locations and sizes. Please provide the accessible route of travel to show how all occupants within this common area gain access to the public way. Applicant's Response; Per a meeting with the building department on August 26, 2004, occupant load exiting from the building into the (accessible) outdoor area in question will be identified on the permit drawings. APR. 1.2005 4 :01PM LP2A PLERSRNTON NO.034 P.6i26 ArmBe(le @ Vail Square (N) Hotel Second Review - Vail, Colorado Vail Colorado LP2A Job No.: 2050114.001 April 1, 2005 Page 5 March 15, 2005 Comment Please review plaza occupant load. The occupant load on page 4 of Administrative Modffication Request PRJ04- 0233 -2 does not agree with the occupant load on Sheet A031 of the drawings, Applicant's Response (3-24 -05): The occupant load tables in AMR PRJ04- 0233 -2 are based on an earlier version of Sheet A031, and are not up to date with the current version of that sheet. The AMR tables and appended sketch will be made current prior to final sign -off of the AMR. March 75, 2005 Common f P /else provide revised AMR conforming with occupant loads on Sheet AOS7. 26. Sheet A032, Fire Department Site Access: Please show on drawings that the location of the emergency escape and rescue windows for the Residential units open directly into a public street, public alley, yard or court per IBC 1009. Show that the location meets the requirements for Fire Department. Applicant's Response: Please see enlarged hotel and condominium plans, Sheet Series A 150 through A 190 for windows keyed as emergency escape and rescue windows. March 15, 2005 Commen# Please confirm with the fire department that the location of the rescue windows adequate meet the fire- rescue requirement that the windows open directly into a public street, pubic alley, yard or court Applicant's Response (3- 24 -05); A review with the Fin: Dept will be included on the agenda for a meeting with the building and fire departments on MarrA 28 We will then be able to confirm locations after the meeting, Please also see updated elevation sheets A201 through A204 for rescue window locations, Current Comment: Please provide confrnnation of Pyre Department approval from March 28, 2005 meeting. 40. Please revise plans to show that the exit enclosure stairway 7 discharges into an exit passageway at this level to the point where egress from the building is provided at door P149-A. APplicant's Response; Please see sheet A021 for exit passageway. March 15,_2005 Comment On Sheet 101 the exit passageway is shown with what appears to be a closet, Per IBC 1020 openings In exit passageways are limited to shoes necessary for exit access to the exit passageway from normally occupied spaces. Please review, Applicant's Response (3- 24-05); Please see corrected Sheet A101 closet space is removed from the plans, Current Comment. Sheet A101 was nbt submitted with revised documents. Please forward copy of revised Sheet Af01. 41. Sheet All 11 C — First Level Floor Plan -- Area C: ndinlignn- FRT 16,49 (TX /R% NO 74931 Q006 APR. 1.2005 4:02PM LP2A PLEASANTON NO.034 P.7i26 ArmBelle @ Vail Square (N) Hotel Second Revlew - Vail, Colorado Vail Colorado LKA Job No.: 2050111.001 April 1, 2005 Page 6 A. Please specify the elevation changes In the floor between Spa Hotel fitness and retails areas and the rear treatments rooms located at the rear of the tenant space. Please specify the slope of all ramps (assumed) between these different levels, S, Please clarify the size of the assumed ramp landing within coh1dor P144.01. C. Please specify the direction of slope for each change in level at all ramps and stairways. Anvlicant's_Response: Please refer to new spa plans for Items A through A. March 15, 2005 Comrne_nt Please address the following: 1. Show on drawings the slopes at the three sloped areas in hallways and show required ramp details if the sloped areas are 5 percent or greater. 2. Drawings show 5 areas in hallway which have steps, Show how accessibility requirements are met at these areas, Applicant's Response Q-- 5): Please see updated Sheet A 111 C sketch and Sheet A132 for addifional stair and ramp information. Please note that Spas P145.12 and P145.32 are actually pools with stair requirements governed by State of Colorado Dept of Health•Swimming Pool Regulations. See Volume Two Sheet W401, detail C for step details at the pods. Please see updated Sheet A051 sketch for accessible egress from this area. Please note on Sheet A051 a spa mezzanine that is not accessible. It is intended that all activities provided on the mezzanine be provided to an equal degree on the accessible levels, Current Comment: 1. Sheet A111C was not provided for our review. Please submit sheet 2. Sheet A051 was not provided for our review. Please submit sheet Shope that access is provided through this area In which have may flights of steps. 3. Revised Sheet A132 shows ramp at building lines H6 as 1:9.6 which exceed maximum allowable slope of 8,33%. Please review. 43. Sheet A111 F — floor plan — Partial First Level. D. Pleas provide an elevation showing details from the north view of the Ice rink at the exterior wall next to the mechanical areas shown on the plans sheet, Applicant's Response: Please see L series Landscape drawings, Volume 2. March 15, 2005 Comment For the north stairs leading to Ice Rink, please indicate how disabled access is provide from north of site to ice rink. Applicant's Response (3- 24 -05): Please see updated Sheet A051 sketch for accessible route. Current Comment: Updated Sheet AM was not submitted with revised documents. Please provide. Also, revised Sheet A050 does not show accessible route near the north stairs to Ice Rink. Please review. 55. Sheet Al 14B — Fourth Level Floor Plan -- Area B: 04/01/2005 FRI 16:49 [T% /R% NO 74931 14007 APR. 1.2005 4 :02PM LP2A PLEASANTON NO.034 P.8/26 ArraBelle @ Vail Squ4re (N) Hotel Second Review - Valli, Colorado Vail Colorado LP2A Job No.: 2050114.001 April 1, 2005 Page 7 B. Because the door from the roof top pool must swing in, this will created a dead end corridor that exceed 20' past the point where access to the exit enclosure of stairway 8 is provided. Applicant's icant's Response: Doorway will be required in Corridor P410 to limit length of dead end corridor. Correction to be picked up with other revisions required in response to LP2A plan review comments on permit drawings. March 15 2005 Comment In next submitted drawings, please show revised layout to eliminate dead end corridor, Applicant's Response (3- 24 -05): Please see corrected Sheet A114B sketch. Please note that door P401B creates a oomidor that exceeds the 20 ft: required maximum distance. A request for consideration of this condition will be directed to the building department in a meeting scheduled for March 28. Current Comment: Please provide documentation of approval of corridor from the March 28, 2005 meeting. 67. Sheet Al 17C — Seventh level Floor Plan — Area Q A. Please provide an exiting plan that will clearly show the designed exiting for this level. Indicate occupancy loads and number of exits required from Level 7. The seventh floor appears to require two exits. Applicant's Response: Please see sheet A037C for exiting diagrams and sheet A027 for occupant loads. March 15, 2005 Comment Sheet A027 shows occupant load at this level as 23 requiring two means of egress per IBC Table 1014.1. Please review number of exits. Applicant's Response (3- 24 -05): Since the occupant load on this level is the upper level of three separate condos only, it has been our intent to provide the 2 means of egress within each unit. Please see administrative modification PRJ04 -02335 for further discussion of egress considerations from these condos. Current Comment: Administrative Modification PRJ04 -02335 does not address corridors requiring 2 means of ®grass. Please revise PRJ04 -2835 to address this situation, 73. Please review the following wood components which are indicated in drawings. The following use of wood does not conform with IBC 603.1 which lists the allowed use of wood in Type 113 buildings; B, Detail 101A561 wood shown on soffit and fascia. Applicant's Response: Fire retardant treated wood is specified for ali wood veneer and trim. ff is our understanding that fire retardant treated veneer complying with the requirements of Section 1405.4, is allowed up to a height not exceeding 4 stories and that fire retardant treated wood #rim complying with Section 1406.2.2, is allowed up to a height of 40 feet Please see general notes on Sheet Series A200's. nd/nl/2nn5 FRT 16:49 1T% /R% NO 74931 Z 008 APR. 1.2005 4:02PM LP2A PLEASANTON NO.034 P.9i26 Arrasel /e {@ Vail Square M Hotel Second (Wiew - Vail, Colorado Vail Colorado UP2A Job No.: 2050114.001 April 1, 2005 Page a C. Sheets A201 through A217, exterior elevations where wood Is used in arras such as shutters, Applicant's Response: Agreement In principle, has been reached with the chief Building Official that isolated amounts of fire retardant treated wood trim will be allowed above the height limits established in Section 1406.22. This is to be finalized by further review with LP2A and the building official durfng the permit review process. Please see general notes on Sheet Series A200's, March 15, 2005 Comment Comment for Item 738 and 73C 1. Provide copy of final agreement with Building Official on requirements for veneers. 2. Revise veneer requirements in `General Notes" on Series A200 drawings to show conformance with Building Official finalized agreement. 3. Amend "General Notes" on Series A200 drawings to indicate specific design and details. 4. On Series A200 drawings amend exterior elevations to show the veneer requirements of the agreement. Applicant's Response 63- 24-05): these issues will be reviewed with the Building and Fire Departments on March 28, The corrections requested above can then be addressed after that meeting. Current Comment: Please provide agreements from the March 28 meeting and provide drawings documenting all requirements. 76. Sheets A621 through A624, Provide window schedule showing window type, size, glazing type, fire- rating requirements, emergency rescue and escape widows, safety glazing and other special window requirements. Applicant's Response: Please see window schedule, Spec Section 09999. March 15, 2005 Comment At window schedule please indicate the following: 1. Indicate type of window. 2. Indicate whether any of the windows are required to be rated assemblies. 3. Indicate which widows are openable. Indicate windows which are openable to meet natural ventilation requirement. IMC has natural ventilation requirement of 4% of floor area for outside air. Applicant's Response t3-24 - The window schedule is in progress. Requested information will be provided before or on March 30. Current Comment. Window schedule has not been received. Please provide window schedule. 80, Sheets A701 to A715, Stairs. Please complete the stair drawings by providing the following information on the drawings: C. Amend drawings to show stair details and structure. Show stair treads and risers details per IBC 1003.3.3.3 Applicant's Response: Please see Sheets A701 A714. ndinii2nn5 FRi 16:49 1TX /RX NO 74931 14 009 APR. 1.2005 4 :03PM LP2A PLEASANTON NO.034 P.10i26 ArmBelle @ Vial/ Square (N) Hotel Second Review - Vail, Colorado Vail ColoriqdA LP2A Job No.: 2050114.001 April 1, 2005 Page 9 March 15, 2005 Comment At Detail 6/A708, amend drawings to show uniform tread. Per IBC 1009.3, the greatest tread depth within a flight of stairs shall not exceed the smallest by more than 0.375". Applicant's Response f3- 24 -05):. Please see corrected detail 6, Sheet A708 sketch. Current Comment; Sketch Sheet A708 with corrected Detail 6 was not received. Please provide. 91. Although smokeproof exit enclosure are not required by the IBC, the applicant has intended to provide smokeproof exit enclosures for the project, Please amend plans as required for smokeproof enclosures as follows: A. The project documents do not show smokeproof enclosures. Amend design to show conformance with the following code sections: a. IBC 403.13, Smokeproof exit enclosures. b. IBC 909.20, Smokeproof enclosures. C. IBC 1019.1.8, Smokeproof enclosures. B. Please amend plans to show compliance with the following: a. Show that enclosed interior stairway conforms with IBC 1019.1 and an outside balcony or ventilated vestibule meeting the requirement of IBC 909.20. b, Access to stair shall be by way of a vestibule or an open exterior balcony. The minimum dimension of the vestibule shall not be less than the required width of the corridor leading to the vestibule but shall not have a width of less than 44" and shall not have a length of less than 72" in the direction of egress travel. IBC 909.20.1 c. Smokeproof enclosure shall be separated from remainder of the building by not less than 2 -hour fire - resistive -rated fire barrier without openings other than the required means of egress doors. The vestibule shall be separated from the stairway by not less than a 2 -hoyr fine - resistive -rated fire barrier. The open exterior balcony shall be constructed in accordance with the fire- resistance - rating requirements for floor construction. IBC 909.20,2 d, See requirements for door closures, IBC 909.20.2.1 e. See IBC 909.20.3 through 909,20.5 for ventilation systems. f. See IBC 909,20.6 for ventilating egtyipment, g. See IBC 909.21 for underground building smoke exhaust systems, h. See IBC 909,21.3 for alarms required. C. Please amend plans to show compliance with the following: a. A smokeproof enclosure or pressurized stairway shall exit into a public way or into an exit passageway, yard or open space having direct access to a public way. The exit passageway shall be without other openings and shall be separated from the remainder of the building by a 2 -hour fire - resistive -rated construction. IBC 1019.1.8.1 b. Access to the stairway within a smokeproof enclosures shall be by way of a vestibule or an open exterior balcony. 113C1019.1.8-2 04/01/2005 FRI 16:49 (T% /RX NO 74931 0 010 APR. 1.2005 4 :03PM LP2A PLEASANTON NO.034 P.11i26 ArmBel/e @ Vail Square (N} Hotel Second Review - Vail, Colorado Vail Colomdo LP2A Job No.: 2050114.001 April 1, 2005 Page 10 Applicant's Response: Certain exit enclosures will feature 'smoke managed'systems. The building and fire departments have agreed that these systems will be desi9ned to conform to a distinct set of criteria separate from smokeproof exit enclosures System details will be provided in documents issued for permit Applicant's Response: Please see adminlstroYve mod cation PRJ04- 0233 -1 for features associated with stair pressurization. it is critical to note that the pressurization design is intended to conform only to those parameters listed in the admin mod. It has not been requested or Intended to conform to the requirements noted below. March 15, 2005_ Comment In next submitted drawings, please show all requirements, details, and calculatlons conforming with final agreements for smoke management system. Applicant's Response (3- 24 -05): The smoke management fan schedule is shown on 440025. Details and sequence of operations for the system are shown on the fire alarm drawings. Calculations will be submitted by March 30, 2005, Currant Comment: Please provide complete design and documentation of smokeproof system, 93A. March 15, 2005 Comment Sheet A028, Roof Plan: C. Confirm that the location and size of roof accesses meet requirements of the Fire Department. Applicant's Response (3 -247 05): C. A review with the Fire Dept will be included on the agenda for a meeting with the building and fire departments on March 28. 777e status of confirmation will then be addressed after the meeting. Current Comment. Please provide agreements from March 28 meeting and provide drawings showing agreed requirements. 93B. March 15, 2005 Comment Sheets A011, A031 and A041, Site Plans: On drawings clearly show grades from adjacent pedestrian mail and adjacent yards onto the plaza level of the project. Show required grades and details to show conformance with access to the plaza and accessible access to the plaza. AW icant's Response (3724 7-05): Please see sheet 000, Volume 2 for requested grade information. This same sheet is also being reissued as Sheet A050, to be Integrated with building accessibl7ity plans and details, Current Comment: Please show how i wccessible route is provide at stairs east of Zone 5 and south of Zone 7 (See A041 for zone designation.). 931). March 15, 2005 Comment Sheet A`100.11-1: Review width of drive lane at entry gate. Confirm that width Is sufficient for vehicles. Applicant's Response (n2445): See sheetASKA110.1H (page 1 of 2) dated 3- 24-05, which reflects the design revisions using 8 =3" in lane width at each side of the control gate 11 APR. 1.2005 4:03PM LP2A PLEASANTON NO.034 P.12126 ArmBoAe @ Vail Square (N) Hotel Second ReVIBW - Vak Colorado Vail Colorado LP2A Job No.: 2050114.001 ApOl 1, 2005 Page 11 Island. The width is still to be resolved arld will be finalized and documented for review by March 30. Current Comment: 1. Please provide agreements from March 28 meeting and provide drawings showing agreed requirements. 