HomeMy WebLinkAboutA502.1ALEVEL 05
153' - 5 1/2"
G
ICE AND WATER SHIELD, 2'-0" BEYOND
INSIDE FACE OF WALL, AND CONT.
DOWN EXT. FACE OF WALL (2 LAYERS)
8"
KNIGHT WALL VERTICAL CI-
GIRT, FASTENED TO STUD
5/8" EXT. GYP. BOARD
SHEATHING
THERMAX C.I.
FIBER CEMENT BOARD
VERTICAL PANEL SYSTEM
STANDING SEAM METAL ROOF PANEL
MTL TRANSITION FLASHING OVER TOP OF
WALL, SLOPE AWAY FROM ROOF
W/ CONT. BUTYL TAPE AT FACE OF WALL
CONT. STARTER STRIP SET IN CONT. BUTYL TAPE
PRE-FINISHED 24
GA METAL
GUTTER WITH
HEAT TRACE.
SLOPE 1/8"/ 1'- 0".
ROOF UNDERLAYMENT, LAPPED OVER FASTENERS
5/8" GYP. BD. DECK
MTL. ROOF DECK
MANSARD TRUSS RE: STRUCT.
R30 ROCK WOOL
BATT INSUL.
LEADER FROM
GUTTER WITH
HEAT TRACE
RE: PLUMB.
5/8" EXT. GYP. BOARD
(2) ROWS SNOWFENCE W/ ROOF MFG. APPROVED FASTENERS
6" R25 ROOK WOOL
INSULATION.
CONTINUOUS CLEAT
VENT STRIP
6" VARIES, MAX - 10" 6" MAX 1 1/2"
VARIES
SHEET MTL UNDER
UNDERLAYMENT TO
SUPPORT MEMBRANE @
TRANSITION
STRIP-IN FLASHING ON TOP
OF BACK LEG OF GUTTER W/
ICE AND WATER SHIELD
LOW-SLOPE AIR
BARRIER &VAPOR
RETARDER CONTINOUS
OVER GYP. BD DECK;
INSTALL BEFORE OVER
FRAMING
SEALANT AT ENTIRE
PERIMETER OF PIPE
PENETRATION
WEATHERMATE FLEXIBLE
OR LIQUID FLASHING
ICE AND WATER SHIELD;
LAP OVER FACE OF
THERMAX 4" MIN.
SHEET MTL
FLASHING W/
HEMMED DRIP
BRAZE
CONTINUOUS 24 GA
PIPE LEADER BOX
ENCLOSURE
PIPE INSULATION
SLOPE
FLEXIBLE OR LIQUID
FLASHING SEAL PIPE
PENETRATION AT
WEATHER BARRIER
3/4" FRT.
PLYWOOD 1'-4 3/4"
3/8" 3 1/2"
FIXED
ELEVATION
23
SPRAY APPLIED SEALANT
37
FIBER CEMENT BOARD VERTICAL
PANEL SYSTEM
KNIGHT WALL VERTICAL CI-GIRT,
FASTENED TO STUD
THERMAX C.I.
5/8" TYPE-X GYP. BOARD
SUSP. CLG. GRID AND ACT
RE: FINISH SCHEDULE
5/8" TYPE-X GYP. BOARD RETURN AT HEAD
MTL. STUD BOX HEADER
FRT. WOOD BLOCKING
CENTER HORIZONTAL PIVOT WINDOW
EXT. FACE ALIGNED W/ EXT. FACE OF SHEATHING
5/8" EXT. GYP. BOARD SHEATHING
6" MTL. STUD
VENT STRIP
SHEET MTL FLASHING
W/ DRIP EDGE
WEATHERMATE FLASHING,
PRIOR TO ALL PENETRATIONS, AND
LAPPED OVER VENT STRIP
SHIMS
1" X 3 1/2" WINDOW SNAP TRIM
CONT. BACKER ROD AND SEALANT
AT 1/2" PERIMETER JOINT
1/2"
HORIZONTAL TRIM
NOTE: AT LEVEL 4 ONLY, ALIGN
INSIDE FACE OF WINDOW FRAME
W/ INSIDE FACE OF GYP.BD.
FLEXIBLE FLASHING
2" RIGID INSULATION
BOARD
6" R23 BLOWN IN
FIBERGLASS INSULATION
BLOWN IN INSULATION
NETTING
VAPOR RETARDER/AIR
BARRER FILM
37
J.2
1 1/8"
1/2"
MTL. COPING
5"
CONTINUOUS FRT
WD. BLOCKING
VENT STRIP
FIBER CEMENT BOARD
VERTICAL PANEL SYSTEM
KNIGHT WALL VERTICAL CI-
GIRT, FASTENED TO DECKING
MTL. DECK
RE: STRUCT.
HORIZONTAL TRIM AT
PANEL JOINT
STL. TUBE FRAME
RE: STRUCT.