951. Current Comment: It has recent come to our attention that the Garage may have accesses which run through property lines to acyacent existing garage areas. As structures are not allowed to have openings at property lines. please idenff& any such areas and provide solutions to addressing easements and IBC restrictions for openings at exterior walls adjacent to property lines. DISABLED ACCESS COMMENTS: DA7. Amend plans to clearly specify and show how all accessible exit doors provide accessible means of egress continuously to the public way. Currently the building has numerous. exit door and plans fail to show an accessible means of egress. Please be very specific in your response, showing thresholds, landings, ramps (where necessary) complying with IBC 1010, exterior walkways, exterior paving sloped maAmum 2% up to door threshold, etc., to show the accessible routes of egress, For instance plans show accessible doors at the Fast side of the building, however it appears that there are no ramps along the East side of the building. Sheet A051 through A055, 113C 1104.3 Please refer to Drawing A050— (renumbered from 1.500) Drawing A051 and the Specification Sections 08710 and 09999. These Drawings and Specfcation Sections in unison, resolve the door hardware and threshold issues for doors along the accessible route. Drawing A050 and A051 indicate the accessible route from the building to the public way. Once in the public way, there are multiple altemative accessible paths that can be followed to areas of safety that met the relevant code criteria. This item wasn't fully addressed in the re- submittal. Plans show several stairs along the ,astern side of the building. Please clarify why this side of the building should not be accessible for people with disabilities. DA11. Revise plans to show Area of Refuge" at all enclosed stairways per IBC 1007.3 An "Area of Refuge is not required at enclosed stairways per Exception 2, ISC 10073 Enclosed Exit Stairways, provided the building is fully sprinklered in accordance. with Sectlon 903,3.1.1. This item wasn't adequately addressed in the re-submittal. Exception $ IBC 1007.3 applies to open stairways. Original comment still applies DAl2. Where areas of refuge are required, amend plans to specify a method of two-way communication (with both visible and audible communication) between areas of evacuation assistance and the primary entry. All doors into the area of refuge shall be identified with a nein1i9nnA FRT 1R•49 rT% /RX NO 74931 0012 APR. 1.2005 4 :04PM LP2A PLEASANTON NO.034 P.13i26 ArraBelle @ Vail Square (N) Hotel Second Review - Vall, Colorado Vail Colorado LP?-4 Job Nc.: 2050174,001 ApHl 1, 2005 Pege 12 sign stating "Area of Refuge" along with the international Symbol of Accessibility, IBC 1007.6, 1110.1 An "Area of Refuge' is not required per Exception 2, IBC 1007.3 Enclosed Exit Stairways, Exception 2, IBC 1007.4 Elevators, and Exception 2, IBC 1007.6,2 Separation, provided the building Is fully sprinklered in accordance with Section 903.3. 1. 1 or 903.3.1.2. This item wasn't adequately addressed In the re -submittal. Exception 2, IBC 1007.3 applies to open stairways. Original comment still applies DA13. Amend the plans to indicate an International symbol of accessibility shall be provided at the area of refuge. IBC 1110.1 An "Area of Refuge" is not required per Exception 2, IBC 1007.3 Enclosed Exit Stairways, Exception 2, BC 1007,4 Elevators, and Exception 2, IBC 1007.6,2 Separation, provided the building is fully sprinklered in accordance with Section 903.3.1.1 or 903.3.1.2. This item wasn't adequately addressed in the re- submittal. Exception 2, IBC 1007.3 applies to open stairways. Original comment still applies. DA45. Clarify on the plans how many Type "A" and how many Type "B" condos, Please refer to Drawing A052 and A053. Type A condominiums are designated in the shaded areas of the plan. All other condominiums are Type B units Provide calculations to justify allocation of Type "A" and Type "B" condos DA46. Clarify on the plans how many Type "A" and how many Type "B" "lock -off units Please refer to Drawing A052 and A053. Type A lock -off units are designated in the shaded areas of the plan. All other lock -off units are Type B units Provide calculations to ju .5tify allocation of Type "A "and Type "B" lock -off units MECHANICAL. PLUMBING, ELECTRICAL COMMI =NTS: Mechanical: 111. For garage ventilation: D, if garage fans area not operating continuously confirm that carbon monoxide detectors have capacity to maintain a maximum average concentration of carbon monoxide ooncentration of not greater than 25 parts per million. Applicant's Response. Carbon monoxide detectors will be installed in the garage to contra! CO concentrations to less than 25 PPM Provide location of CO sensors in the garage as specified in the response. IMC 404.1. Response indicates revise complying drawings will be submitted. 04/01/2005 FRI 16:49 [T% /R% NO 74931 14 013 APR. 1.2005 4 :04PM LP2A PLEASANTON Arr'aAella (a3 Vail Square (N) Hotel Vail Colorado April 1, 2005 124, Type I Hood Additional comment NO.034 P.14i26 Second Review - Vail, Colorado LP2A Job No.: 2050114.001 Page 13 (1) Response indicates that the hood sizing, fire suppression and hood clearances are the responsibility of the kitchen consultant and will appear on the kitchen plans to be submitted later. Provide note on plan. Response states revise drawings will be supmitted. (2) Provide speoifloatlon for the makeup air unit will provide an equal amount to the amount exhausted. Response states revise drawings will be submitted. (3) Specify on plan vertical distance between lip of hood and cooking surface to not more than four (4) feet. IMC 507,12. Response states revise drawings will be submitted. (4) Specify exhaust outlet termination serving Type I hood is not less than 10 feet horizontally from any part of the building and air Intake openings. IPC 506.3.12.3. Response states revise drawings will be submitted. (5) Provide typical detail for the construction of the fire resisWe duct enclosure per IPC 506.3.10., Response states revise drawings will be submitted. 133. Provide a refrigeration machinery room for the refrigeration system complying with several requirements such as ventilation, refrigerant detectors, discharge location, make -up air, etc. per IMC sectons 1105.1106, 1107 & 1108. (a) Specify all exit doors from machinery room to swing in the direction of travel and shall be tight fining and self- closing per IBC 1014.4. Sheets M110.1 B & M110.2D, Response states revise drawings will be submitted. (c) Provide confirmation that exhaust from mechanical ventilation Is not less than 20 feet from openings into building. IPC 1105.6.1. Response states revise drawings will be submitted. (co Specify clearly identified switch for the emergency purge ventilation to be in a break -glass type providing on-on control, IMC 1106.5, 2. Response states revise drawings will be submitted. (e) Specify a clearly identified switch of bleak -glass type providing o -on carttrol of electrically energized equipment/devices within the refrigeration machinery room and to be ndin1i2005 FRI 16:49 [TX /R% NO 74931 0 014 APR. 1.2005 4 :04PM LP2A PLEASANTON NO.034 P.15/26 ArraBelle 0 Vail Square (N) Hotel Second Review - Vail, Colorado Vail Colorado LP2A Job No.: 2050114.001 April 1, 2005 Page 14 provided immediately acVacent to and outside of each refrigeration machinery room exit, IMC 1106,5, 1. Response states revise drawings will be submitted. (f) Specify approved emergency signs, charts, labels In accordance w9h the Intemational Fire Code for the refrigeration units and systems. IMC 1106.6 Response states revise drawings will be submitted. (g) Because the machinery room G155 is more than 1,000 sf provide two exits separated = to M of the maximum horizontal dimension of the room per iBC 1014.4, Sheet M110.2D. Responses states revise drawings will be submitted. Additional mechanical comments; M1. Provide complete mechanical plans and details at lev ®15, areas A, B, C & D where duct layout and duct sizes were missing. Sheets M116.A through M116.D. Response states revise drawings will be submitted. M2. Specffy exhaust termination of exhaust outlets serving Type 1 hoods to have the discharge outlet located not less than 40 inches above the roof surface, IMC 506,3.11, 1. sheet A4117 B. Response states revise specification will be submitted, M3. Provide continuation of 6" duct to upper level for bathroom exhaust of bathroom G205. Sheet MI 10-A. Response states revise drawings will be submitted. M4. Clarify outside air supply d ®tail for the 72x30 duct to boiler room. It is not clear how outside air will flow through this duct Sheet M111 C. Response states revise drawings will be submitted M5. Provide continuation of garage exhaust duct located at grid lines D.1 & 21.9 on sheet Mi 10,1 D to the upper garage level. Response states revise drawings will be submitted. M6. Provide installation detail and listing (e.g. UL, 555C) for the horizontally installed combination firelsmoke dampers on the plan. Sheet M600.1. Response states revise drawings will be submitted. 04/01/2005 FRI 16:49 [T% /R% NO 74957 191015 APR. 1.2005 4 :05PM LP2A PLERSRNTON NO.034 P.16i26 AMBelle Q Vag Square (N) Hotel Second Review - Vail, Colorado Vail Colorado LP2A Job No.: 2050114.001 Ap111.2005 P &ge 15 M8, For the ski Instructor locker room (G 102.05: (a) Outdoor air flow supply is not adequate for an area of 2,261sf. Per IMC table 403.3 locker rooms requires a minimum of 0.5 cfm /sf therefore 2261 x 0.5 =1131 cfm. The total supply cfm shown on sheet M110,2A is only 250 x 4 =1000 cfm. Sheet A020.2. Response states revise drawings will be submitted. (b) Recirculation of air from this space is prohibited per footnote b of IMC table 403.3. Delete 24x 12 transfer air duct to public storage G 101. Sheet M1 10-2A. Response indicates us footnote g of table 403.3 but footnote g is applicable to shower room only not for locker room. M9, Identify exhaust fan labeled EF - -xx located near grid lines 12.2 & S.3. Sheet M110,2S. Response states revise drawings will be submitted. M12. Include on the air handling unit schedule sheet A4002,1 AHU-4 unit for the mechanical morn G117. Sheet M110.2B. Response states revise drawings will be submitted. M15. Specify make -up air opening not less than 100 square inches at the door of the dryer enclosure. IMC 504.5. Response states revise drawings will be submitted. M16. Typical for all hotel rooms and tenant spaces levels 2 through 7: (2) Confirm all ducts penetrating fire partition walls separating tenant spaces and corridor are constructed of steel of not less than 0.019 —inch to comply with exception 2 of IBC 716.5.4.1. Response states revise drawings will be submitted. Plumbing: P3, For the Boilers (2) Provide note on plan that upon completion of the assembly and installation of the boilers acceptance test shall be conducted In accordance with the requirements of the ASME Boiler and Pressure Vessel Code. A copy shall be submitted to the field Inspector: IMC 1011.1. Response states revise drawings will be submitted. (3) Provide detail showing relief valve discharge piping of boiler through an indirect waste pipe by means of an air break or air gap. Sheet M600,21boiler detail, IPC 802.1.5. 04/01/2005 FRI 16:49 M /R% NO 74931 0 016 APR. 1.2005 4:05PM LP2A PLEASANTON NO.034 P.17i26 Airadelle @ Vall Square (N) Hotel Second Review - Vall, Colorado VA 11 Colorado LP24 Job No.; 2050114.001 April L 2005 Page 16 Response states revise drawings will be submitted. (4) Provide confirmation that no steam or water with temperature greater than 140 degree F is discharging into the waste receptor connected to the drainage system. A means of cooling the waste to 140 degree F or below should be provided or special piping material must be specified. Sheet M600.21boller detail, IPC 803.1. Response states revise drawings will be submitted. Electrical Comments: E1. Indicate the locations for load centers In the condo units. The only plans that show the load centers are the Reference Electrical Plans and they indicate panels located in clothes closets. Article 240.24 (D) prohibits panels being located in clothes closets. Applicant's Response Q- 24 -05): Condo load centers will be relocated flush in wall behind entry door, or flush in wall behind secondary entry door where available. Current Comment Please provide revised drawings showing location of condo load centers at locations stated In applicant's response. ENERGI,,,LCONSE,RVATION COMMENTS: EC1. The submitted calculation does not appear to include the compliance certificate requirements for the residential portion of the project. Clarify if the activity type designated 'others" represents the residential area. No response submitted. STRUCTURAL COMMENTS: Structural Drawings Review: SD3. Section 1 on sheet S2.1 refers to schedule on sheet 85.0, sheet S5.0 Is not included in the package. Please either provide sheet S5 or revise the reference if the above mentioned reference is a typo. PcI Section 7 on sheet S2.1 still refers to sheet S5.0. Although the response indicates that the permit drawing have been revised, sheet S5.0 is still missing from the package. Please provide the missing sheet Pct The revised sectlon has not been submitted, Please provide a copy. SD12. Cannot find any information about the lap splices in masonry walls. Please note that the lap shall not be less than as recommended by IBC Section 2107.2.3 as stated below: 04/01/2005 FRI 16:49 IT% /Rg NO 74931 0 017 APR. 1.2005 4:05PM LP2A PLEASANTON AM8011e @ Vall Square (N) Hotel Vall Colorado April 1, 2005 NO.034 P.18i26 Second Review - Vail, Colorado LP2A Job No,: 2050! 94.009 Page 1 7 2107.23 ACI 530 /ASCE 5/TVs 402, Seetign 2,1,10.6.1,1, kp splices. The minimum length of lap splices for reinforcing bars in tenaioA or compression, lid, shall be calculated by Equation 21 -2, but shall not be less than 15 inches (380 mm). U4 a 0.16 4 fp y /(KNP-) (Equation 21 -2) where: db = Diameter of reinforcement, inches. fy - Specified yield stress of the roinforcement or the anchor bole, psi f m Specified compressive strength of masoxuy at age of 28 days, psi ba = Minimum lap splice length, inches. K The lesser of the masonry cover, clear spacing between adjacent reinforcement or five times 4, inche$, T = 1.0 for N0.3 through No, 5 bars, 1.4 for No. 6 and No. 7 reinforcing bars. 1.5 fox No. 8 through No, 9 reinforcing bass. pci Cannot find calculations In the package, please note for the following data, the development length shall be calculated as under, Data K the lesser of the masonry cover, clear spacing between adjacent reinforcement or five times db = 2.815inches Cover = 2.815 inches Spacing = 12inches 5 x db ° 3,125incbes db — 0.625inches f�� = 1500psi f A 60000psi Y 1 for #3 through #5 1.4 for #6 through #7 1.5 for #8 through #9 reinforcing bars. Solution: 14 = 0.164 f r / PK(P.3 / 2 ] 0.16d$ = 0.062b fy Y M 60000 (p01 = 98.72983 pf'MY / = 109,0245 h4 ° 34AOinc'hes please provide such calculations and the schedule showing the splices for different diameter of bars used in the project, pct Section 6 does not have any Information about the splice, please provide the same, SD18. Please revlse detail 2/S5.1, please locate #4 bars from top of slab. Pct a. The detail has not been revised to Include the requested information. Please revise detail accordingly. 04/01/2005 FRI 16:49 [TX /R% NO 74931 Q018 APR. 1.2005 4 :061`11 LP2R PLERSRNTON NO.034 P.19i26 ArraBelle @ Vail Square (N) Hotel Second Review - VaIG ColoMdo Vail Colorado LP24 Job No.: 2050794.001 April 1, 2005 Page f8 b. Plan on sheet S110.2A refers to detail 9 /S4.1 (see between grid line H & J.8 and 20 & 21.8). This does not seem to be correct reference. Please revise plan accordingly. PC2 The plan on sheet S110.2A now refers to detail 51SIA, sheet SIA (original submittal) does not include detail 5. There are only 4 (four) details. Please clarify. SD19. Please revise plan on sheet 8110,2A to indicate the spacing of the steel beams which may or may not be equally spaced, PCI a. The response Indicates that the sheet has been revised, the plan still missing the required information. b. The plan refers to detail 17/S4.1 (see at the intersection of grid line P.3 & 15.6),and also (see at the intersection of grid line 1V.6 & 13.2) there is no such detail on sheet S4.1. Please provide the missing detail or revise the reference if the detail Is provided elsewhere, PC2 Detail 171S5.1 refers to plan for beam to beam connection, cannot find such Information on the plan. Please provide missing information. Sg21. Detail 17/S5,1 refers to plan for projection of steel beam beyond center line of pre -cast column, cannot find such detail on the plan on sheet S110.2A. Please provide missing information. PCI a. Detail VS5.2 Indicates that the center line of column will be eccentric to the center line of the steel beam. Please clarify if the beam has been checked for this condition. PC2 Although the response Indicates that the detail has been revised, the package does not Include the copy of the revised detail. PCI C. Detail 111S5,2 indicates that the column will be hanging from the plate girder, please clarify if this load has been included in the design of plate girder. PC21 The calculations seem to be incorrect and incomplete. Please note that the column will be in tension, and all the connecting bolts will also be in tension. If welding will be used to connect the column to the plate girder, the adequacy of the weld should also be checked, Pct d Cannot find calculations for plate girders, Please note that the plate girder calculations shall be per Allowable Stress Design (RISC 335) or LRFD Method (Appendix G). PC2 calculations for plate girder Include a section of the plate girder, this information could not be found on the drawings. Please provide the missing Information (particularly the information about welding and location of the stlfl'erler plates). S1326. Plan on sheet S1 10.2B & S1 10.2C refers to detail 8/S1.1 on grid line 1 between grid line L.9 & N.3, this does not seem to be correct reference. Please revise plan accordingly. 04/01/2005 FRI 16:49 [T% /R% NO 74931 191 019 APR. 1.2005 4 :06PM LP2R PLEASANTON NO.034 P.20i26 AaQBelle @ Vall Square M HOW Second Review - Vail, Colorado Vail Colorado LP2A Job No.: 2050114.001 April 1, 2005 Page 19 Pei C. Detail 1/S1.2 Indicates that floor will be carrying the Plaza Finish Assembly, what Is It? Cannot find this information in the Architectural plans. PC2 Please verify If the load of 2 318" pavers, 2" sand, 4" rigid insulation, 2" road base, waterproofing, 4 1 ' rigid Insulation was included in addition to the weight of concrete and steel framing was included In the dead load supported by the framing In this area. Pei. d. The plan on sheet S110.2B refers to detail 17/S4.1, sheet S4.1 does not include this detail. Other provide the missing sheet or revise the reference (see at the intersection of grid line 13.2 & N.6 and also at the intersection of grid line 15.6 & N8). Pct Detail 171S5.1 refers to plan for length of the overhang, cannot find this information on the plan. Please provide the missing information, SD28. Please revise sheet S11JA. Please note that the section out on grid line V is blank without any reference to detail and sheet number, please provide the missing Information. Pct Plan on sheet S711A refers to detail 9157.4, this seems to be In- correct reference, please revise plan accordingly. Pct Sheet S111A refers to 51SIA, but sheet SIA does not Include detail 5, there are only four details. Please provide the missing detail. SD32. Plan on sheet S111 B & S111 C refer to detail BIS1.1 (see between grid line K & L.,9 on grid line 1), this does not seem to be correct reference. Please revise plan accordingly. Pei a. The plan on sheet S1119 now refers to detail 11151.3, there Is no detail 11 on sheet S1.3, Please revise the reference or provide the missing detail. Pct Sheet S111 S has not been submitted. Pct b. The plan on sheet S114B refers to 3/S5.2 (see on line H between grid line 6.6 & 9. 1), the detail Is correct If the section out moves towards left, Please revise plan accordingly. P02 Sheet S111B has not been submitted. PC1 C. The two section cuts at Elevator #12 on sheet S111B have wrong reference. Please revise plan accordingly. PC2 Sheet S141 B has not been submitted. Pct d. Plan refers to detail 4✓S5.2 (see between grid line 14 & 16 at lower right hand corner), this does not seem to be correct reference. Please revise plan accordingly. PC2 Shoot S111B has not been submitted. Pci e. Provide missing reference on sheet S111C, (please see at the Intersection of grid line 9.9 & F.2). 04/01/2005 FRI 16:49 [T% /R% NO 74931 Q020 APR. 1.2005 4 :06PM LP2A PLEASANTON NO.034 P.21/26 ArmRells @ Val/ Square (N) Hotel Second Review - Vail, Colorado Vail Colorado LP2A .lob No,: 2050114.001 AP611, 2405 Page 20 PC2 sheet S111C has not been submitted. PC1 f. Plan on sheet 5111 C refers to 48/55,2, 17/55,2 at few locations. These are not correct references, please revise plan accordingly. PC2 sheet s111C has not been submitted. PC1 g. Plan refers to detail 12/S5.2 and 15✓S5.2 at Elevator #12 and IIIS5.2 at Elevator # 10, these are not the correct references. Please revise plan accordingly. PC2 Sheet S1 IC has not boon submitted, Pei h. Plan on sheet S11I C refers to details 10 & 11 on sheet S1.3, these are not corMct references, please revise plan accordingly. PC2 sheet S11 1C has not been submltted. SD37. Plan on sheet 5111 P refers to detail 12155.1 (see between grid line 18.3 & 20.2 on grid line D,1), the detail does not show the correct framing. Please note the deck is parallel to the wall. detail 12 shows differently. Please revise accordingly. Pct C. Plan on sheet S111D refers to detail 9/S1.4, this is not the correct reference (see on grid line 26 between grid line J.8 & K.9). Please revise plan accordingly. PC2 Sheet S111D refers to 5 /SIA, but sheet SIA does not include detail 5, there are only four details. Please provide the missing detail. Pei e, The plan on sheaf SIIID refers to detail 18IS5.2 (see between grid line 13.2 & 14 on line F,1). This does not seem to be correct reference. Please revise plan accordingly. p02 Detail Ialss.1 refers to plan for the distance of splice, the plan does not include this information. Please revise plan accordingly. SD38. Section 8 on sheet S5.1 refers to plan for locating the column from the center line of column supporting the floor, the plan on sheet S1 12A (see grid line Z3) does not include this information. Please provide the missing information. Also check plan on sheet S1 12D (grid line'YC,6). Pct The plans still do not have this Information. PC2 There are still some columns which have not been located. Please provide the missing Information, SD41. Please revise plan on sheet S1 13A, please note that the plan refers to detail 2/S5.1 (see between grid line N.8 & P and between grid line 23,2 and 24), which does not seem to be correct reference. Pei a. Plan refers to detail 13ISS.1 (see between N,2 & P on line 25.5), this does not seem to be correct reference, Please note that plan Indicates that the 04/01/2005 FRI 16:49 [T% /R% NO 74931 0 021 APR. 1.2005 4 :e6PM LP2A PLEASANTON NO.034 P.22i26 ArraBelle @ Vail Square (N) Hotel Second Review - Vail, Colorado Vail Colorado LP2A Job No.: 2050114.001 April 1, 2005 Page 21 beam Is supporUng a column from above at the edge and is supported by a column below 2'4" away from the center line of the column above. Please provide correct detail at this location. pct Sheet S5.3 Is not part of the package, please provide the missing sheet. Please note that it was not part of the original package either. SD43. Flan on sheet S113D refers to detail 13/S5.1 (see between grid line Z9 & Z10 and on N6). This does not seem to be correct reference. Please revise plan accordingly. Pct a. Plan refers to detail 13/S5.1 (see between J.4 & K.7 and between 22 & 23), this does .not seem to be correct reference. Please revise plan accordingly. Pct Revised sheet S113D showing this change was not submitted. Please provide a copy of the same. Sp53. Clarify where detail #: 7, 16 and 18 on sheet S5.1 located on plans. pct No response found. Pct The original plan (Sheet S115 -G) does not include this reference (7/S5.1) at the location Indicated in the response to the comments, if this information has been added to the plan a copy of the revised plan shall be submitted. SD54. The roof framing plans do not refer to any details, please revise plans showing details at several locations. Provide details for different framing connections and sections, Structural Calculations Review: S01. The package does not include the calculations, please provide set of calculations including (but not limited to) the following; A. The vertical load calculations including the live load reduction calculations per ISC 2003 Section 1607.9,1 stated below: The minimum uniformly distributed live loads, 4, in Table 1607.1 are permitted to be reduced according to the following provisions. 1607.9.1 General. Subject to the limitations of Sections 1607.9.1.1 through 1607,9.1.4, members for which a value of KuAT is 400 square feet (37.16m2) or more are permitted to be designed for a reduced We load in accordance with the followiulg equation; L = L o 10.25 * 15 /AK„xAr) (Equation 16-21) where: L = Reduced design live load per square foot (male') of area supported by the member - 4 - Unreduced design live load per square foot (meter) of area supported by the member (see Table 1607.1). Ku. ;-- Live load element factor (gee Table 1607.9.1). AT = Tributary area, in square feet (square meters). L shall not be less than 0.50 Lo for members supportirtg one floor and L shall not be less than 0.40 Lo for members supporting two or more floors. 04/01/2005 FRI 16:49 [T% /R% NO 74931 Q 022 APR, 1.2005 4 :07PM LPRR PLEASANTON NO.034 P.23i26 ArmB911e Q Vail Square (N) Hotel Secopd Review - Vall, Colorado Vail Colorado LP2A Job No,: 2050f 14.001 April 1, 2005 Page 22 B. Alternate calculations for the reduction of live load can be submitted per IBC 2003 Section 1607.9.1, C, Design of slab, beams, columns, retalning walls, walls, piers and their foundations. When designing the beams, please note that the distribution of floor loads shall be per I13C Section 1607.10 which is staffed below: 1607.10 Distribution of floor loads. Where uniform floor live loads are involved in the design of structural members arranged so as to create continuity, the minimum applied loads shall be the full dead loads on all spans in combination with the floor live loads on spans selected to produce the greatest effect at each location under consideration. It shall be pmvatted to reduce floor live loads in accordance with Section 1607.9. D. The interior walls exceeding 6 ft, in height shall be designed to include their finish material, shall have adequate strength to resist the loads to which they are subjected but not less than a horizontal load of 5 psf per IBC Section 1607.13. E. Provide snow load calculations per Section 7 of ASCE 7. please note that design roof load shall not be less than that determined by Section 1607. Please note that the snow load pr on the roof shall be calculated using the following formula: pr - 0.7C,CJpg (Eq. 7 -1) but not less than the following minimum values for low -slope roofs as defined in Section 7.3,4, the value of C. shall be determined from Table 7 -2, the value of C shall be determined form Table 7 -3 and the value of I shall be determined from Table 7-4 of ASCE Standard. Please note that snow that forms drifts comes from a higher roof or, either the wind from the opposite direction, from the roof on which the drift is located, the drift loads shall be superimposed on the balanced snow load. Please note that the maximum intensity of the drift surcharge load pd , equals hdy where snow density, y, is defined as under. Y = 0.13p + 14 but not more than 30 pcf. F. Provide calculations to check the adequacy of the walls as shown at detail 9, 10 and 11 on sheet S1.1. G. Provide calculations to check the adequacy of the floor to wall connection as shown at detail 9, 10 and 11 on sheet S1,1, Please note that this connection shall be designed per IBC Section 160442 as stated below: 160.8.2 Concrete and masonry walls. Concrete and masonry walls shall be anchored to floors, roofs and other strucWal elements that provide lateral support for the walL Such anchorage shall prc de a positive direct connection capable of resisting the horizontal forces speafted in this chapter but not less than a minimum Strength design horizontal force of 280 plf (4.10 kN/m) of wall, substituted for "B" in the load combinations of Section 16052 or 1605.3. Walls shall be designed to resist bending between anchors where the anchor spacing exceeds 4 feet (1219 mm). Required anchors in masonry walls of hollow units or 04/01/2005 FRI 16:49 (T% /R% NO 74931 14 023 APR. 1.2005 4 :07PM LP2A PLEASANTON NO.034 P.24i26 grraBelle vall Square (N) Hotel Second Review - Vail, Colorado Vsll Colorado LKA Job No.: 2050114.001 April f, 2005 Page 23 cavity 'w'alis shall be embedded in a reinforced grouted structural element of the wall. See Sections 1609.62.2 and 1620 for wind and earthquake design requirements. H. Provide calculations for double tee beams as shown at detail 11/S1.1, and other precast beams/Steel beams shown on sheet S4.1 /S5:1. I. Provide calculations for beam seat for double tee beams as shown at detail 11/S1.1. J. Provide calculations to check the adequacy of the embed plates as shown on sheet S2.1. K, Provide calculations to check the adequacy of the base plates as included on sheet 82.1 and elsewhere, L, Provide wind load calculations per IBC Section 1609 in accordance with Section 6 of ASCE 7. Please note that the design wind load shall be cpiculated per ASCE 7- 98, Section 6.5,12 and 6.5,13, as applicable. M. Provide Earthquake Loads calculations per IBC Section 1614. PCi a. Cannot find calculations for the following beams: Beam ,Nos: 72, PC2 Please provide out put for all beams. Pei b. The calculations on page R64 Indicate that fhe size of beam #57 shall be W1245, the plan on sheet S117C does not indicate the same. Please provide the missing Information. PC2 Revised sheet (S11IC) was not sent for revlew, please provide a copy. PCI e. The plan on sheet S117B indicates that beam number 16 shall be W21x44 (Bent). What does this mean, does it mean that the beam will have a camber, what are the details of bend. Please clarify: Pct The note does not indicate details of the bent, please provide missing Information. PCi J. Please clarify the locations for the following beams W Roof B (on page R8 through R33). Beam nos: R05, R86, R811, RB14, RB16, RB17,RB21, RB28, 8833, RB36, R837, RR41, RB43, RB41, RB48, RB49, RB53, RB551 RB561 RB57 R858 R963, R864, RB66 etc.... PC2 The response Indicates that a plan reference guide was submitted, cannot find it in the package. Please provide the missing plan. PCi p. Please clarify the location of the following beams. RC1, RC2, RC3, R06, RC7, RC14, - RC17, RC19, RC21, RC22, RC37, RC38, RC44, RC49, RC50, RC54, R069, RC71, RC72, RC74, RC78, RC88, RC89 and RC90. Cannot Find these beams on the key plans, AA /AI/9nn5 PRT 16 ,49 [T% /R% NO 74931 01 024 APR. 1.2005 4:07PM LP2A PLEASANTON NO.034 P.25i26 Arla9elle @ Vail Square (N) Hotel Second Reyiew - Vail, Colorado Va ll Colorado LP2A Job No.: 2050f 14,001 April 1, 2005 Page 24 PC2 Cannot find the key plan in the package. Please provide a copy of the same. pct Z. Cannot find location of the following beams. Beam #s; RA2, RAII, RA 92 RA21, RA2$ RA26, RA29 thm RA31, RA39, RA42, RA45, RA53 thru RA55, RA57, RA50, RA64, RA65 RA66, RA68, RA69 & RA71. Please provide the missing information, PC2 The key plan could not he found In the package, please provide a copy of the same. Pct am. Provide complete set of calculations for all floors, the calculation package includes key plan from Ram Steel, but does not include MO calculations. Provide complete package for the floor beams. Roor beams have not been checked at this time, will be done on receiving the response to these comments, PC2 Atieast provide one copy of the calculations. PC1 an. Please provide lateral calculations including the following. a, Key plan for the lateral load resisting elements at each floor of each building, b. Lateral load calculations for each building (presently the load calculations are mixed for all buildings, please arrange the calculations so that the lateral calculations of each building Is separate. The calculations are confusing. PC2 The calculations indicate that the diaphragm Is dgld, the distribution of lateral force will be proportional to the rigidity of the frame, cannot find such rigidity calculations in the package. Please clarify. Calculations shall also Include the sketches of the frames resisting the lateral loads.. SC3. Please provide calculations for the design of brace frames as shown on sheet S6.4 including the welded connections. Pci No response found, PC2 provide Include sketches showing the configuration of the frames and their connections In the calculations package, SC4, Provide caloulations for the design of tunnel as shown on sheet S8.1. pci No response found. PC2 Please Indicate the page number on Which such calculations could be found. SC5. Masonry walls which are not part of lateral- force-resisting system shall be designed per IBC Section 2106.3.1 as stated below: 21063.1 Masonry walla not VW of the laterdl fvsce- resisting system. Masonry partition walls, masonry screen walls and other Mas o nry elements that ate not designed to resist vertical or lateral loads, other than those induced by their own mass, shall be isolated from the structure so that the .,vertical and lateral forces 04/01/2005 FRI 16:49 (T% /R% NO 74931 @1025 APR. 1.2005 4 :08PM LP2A PLEASANTON NO.034 P.26i26 ArraBelle @ Vail Square (M Hotel Second Review - Vail, Colorado Vail Colorado l.P2A Job No,: 2050914.009 April 1, 2005 Page 25 are not imparted to these elements. Isolation joints and connectors between these elements and the atntcture shall be designed to accommodate the 4esign story drift, Pct No response found. PC2 Cannot find detall 2152.9 In the padcage, SC7. Provide calculations for steel columns, concrete columns and others. PCI No response found. PC2 Please Indicate the page number on which the steel column design could be found for all bulldings. SCS. Provide calculations to design the metal deck and it's welding to the framing below. Pct No response found. pct Please provide sketches of the plan showing loads for each building. SOIL & FOUNDATION COMMENTS: F4. Submit a letter from the soil engineer confirming that the foundation plan, grading plan, and specifications have been reviewed and that it has been determined that the recommendations in the soil report are properly incorporated into the plans. Pct The soil engineer's letter Is not Included In the package, Please provide a copy of the same. PC2 The soil engineer's letter is still awaited. F5. Provide calculations for the retaining walls, the retaining walls shall be designed for a safety factor of 1.5 against lateral sliding and overtuming per ISO Section 1610.2. Pc9 These calculations could not be found in the package. Please provide the calculations so that the plan review could be completed PC2 Please provide details for all the retaining walls as deigned on page RT1 through RT16 F10, Sheet C1 DID indicates that a tunnel is also a part of this project, please provide calculations and derails for the same. Pc9 No response found pee Please indicate the page number on which the calculations could be found. If you have any questions regarding the above comments, please contact Val Dizitser (x233) or Norman Hong (x224) for non - structural comments and Talat Abbasi (x222) for structural comments at 925 / 226 -1320 between 6:00 A.M. to 5:00 P.M,, M -F. [END OF COMMENTS] nAin,ignnr VOT in-AA rTX /R% NO 74931 131 026 Civil Sheets COA — COVER SHEET C3A — UTILITY DEMO PLAN C313 —TREE DEMOLITION PLAN C3C - SITE DEMO PLAN C4 — PROPSED COMCAST CATV PLAN C5A — PROPOSED HOLY CROSS ELECTRIC PLAN C513 — PROPOSED HOLY CROSS ELECTRIC PLAN C6 — PROPOSED XCEL GAS PLAN C7A — PROPOSED QWEST & VAIL RESORTS PHONE PLAN C713 — PROPOSED QWEST & VAIL RESORTS PHONE PLAN C813 — PROPOSED WATER AND SEWER PLAN C8C — PROPOSED WATER AND SEWER PLAN C81D — SANITARY SEWER & WATER PROFILES C8E — SANITARY SEWER & WATER PROFILES C9A — PROPOSED DRAINAGE PLAN C913 — PROPOSED DRAINAGE PLAN C9C— PROPOSED DRAINAGE PLAN C9D — PROPOSED DRAINAGE PROFILES C9E —PROPOSED DRAINAGE PROFILES C1 OA- PROPSED GRADING PLAN C1 013- PROPOSED GRADING PLAN C1 OE- PROPOSED SITE WALL PLAN C10E- PROPOSED SITE WALL PLAN C10G- PROPOSED SITE WALL PROFILES C11 D- LIONSHEAD PLACE, HORIZONTAL LAYOUT PLAN C12 — PROPOSED TOWN OF VAIL UTILITY TRENCH C15A -STORM DRAINAGE STRUCTURE DETAILS AND NOTES C1513- STORM DRAINAGE STRUCTURE DETAILS AND NOTES C18- HARDSCAPE AND SNOWMELT DETAILS AND NOTES Koechlein Consulting Engineers, Inc. Consulting Geotechnical Engineers 12364 W. Alameda Pkwy • Suite 115 • Lakewood, CO 80228 -2845 www.KCE- Denver.com LAKEWOOD AVON /SILVERTHORNE (303) 989 -1223 (970) 949 -6009 (303) 989 -0204 FAX (970) 949 -9223 FAX April 4, 2005 Dan Feeney Vail Resorts Development Company P.O. BOX 959 Avon, CO 81620 Subject: Plans and Specifications Review The ArraBelle At Vail Square Vail, Colorado Job No. 03 -184 As requested I have reviewed the plans and specifications for the subject project from a geotechnical perspective. Based on my review of the plans and specifications, it is my opinion that the design team has followed the geotechnical recommendations presented in our report dated July 2, 2002, Job No. 02 -058. KOECHLEIN CONSULTING ENGINEERS, INC. 1101 William H. Koechle President (3 copies sent) cc: Monroe & Newell — Craig Carroll cc: 4240 Architecture — Ali Charafeddine cc: Alpine Engineering — Glenn Palmer Memo:Charlie Davis, CBO From: Tom Kassmel, Town Engineer Re: Arrabelle Building Permit Submittal Revised Comments Date: 3/31/05, 4/5/05 response in red The Public Works Department received responses to the Public Works comments dated 3/4/05 and received a set of revised Civil plans dated 3/24/05. We have reviewed the responses and the revised Civil plans and still have the following outstanding issues that must be resolved prior to building permit. General Comments 1. Add a note to the grading plan to demo and reconstruct concert hall plaza stairs. The note shall provide the necessary rise and run to make up for the cut at the foot of the stairs or additional risers shall be added. Please provide a spot elevation at top of stairs. AEI: Completed, re: C 10B. 2. Demo limits shall include concert hall plaza stairs and the bike path in Vail's Tract A now that the sanitary sewer is going down the center of the path. AEI: Completed, re: C 3C. 3. It is assumed all utility conflicts are to be addressed during your final QC. As stated in our 3/24/05 meeting. AEI: Completed. 4. All easements shall be received, approved and recorded prior to BP approval. VR: Item will be completed prior to BP approval. 5. Utility approval signature block shall be signed prior to BP approval. AEI: Anticipated completion within next several days. Item will be completed prior to BP approval. 6. All construction staging issues shall be resolved between Shaw and TOV (Leonard Sandoval) prior to approval (i.e. ROW permit, CDPHE Permit, ACOE permits, staging plan, traffic control plan, Revocable ROW permit, bonds, etc...) Shaw: Item will be completed prior to BP approval 7. Revised shoring plans shall be provided per 2/10/05 comments. Shaw: Signed, stamped shoring shop drawings are being provided as part of supplementary plan submittal. 8. Maintenance agreements shall be in place for storm sewer and Lionshead Place prior to approval. VR: Item will be completed prior to BP approval. 9. An Additional agreement shall be in place referencing lighting, signage, irrigation, etc... as per our discussions with David Thorpe and Jay Peterson. VR: Item will be completed prior to BP approval. 10. Site plan calling out dimensions and transitions required as per 3/24/05 meeting and previous comments. AEI: Completed, re: C 11 D. 11. The inlet at Antlers entrance still needs to be moved to low point. AEI: Completed, re: C 10A. 12. Storm sewer from concert hall plaza steps shall remain completely on Tract C per VR. AEI: Completed, re: C 9B. 13. Note clearance of storm sewer over proposed tunnel. AEI: Completed, re: C 9D. 14. Provide stamped copies of Final Drainage Report, Final Pavement Design, and Civil Plans. AEI: Per directive from Charlie Davis, all supplementary material will be stamped and signed prior to BP issuance. 15. Section line A -A missing on C4 AEI: Completed, re: C 4. 16. Note that bike path in ski yard is to be reconstructed. AEI: Completed, re: C IOA and C IOB. 17. Bike path detail shall show 18" road base shoulders. AEI: Completed, re: C 18. 18. Coordinate Transformer locations /size (scale on dwgs) with the fire lane route. AEI/DHM: Completed, transformer enclosure has been revised to stay out of fire truck swept path and 2' buffer. 19. Add note to utility trench on Alpine plans indicating that irrigation and lighting will be in and branch from utility trench to each light pole and planter as needed. AEI: Completed, re: C12. 20. In regards to the internal drainage comments (garage drainage, plaza level drains, roof drains) the responses received do not clarify my initial comments. I suggest we meet to discuss this issue. At a minimum the plans need to be better coordinated. VR/Cator- Ruma/AEI: A meeting is scheduled for the week of April 11 to review this item. Item will be completed prior to BP approval. 21. A discussion regarding heats mains and zones is needed, to resolve previous comments. VR/Shaw: Item will be completed prior to BP approval. 22. All streetscape issues shall be resolved as per our 3/30/05 meeting. VR/DHM: DHM provided plans to the TOV on 3/31/05 that we believe have addressed previous comments. March 10, 2005 Charlie Davis Chief Building Official, Building Safety & Inspection Services Town of Vail 75 South Frontage Road Vail, Colorado 81657 Fax: (970) 479 -2452 Re: Plan Review: ArraBelle At Vail Square Address: Vail, Colorado Dear Mr. Davis: TOWN OF VAIL — FIRST REVIEW LP Job No.: 2050114.001 Linhart Petersen Powers Associates (LP has completed a first review of the following documents on behalf of the Town of Vail: 1. Plans: Two (2) copies each: Volume One of Four –cover through sheet A062 (61 sheets), sheets A100.1 through WP8 (283 sheets) dated ( "delta 6 ") February 15, 2005, by Hart / Howerton & 4240 Architecture, Inc. Volume Two of Four - -cover through sheet S118D (56 sheets) dated ( "delta 6 ") February 15, 2005, by Monroe & Newell, Engineers, Inc.; sheets M001 through M800.2 (146 sheets) dated ( "delta 6 ") February 15, 2005, by Cator, Ruma & Associates; sheets FS1.1 through LD1.1 (6 sheets) dated ( "delta 6 ") February 15, 2005, by Ricca Newmark Design; sheet IR -01 by Pace Industrial, Inc.; sheets VT01 through VT18 (18 sheets) dated ( "delta 6 ") February 15, 2005; sheets W000 through W604 (31 sheets) dated ( "delta 6 ") February 15, 2005, by STO Design Group, Inc. Volume Three of Four —cover through E700.10 (148 sheets) dated ( "delta 6 ") February 15, 2005, by Cator, Ruma & Associates; sheets LD.151 through LD.867D (57 sheets) dated ( "delta 6 ") February 15, 2005. Volume Four of 4 —cover through sheet ID 862.10 dated February 15, 2005, for reference. 2. Project Manuals: Four (4) copies each of Volumes 1, 2, 3, 4, 5, 6, 7 and one (1) additional copy of Volume 5 dated February 15, 2005, by 4240 Architecture, Inc. 3. Structural Calculations: One (1) bound copy each of Volume #1 and Volume #2 with various dates, by Monroe & Newell, Engineers, Inc. 4. Energy Calculations: Two (2) bound copies (Volume 8) of IECC Compliance Certificates dated February 15, 2005, by 4240 Architecture, Inc. 5. Geotechnical Report: One (1) bound copy dated July 2, 2002, by Koechlein Consulting Engineers, Inc. The 2003 International Building Code, 2003 international Mechanical Code, 2003 International Plumbing Code, 2002 National Electrical Code, 2003 International Fire Code, 2003 International Energy Conservation Code and 2003 International Fuel Gas Piping Code were used as the basis of the review. Our comments follow on the attached list. Please submit an itemized response letter and three (3) sets of complete and revised documents with all revisions clouded, directly to LP Sincerely, LINHART PETERSEN POWERS ASSOCIATES Val Dizitser, PE ICBO Plans Examiner Associate Talat Abbasi, PE Norman Hong ICBO Plans Examiner Architect Senior Associate Senior Plans Examiner NHNLDrrAA/GB p: \Vai12005\2050114.001- pc1.doc (Bin 400) Enclosures cc: Mr. Ali Charafeddine, 4240 Architecture, Inc.: Fax (303) 292 -3113 Mr. Dan Feeney, Vail Resorts Development Company: fax (970) 845 -2358 ArraBelle @ Vail Square (N) Hotel Vail Colorado March 10, 2005 First Review - Vail, Colorado LP2A Job No.: 2050114.001 Page 2 Following are comments for the first review of the ArraBelle project. Please note that there are also comments requiring further response from the second review of preliminary documents dated December 7, 2004. The format includes a restatement of any previous comments followed by the applicant's response. Current new or re -check comments are shown in a separate bold italicized paragraph.. Re: Occupancy Groups: R -1, R -2, S -1, S -2, A -2, A -3, B, M Type of Construction: IB Stories: Seven and two garage levels Sprinklers: Yes Building Area (sq. ft.): 539,663 MECHANICAL, PLUMBING, ELECTRICAL COMMENTS: Mechanical: 114 For -garage ventilation: D. If garage fans area not operating continuously confirm that carbon monoxide detectors have capacity to maintain a maximum average concentration of carbon monoxide concentration of not greater than 25 parts per million. Applicant's Response: Carbon monoxide detectors will be installed in the garage to control CO concentrations to less than 25 PPM. Provide location of CO sensors in the garage as specified in the response. IMC 404.1. Response indicates revise complying drawings will be submitted. (417105) CO Sensors are shown on sheets M110.1A, M110.1B, M110.1C, M110.1 D, M110.2C and M110.2D, which were issued under the first set of responses dated 3123105. 124. Type I Hood: Additional comment: Response indicates that the hood sizing, fire suppression and hood clearances are the responsibility of the kitchen consultant and will appear on the kitchen plans to be submitted later. Provide note on plan Response indicates revise complying drawings will be submitted. (417105) A note was added to address this comment on Sheets M110.2B and M111.B, which were issued under the first set of responses dated 3123105. ArraBelle @ Vail Square (N) Hotel First Review - Vail, Colorado Vail Colorado LP2A Job No.: 2050114.001 March 10, 2005 Page 3 ; (2) Provide specification for the make -up air unit will provide an equal amount to the amount exhausted. Response indicates revise complying drawings will be submitted. (417105) A note was added to the AHU schedule to address this comment. Reference sketches MSK01 and MSK02 dated 417105, attached to this response. (3) , Specify on plan vertical distance between lip of hood and cooking surface to not more than four (4) feet. IMC 507.12. Response states revise drawings will be submitted. (417105) Please see new kitchen hood detail sheets, FS -7.1, 7.2, 7.6, 7.7, 7.8 and 7.9. Issued 3130105, but included in this response. (4)'� Specify exhaust outlet termination serving Type I hood is not less than 10 feet horizontally from any part of the building and air intake openings. /PC 506.3.12.3. Response states revise drawings will be submitted. (417105) See page 14 of specification section 15851, attached to this response. (5) " Provide typical detail for the construction of the fire resistive duct enclosure per /PC 506.3.10.. Response states revise drawings will be submitted. (417105) Please see architectural sketches ASK -512 1 of 2 and 2 of 2, originally dated 3124105, and reissued herewith, dated 04107105. The details reference shaft floor and roof terminations. The actual shaft wall is architectural detail W, Sheet A501. 133. Provide a refrigeration machinery room for the refrigeration system complying with several requirements such as ventilation, refrigerant detectors, discharge location, make -up air, etc. per IMC sections 1105, 1106, 1107 & 1108. (a) Specify all exit doors from machinery room to swing in the direction of travel and shall be tight fitting and self - closing per IBC 1014.4. Sheets M110.1 B & M110.2D. Response states revise drawings will be submitted. (417105) Please see architectural sketches ASK -A 110.1 B 1 of 3 and 2 of 3, originally dated 3124105, and reissued herewith, dated 04107105. The doors are specified in the door schedule as fire rated doors with closers and smoke seals (hardware set no. 69). re) f Provide confirmation that exhaust from mechanical ventilation is not less than 20 feet from openings into building. /PC 1105.6.1. ArraBelle @ Vail Square (N) Hotel First Review - Vail, Colorado Vail Colorado LP2A Job No.: 2050114.001 March 10, 2005 Page 4 Response states revise drawings will be submitted. (417105) Reference sketches MSK -05, MSK -07, MSK -09, MSK -15, MSK -16, MSK -17, MSK -18, MSK -19, and MSK -20 dated 417105, and attached to this response. ,s (d) Specify clearly identified switch for the emergency purge ventilation to be in a break -glass type providing on -only control. IMC 1106.5.2 Response states revise drawings will be submitted. (417105) Drawings M110.1 B and M110.2D were issued under the first set of responses dated 3123105. The keynotes on these drawings include the required specification. (e/ Specify a clearly identified switch of break -glass type providing off only control of electrically energized equipment/devices within the refrigeration machinery room and to be provided immediately adjacent to and outside of each refrigeration machinery room exit. IMC 1106.5.1. Response states revise drawings will be submitted. (417105) Drawings M110.1 B and M1110.2D were issued under the first set of responses dated 3123105. The keynotes on these drawings include the required specification. ( Specify approved emergency signs, charts, labels in accordance with the International Fire Code for the refrigeration units and systems. IMC 1106.6. Response states revise drawings will be submitted. (417105) Drawings M110.1 B and M110.2D were issued under the first set of responses dated 3123105. The keynotes on these drawings include the required specification. s (g) Because the machinery room G155 is more than 1,000 sf provide two exits 'separated = to % of the maximum horizontal dimension of the room per IBC 1014.4. Sheet M110.2D. Response states revise drawings will be submitted. (417105) Please see architectural sketch A SKI 10.1 D dated 04107105 for additional exit meeting the required minimum separation distance, and for correction of door swings. Additional mechanical comments: M1. Provide complete mechanical plans and details at level 5, areas A, B, C & D where duct layout and duct sizes were missing. Sheets MI 16.A through MI 16.D. ArraBelle @ Vail Square (N) Hotel First Review - Vail, Colorado Vail Colorado LP2A Job No.: 2050114.001 March 10, 2005 Page 5 Response states revised drawings will be submitted. (417105) Drawings M115.A, M115.B, M115.C, and M115.D were issued under the first set of responses dated 3123105. M2: Specify exhaust termination of exhaust outlets serving Type I hoods to have the discharge outlet located not less than 40 inches above the roof surface. IMC 506.3.11.1. sheet M117.B. Response states revise specification will be submitted. (417105) See page 14 of specification section 15851, attached. N13. Provide continuation of 6" duct to upper level for bathroom exhaust of bathroom G205. Sheet M110.A. Response states revise drawings will be submitted. (417105) The routing was clarified on Drawing M110.A, which was issued under the first set of responses dated 3123105. W. Clarify outside air supply detail for the 72x30 duct to boiler room. It is not clear how -' outside air will flow through this duct. Sheet M111 C. Response states revise drawings will be submitted. (4/7/05) The outside air was clarified on Drawing M111.C, which was issued under the first set of responses dated 3123105. M5. Provide continuation of garage exhaust duct located at grid lines D.1 & 2 1. 9 on sheet M110.1D to the upper garage level. Resonse states revise drawings will be submitted. (417105) Drawing M110.1D was issued with the duct in question removed issued under the first set of responses dated 3123105. . r� M6. Provide installation detail and listing (e.g. UL 555C) for the horizontally installed combination fire /smoke dampers on the plan. Sheet M600.1. Response states revise drawings will be submitted. (417105) As stated previously, there will not be any horizontal FSD installations. The elbow into the bottom of the shaft would hamper access to the FSD. The shaft enclosures will be coordinated with the architect to install vertical FSD. M8. For the ski instructor locker room (G 102.05: ArraBelle @ Vail Square (N) Hotel Vail Colorado March 10, 2005 First Review - Vail, Colorado LP2A Job No.: 2050114.001 Page 6 Outdoor air flow supply is not adequate for an area of 2,261sf. Per I _ - 403. locker rooms requires a minimum of 0.5 cfm /sf therefore 2261 x 0.5 1131 cfm. total supply cfm shown on sheet M110.2A is only 250x 4 = 1000 cfm. - - A020.2. Response states revise drawings will be submitted. (417105) The outside air flow rate was shown on Drawing M14 1 0.2A, which was issued under the first set of responses dated 3123105. (b)" Recirculation of air from this space is prohibited per footnote b of /MC table 403.3. Delete 24x 12 transfer air duct to public storage G 101. Sheet M1 10.2A. Response indicates using footnote g of table 403.3 but footnote g is applicable to shower room only not for locker room. (417105) The transfer duct is deleted. Reference sketch MSK14 dated 417105, attached to this response. M9." 9 Identify exhaust fan labeled EF -xx located near grid lines 12.2 & S.3. Sheet M110.2B. Response states revise drawings will be submitted. (417105) The fan tag was shown on Drawing M110.2B, which was issued under the first set of responses dated 3123105. M12" on the air handling unit schedule sheet M002.1 AHU -4 unit for the mechanical room G117. Sheet M110.2B. Response states revise drawings will be submitted. (417105) The unit is mislabeled, it is MUA -4, not AHU -4. The tag was changed on Drawing M110.2B, which was issued under the first set of responses dated 3123105. M15. ­ Specify make -up air opening not less than 100 square inches at the door of the dryer enclosure. IMC 504.5. Response states revise drawings will be submitted. (417105) Reference sketch MSK13 dated 417105, attached to this response. M16. Typical for all hotel rooms and tenant spaces levels 2 through 7. (2) Confirm all ducts penetrating fire partition walls separating tenant spaces and corridor are constructed of steel of not less than 0.019 —inch to comply with exception 2 of IBC 716.5.4.1. Response states revise drawings will be submitted. (417105) Reference sketch MSK03 dated 417105, attached to this response. ArraBelle @ Vail Square (N) Hotel Vail Colorado March 10, 2005 Plumbing: P3. For the Boilers First Review - Vail, Colorado LP2A Job No.: 2050114.001 Page 7 (2) Provide note on plan that upon completion of the assembly and installation of the boilers acceptance test shall be conducted in accordance with the requirements of the ASME Boiler and Pressure Vessel Code. A copy shall be submitted to the field Inspector. IMC 1011.1. Response states revise drawings will be submitted. (417105) A note addressing this item was added to Drawing M110.1B, which was issued under the first set of responses dated 3123105. (3) Provide detail Showing relief valve discharge piping of boiler through an indirect waste pipe by means of an air break or air gap. Sheet M600.21boiler detail, /PC 802.1.5. Response states revise drawings will be submitted. (417105) Reference sketch MSK03 dated 417105, attached to this response. Provide confirmation that no steam or water with temperature greater than140 degree F is discharging into the waste receptor connected to the drainage system. A means of cooling the waste to 140 degree F or below should be provided or special piping material must be specified. Sheet M600.21boiler detail, /PC 803.1. Response states revise drawings will be submitted. (417105) Reference sketch MSK03 dated 417105, attached to this response. Electrical Comments: E1. Indicate the locations for load centers in the condo units. The only plans that show the load centers are the Reference Electrical Plans and they indicate panels located in clothes closets. Article 240.24 (D) prohibits panels being located in clothes closets. Condo load centers will be relocated flush in wall behind entry door, or flush in wall behind secondary entry door where available. (417105) Drawings E102 — E107 have been re- issued with revised locations for condo unit load centers. E2. Provide panel schedules for the condo units. See E700.11 (new drawing) for typical condo panel schedules, shown for circuit breaker quantity and size only. Panel calculated service and feeder load is indicated on drawing E600.4, based on loads and demand factors as described in NEC 220 (B). E3. Provide a note on the plans that all conduits passing through the walls, ceilings or floors of the cooler /freezer units shall be sealed per Article 300 -7. ArraBelle @ Vail Square (N) Hotel First Review - Vail, Colorado Vail Colorado LP2A Job No.: 2050114.001 March 10, 2005 Page 8 This note appears in the Kitchen Plan Notes on drawing E002.2. E4. Provide a note on the plans that all underground service conduits shall be sealed per Article 230.8. This note appears in the General Notes on drawing E003. E5. Provide a note on the plans that the service Ground Fault Protection shall be Performance Tested per Article 230.95 (C). See ESK- E600.1, reference 1 of 1, ESK- 600.2, reference 1of 1, and ESK- 600.3, reference 1 of 1 for additional general note. ENERGY CONSERVATION COMMENTS: EGA:" The submitted calculation does not appear to include the compliance certificate requirements for the residential portion of the project. Clarify if the activity type designated "others "represents the residential area. No response submitted. (417105) The 2003 version of COM Check does not recognize input of residential areas. The residential portions of the building were input under the area type "others" [END OF COMMENTS] {=0>2 � SECTION 15851 AIR HANDLING FANS Procedures and schedules related to start -up and shutdown, troubleshooting, servicing, preventative maintenance, and how to obtain replacement parts. 2. Familiarization with contents of Operating and Maintenance Manuals specified in Division 1 Section "Project Closeout" and Division 15 Section "Basic Mechanical Requirements." B. Schedule training with at least 7 days' advance notice. C. The outlet termination of all grease fans serving type I hoods shall be no less than 10 feet horizontally from any part of the building and air intake openings. The outlets shall also discharge no less than 40 In ches above the roof surface. END OF SECTION 15851 �C �1M l CTS Lq Air Handling Fans 15851-14 The ArraBelle at Vail Square Vail, Colorado 15 February 2005 vej Q 9 g 6 0 7 LL � W z C. J C. w C t- Q < 3 c O ° U ° U ❑ u w I z � W 1 LL C 0 F CO u x:I! = F -:3 C 3w C c OM 2 Uw C ai a C Ux c Z() 2 Np a C; U❑ 2 Z a W 2 m I ❑ a J a o zo. a au� a w wJ ❑ 20 CO 'a C7 y W Z W ❑ J > 00 z IY U i1. a vi -j a : 2u) O ❑ xV U z a Za z a-� -, 0 O ii WO =U U H a s m x r2 z_ D W J ~? ❑ aWk N 0 �w ❑ x OF m Q Q IX W LL. U F.. x 3 OLL N 3 550E xa z Qx O :3 I- a 2QQ O F2 O w0 0 3w N w 2 W — M N T r O M aM22 Architect of Record The ArraBelle U W 424 ~— at Vail Square °�� No: MSKO1 Denver, Colorado Owner /Developer � u002.1 SM' PEWrr REV MEP Engineers (Mechanical) Vail Resorts DAM 03/24/05 Cator, Ruma and Associates, co. Development Company NONE Denver, Colorado Avon, Colorado DRM BY. HDY = w LL � LL TH-- ? Q W U O - C7 C7 O 0 C7 C7 (� C7 C7 O C7 C7 0 U 0 0 a 0 Q > Z Z Z Z Z Z Z Z 2 w a s O O a w a w O 0 a w O O a O O Q w o 0 a w O 0 a w 0 O a w O O a w O O a w O a w O 0 a 0 U x x U x U U x U s U x U x U x U x s U w x 0 U Z O_ ~ �° w . m O >N z a x N N M r r r N N r a a J Zw � a w LL x 30 rn J LU Z a LL = 3 ❑ z a tU J LL jL W F M M •f M M M M M N M N N Z Q ci (L 3i ~ 2i 0 N a G a O O C2. O O O O O O O O IL CO U O �... O O O N N O O O O O O O O o lrt O O N O O a ," ," r r N r N 0 Q '� o o ° 0 0 0 0 0 o O o LL F op O O p O O O O O O O O ° U O F - Q N N e ln CD C3 C] O N N O r r G N J W ❑ O a a U F O tnO ac J W W W J W W W J J J d' Z W O N❑ x LLI O N y F. ? z w2 _ 0 O IL w w 3 O W 00 1_ t- x Y f- w IY W Ix W w O m� F y J Y Y m w w z w z 0 w z w z w z w z w z w z w z w z w z w Z LL a a a a a a a a a a a a a tr tr a tY F- F- tr a tY K N C, v to tp C, Q L W o a a 0 z vej Q 9 g 6 0 7 LL � W z C. J C. w C t- Q < 3 c O ° U ° U ❑ u w I z � W 1 LL C 0 F CO u x:I! = F -:3 C 3w C c OM 2 Uw C ai a C Ux c Z() 2 Np a C; U❑ 2 Z a W 2 m I ❑ a J a o zo. a au� a w wJ ❑ 20 CO 'a C7 y W Z W ❑ J > 00 z IY U i1. a vi -j a : 2u) O ❑ xV U z a Za z a-� -, 0 O ii WO =U U H a s m x r2 z_ D W J ~? ❑ aWk N 0 �w ❑ x OF m Q Q IX W LL. U F.. x 3 OLL N 3 550E xa z Qx O :3 I- a 2QQ O F2 O w0 0 3w N w 2 W — M N T r O M aM22 Architect of Record The ArraBelle 424 ~— at Vail Square °�� No: MSKO1 Denver, Colorado Owner /Developer � u002.1 SM' PEWrr REV MEP Engineers (Mechanical) Vail Resorts DAM 03/24/05 Cator, Ruma and Associates, co. Development Company NONE Denver, Colorado Avon, Colorado DRM BY. HDY C-4 1 N 1 W 0 U ° a 0 J 04 N J 0 Uj Z J z a =1 A Architect of Record The ArraBelle 4 at Vail Square °�� No: MSK02 Denver, Colorado Owner / Developer M002.1 WX' PERMIT REV MEP Engineers (Mechanical) Vail Resorts WE 03/24/04 Cator, Ruma and Associates, co. Development Company S'�: NONE Denver, Colorado Avon, Colorado ORW OP HDY � �I Hui M111110111111111 I �I 6 � Sol 1211 � 1 I 1 A Architect of Record The ArraBelle 4 at Vail Square °�� No: MSK02 Denver, Colorado Owner / Developer M002.1 WX' PERMIT REV MEP Engineers (Mechanical) Vail Resorts WE 03/24/04 Cator, Ruma and Associates, co. Development Company S'�: NONE Denver, Colorado Avon, Colorado ORW OP HDY U7 CL 2 D IL J O U O Z Q : :f 2 ❑0 MECHANICAL GENERAL NOTES: 1. ALL NATURAL GAS PRESSURE REGULATORS SHALL BE INSTALLED IN AN ACCESSIBLE LOCATION. 2 INDEPENDENTLY VENT ALL PRESSURE REGULATORS REQUIRING VENTS OUTSIDE THE BUILDING. TH( REGULATORS EQUIPPED AND LABELED FOR UTILIZATION WITH VENT LIMITING DEVICES INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS DO NOT NEED VENT PIPING. 3. ALL DUCTS PENETRATING FIRE PARTITION WALLS SEPARATING THE CONDOMINIUMS/HOTEL ROOMS I CORRIDORS SHALL BE CONSTRUCTED OF STEEL. NO LESS THAN 0.019 INCH THICK. PLUMBING GENERAL NOTES: 1, NO AIR ADMITTANCE VALVES SHALL BE USED ON THE PROJECT. DELETE ALL REFERENCE TO THE VALVES ON THE PLANS. 2. INDIVIDUAL AND BRANCH VENTS WITH A DEVELOPED LENGTH MORE THAN 40 FEET SHALL BE INCREASED ONE PIPE SIZE 3. PROVIDE A CLEANOUT AT THE FOOT VENT OF ALL ISLAND VENTING SYSTEMS. 4. INDIRECT WASTES FROM BOILER RELIEF VALVES SHALL TERMINATE AT A FLOOR SINK WITH AN AIR C AS REQUIRED BY THE INTERNATIONAL PLUMBING CODE 5. BRANCH PIPING TO FLOOR SINKS THAT RECEIVE DISCHARGE FROM BOILER RELIEF VALVES SHALL BE DUCTILE CAST IRON. ge-"M-4f4 q 1-1 /05- Architect of Record The ArraBelle 4 at Vail Square °RAwINC No- MSK03 -- Denver, Colorado Owner / Developer rffeem. wool MM* PERMIT REV MEP Engineers MECHANICAL Vail Resorts DATE 0 Cator, Ruma and Associates, co. Development Company 1 8'3/2�4/05 SCALE' 0 1 � Denver, Colorado Avon, Colorado DRAwN BY' HDY 0 Y N M N I M O O N / M O O N H U W d' a Architect of Record The ArraBelle 4' 2 4 0 - � at Vail Square °�'�^ M SK05 Denver, Colorado Owner /Developer INSEM' MI 12.B WE PERW REV MEP Engineers (Mechanical) Vail Resorts ah: �4 07/05 Cator, Ruma and Associates, co. Development Company scxE: 1 e'�t' —o' Denver, Colorado Avon, Colorado Y a a - C-4 C \«? \ \ ,11'•'I ��� �, Y BOA= M O O N U W a d' a Architect of Record The ArraBelle 4 at Vail Square URAMANG No. MSK07 Denver, Colorado Owner /Developer REFFABJCE M1 13.B PERW REV MEP Engineers (Mechanical) Vail Resorts 04 5 Cator, Ruma and Associates, co. Development Company Denver, Colorado Avon, Colorado pp gr* D Y 0, Y N Architect of Record The A 4 —�� at Vail Square wim Ho: MSK09 Denver, Colorado Owner /Developer WEROM M114.6 MM- PERMIT REV MEP Engineers (mechanical) Vail Resorts alE � 070$ Cator, Ruma and Associates, co. Development Company SORE= 1 BLV_O" Denver, Colorado Avon, Colorado DWM BY: D Y Q Q o 0 --- 1 05- Architect of Record The ArraBelle at Vail Square mwNG w. MSK13 Denver, Colorado Owner /Developer REFERF?IM* M1 M PER MR REV MEP Engineers (Mechanical) Vail Resorts DALE 03 24/05 Cator, Ruma and Associates, co. Development Company 9011E 1 ���� -0. Denver, Colorado Avon, Colorado MW W. CDB 6 7 n g Architect of Record _ The A 4 — at Vail Square °"� M SK14 Denver, Colorado Owner /Developer aEo�: M »o.2A ME' PERM REV MEP Engineers (Mechanical) Vail Resorts am- Cator, Ruma and Assoc>ates, co. Development Company 77/05 ME t.t Denver, Colorado Avon, Colorado W. M N O O _ o M O N N f- U W Z3 a d Architect Ocord The ArraBelle — � at Vail Square o�►wiNG N; MSK15 Denver, Colorado Owner /Developer REPSUCE: MII&D ISSLIE POW MV MEP Engineers (Mechanical) Vail Resorts a17E: 04 0708 Cator, Ruma and Associates, co. Development Company SCALE: i 40v 0� Denver, Colorado Avon, Colorado ORAIMI) N' D Y ^ M N / p I O O \ I D I cli W) �� O to n U 0 O a a Architect of Record The ArraBelle 4 -- at Vail Square °��"� "�� MSK16 Denver, Colorado Owner /Developer REFERENCE: M1 17.B MM* PERMR REV MEP Engineers (Mechanical) Vail Resorts DAT 04 07/py Cator, Ruma and Associates, co. Development Company SME 1 8' - 1' - 0' Denver, Colorado Avon, Colorado ORM B ' Y Architect of Record The ArraBelle x'2' at Vail Square MSK17 �%- Denver, Colorado Owner / Developer NTEW C * MI I &B WE' PERW REV MEP Engineers (Mechanical) Vail Resorts DA7Ea 04/07/05 Cator, Ruma and Associates, co. Development Company SrA 1/ 8 - 1 - 0 - Denver, Colorado Avon, Colorado DRNNN R KY Y N Architect of Record The ArraBelle 4 ----- at Vail Square °�� MSK18 %- Denver, Colorado Owner / Developer M7EMUCE A1115.8 WM* PERM[? REV MEP Engineers (Mechanical) Vail Resorts DATE 04 07 05 Cator, Ruma and Associates, co. Development Company cry c• 1 8k.V_.0' Denver, Colorado Avon, Colorado MM W. D Y Q Q Q 0 Archie , O cord The ArraBelle 4!4 —~— at Vail Square pww w- MSK19 Denver, Colorado Owner / Developers REFEAOiCE M111.B PEAR REV MEP Engineers (Mechanical) Vail Resorts WX- N 07/05 Cator, Ruma and Associates, co. Development Company SM& � 8� _.O Denver, Colorado Avon, Colorado OWN W. D Y Q o Q Architect of Record The ArraBelle 4 - at Vail Square °�� Ho: MSK20 -� Denver, Colorado Owner /Developer FEFFHDiCE: MI 10.2B SM PERMR REV I MEP Engineers (Mechanical) Vail Resorts DATE 04 Cator, Ruma and Associates, co. Development Company s0uE 1/8-1-0 Denver, Colorado Avon, Colorado DRAWN BY DLY ArraBelle at Vail Square Responses to 2" Round Architectural Comments of April 1, 2005 Submitted by Steve Roberts, 4240 Architecture ph. 303.292.3388 15.1: Please see updated sheet A050 dated 04.07.05. Accessible routes have been added to the drawing to suggest particular paths within the larger accessible paved plaza area. Please note accessible exit paths to the public way that do not require use of the stairs in the walkway of the east yard. Exit discharge from Stair 1 and from doorways at Portico P108 and everywhere along the south side of the building is provided access to the public way, either by way of a route to the bike path in the Ski yard or by way of a route moving west along the south side of the building to the entrance plaza in front of the Porte Cochere. Please also note that the entire shaded area on the plan is accessible. 15.2: Please see updated sheet A050 dated 04.07.05. The existing bridge and the bike path are labeled. The alignment of the bike path shown on the drawing is proposed. The Town of Vail Building Official has noted that the bike path at the ski yard is a public way from the Town's perspective, and intends to send confirmation of this to LP2A under separate cover, no later than receipt of this package of responses. Where linked to the accessible building plaza, the bike path is accessible, per spot elevations noted on the path. 15.3: Please see the accessible route at Zone 7 on updated sheet A050 dated 04.07.05 that leads to public ways at either the Porte Cochere to the west or the Ski Yard bike path to the east. 21. Please see copy of updated AMR PRJ04- 0233 -2 page 5, attached here with other architectural sketches, with occupant loads now corresponding to Sheet A031 (in the Feb.15 Permit & Bid Package - not issued here). 26: Please note the Town of Vail Building Official intends to send a notice of approval to LP2A under separate cover, no later than receipt of this package of responses. Elevations showing emergency escape and rescue windows were submitted March 30 and are resubmitted with this package of responses dated 04.07.05. Please see elevation Sheets A211 through A223. 40. The required revision was actually shown on Sheet A021, Code Summary Level 1, submitted on March 24, but the wrong sheet was referenced in the original answer. Please find attached sketch ASK 101 dated 04.07.05 showing the correction. 41.1. A sketch of Sheet A111 C was inadvertently left out of the package of responses sent March 24. Please see attached sketch ASK - 111 C dated 04.07.05, which is now included for reference. 41.2. Please note a sketch from sheet A051 (ASK —051, 1 of 2, 3.24.05) was included with the return submittal of March 24, which was intended to convey the required information. However, please see attached new sketch ASK -051 dated 04.07.05, showing more context than the original sketch. Two separate accessible paths of egress are shown from all portions of the spa that are accessible. 41.3. Please see attached sketch ASK - 111 C, dated 04.07.05 for required ramp corrections. 101 Please note a sketch from sheet A051 (ASK —051, 2 of 2, 3.24.05) was included with the return submittal of March 24, which was intended to convey the required information. However, please see attached Sheet A050 dated 04.07.05, which more clearly shows the intended accessible route to the north stairs of the ice rink. It is intended that the accessible route from the north pedestrian portal connect to public elevator number 10, then through Outdoor Vestibule P141, and from there to the ramp on the west side of the ice rink. 55. Please note the Town of Vail Building Official intends to send a notice of approval to LP2A under separate cover, no later than receipt of this package of responses. 67. Please see sketch ASK - 027 dated 04.07.05. As Corridor P701 is solely intended for egress and is not intended as a path of access to the upper floor of the three adjoining condos, it is our intent to identify it as an exit passageway in the means of egress system from that floor level of the condos. The fire resistive rating of the walls of the corridor is revised to show a 1 -hour fire barrier, as required per IBC Section 1020.3 Z{� Please see all elevation Sheets A211 through A223 dated 04.07.05. General notes have been expanded to clarify our understanding of the use of materials on all exterior facades of the building as discussed and approved by the TOV Building Official and Fire Marshall on March 28. Sprinkler coverage, intended to provide equivalency to the use of fully non - combustible materials, has been added to specific balconies per suggestion of the Fire Marshal and Building Official to allow for their approval of fire retardant treated wood trim greater than 40 ft above grade in those areas. Please note the Town of Vail Building Official intends to send a notice of agreement to LP2A under separate cover, no later than receipt of this package of responses. Also please note sprinkler coverage listed on sheet A218 at the courtyard GlockenspeiUClock Tower. As originally discussed with the Building Official and Fire Marshall on March 28, noncombustible fiber cement board was to be provided at this location above 40 ft above grade. However, the eaves are much deeper at this location than was understood on the drawings at that time. Therefore, the design team wishes to ask for agreement from the Building Official and the Fire Marshall to allow sprinkler protection (from the eaves) for fire retardant treated wood timber and trim noted in this area, in lieu of noncombustible material. The reason for this request is due to the very public nature of the Glockenspeil, and the intent to provide authenticity of materials for what will truly be a unique landmark experience in this region of the country. 76.1. Please see updated Window Schedule dated April 7, 2005, attached here with other architectural sketches. Please see notes that have been added to the heading of the schedule to cross reference window types and materials to the appropriate details and specifications. 76.2. As we understand the requirements of IBC Sections 704.8, 704.9, 704.10, and 704.12, fire window assemblies are not required at any exterior openings, principally due to automatic sprinkler protection provided throughout the building. Interior courtyard openings also do not require opening protection since the project is defined as a single building on Sheet A004, under Code Note Item 11.6 (not included here) and since courtyard dimensions conform to the minimum requirements of Section 1206. 76.3. Please see all elevation Sheets A211 through A223 included with this response dated 04.07.05 for designations of all openable windows. For residential spaces requiring natural ventilation, please see the worksheet dated April 6, 2005, attached here with other architectural sketches. Please note the response to mechanical comment M7, from March 24, 2005, that provides a tabulation of requirements for mechanically ventilated spaces. 80. A sketch of detail 6 on sheet A708 containing the requested information was inadvertently not included with the responses issued March 24, and is issued here as Sketch ASK — 708, dated April 7, 2005 rS111 Response (3- 30 -05): A smoke control management specification developed in June 2004, providing detailed criteria for the system design in each pressurized shaft, is being rechecked with the current building configuration and will be issued with calculations and drawings under separate cover. Additional Response (04- 07 -05): The Town of Vail Building Official has determined that the smoke management specification calculations and drawings may be issued as a deferred submittal. Please see attached sketch ASK — 004 dated 04.07.05 for addition of this s -red submittals list. Please note the Building Official intends to send confirmation of this arrangement to LP2A under separate cover, no later than receipt of this package of responses. 93A. Response (3- 30 -05): Roof access was reviewed on March 28. Please see updated Sheet A028 for additional roof hatches added at Stairs 2 and 11. It is our understanding that roof access will meet Fire Dept requirements as shown in this revised sketch, which is now submitted for review. Additional Response (04- 07 -05): Please see sheet A028 included with this response, dated 04.07.05. Please note the Building Official intends to send confirmation of the Fire Department's agreement with the location and size of roof access features to LP2A under separate cover, no later than receipt of this package of responses. 9313. Please see the response to Item Numbers 15.1 and 15.3 above. Accessible paths to the doorways fronting the east yard walkway do not cross the several flights of steps in the walkway. It is intended that general public circulation to those doorways and to the ski yard is to be drawn through the building courtyard from the east pedestrian portal, along the accessible routes diagramed, and that the east walkway is intended to provide very secondary access. Further, the elevator no. 6 vestibule that opens to this walkway is intended as a link for deliveries from the loading dock at the lower garage level to businesses throughout the pedestrian mall. 93D. Response (3- 30 -05): Please see sketch ASK -AO41 dated 3- 24 -05, with 10 -0" drive lane widths at each side of the control gate island. Additional Response (04- 07 -05): The above referenced sketch is reissued here with the correct sketch title: ASK— A110.1 H, dated 04.07.05. Please note the Town of Vail Building Official intends to send a notice of agreement to LP2A under separate cover, no later than receipt of this package of responses. 951. In the March 28 meeting with the Building Official and the Fire Marshall, it was determined that sprinkler protection at the opening, aligned with the property line, could provide adequate protection under this unique circumstance. The Building Official intends to send a notice of agreement with the basic design solutions to LP2A under separate cover, no later than receipt of this package of responses. DA7. Please see the response to Item Number 93B above. DA11. Please note the exception number to IBC 1007.3 was mis- referenced to exception number 2 in the March 24 responses. The correct exception reference is number 3, which states that areas of refuge are not required at exit stairways, provided the building is fully sprinklered as noted. DAl2. Please note the exception number to IBC 1007.3 was mis- referenced to exception number 2 in the March 24 responses. The correct exception reference is number 3, which states that areas of refuge are not required at exit stairways, provided the building is fully sprinklered as noted. DA13. Please note the exception number to IBC 1007.3 was mis- referenced to exception number 2 in the March 24 responses. The correct exception reference is number 3, which states that areas of refuge are not required at exit stairways, provided the building is fully sprinklered as noted. DA45. Please see Sheet A051 included with this response dated 04.07.05. A summary of the number of required Type `A" and Type "B" condos is provided. DA46. Please see Sheet A051 included with this response dated 04.07.05. A summary of the number of required Type `A" and Type "B" lockoffs is provided. Pleas note lockoffs are considered integral with hotel room accommodations and are therefore not listed with separate requirements apart from the hotel rooms. ROLF JENSEN & ASSOCIATES, INC THE ARRABELLE AT VAIL SQUARE AM /MOU PRJ04 -0233 -2 VAIL, COLORADO PAGE 5 D32909 February 7, 2005 2. The comparison of actual egress width to required egress width for each Plaza exit is provided in the table below: Plaza Exit Actual Egress Population Required Width Actual Width East Portal 1,509 18' -11" 0.15" /occ. 23' -6" West Portal 960 1 ' -0" 0.15 "/occ. 12'-6" South Ski Yard 1,5Q8 18' -11" 0.15 " /occ. 24' -0" North Stair 300 5'-T 0.20 " /occ. 7' -0" Northeast Stair around Ice Rink 390 6'" (0.20" /occ.) 7' -0" Northwest routs around Ice Rink Ramp: Stair: 520 ........_. 6' -6' (0.15" /occ.) 7' 4' ' -0" f- p" 0.20 " /occ. Total 5187 67' -1 ' 80' -0" In all cases the Required Width < Actual Width. Also, the loss of any one exit does not reduce the available capacity to less than 50% of the required capacity. 3. The unobstructed width of the Egress Court will comply with the code requirements to a height of 7 feet. This width will be permanently defined by the Plaza Egress Easement approved drawing. Requirements for doors and nonstructural projections for 7 feet above the court floor will be complied with. Deletes: 8a Deleted: 9 {Deleted: o - Deleted: 800 Deleted: 0 Deleted: 84 Deleted. 9 D 0 Deleted: 3 Deleted: 36 Deleted: 7 Deleted: 36 D: 5 d: 7 _ - Deleted: stair Deleted: 336 Deleted: 5 Deleted: 7 neleted. 7 Deleted: 4 976 Deleted: 6 4. Where the Egress Court width exceeds the minimum I Deleted0 5 required egress width and the width is reduced along the path of exit travel, the reduction will be gradual and will be defined by building exterior walls on the Plaza Level. 5. The Egress Court width is more than 10 feet in all areas. In addition to the minimum code requirements the design will consist of automatic sprinkler protection at the ceiling of the East and West Portal exits from the Plaza as well as — Off —Site Fabrication inspection: Pre —cast concrete. Per IBC Section 1704.2 — Steel Construction welds, cuts and high— strength bolting. Per IBC Section 1704.3 — Concrete Construction. Per IBC Section 1704.4 — Masonry construction. Per IBC Section 1704.5 — Soils. Per IBC Section 1704.7 — Piles /piers (shoring). Per IBC Section 1704.8 — Spray fire — resistont materials (fire — proofing steel and floors). Per IBC Section 1704.11 — Special Cases. Per IBC Section 1704.13: Smoke management systems — Sprinkler per NFPA 13, and Alarm tests per NFPA 72. Final tests are required to be preformed by the contractor of record and documentation of each test shall be submitted to the Fire Department at the time of final inspection request of each of the systems. No additional special inspector is required for these systems. — Elevator hoistways will be permitted, assessed fees and inspected by NWCOG elevator inspection program. Contact Wayne Martin: 970- 468 -0295 ext. 108. — See Sheet S1.0, Note 2 for description of structural special tests and inspections 8. Final Plat of Survey 9. Code Required Signage, including and not limited to: — Accessibility per IBC Sections 1007 and 1110 — Doors per IBC Section 1008 — Elevators per IBC Section 1109 — Assembly Occupant Content per IBC Section 1004 — Parking Spaces per IBC Section 1109 — Tactile Exit Signage per IBC Section 1011.3 — Stair Identification per IBC Section 1019 — Standpipe Control per IBC Section 905 11. Public Safety Radio Amplification System 12. Egress Easement Agreement 13. Smoke Control Management Specification Calculations and Supporting Drawings VIII. ADMINISTRATIVE MODIFICATION 1. Administrative Modifications are included under separate cover. AcbieadRmwd he `aBeuk fa Vail ASK -004 at Squa�e DRAWING No: 4240 0WM / DmAopff REFERENCE: A004 ISSUE: PERMIT REV vad Rifto S DATE: 04/07/05 Dwvc4C*1m& DevdopmeAtCompmy SCALE: NTS BY: AEP Avon, Cobrado DRAWN fTA IM 1 I Arcbkea Record The AnaBefle DRAWING No: ASK -027 at Vail square 4240 Owner / DevelloM REFERENCE: A027 ISSUE: PERMIT REV vajl Rewrt3 DATE: 04/07/05 Dmvc4Cobrdo Devebpn=tCompany SCALE: " -1' -0" Avon, Colorado DRAWN : AEP6 Architect of Record 4 2 4 0 Denver, Colorado The ArraBelle at Vail Square Owner / Developer Vail Resorts Development Company Avon, Colorado DRAWING N0: ASK -051 REFERENCE: A051 1 OF 1 ISSUE: PERMfi REV DATE: 007/05 SCALE: 1 16' =1' -0' DRAWN BY: SK Iff SKI CLUB LOBBY , 147 i Pq RETAIL P149 ■ STAIR 7 I I'' S107 ■ I� Architect Record The ArraBelle ASK -101 of at Vail Square DRAWING No: 4� 4o REFERENCE: A101 Owner /Developer ISSUE: PERMIT REV Vail Resorts DATE: 04/07/05 Denver, Colorado Development Company P 1' Y SCALE: 1 6 "= 1 ' -0" DRAWN BY: AE P Avon, Colorado Rmr •:: Oil. CHILLERS G213 / 8095' -0" / 'G213 .0 I -0" A 93* G212.6 ' 16i F G213.A 8094'- - FL00R G213.6 >k INLET �b 8095' -00" �O �O 0 h F / ArcWiea of Rccoid The ArraBelle DRam w. ASK—Al 10.1B at Vail Square 424 o.� / nn� A110.18 oF a �: PERL41r tzEv Vail Resorts Mc. 03/24/05 D arm. colorAo Development Compan SOILE, �/8.!�P0. n%va, Coloddo DRAWN BY. GSe ;P J" 1 I I I 1' -0" 1 � 1 , 9 » 2 F — /4� IK - GARAGE EXHAUS • ROOM (SW) 'S gy p, - 0 l G214 r tK Ik r E E L G E 216 �O Ik \ o � •TiELECOM�\ 2 %2 G228.01 A738 3 / 4 ". PLYWOOD: . . \1' TO 9' AFF. 095'-0" A G 12.A \ \ 5i ISIA. PI r \ BOLLARDS 93' G212.B �\ \ REF. / o 2 O ABOV� FOR BOILER \ X3 G213.A PIPING r Arditm of Rword The ArraBelle DmmNG N o- ASK-- A110.1B at Vail Square 4 O Ow= ��4" A 2 Of 3 ISSItE PERW E>tFtlT REY Vail Resorts DATE: 03/24/05 th,c�toraa Development Company / -T��� Aron. Cobcaclo DRAY -^ 1O�'-O" CONCRETE RETA|N|NG WALLS REF. STRUCTU| IVY-� 2 �'-0^ --00NCRETE CU�8 --TRAFFIC L ARMATURE� RE� S�EC 4"40 Architect of Record 4 Denver, Colorado The ArraBelle at Vail Square Owner / Developer Vail Resorts Development Company Avon, Colorado DRAWING N0: ASK- 110.2D REFERENCE: Al 10.2D ISSUE: PERMfr REV DATE 04/07/05 SCALE: 1 8" .1'-0" DRAWN BY: SK f ICE RINK REF. & ELEV. 9 MACH. RM. G155 G155.A � o 8 COM 9 COM i 5 C0V 6 COM ii 7 COM Architect of Record 4 Denver, Colorado The ArraBelle at Vail Square Owner / Developer Vail Resorts Development Company Avon, Colorado DRAWING N0: ASK- 110.2D REFERENCE: Al 10.2D ISSUE: PERMfr REV DATE 04/07/05 SCALE: 1 8" .1'-0" DRAWN BY: SK Architect of Record The ArraBelle DRAWING N0: ASK 1 1 1 C at Vail Square VESTIBULE 4240 Iml REFERENCE: A111C/A132 POIJ I ISSUE: PERMIT REV DATE: 04/07/05 Denver, Colorado Development Company SCALE: t /8 = t -o DRAWN BY: SK Avon, Colorado 1� E71 !TREATMENT ROOM MW ,,. , . . .,. II � �I ■il�f�it Qgt[F7 O L \ NJ jTVJ,, �' . .�� 111 �� •� 1 - 0 WM P '.-�1.'... L N O — I I i Architect of Record The ArraBelle DRAWING N0: ASK 1 1 1 C at Vail Square 4240 Owner / Developer REFERENCE: A111C/A132 Vail Resorts ISSUE: PERMIT REV DATE: 04/07/05 Denver, Colorado Development Company SCALE: t /8 = t -o DRAWN BY: SK Avon, Colorado 1� f f i I f f WALL TYPE "M" f f RE: M /A501 f DUCT_ f f FLOOR TYPE f RE: V/A512 f I o a a o a \ \—HORIZONTAL SHAFT WALL RE: M/A511 X SI -DAFT TERMINATION Architect of Record The ArraBelle DRAWING N O: ASK -512 at Vail square 4240 Owner / Developer REFERENCE: PE R K 1 OF 2 ISSUE: PE►j11T REV Vail Resorts DATE: 03/24/05 Denver, Colorado Development Company SCALE: t 1/2 " =t' —o" Avon, Colorado DRAWN BY: SEK /sG� FAN UNIT RE: MECHANICAL CURB RE: MECHANICAL ROOF TYPE "D" RE: D/A511 D D 1 . C DUCT a d d ACOUSTICAL SEALANT WALL TYPE "M" RE: M /A501 ROOF TYPE -SHAFT 1 1 1 /2"= V -0" DTFLTYOA Arclricectafkxord The ArraBelle DRAWING N O: ASK -512 at Vail Squa 4240 ow ner / D eveloper REFERENCE: PER 2 REV ISSUE: PERMIT REV Vail Resorts DATE. 03/2 Denver, Colorado Develo mentCom an p p y ' Avon, Colorado SCALE. I 1 /2 " = � -0" PRAWN BY: SEK G- � t _ ENETRATION Architect of Record 4 2 4 0 Denver, Colorado The ArraBelle at Vail Square Owner / Developer Vail Resorts Development Company Avon, Colorado DRAWING NO: ASK —A708 REFERENCE: A708 1 OF 1 ISSUE: PERM(T REV DATE: 04/07/05 SCALE: 1/4-1-0 DRAWN BY: GSB � � o ^3 L N � � o Ca d s F a o� a\ a 0 0) 0 a I d I I I I i i i 3 � I i N N b b I � I I 7 o a Q o o o a Q I I v .rj y F•' W j rq 3 h o> • o o ,� � �� v o y m h h o N g q q q q q q q q q q A ! q q Q q q q q A q A q q q q q a r c •O C � o�i � tl � y C x �_ , I, Zs r o d o d w i W r a V `'��`i`i`°�i`;`i`� m i l `' �i` �i` � • o b i � m Z r � i` ti`` i` ti` 1 N i M i a i �� � F" m 4aaaaaaaa4aawwa4wwa�aaaa4aaa m o m m, m o o o o m m of v of Z o m I m o m m o o m m H ; c? c? g 4 q q `° Cl q O W 00 M 00 00 N lD [- 00 N 7 e{ h �c 00 N N �o N 0o N N fV M In Z x I i n• ^' FV (V r4 N cV N N NI r4 iV cV r4 iV 5 N W a' .-. N M et h �O I� o0 O� O_ ' N_ M I I � ti � r 00 T O -• N M I d' �n �O [� W U 0 0 0 OO O O'O O I _ i-• NN N N N N N N z z I � � o ^3 L N � � o Ca d s F a o� a\ a 0 0) 0 C> O V i C (Z p it N v) o ►. U > 0 > o Q a> d d s F cu "O .a u 0 "C i I I I i ' I I N b rr rr I ^ R ] I Q a I j v 0 0 y <r O hi v II h ti ti tl y o i C 04 x W � Olp y h � y y y d �i44�44a4'a4iaC�aaa`4444C't 4w�ia �O O ,�_, '" � a0 O O 'O O m N .^ b r 00 C4 V7 10 N fV �D 10 10 �D �O ,� O Oi O O O O 0 0 0 0 0 0 0 0 ! 0 0 _ N I N N (V N <V cV fV (V M M M M M M M M M M M M M M M A U F N Q N Qd M M d M Q M Q m M dl¢i¢ h j M M In M Q 00 M Q�QIQ m O M , 7 _ 7 Q N � Q M 7 Q 7 Q . Q d' Qi V Qi V ¢ d ¢Q, ¢i d Q 3 3 o z z I I I �o 3 I C> O V i C (Z p it N v) o ►. U > 0 > o Q a> d d s F cu "O .a u 0 "C w o tn c o 0 C L N - U a ca d � � o Pa c� d F M a o� o� a� 0 Y C b U O "C C i o i I I I I II A ;i a a a � d d ao y � C � O O N w� 3 a �� °' ti 333��i��i�i33333�i33�i333�33� �i3'� •� � 3 ,� � y� �' W U G U V UV U U U U U G V U U V G U U U V U V V U �( y ti r- L ° L Vl � r - :: 41 Ci q rx w •y � � � � rn i Oa 3 o�i m F" m ' d 'm d m d `m an d d u v; an d � i i � i i i •r N M a h b n o 4 : o�i 4 o �Y 4 o 4, o'i 4 4, 0. �Y �Y �Y 4, 4, 4, o 4� o 4� 4 �Y o 4 o 4 14, o 4 o 4, �y a, o C - o 10 o 10 0 0 10 o0 00 0 0 o o O O M M t M �T 7 v1 �n �c �c �D 00 O� N N N U oW. V1 V1 r h 00 V1 O V1 O 1D -- �c N � c M �c �0 n �c O 'O r �c 00 IO Cl 'c r r N r M r 7 r h r r r r - O N O M 0 op w o tn c o 0 C L N - U a ca d � � o Pa c� d F M a o� o� a� 0 Y C b U O "C C i � o � � � o � > o d w. d a> 0 F a a a 0 cu d U 0 'o a I I i A � c m 'a I I I ' x � � x 0 0 q W rA It r} V , h O In F W W y 0 r w H ro O � a I j l j i rTi 00 +0•• 3 00 �• 00 �. 00--� 00 00 00 .-• .-+ 00 W Q � x x � � •� ti� 1 1 �� i I� i t .� 3 3z I v i m o s co F L L i L L L i i L L L L I L L L i L i L L L L L L N Md h 44444444444'4'44 4 444444444 �� o 0 0 e 10 o o�oi� o o M o 'o 0 o c o 00 v "o n o' ol�i Co v a v v n n n z x I N N N N N N N i N N M M M M (V V N m t' ;r 7 7 A a N r- ! 00 O, O_ ^� N_ M_ U U O U O U O U O U O f O U O! U O U O U:U U U U O 0 O W O W O W O W O W O W O W O WIW O j � I'll � 0 � o � � � o � > o d w. d a> 0 F a a a 0 cu d U 0 'o a u o � e c o � o � c� � � o u u z�. d u Z F O� o� a a� 0 Q b u 0 b a I L a I I I A I i c I I W W � I I I I i b b I a I I I ! 4 Ck a I I I � i � 40 I i O � � o t �� � O y O .� 0 0 y y y u y AA A ALA A AIA A A A AIA A 'A A A A A A A A A A A m�k W U U U U U V V V U U U V U VL U V U U V U U U U VU V � � ;. O y O � p � � , ; O '• O� N N o0 .�-. o0 00 ; C Ca CV Cv y 0 i e � m h d m d m o d i r o Q A G a F 'r N i i i h rA d ti F" d m m m m `m m � � � � � i i o o o o o o i o o o o o o o o o o o o j F N O fV --i O ID O 10 O �D O O O O 10 10 10 Vn �o k^ V1 10 NMaa�;���Dl (� a O-- N M V' V'1 ^ �O -� h 00 D1 O N N N N 'n, N 0 0 0 0 0 0 0 1 0 O O O CIO w w w w wow w ww w w,w w w w w wlw w w wjw c7 C7!c7'i Z Z 0.0 u o � e c o � o � c� � � o u u z�. d u Z F O� o� a a� 0 Q b u 0 b a d o � •� U d � � o u d L s F b Q a ^a v s u 0 x I I I I I I i j I j i 0 3 j ilk I � I I N `r c o C4 I ao d c4 i a I � � d I op p O N Q A �! V � erj y O F•' W •y �+ 0 .� 00 U y I c i o r r i D i o C7 0 00 • 01 •Zy` -0 i' h Ol Y Oyi O U Q �p �p p �' ^ �' j ... ' �' �' 10 O v oo N c ; I ' I •°o i � � � W 'r .a I �' I x 'Zt Zs Zt � h 0. 4i 0. � 4 •ter N 'Y'+ a h �o � C 4 4 � 0. � 4 4� � 4� 4 0.' 0. 4�i 4� O O O O O �O O fJ 7 O OI� O O:�O oo O O - '-• 7 O w v) 7 0 z x x � I O.O O C ? C? O O ,10 AfV O O O O N �D I UD 1�1 , O� M �O �O' �O ! � � O h "- h I O Vl �' ' �D 3 I, i j A M W � >' 7!vi oio OHO o O� io �x N` o �ol0 � IN —,',.� m 0 -� 7 0 .� kn 0 •, 'p 0 •, r� 0 -� 0 x = M 0 xlx�x� 0101 0 .a�.a 0 0 awl Cl ICI 3 3 z 0 O I ! I I d o � •� U d � � o u d L s F b Q a ^a v s u 0 � o � c � o � � o Fr F ON ON a\ a\ 0 Y 0 rA a I i 0 m 00 cn V A 0 m QD cn A f oo A m �1 w oo w q A 3 o 0 0 W o 0 i W rn 3 0 W 03 cn w z z � w cn w I I LL LL O Ln O v e e A A Q o O 0 O A F 3 3 3 ti° ti 3 3 d Loo U O O O U 0 o U U U y U U 0o d GL d .a r. d o 7 0 Q h ri h <F C N W W m j ti 4 �� ro � d ^a I I 07 I I c0 h u v 3 y y N N U U y y w a m y '� ° y V O xi N N N N N ^O C ZS� rte- 00 �c C, �o �o o x , I o� j 3 3 •� o� i I 3 y m e tu � � � � � � � F I o m o o o o m o o o o o o o o o o�i o'i o�i o o N �' n. ip O lo N O fV M x A I I N N O', O O r r l oo N N M M 7 ', M M O N O ^. 0 N 0 j m 0 7 vi 0 0 O 0 0 I .-. O .-. 1 0 ... N m t �n 0 �D o 1� o oo 0 1 cl 0 r„ H O is a a a,a a o, x l F' o � Cl Ln 0 � 0 cn c Ln u) �,� 3 3 II I O o� z ° a 3 � o � c � o � � o Fr F ON ON a\ a\ 0 Y 0 rA U a � , o O L d H 0 a a\ C7, a 0 Q C rQ Y U cn PC 3 O 0 W i a I � A IA A r A 4 A A A A Q A A A 00 00 Q A A 0 o A 0 w 0 o 0 0 w o 0 0 25 0 w w o 25 0 0 0 0 w o O 0 0 0 M M 0 M M 0 O M w o M M W o O M i O M M 00 M M 00 M M 00 P: M M m M M o0 M M 00 M M 00 �.. tY� FL M M o0 M 00 M M 00 M M 00 w R: M o0 M 00 00 00 00 oo LC o0 y o cn www En m rn U) v, CA cn v W v, w zaR3aacza333�a�c3�x��c ( z 3 a3a w R www C40 0 wwww Ln cn En v, 0 0 0 w www w�� 0 A A wwww cn cn Ln w v, 0A w UA O �L 333z3333zzz3333z 3z3�3 0 0 0 3 0 0 0 0 3 3 3 0 0 0 0 3 0 0 0 0 0 3 0 0 z z z z z z 0 0 z z z 0 0 z z z z z o� 000� oo- ---� -- o „„ 0 0 0 U 0 0 0 0 U U 0 0 0 0 U U 0 0 0 0 o U o U o u F» CA F 'A E4 F . F . F F E 4 N F ' F ' F Cn F v, h F CA F [A F cn F W F CA Eh F cn E F Con WW N .: � � � N N N � � � � N y � � � � � V � N � 00 0� a U U U U U U U U U U U U U U U U U U O � a I I o� °�° 7 ti °p ' .� h y o � � ro y o r y o o r n o a W D3 a�aaaa���a�aa3���a�3 143143Qi a Ts m h N Q N V N N �1 V U N V N N V �4 V N U 14 U V � I o r o ti o 3 r 3� x I 0 o d g V Q r Ol C ai CQ rg d ti �c x i o 3= M Q N J ts F m `m m v `m m i i h 10 n 4, o y ry a, o o o' a, o a, o'" aa, o o a, a, o a ,ry o o o o o o o o o o o`i o F x I x I a a II�II!I W 10 [� 00 O O — N M V 10 VI U7 U) U1 C6 U) U1 U] U) - U) N V) N U] N V] N Ul N U1 N U1 N U) N V] N U] N U) M V] M V) M U1 M U1 M U1 M V] M V) F 0 C A A -0 0 LLL U a � , o O L d H 0 a a\ C7, a 0 Q C rQ Y U cn PC 3 O 0 o kn (m c o 17 C6 id 0. U d � > o PQ d F a a a O .7 p o U 0 b c 1 i W > CG A A 0 0 0 C. 0 CD o o00 0 0 A A A A A r A A A A A 00 A � A '- 00 00 m p o o 0 0 o"I o W o o o 0 rA w o 0 o o 1 ' W 0 o 0 0 0 0 0 0 0 o W 0 o 0 0 0- o W W W y y A 00 M M 00 M 00 �+ M 00 M 00 �• M 00 M 00 (�+ M 00 M 00 M 00 M a0 M 00 Ri M 00 M 00 M a0 Ki lYi �i vn vA � � (A En cn � 11 cn Ln � CA � rn cn i w cn w rn w Ln w CA w V) w v w O w w v w w w O w rn w v w v �L GL CA v A Ln v v A A Q A 3 3 3 2 3 3 z 3 3 z 3 3 3 3 3 z 3 3 3 z z z o o o�: o o 3 0 0 3 0 o o o o 3 0 0 0 3 3 3 A A A A z A A A A A A A n c) A qq A Z z z z z� O z z z z z O-- z z z 4 O O O 0 0 0 U 0 0 U o 0 U 0 0 0 0 0 U o 0 0 U U U y y F F- w F F F F F F cn E4 F F-F F-F F F-F Ln �4 F F F A A A N A A N A N N A A A A A N A A A N N N 0; a U U U U U U U U U U U 7 U U U Y .a ao CG (% u ti j c y C y v] h r o y 3 y o�i vi a F a4 r N V N N NV N'N 4 U N N N N N N V 14 N N N U V c� p4 a � •. � ,� � � F ,, fi y Zt t3 p 0� y 0 y d y „O v "• v] V O tl Z!� � O x� rA I it .S' o a R W y o d F" m m m 'm o` m m i i i i i i i o o� o o o o� o o 4, o 4, o �y o 4, o �y o a, o a, o 4, o a, o a o a, a, o y a, 4, o 4, 4 � F I I i o w A I i W (, w a r M 00 M en M o 7 M V 7 7 7 7 V h h h h j v' In V'1 V) �n w) b b �O �O w cn (A � 07 V), rA N 07 cn rA V) Gn G� Gn � � 'A cn 'A I � � coo W 0 0 O Z °a LL .� o kn (m c o 17 C6 id 0. U d � > o PQ d F a a a O .7 p o U 0 b c 1 i � o � a. � > o d fY1 L Q d O O� a a, O� 0 Q a d U 0 b W � I a I � d I I i i i l i I y b b I I I i d 01 i 4 4 w a � � d I � O � a � y y� U U ►� I 0 0 3 y y o d y ti no F 4 Q Z ? I � V � •� C '" QO x � � I o� i y y y ad •. N M a h� � a a a w 4 a. a a w a a a a w � w� � wl a al I I I I o z w x ' I x I I I I I W m U w 10 �O b I� 1 00 O� b O n _ n N M [� (� r r b [� 00 h n O� n O W _ o0 N = M w o r A z z I I I � o � a. � > o d fY1 L Q d O O� a a, O� 0 Q a d U 0 b k k \ � k k � Q a � / � / $ a \ \ k : w k � ■ ) ƒ k %§ k \ k � \ . \ \ k ] - \ \ \ I I? 4 & § � ) § ¥ � % k 2 ® ® \ \ \ cs �) % - » G - { $ o '21, a � k � , � � n ! m 2 k x � g = / d _ k § z w z \ /R / kc k k \ � k k � Q a � / � / $ a \ \ k : � � 1 � E f � ƒ \� 0 . k� 0� >\ CU ` 2� UC k < § co J § f� 0 / �f 2 � 0 \ 2 E _ § if 0 2k �o0 } ƒcu Cc , � cu ;2f �5f } \§ �c/ } \ ca ;]§ -} ; o , ! & m �0> } k $ ;75 | (�k | E 2 (2� , m = 5E0 } \ \ / ;±5 - « g m / / / / r # r r MENERIER I ,., III „ „ III ,., I CV) �2 04 7 LO 2 / OD #m - OgQ/ IR�RIR2 7 £ or 7 G QoQ Qg / O !Ol O < C �(� - qT 0-1 �a- EL 2 � # / / M a��J m 2 § « ■ k 2 LL o . c § ` O k \ ; � o 0 $ § ° ■ \ U- 2 o o E�k� § 0 » CL o § § « O % � J ■ _ co ) e cm 0 § o / § m E : 0 § CL 0 J E / � Q > a Q k / e § e # # 0 I c c g g \ \ � } / / k k [ ] 7 § > Q U Cl) E j 2 o 2 £ £ ) 7 \ c t a e o 0 o 0 M c c o A$ 0 m m / k .2 / / f CD , C. & E k Co $ ) / } $ 2 3 : # &af E-0$ >E 0 t e Q cc / & a ® j ® § o / \ ƒ k --s - 6 � E E e a = 2 2 y > ° o 2 = m © 70 § / / .0 /k��\ // 2 k \ A ¥ § $ = w 4) a o IL) ± » a E \ \ b) § E ® § > 2 © § \ 2 q — £ e 3 W of § w w w 16 0 2 2 2 2 � -i -j -i / / / / r # r r MENERIER I ,., III „ „ III ,., I CV) �2 04 7 LO 2 / OD #m - OgQ/ IR�RIR2 7 £ or 7 G QoQ Qg / O !Ol O < C �(� - qT 0-1 �a- EL 2 � # / / M r + d m \° \° \° \° \° \° \° \° L OD GO In NT V) 00 O 00 L C LG� L 00 aoQ CL M d N N � N M N L Q V) O C 0 m CL t 0 C O E rO+ i O C .O LL L 0 0 C 0 Gl m 0 L Q m Q 0 0 CL Q L c E c N .0 o o - a LL Q 't co - co LL co LO N m to -0 M M O O O M N m I m � O _O LL Q�'o0 c Q a0E'00 a 0EOE V Q U Q O Q J Q J Q J Q Q Q "O O O) -3 + N m� j Q =��Qm N to Z CY D 0 ICY Cy 0 EC'1 Cyr O p O D Fu c� o �0 0 0 10 0 0 T r ic cyl)) N N N N iM M M Z N CO) E W w v 0 N N O c0 a- 41 \° \° \° \° E Z Lf1 L O V N_I I V ti O M 00 L C L L a r c � J I O ! I J LL M - 0 - C - N lC 3 o- �v� 00 c L o CL O L m C O o — s - 0 o 0— 0 o • C I 1 1 3 a O CL O LO ` � E a LL :� L O o I I 1 0 o oy=ao ti a 0 M I M 00 M d LO i `� / I 0 Q Q1 c . E USE . p� 0�� F Q Q a�QmQ D [ 0 0 0 0 0 0 o � LO LO COI M It i N I i l 1 1 CD � -- I (fl N O)l ILo CO E U. p > > J Z_0 Z J Z J m y Imo; O O� I I V -- Cfl - d 00 o V CO Lr) LO LO� In I O M 0) (0 a- 9 O E Z Lf1 O ioi N_I I :M O M O � J I ! I J 0 0 0 0 o � LO LO COI M It i N I i l 1 1 CD � -- I (fl N O)l ILo CO E U. p > > J Z_0 Z J Z J m y Imo; O O� I I V -- Cfl - d 00 o V CO Lr) LO LO� In I O M 0) (0 a- 0 0 0 0 0 l o ti to I' �1 � av t L � L L Q °o a _ 0 N O EL � _ IC L � O L Q O m O LL ° o LZJZ JZJ C O I 3 m a ! O L O S O O LL 0 �-. LL Q C t 2 0 C Lo OO a Q m R m L Q LL C O N O LL a M L N 'C I m G1 1C L — a o > 0 O v t) O J R Z I O O 0 0 0 0 0 l o ti to I' �1 11 !,1 ! 1 l l ! l ti N N I I I I 1 1 I I I I I 1 1 M r-- CD I M N N N N O � � U EQE ° o LZJZ JZJ I ! Z ° O~ L ° o m Q O _ Q m Q m M I 11 !,1 ! 1 l l ! l ti N N I I I I 1 1 I I I I I 1 1 M r-- CD I M N L 0) 0) O O O O O O O I mo! i(o (, N 1 (0 r- Z m h o > ; > � J I J Lu I I O d' N 0) c0 a E U EQE ° o LZJZ JZJ Z ° O~ L ° o m Q O Q Q m Q m I I L 0) 0) O O O O O O O I mo! i(o (, N 1 (0 r- Z m h o > ; > � J I J Lu I I O d' N 0) c0 a Vail, Colorado Denver, Colorado _ Dillon, Colorado ll Monroe & Newell Engineers, Inc. April 7, 2005 4240 Architecture 1621 Eighteenth Street, Suite 200 Denver, CO 80202 Attn: Mr. Steve Roberts Re: Arrabelle at Vail Square (M &N #6250) LP2A Building Review Comments dated 4/1/2005 Gentlemen: The following is an itemized response to the structural comments listed in the LP2A plan review dated 4/1/2005 SD'): See revised section 1/52.1 SD12: See attached CMU lap splice calculation and schedule. R a. Section 2/55.1 was reissued with the first response list. Please see attached copy. b. The detail in question is at a precast double tee to double tee joint, so Section 5/54.1 is appropriate as stated. SDI 9: All steel beam connections are defined in Section 9 -D of the General Notes. ON.MIT -.rte;= 2005 Platinum Sponsor The Colorado Chapter of The American Institute of Architects www.monroe- newell.corn 1701 Wynkoop Street • Suite 200 • Denver, Colorado 80202 SD21: SD26: a. Section 2/S5.2 does not need to be revised as it correctly shows the stud wall offset from the beam centerline. The column is not eccentric to the beam. c. See attached supplemental calculation & revised detail 11/S5.2 d. The supplemental plate girder calculations submitted with the PCI pages SGD11 — SGD30 show that no web stiffeners are required. See attached supplemental calculation for welding of flange to webs and modified detail 13/S5.2. c. See attached plaza level load summary. d. See revised partial plan of sheet S110.213 for transfer beam splices. SD28: See attached Section 5/S 1.4 SD32: SD37: a. A partial plan of sheet S 111 B was submitted with the detail reference 11 /S 1.1 called out. Please see attached additional copy. b. A partial plan of Sheet S 11C was submitted with the detail 3/S5.2 adjusted. Please see additional copy attached. c. See Item SD32a d. See Item SD32a e. Section cut has been removed. f. A partial plan of Sheet S 111 C was submitted. See additional copy attached. g. See Item SD' 2g h. See Item SD32g c. See Item SD28. e. See attached partial plan of sheets S 111 D for splices. SD38: The column and grid dimensions not defined on Sheet S1 12A are shown on sheet S i i i A. See attached partial plan of S 112A for grids and dimensions. SD41: a. Please see attached Section I /S5.3. SD43: A partial plan of Sheet S113D was submitted with the PC package. Please see attached for additional copy. SD53: The location of 7/S5.1 is on Sheet SI15C @ grid C -8. See attached partial plan. SD54: The section cuts for the roof in question are shown on sheet S 17B that was reissued with PC I. SCI: a. Please see attached full Ramsteel output. b. The beam in question ( #57) is on S11413, grid 8.5, L -M (W12x50). See previously submitted key plan Sheet R41 for location and beam has always been shown as W12x50. e. See attached detail 4/S5.3 for typical bent beam. J. The roof key plan was submitted with PC 1 but see the attached for an additional copy. p. The roof key plan was submitted with PC I but see the attached for an additional copy. z. The roof key plan was submitted with PC but see the attached for an additional copy. am. See Item SCla an. Building A: Wall rigidity calculations pages L67 to L85 and load distribution to each wall pages L86 to L100 with summary on page L101. Resisting frames on pages L103 to L129. Building B: Frame rigidity calculations pages L140 to L141 and load distributions pages L142 to 149 with summary on page L150 for North/South loads and page L153 for East/West loads. Resisting frames calculations pages L155 to L194. Building C: Lateral calculations for Building C are shown on attached supplemental calculations. Included are wall rigidities, load distribution and frame calculations. Building D: Wall and frame rigidity calculations pages L226 to L243 and load distribution to each wall pages L244 to L246 with summary on pages L247 to L255 for North/South loading and pages L259 to L271 for East /West loading. Resisting frame calculations pages 1 1.273 to 1 1-34 7 /. SC' The steel frame sketches and calculations are referenced in Item SCI -an for the frames detailed on the structural sheets S7.0 to S7.5. The supplemental lateral element key plans issued in PCI correspond with frames in calculations and frames on plans. SC4: Please see attached copy of tunnel calculations. SC5: Section 2/S2.1 was submitted with SCL Please see attached for additional copy. SC7: See attached Ram steel output SC8: The supplemental diaphragm calculations submitted with PCl (pages DI- D 15) show the capacities at each collecting element. The supplemental resisting element key plan submitted with PC shows the resisting elements at each level for all buildings. See attached sketch plan of the resisting load elements at base with base loads. 174: See attached letter from geotechnical engineer. F5: Retaining wall schedule was submitted with SCI (5/51.0). Please see additional copy attached. If you have any questions or comments, please call. Very truly yours, MONROE & NEWELL ENGINEERS, INC. r g Carroll, P.E. Pr' cipal - . tip N ~' 13 ! �L J'D G -_ -- !! ! I I! ! I �.5 ®. b O 26 417 0 00 i© 16A (6. I£8 - 17 1T,� 175 fZ6 179 1 / / u v 0 12' l5 era {, / �b i I i (22 Monroe & NeNw,Tell Engineers, Inc. Structural Engineers Vail • Denver • Dillon -i ne Arra belle at Vail Square Vasil, Colorado PROJECT NUMBER: 6250 TUNNEL DESIGN T --)(l _ 1 Y d V; 1!42: t= 1: . . ...... .. . '' �lr ........ .... ... 2 -4 �.l Monroe & Newell A Engineers, Inc. va�,= ......... ... .......... .. Title : Dsgnr: Description Scope : T3 Job # t Date: 2:11 PM, 3 FEB 05 User. KW -060365 ver5.6.1, 25 -0« -2002 Multi-Span Concrete Beam Page 1 (c)1983 -2002 ENERCALC Engineering Software f Description lionshead core — _"IXWY)�1, V General Information Calculations are designed to ACI 318 -95 and 1997 UBC Requirements Fy 60,000-0 psi r_ - All Spans Considered as Individual Beams ACI Dead Load -Factor — '1.40 Pc 5,000.0 psi Stirrup Fy 40,000.0 psi ACI Live Load Factor 1.70 Concrete Member Information 74.95 12.00 Description I � �� simple 75.10 Span ft 24.00 0.00 Beam Width Beam Depth in in 12.00 16.00 0.00 End Fixity 12.00 Pin -Pin 0.00 Reinforcing Center Area 1.29in2 }! Rebar Area Bar Depth 13.75in Bending OK in Left Area Shear @ Left k 12.49 Not Req'd Bar Depth Shear @ Right k 12.49 Right Bar Loads Using Live Load This Span ?? Dead Load k/ft Live Load k/ft ZiL Yes 0.440 0.250 0.46 - - Results Beam OK Total @ Left k Mmax @ Cntr k -ft @X= ft 74.95 12.00 k I � �� Mn *Phi k -ft 75.10 VV V1?x f��r, Max @ Left End k -ft 0.00 Max. Deflection 6 Mn * Phi k -ft 0.00 ft 12.00 Max @ Right End k -ftl 0.00 1,417.31 Shear Stirru Mn * Phi k -ft 0.00 Rebar Area in2 0.000 Bending OK in 0.00 Shear @ Left k 12.49 Not Req'd Spacing @ .4 *L Shear @ Right k 12.49 Spacing @ .6 *L in Reactions & Deflections Spacing @ .8 *L in l Not Req'd v� Lw �cu K 0.46 - LL @ Left k 3.00 Total @ Left k 8.28 DL @ Right k 5.28 LL @ Right k 3.00 Total @ Right k 8.28 Max. Deflection in -0 ;902 @X= ft 12.00 Inertia : Effective in4 1,417.31 Shear Stirru Rebar Area in2 0.000 Spacing @ Left in 0.00 Spacing @ .2 *L in Not Req'd Spacing @ .4 *L in Not Req'd Spacing @ .6 *L in Not Req'd Spacing @ .8 *L in l Not Req'd Spacing @ Right in 0.00 Title : I t Job # Dsgnr: Date: 2:11 PM, 3 FEB 05 Description Scope: Rev: 560100 User: KW- 060365,Ver 5.6.1, 25 -Oct -2002 Multi -Spars Concrete Beam Page 2 (c)1983 -2002 ENERCALC Engineering Software Description lionshead core Location, ft 0:00 Moment k -ft 0.0 Shear k 12.5 Deflection in 0.0000 8 Title : Job # Dsgnr: Date: 4:06PM, 3 FEB 05 Description Scope : User: KW- 060365,Ver 5.6.1, 25 -Oct -2002 Multi -Span Concrete Beans Page 1 (c)1983 -2002 ENERCALC Engineering Software _ mac Description loinshead tunnel roof General Information Calculations are designed to ACI 318 -95 and 1997 UBC Requirements . Fy 60,000.0 psi Spans Considered Continuous Over Supports ACI Dead Load Factor 1.40 fc 5,000.0 psi Stirrup Fy 40,000.0 psi ACI Live Load Factor 1.70 Concrete member Information im Description 30 foot span - Span ft 30.00 Beam Width in 12.00 Beam Depth in 16.00 End Fixity Pin -Pin c Reinforcing Center Areal 2.10in2 Bar Depthi 13.75in ( j Left Bar Right Bar 'I St::Y Load Using Live Load This Span ?? Dead Load k/ft Live Load k/ft Yes u 0.440 0.250 Results Beam OK Mmax @ Cntr k -ft 117.11 @X= ft 15.00 Mn * Phi k -ft 117.48 Max @ Left End k -ft 0.00 Mn * Phi k -ft 0 -00 I Max @ Right End k -ft 0.00 Mn * Phi k -ft 0.00 Max. Deflection Bending OK Shear @ Left k 15.61 Shear @ Right k 15.61 Reactions & Deflections an Shear Stirrups -: •�'..�... �_�.::.�;:�.:, ��4:s.:. K.,, . ":_tea � :,:.a _; a� .fi.,w - . , f -. ��„ ,� ........�.s�<...�,��.�__.,.3i,. 3..,....c, .= wti,,:as...r. �,.:-:-zi. a....vw_cx- s.,. a:.ar. .. .,..xr�, m,us Stirrup Rebar Area in2 0.000 Spacing @ Left in 0.00 Spacing @ .2 *L in Not Req'd Spacing @ .4 *L in Not Req'd Spacing @ .6 *L in Not Req'd Spacing @ .8 *L in Not Req'd Spacing @ Right in 0.00 LL @ Left k 3.75 Total @ Left k 10.35 DL @ Right k 6.60 LL @ Right k 3.75 Total @ Right k 10.35 Max. Deflection in -1.821 @X= ft 15.00 Inertia : Effective in4 1,713.09 Shear Stirrups -: •�'..�... �_�.::.�;:�.:, ��4:s.:. K.,, . ":_tea � :,:.a _; a� .fi.,w - . , f -. ��„ ,� ........�.s�<...�,��.�__.,.3i,. 3..,....c, .= wti,,:as...r. �,.:-:-zi. a....vw_cx- s.,. a:.ar. .. .,..xr�, m,us Stirrup Rebar Area in2 0.000 Spacing @ Left in 0.00 Spacing @ .2 *L in Not Req'd Spacing @ .4 *L in Not Req'd Spacing @ .6 *L in Not Req'd Spacing @ .8 *L in Not Req'd Spacing @ Right in 0.00 Title : 1 Job # Dsgnr: Date: 4:06PM, 3 FEB 05 Description Scope : User. KW- 060365,Ver 5.6.1, 25 -Od -2002 Multi -Span Concrete Beam Page 2 (c)1983 -2002 ENERCALC Engineering Software Description loinshead tunnel roof Query Values Location It -0.00. Moment k -ft -0.0 Shear k 15.6 Deflection in 0.0000 _ bU1,�. Monroe & Newell Engineers, Inc. JOB SHEET NO. 1 - 7 9 OF CALCULATED BY. CHECKED BY_ SCALE DATE Monroe & Newell Engineers, Inc. JOB SHEET NO. OF CALCULATED BY DATE CHECKED BY DATE SCALE JOB Monroe & Newell Engineers, Inc. SHEET NO. — - OF-- CALCULATED BY DATE v 1 CHECKED BY DATE Title : �7^/'� �ouw / /�, Date: 3:13Pm. n FEB ns Scope: Rev: 560100 User: KW-060365, Ver 5.6.1, 25-Oct-2002 Multi-Span Concrete Beam Page I (c)1983-2002 ENERCALC Engineering Software Description lionshead core tunnel walls General information Calculations are designed to ACI 318-95 and 1997 UBC Requirements --~-'y~— -- 60 ps AII,S aeamu --- '-1/0 ~- -^ fc 5,000.0 psi Stirrup Fy 40,000.0 psi - ACI Live Load Factor 1.70 Concrete Member Information asomm Description simple Span ft 15 * 50 Beam Width in 12.00 Beam Depth in 14 ' 00 End Fixity Pin-Pin Reinforcing Center Area 1-14in2 Bar Depth 11.75in Left Area Bar Depth Right Are Bar Depth Max @ Left End k-ft Using Live Load This Span ?? Yes Dead Load k/ft Live Load k/ft 0.250 LL @ Right k/ft Start ft 0.000 End ft 15.000 Results Overstress @X= ft� 8.16 1o6 q:331 Max @ Left End k-ft 0.00 Max @ Right End k-ft Bending NG Shear @ Left k 13.13 Reactions & Deflections LL Left k 1.94 Total @ Left k 8.97 Total @ Right k 10.28 Max. Deflection in -0.455 Inertia : Effective in4 910.29 Title : Dsgnr: Description : Scope: Job # Date: 3:13PM, 3 FEB 05 User: KW -060365,Ver 5.6.1, 25 -Oct -2002 Multi-Span Concrete Beam Page 2 (c)1983 -2002 ENERCALC Engineering Software Description lionshead core tunnel walls Shear Stirrups =-Stirrup Rebar Area Spacing `@ Left' Spacing @ .2 *L Spacing @ .4 *L Spacing @ .6 *L Spacing @ .8 *L Spacing @ Right Query Values Location Moment Shear Deflection in2 0:000 _ in 0.00 in 0.00 in Not Req'd in Not Req'd in 0.00 in 0.00 0.00 0.0 13.1 0.0000 k in Title : Dsgnr: Description: Scope : T 1 4 Job # Date: 3:11 PM. 3 FEB 05 Rev: 560100 User. KW- 060365,Ver 5.6.1, 25- Oct -2002 Multi-Span Concrete Beam Page 1 (c)1983 -2002 ENERCALC Engineering Software P' Description lionshead core tunnel walls Genera{ {nformation Calculations are designed to ACI 318 -95 and 1997 UBC Requirements Fy 60,000A,psi All Spans Considered aslndividual Beams ACI Dead Load Factor 1,40 fic 5,000.0 psi Stirrup Fy 40,000.0 psi ACI Live Load Factor 1.70 Concrete Member information Description simple Span ft 15:50 Beam Width in 12.00 Beam Depth in 16.00 End Fixity Pin -Pin Reinforcing Center Area 0;96M2 Bar Depth 13.75in Left Area k Bar Depth Max. Deflection Right Area -0.269 Bar Depth ft Loads Using Live Load This Span ?? Yes Dead Load k/ft Live Load k/ft 0.250 DL @ Left k/ft 0.650 DL @ Right k/ft 1.400 LL @ Left k/ft LL @ Right k/ft Start ft 0.000 End ft 15.000 Resu {ts Overstress Mmax @ Cntr k -ft 56.38 @X= ft 8.16 Mn * Phi k -ft 56.77 Max @ Left End k -ft 0.00 Mn * Phi k -ft 0.00 Max @ Right End k -ft 0.00 Mn * Phi k -ft 0.00 Bending NG Shear @ Left k 13.13 Shear @ Right k 14.98 Reactions & Deflections DL @ Left k 7.03 LL @ Left k 1.94 Total @ Left k 8.97 DL @ Right k 8.35 LL @ Right k 1.94 Total @ Right k 10.28 Max. Deflection in -0.269 @X= ft 7.85 Inertia : Effective in4 1,538.03 - F 15 Title : Job # Dsgnr: Date: 3:11PM, 3 FEB 05 Description Scope Rev: 560100 Pa e 2 w User: KW- 060365, Ver5.6.1, 25 -Oct -2002 Multi-Span Concrete deem s (c)1983 -2002 ENERCALC Engineering Software Description lionshead core tunnel walls Shear Stirrups "Stirrup Rebar Area - Spacing @ Left Spacing @ .2 *L Spacing @ .4 *L Spacing @ .6 *L Spacing @ .8 *L Spacing @ Right Query Values Location Moment Shear Deflection 12 0.000 in 0.00 in Not Req'd in Not Req'd in Not Req'd in Not Req'd in 0.00 in 0.00 0.0 13.1 0.0000 Title : ` Job # Dsgnr. Date: 3:06PM, 3 FEB 05 Description Scope: Rev: 560100 User: KW- 060365,Ver 5.6-1, 25-Oct-2002 Multi-Span Concrete Beam Page 1 (c)1963 -2002 ENERCALC Engineering Software Description - lionshead core tunnel walls General information Calculations are designed to ACI 318 -95 and 1997 UBC Requirements -- Fy "60,000.0 psi All Spans Considered as Individual Beams - ACI Dead Load 1.40 - Pc 5,000.0 psi Stirrup Fy 40,000.0 psi ACI Live Load Factor 1.70 Concrete Member Information Description simple Span ft 18.00 Beam Width in 12.00 Beam Depth in 16.00 End Fixity Pin -Pin Reinforcing Center Areal 1.38in2 Bar Depth 13.75in Left Area Bar Deoth Right Bar Loads ^ DL @ Left kl Using Live Load This Span ?? Yes_ Dead Load k/ft 2.25 Live Load k/ft 0.250 DL @ Left k/ft 0.650 DL @ Right k/ft 1.550 LL @ Left k/ft k LL @ Right k/ft Total @ Right Start ft 0.000 End ft 18.000 Results Overstress Mmax @ Cntr k -ft 79.81 @X= ft 9.48 Mn * Phi k -ft 79.95 Max @ Left End k -ft 0.00 Mn * Phi k -ft 0.00 Max @ Right End k -ft -0.00 Mn * Phi k -ft 0.00 Bending NG Shear @ Left k 15.79 Shear @Right k 19.57 Reactions & Deflections ^ DL @ Left kl 8.55 LL @ Left k 2.25 Total @ Left k 10.80 DL @ Right k 11.25 LL @ Right k 2.25 Total @ Right k 13.50 Max. Deflection in -0.564 @X= ft 9.12 Inertia : Effective in4 1,403.30 Title Dsgnr: Description: Scope Rev: 560100 User: Kw- 060365, ver5.6.1, 25-Oct 1i��1 - Sp an Concrete Beam (c)1983 -2002 ENERCALC Engine ering So ftware Description lionshead core tunnel walls _ j Job # Date: 3:06PM, 3 FEB 05 Page 2 Shear Stirrups Stirrup.RebarArea in 0110 Spacing @Left in 6.88 Spacing @ .2 *L in 6.88 Spacing @ .4 *L in Not Req'd Spacing @ .6 *L in Not Req'd Spacing @ .8 *L in 6.88 Spacing @ Right in 6.88 Query Values Location ft, 0.00 Moment k -ft 0.0 Shear k 15.8 Deflection in 0.0000 _ j Job # Date: 3:06PM, 3 FEB 05 Page 2 CONCRETE SLAB ON METAL DECK 4, a (2) - -5 IN BOND BEAM LbX4X1 /4 X 2' -0" EACH SIDE AT 8' -O" WITH (2) -1/2" m EPDXY BOLTS CMU WALL 7/0 < Architect of Record The ArraBelle DRAW1Nc No. 4240 at Vail Square Owner / Devdo er REFERENCE: S2.1 2 OF 2 P ISSUE: PERMIT REY Vail Resorts DATE: 03/24/05 Denacr,Colo :ado SCALE: 3/4� = 1'- Development o n Company I DRAG Br MSH - Aeon , Col i ri�� Monroe & Newell J OB Engineers Inc. SHEET NO. OF _�.. CALCULATED BY DATF Monroe & Newell JOB Engineers, Inc. SHEET NO. OF CALCULATED BY DATE Monroe & Newell J OB Engineers Inc. SHEET NO. CALCULATED BY CHECKED BY— SCAT F OF_ DATE DATE ...... C xn �r7 ...... �r7 � 1�' 1 � . ..._.. ..._.. ._ rC . �2 G 1! � �K1- Monroe & Newell JOB Engineers, Inc. SHEET NO. OF CALCULATED BY DATE Koechlein Consulting Engineers, Inc. Consulting Geotechnical Engineers 12364 W. Alameda Pkwy • Suite 115 • Lakewood, CO 80228 -2845 www.KCE- Denver.com LAKEWOOD AVON /SILVERTHORNE (303) 989 -1223 (970) 949 -6009 (303) 989 -0204 FAX (970) 949 -9223 FAX April 4, 2005 Dan Feeney Vail Resorts Development Company P.O. Box 959 Avon, CO 81620 Subject: Plans and Specifications Review The ArraBelle At Vail Square Vail, Colorado Job No. 03 -184 As requested I have reviewed the plans and specifications for the subject project from a geotechnical perspective. Based on my review of the plans and specifications, it is my opinion that the design team has followed the geotechnical recommendations presented in our report dated July 2, 2002, Job No. 02 -058. KOECHLEIN CO SUIJ J�fin,�„�;1GINEERS, INC. 15962 ; e � ��� ZON AXA ", William H. Koechl'ein, P President (3 copies sent) cc: Monroe & Newell — Craig Carroll cc: 4240 Architecture — Ali Charafeddine 1 M I QI V _2 E O EASE s- IDr.� 1. RE5AR 6RADE 60 kst -2, CONCRETE FG . -4000 p51 - 3. ALLOh1AE1LE SOIL PRESSURE • 6000 P5F .4 ACTIVE PRESSIFtE 35 PGF 5. HORIZONTAL 5AC<FILL ONLY - NO SURCHAR5E5 A I I J aTr — � i � I 3/4' CHAMFER BOTH SIDES AND AT END OF RETAININS WALL (TYPICAL) (2) - +5 CONTINUOUS .. P0551BLE DEFLECTIONS OF APPROXIMATELY 5 /8' o•:ACYoo °.()C�'o•�.4 BATTER ALL WALLS 7(2" MIN) . _ I ctt1 1^I=EP HOLES AT 8' -0' O.C. b' ABOVE TOE SIDE BACYFILL 5 /C X - -0 -- .ZOI:. .— GREASED ONE END - TYPICAL TYPICAL 3 CLEAR H +5 AT t' -0" TT T - � Qs TYPICAL SL CONTROL AND C L ie" Q . . 1 W , WIDTH U 5 v D _ E .I i 1111 _ 1 � Fll�l EII +5 AT 1' -4'�+5 F z +5 AT 1' -5" I -1 4' - � 8" 1'-4" -1 EASE s- IDr.� 1. RE5AR 6RADE 60 kst -2, CONCRETE FG . -4000 p51 - 3. ALLOh1AE1LE SOIL PRESSURE • 6000 P5F .4 ACTIVE PRESSIFtE 35 PGF 5. HORIZONTAL 5AC<FILL ONLY - NO SURCHAR5E5 A I I J aTr — � i � I 3/4' CHAMFER BOTH SIDES AND AT END OF RETAININS WALL (TYPICAL) (2) - +5 CONTINUOUS .. P0551BLE DEFLECTIONS OF APPROXIMATELY 5 /8' o•:ACYoo °.()C�'o•�.4 BATTER ALL WALLS 7(2" MIN) . _ I ctt1 1^I=EP HOLES AT 8' -0' O.C. b' ABOVE TOE SIDE BACYFILL 5 /C X - -0 -- .ZOI:. .— GREASED ONE END - TYPICAL TYPICAL 3 CLEAR H +5 AT t' -0" TT T - � Qs TYPICAL SL CONTROL AND C L ie" - BASE ,I. 1 , WIDTH A ; 5 G 1 D _ E i 1111 1 1+5 AT 1' -4 "� +5 AT 1' -4'�+5 AT 1'-4 1 +5 AT 1' -5" NONE -2' -0' 4' - � 8" 1'-4" -1 1 1' -0" 1 +'S AT 1'-4" +5 AT 1' -4 " +5 AT 1'-4" +5 AT 1' -B`� 1 NONE 6' -0 3' -0 " 1' -3" 8' 1'-'P 1' -0' +5 AT 1' -3" •5 AT I' -4" +5 AT P -3 +5 AT I' -&' NONE 8' -0" .4'-4 I' -10" 8" 1' -10" d• -0" +5 AT 1" +5 AT 1'-4" +5 AT 1" +5 AT t' -8" 11 +5 AT f' -B 1 5' -B" �' -b" 8 , -2' -6 1' -3' +6 AT 6' +5 AT 1• -O"1 i +6 AT 6 - +5 AT 1' - 0 - i i +5 �A7 1'-4 - -4 10' �' -10' �' 1' - +� AT b' +1 AT 6' AT -O' +5 A7 16' +1 AT 6" +1 AT 6" +5 AT 10 +5 AT 10' -5 AT AT I'-4 +S AT I'-4 6' - 4 - _2' - 9' Q' 3' - 0 1 ' '1' - 3' +1 AT 6" +5 AT 1' - 0' +1 AT b +b AT 10" 105 AT 1 3' - 3" 14" 3' -10 1'-4 +1 AT 5 +5 AT P -d' +1 AT 5" +6 AT W +5 AT i'-4 � PICAL °s►T� _,,z� , ,,, R AINING ll1aL � SE C T ION S 3/-4 . 1' -0 F! � 4/7/ 5 3/-4' =1' -O A DF 3i4' . i• -G RTICAL (TYPJ CORNER EAR X HOR REI .. REIN i (TYF MATCH HORIZONTAL - 9—'5AR SIZE AND SPACINS (TYPJ . Ard,iteccofRecord The ArraBelle DRAINING NO: SOK 424^ at Vail Square O rncr / De clops: REFERENCE: S 1.0 1 2 4J ISSUE: PER�Ii RE REV Vail Resorts DATE: 03/24/05 Dcnver, Colo Development Company SCALE: N.T.S. _ Avon, Colorado _ DRAWN BY: I SH CORNER BARS TO MATCH HORIZONTAL REINFORCING IN SIZE AND SPACING m m a N O _O n N O O N n c m 3 3/4" = I' -O" X173 in Arch �ct of Record The ArraBelle O RAy�nN (i N o: Q at Vail Square 4 Owner / Developer �' � SM: PE I RE 2 I SSUE: PERMIT REV w Vail Resorts DATE: 04 /07/05 D engr, Colorado Development Company �? �(H ` I' -o' II1I �O�r RE I NFORGI NG RE= SCHEDULE Avon, Colorado SHEET 52.I HORIZONTAL REINFORCING RE: PLAN AND SCHEDULE A n;l RE: PLAN SE CTION 1 z Q a w VERTICAL A RE I NFORGI NG RE= SCHEDULE SHEET 52.I n;l RE: PLAN SE CTION 1 Monroe &Newell JOB Engineers, Inc. SHEET No. OF C1" CU L AF= 5FL I CE SC E DIAL E D Q M M C) 0 0 n v 3 7 u� Arcict of Record The ArraBelle DPAON No: OOK -02.1 O Vail Square 4:2 <4 wner O / Developer evea er P REEE ISSUE: PE 4 T R E 2 ISSUE: PERMtT REV 0 Vail Resorts DATE: 04/07/05 Dengr, Colorado Development Company SCALE: a 1' -0' Avon, Colorado RED GENERAL NOTES 3/4'm PIN FOR METAL DECKING NEEDING STEEL COLUMN I' 50TTOM P 4 I(2• ONCR L CONCRETE SAG RE. PLAN - ON2" METAL DECK 3/4' o X 3 1(2• HA.5. .. .. AT.I'- 0" MINK" SPA41H6 I 1 RE. PLAN R.E. FLAN TOP OF 3/8 - ST_ L FZ--, PLAN / RED LAN 1 / 4 IQ' CONCRETE SLAB I I TOP It ON2' METAL DECK ' — s.�r•— �j. s.� =,r �...F- -r —s —r STEEL COLUMN r— i -- -----•--- ---'-----'---"-- WITH HA.S, �, PLAN 1 - -- sue —.sus � �. — in TEEL BEAM WITH 1 TYPICAL COLUM A'S' RE. PLAN C SPLICE DETAIL a 5 L— C ION - 1 3F4' P -C" STEEL SEAM RE. PLAN RED P AN ! t RE PLAN RE- PLAN . SOP OF TEEL I I �t O 11 u O n F 4 WITH CONCRETE SLAB METAL I ON-2 aEGK 1 WITH K.K.F. s —s— I 1 1 STEEL TRANSFER BEAM STEEL COLUMN .ME, PLAN ' RE, PLAN i t' STIFFENER EACH i SIDE OF BEAM 4 h ISSUE: PERMIT REV (� AT SIMILAR SECTION, DATE: 03/24/05 COLUMN ABOVE Dev elopment Company DOES NOT EXIST SECT 1 3 /4 • . J' -0 31-4' 0 HA.S. RE, PLAN 4 IM - CONCRETE TOPPING K4 X 4' -O AT �CENTER OVER ( / / RE, PLAN RE, PLAN AND _STEEL SEAM GENERAL HOTE5 RED PLAN FOR CONNECTION DESIGN (DOUBLE SHEAR _ PLATE CONNECTION IS TYPICAL) 51"ECTION2 ^ ' ION 0 STEEL COLUMN (`,•/^ RE. SCHEDULE WITH 1/2' BASE gµ• a i•_O_ - PLATE I(2' CONCRETE SL AS RED PLAN - ON 2' METAL DECK WITH K.K.F. it X 4' -O" AT i' - G' Z7 . CENTER OVER ... REi PLAN. . ___ =s TOP OF 61RDER$ STEEL I (4) -3/4'0 THRU -M:X -T 4 IQ' CONCRETE SLAB ON 2" METAL DECK WITH W}•LF. AnthiEect of Accord The ArraBelle DRAW No:. at Vail Square 4240 REFERENCE: S5.1 1 OF 3 C)"Mcr / Dcvcloper ISSUE: PERMIT REV Vail Resorts DATE: 03/24/05 Denver, Colorado Dev elopment Company SCALE: N.T.S. DRAWN BY: uSH Avon, Colorado Monroe & Newell JOB Engineers, Inc. SHEET NO. _ CALCULATED BY CHECKED BY_ SCAI F nF DATE DATE I i rLAZA NMgN M1N MyU AMY � RE. ARCM LAx4x3A& •' STEEL M /REC.AST P40UPOAT ins w.i SECTION 13 a STEEL BeAK RE. Rµ �9 AT W" ` RE. RAN SECTION II FJ N lfJ (!5 O v i - Ln N �--- i Lo Archi9 crofRecord The ArraBelle DRAWING No: OOK -05.2 at Vail. Square 4 Owner / Develop 2 REFERENCE: S5 4 I SSUE: RE 2 C) Vail Resort DATE: 04 /07/05 D engr, Colorado Development Company DRAIN S CALE : : N. Avon, Colorado LOHCAMTE SLAB ON .e TAL oarAC .�,...a........ I SECTION SECTION S W. . r -0- Monroe &Newell JOB AULAWAt.0 Engineers, Inc. SHEET No. of j, f {- CALCULATED BY "`� DATE ` — 5 ^ CHECKED BY DATE Cr:AI F 5j7Z CONCRETE SLAB ON METAL DECK : 4 — ; 's-- -rx x X— & —x —x— .— s -- ;----70-- , 7 .7 —=------ ------ -. —. -- ° — =— ---- - - - - -- 3/8 3/8 5TEEL BEAM RE. PLAN WITH CONNECTION BY FABRICATOR 3/8 3/8 3/8 3/8 I" GAP PLATE I" STIFFENER PLATE EACH SIDE AT SEARING BUILT –UP STEEL PLATE GIRDER RE: PLAN STEEL COLUMN RE: PLAN. co v iri v 0 CD N r C 0 N co 0 n� �I Arch get of Record 4240 _Q _.. Dengr, Colorado FAI m in 1I1 ! SECTION 13 The ArraBelle at Vail Square Owner / Developer Vail Resorts Development Company Avon, Colorado DRAWING NO O$K —$5.2 REFERENCE: S5.4 OF 2 ISSUE: PERMIT REV DATE: 04 /07/05 SCALE: N1 T.S. DRA" BY: M SH JOB I ` % ' .Y"� li✓✓ Monroe & Newell rni i )19-M TbM r 0 [n 0 0 N The ArraBelle LL at Vail Square 4 2 4 0 Owner / Develop P REFERENCE: PERVIT 1 OF 1 ISSUE: PERMIT REV x DATE: 04 /07/05 x Development Company x �_ ;' d ' m x i )19-M TbM r 0 [n 0 0 N W 1 f `, i The ArraBelle LL at Vail Square 4 2 4 0 Owner / Develop P REFERENCE: PERVIT 1 OF 1 ISSUE: PERMIT REV Vail Resorts DATE: 04 /07/05 $enver, Colorado Development Company S CALE: t H ` t' -0" DRAWN BY: VH d5 ..9 -.1 Avon, Colorado m x ry � X I:— x� XW W 1 f `, i "��71 ci I 3 1 ��A-chirec[ of Rccord The ArraBelle DRAWING NO- 00K 10.2 B at Vail Square 4 2 4 0 Owner / Develop P REFERENCE: PERVIT 1 OF 1 ISSUE: PERMIT REV Vail Resorts DATE: 04 /07/05 $enver, Colorado Development Company S CALE: t H ` t' -0" DRAWN BY: VH Avon, Colorado , "��71 ci I 3 1 ��A-chirec[ of Rccord The ArraBelle DRAWING NO- 00K 10.2 B at Vail Square 4 2 4 0 Owner / Develop P REFERENCE: PERVIT 1 OF 1 ISSUE: PERMIT REV Vail Resorts DATE: 04 /07/05 $enver, Colorado Development Company S CALE: t H ` t' -0" DRAWN BY: VH Avon, Colorado -;?77ZGi-� a N lfJ r` tr) O O N a m 3 SECTION 5 q ofRetord The ArraBelle 4o at Vail Square Owner / Developer Vail Resorts Colorado Development Company Avon, Colorado z 5;p, i 8 DRAWING NO: OOK -01.4 REFERENCE: S1,4 2 OF 2 ISSUE: PERMIT REY DATE: 04 /07/05 SCALE: 40T TO SCALE DRA" BY; MSH n 4BLr r f� ArchrtctofRecord The ArraBeUe DRAWIN No: (SDK -0 1.4 at Vail Square 4 REFERENCE: S1.4 1 OF 2 Owner / D eveloper P ISSUE: PERMIT REV U Vail Resorts DATE: 04 /07/05 — — g Dengr, Colorado Development Company SCALE: NOT TO SCALE DRAW By. M SH Avon, Colorado <8131' - 1/2 "> <8131' -4 li - I N12X12COD UP t- <8131' -4 1/2 "> V414X426. WI6X: S} — - i W18X50 <8128' -I1 I/2 " >_ VrbXlO ;t^18XI0 8 �Y 6 U X = x I Il ttE x't N Q d� f� 15 ELEVATQ 12 LU I � { v Ss.I ' � hL. v joz II w _ LL CO Vill2 X14 f „ I Y v STAIR. ° I I 1 Ia 7 r-a U, I '' - _ _ _ bi2�' - I/2 "> II - 41 3 <b12 - 1' -4 1/2 "> ^\ , ry q7 h , u i 7 x — .. SLI c8I28' -11 112'> VJIOX12 V J i 47 I — z v ry /11 O o Ail { Lv Y a� T� <s Architect of Record 4 Denver, Colorado 5 FF r- � � FF� / \ 3 „ bow P !I �f 2 �. > The ArraBelle at Vail Square owner / Developer Vail Resorts Development Company Avon, Colorado � DRAWING No: $O —$ 111 B REFERENCE: SIIIB i OF 2 ISSUE: PERMIT REV DATE: 03/24/05 SCALE: VS B 1 -0 DRAWN BY: H 0010, Ir 1 The ArraBelle DRAWING NO- C' Ca UP at Vail Square 424 A REFERENCE: S111C 2 OF 2 ISSUE: PERMIT REV 0 Vail Resorts DATE; 03/24/05 ~X!* Development Company SCALE- N.T.S. DRAWN Br MSH Avon, Colorado GO w 1,2 UP X&2 "0098* V42^" d% A 4 r k7 Ca M. 3 in ! —/-- C11 UP , ",Acw M x to PM V-L 0010, Ir 1 " I ID LO ArchN et of Record The ArraBelle DRAWING NO- C' Ca UP at Vail Square 424 A REFERENCE: S111C 2 OF 2 ISSUE: PERMIT REV 0 Vail Resorts DATE; 03/24/05 Den3kr, Colorado Development Company SCALE- N.T.S. DRAWN Br MSH Avon, Colorado "0098* V42^" d% A 4 r 3 in C11 UP V4L2X& 4 x to PM V-L S?- 64444230 MA40,04q I" " I ID LO ArchN et of Record The ArraBelle DRAWING NO- C' Ca UP at Vail Square 424 Owner / Developer REFERENCE: S111C 2 OF 2 ISSUE: PERMIT REV 0 Vail Resorts DATE; 03/24/05 Den3kr, Colorado Development Company SCALE- N.T.S. DRAWN Br MSH Avon, Colorado "0098* V42^" 4 3 in C11 UP V4L2X& 4 x C-1 Lip 64444230 MA40,04q I" Ic 'SM VA2x14 r. 2 wi Q"26 la". cid UP HL " I ID LO ArchN et of Record The ArraBelle DRAWING NO- C' at Vail Square 424 Owner / Developer REFERENCE: S111C 2 OF 2 ISSUE: PERMIT REV 0 Vail Resorts DATE; 03/24/05 Den3kr, Colorado Development Company SCALE- N.T.S. DRAWN Br MSH Avon, Colorado V42X&4 V42X" O oil X00 �D c� F CI LA \3 Q 09- IZ!? I Fi 3 4 07 ` p Q vo CI s X r 55.2. /-a i 7— e 3/-4 X i. /x I i 55.2 � ArchimmofRecord The ArraMe 111 at Vail Square DRAWING NO: ��!K —� B - 4240 Owncr / Dcvcloper m F t i , DATE: 03/24/05 X,.. Development Company- SC ALE: t = V -0" DRA BY: MASH - Avon, Colorado 111. l / X i. /x I i 55.2 � ArchimmofRecord The ArraMe 111 at Vail Square DRAWING NO: ��!K —� B - 4240 Owncr / Dcvcloper REFERENCE: S t 11 B 2 OF 2' ISSUE: PERVIT REV Vail Resorts DATE: 03/24/05 Denver, Colorado Development Company- SC ALE: t = V -0" DRA BY: MASH - Avon, Colorado SPLIGE`° in in r.2 � (1 m -------- - - - - -' DH — _ J ------- - - - - -- -- I------- - - - - -- 0 0 m J.8 - — 0 0 m Arthimcco:Record The Arra DRAWING NO: �'SK —S111 at Vail Square 4240 Owner j Dc� -dopes REFERENCE: SMC ! OF 2 ISSUE: PER�,�(IT REV Vail Resorts DATE: 03/24/05 Denver, Colorado � Development Company SCALE: 1 8' = 1' -o` D RAW N BY: SH IL Avon, Colorado GII UP 6 .i V tat: L WL2X230 OF L e sia — L wL2XL20 UP wt4X42& Arch c' " The ArraBelle DRAW NO 00K —$ 111 D at Vail Square 42 <4 O Owner / Developer REFERENCE: S 111 D 1 OF 1 ISSUE: PERMIT REV U Vail Resorts DATE: 04 /07/05 Deng Colorado Development Company SCALE: 1 8 = 1' -0' DRAWN Br: V r, H Avon, Colorado i I 2q-7 V44OX215 W4 —- SPL1 PLIGE 1 011 — io '7 10 10 0 0 ..• -- UP I .. LICE _ 55.1 SPL �-UP— ' P UP UP _ X 6 2 W4OX3G2 ' W x y Y 18 6 6 r x x ?l X l` X y b x x i I 0 1 V 0' l 0 UP :LEV OR ` �7 — I WI4) COLUI IN l 17 i 5TUB i (y ryry COL. ry 55.1 � UP `t UP X X X Pi X i N SPLIGE PLIGE W33X 30 W44X262 — — u IJ F- Arch c' " The ArraBelle DRAW NO 00K —$ 111 D at Vail Square 42 <4 O Owner / Developer REFERENCE: S 111 D 1 OF 1 ISSUE: PERMIT REV U Vail Resorts DATE: 04 /07/05 Deng Colorado Development Company SCALE: 1 8 = 1' -0' DRAWN Br: V r, H Avon, Colorado Q -) 16.4 6 6.8 17Y 74 ,17.57.6 iZ4�"'"°"°•�' 1.2 15 T 2. �pF \ �, \ I u vo• �(2 , .1 \ M/\ / \/ \ _ ' I i 4-tL': X _. 156 s \ .!• -lt.s. f f t u of a 0, fir'\ J Q 3 / !/' O" \ Hsl► C) 1 K� =� / �/ i x'44 .O �' 0 `\ I I �• 1T N Archt ctofRecord The ArraBelle DRAWI N0: OOK -0112A at Vail Square O 4:2 <4 Owner / Developer REFERENCE: S112A 1OF 1 ISSUE: PERMIT REV U Vail Resorts DATE: 04 /07/05 D e gr, Colorado Development Company SCALE: T.S. DRAWN BY: I�y $H Avon, Colorado 28/55.1 "5 , ON 5X4X3/8 4X4X3/8 T 3' -O" /8 "m 'OXY PINS T I' -O" YPICAL) 0 co 0 ai C) 0 0 N n `c m 3 v ri L S SECTION I 3/4" = 1' -0" 0 . !p I N Arch VctoERecord The ArraBelle DRAWI No: OOK -05.3 at Vail Square 424 REFERENCE: S5.4, OF 1 Owner / Develo er P ISSUE: PERMIT REV U ---- Vail Resorts DATE: 04 /07/05 Denier, Colorado Development Company SCALE: 3 / 4' a 1' -0" pRA�N By-. ASH Avon, Colorado W16X26 1 z W16K26 I I W�XIG WL2XI9 — -A- u- G8 ON G9 DN -7 W ON ! 3 m X. 1z 10 ON - - -X - -_- - -- �I - -- 1, r 4 i , UP 9 ' i UP _; I I WIbX3 J -- T - — : � s —� i : I _ 1 1 El 11 G II I �JI . 7 DN -1 >.. �.�. ' \' �♦ r� DN W16_i 31 G4 DN Ib.X T " " W33XIIB. + : Wt Xi. : .:I I WIOXL2 `� I._. I I Q G5 DN X -2 X I J 0 0 5 x.5. uP-A 1 ' I ON I K2 -7x84 -D 7E) ' 'ZI s _J111 I I– a Gb DN. X G4 DN _.. ' _..� I I - =� = d?� iwL2txta I9 x I =w I�x2bi W�a�t2Z ` - i. Li -PH i 1 P £ f. 1 I .� i -. I DNI TS . 4 X2 XIV4 — __ ,rj ?° w1.2xi.a - 4092X1/4 Gl DN � / A � � W14 X22 i I I * WIC. I Wt2Xl -4 I•._ DNW L4 Gb DN G8 DN X 55.1 I UP >µ 4JCI0 ,X. .�GN GI GI DN Record The 1 1rraB elle DRAWING No: O s K 0 1 1 3 D 1 r ELEVATOF2 -D 7E) ' 'ZI s _J111 I I– a Gb DN. X G4 DN _.. ' _..� I I - =� = d?� iwL2txta I9 x I =w I�x2bi W�a�t2Z ` - i. Li -PH i 1 P £ f. 1 I .� i -. I DNI TS . 4 X2 XIV4 — __ ,rj ?° w1.2xi.a - 4092X1/4 Gl DN � / A � � W14 X22 i I I * WIC. I Wt2Xl -4 I•._ DNW L4 Gb DN G8 DN X 55.1 I UP >µ 4JCI0 ,X. .�GN GI GI DN Record The 1 1rraB elle DRAWING No: O s K 0 1 1 3 D Architect of at Vail Square REFERENCE: 5113D f OF 2 4240 Owner / Developer ISSUE: PERMIT REY Vail Resorts DATE: 03/24/05 Dcnvcr, Corrado Development Company SCALE: N.T.S. DRAWN BY: VSH Avon, Colorado 7 O p vv ( - I VIM i c I vn I tin iy I G5 VN\ - iW8X11O GI X_ - 7 0 -4 1 - 7'- 4 I l' X 4 .D I X -BRACE n1j 3 D21UP X; ,Q ` fl I _0 I `_0 G5 ON -- _ i __ WIOX12 wIOx2 1= { f .9 .D f UP Q I N F_ 0 f j 1 61 R X -BAGS €` ' I I s f I 5 23 DOWN f 14- I 1 _ Xs i w 12*14 _ 1 � - d I W14X2.2 ; It I 12 ON I wbxii - UP 4.12 —4 I V41 r wl I X �Ca /- G8 � i I i S WbXIOi � i DR w14X22 , r X B�AGc 15'25 i rI 9 t l GI ON w p X € / "1026 �DN DN w WBXI DI - - W14X22 }� m �� X X ? GS ON }��— �; J 55.1 -I GS ON d 1 � - -- 1� raxr2T X fI (U= . TT X' "Wl6X-12 I NtllO ON I I r PCIGE ( X -BRACE D -19 I f -- UP , L W X14 V41 I x< X 4 ✓ f G I Wt6X26 0 � I � II ON G9 ON Z' - 6 - s OF I I ... .. - "12x14 I -- i I I I I w1 1_ Architect of Record - The ArraBelle DRAWING NO: OOK — � I 1 3D . at Vail Square ���^ REFERENCE S 113D 2 OF 2 � J ORncr / Developer ISSUE. PERI�ff REV Vail Resorts DATE: 03/24/05 Denver, Colorado Devel Comp P h SCALE: N T.S. DRAWN BY: �(SH Avon, Colorado 5X10 X X X l X X X x �0 I %Z %0 %Z_ --- __..._3 .._.. _._. ...._..........._._...._..._... _ _ _ .. -- - -�. - -- - _ —.. __._..........._....._..., _ c ..............:. 55.1 p 55.1 p i 0 p 6X57 (6 i r W r c Arch" oERecord The ArraBelle at Vail Square DRAWiNG No OOK -0115C 4 :2< 40 REFERENCE: S115C 1 OF 1 Owner /Developer ISSUE: PERMIT REV U Vail Resorts DATE: 04 /07/05 _ Den3jr, Colorado Development Company Y- 1 8 1' -0" Avon, Colorado DRAW W I / B Y: H - TE \TION STEEL TYPICAL BENT BEAM SECTION 4 o k, , A 2 a rn N 7 m N O O N 7 Arch ccoERecord The Ar raBelle DRAWING No: OOK— 15.3 O at Vail Square 42 REFER S5. 1 1 Owner / Developer RE ISSUE: PER�1T REV Vail Resorts DATE: 04 /07/05 Den kr, Colorado Development Company SCALE: 31 a 1' -0" DRAi^IN 6Y: SH Avon, Colorado 01 L INW, I BMW 0.9 09 j R ff� V wl I LOU. f. 10 A 0 '111 41 .M. O OWL 111 .I L%P- M I lull 9 w Ni 7 SO-