DRIP CAP TRIM,
EXTEND ATTACHMENT
FLANGE AS REQUIRED
CAP ALL TUBES TO PREVENT
WATER INFILTRATION
ALIGN T.O COPING W/
T.O COPING @ MANSARD
157' - 8 1/2"
B.O TUBE
SLOPE
3' - 5"
TO ROOF
SELF-ADHESIVE
WEATHER BARRIER
SELF-ADHESIVE
WEATHER BARRIER
LEVEL 05
153' - 5 1/2"
SLOPED PARAPET COPING
FIBER CEMENT BOARD
VERTICAL PANEL SYSTEM
VENT STRIP
KNIGHT WALL VERTICAL CI-GIRT,
FASTENED TO STUD
THERMAX C.I.
5/8" EXT. GYP. BOARD SHEATHING
SINGLE PLY ROOF MEMBRANE,
CONTINUED UP PARAPET WALL
OVER TOP AND LAP OVER FACE OF
THERMAX
5"
5/8" EXT. GRADE FRT PLYWOOD
6" MTL. STUD
COVER BOARD
TAPERED ROOF INSUL.
5/8" GYP. BOARD DECK
MTL. ROOF DECK
6" R25 ROCK WOOL
INSULATION
CANT STRIP
5/8" EXT. GRADE FRT PLYWOOD
SLOPE
SPLICE
AIR BARRIER &
VAPOR RETARDER
SPRAY APPLIED SEALANT
37
LEVEL 4
140' - 8"
K
6 1/8"
EXIST. BRICK VENEER
EXIST. CONC. SLAB
CELL VENT WEEP, 32" O.C.
MTL. FLASHING,
TURNED UP CAVITY
WEATHERMATE FLASHING
GASKETED BRICK TIE, TYP.
SOLDIER COURSE
(SITE SALVAGED)
SLOPED ROW LOCK SILL TO
MATCH EXISTING (SITE
SALVAGED BRICK)
MTL. FLASHING W/ END DAMS
AND HEMMED EDGE
VENT STRIP
FIBER CEMENT BOARD
VERTICAL PANEL SYSTEM
WEATHERMATE FLASHING
1 1/8"
CELL VENT, 32" O.C.
WEEP THROUGH MORTAR DEFLECTOR
162' - 4 1/2"
T.O. TRUSS
STANDING SEAM ROOF PANEL
ROOF UNDERLAYMENT
5/8" GYP. BOARD DECK
MTL. DECK
MANSARD TRUSS
RE: STRUCT.
J-CHANNEL
TRANSITION COPING
VERTICAL STANDING SEAM ROOF PANEL
WEATHER BARRIER/ ROOF UNDERLAYMENT
5/8" EXT. GYP. BOARD SHEATHING
MTL. DECK
Z-CLOSURE
CONTINUOUS FRT WD. BLOCKING
1"
1'-0"
11"
1'-0"
LEVEL 05
153' - 5 1/2"
SINGLE PLY ROOFING
MEMBRANE FLASHING,
CONTINUE UP WALL AND
TERMINATE BEHIND
WEATHER BARRIER
CONTINUE LOW SLOPE
AIR BARRIER & VAPOR
RETARDER
SELF-ADHERING AIR
BARRIER & VAPOR
RETARDER CONTINOUS
OVER GYP. BD. DECK;
INSTALL BEFORE OVER
FRAMING
CANT STRIP
VERTICAL STANDING SEAM ROOF PANEL
WEATHER BARRIER, LAPPED OVER
ROOFING MEMBRANE & BACK LEG OF
COUNTER FLASHING
5/8" EXT. GYP. BOARD SHEATHING
MTL. DECK
MANSARD TRUSS
RE: STRUCT.
R30 ROCK WOOL BATT INSUL.
TERMINATION BAR
2-PIECE FLASHING, W/ SNAP-IN
COUNTERFLASHING
MTL. DECK
RE: STRUCT.
EXT. GYP. BOARD DECK
RE: STRUCT. MIN.
7"
MIN.
1'-0"
23
FIBER CEMENT
BOARD VERTICAL
PANEL SYSTEM
THERMAX C.I.
5/8" EXT. GYP. BOARD
SHEATHING
5/8" GYP. BOARD
6" MTL. STUD JAMB
J-CHANNEL TRIM (OMIT FRONT LEG)
KNIGHT WALL VERTICAL C.I. GIRT
5/8" GYP. BOARD JAMB
1/2"
1/2"
WEATHERMATE FLASHING
WRAPPED AROUND OPENING
BACKER ROD AND SEALANT
CENTER HORIZONTAL PIVOT WINDOW
1" X 3 1/2" WINDOW SNAP TRIM
JOINT SEALANT
2" RIGID INSULATION
BOARD
6" R23 BLOWN IN
FIBERGLASS
INSULATION
VAPOR RETARDER/AIR
BARRIER FILM
37
B
CURTAIN WALL
INSUL. MTL. PANEL
POCKET CLOSURE
BATT INSUL.
TERM. BAR W/ SEALANT AT JOINT
WEATHERMATE WRAPPED AROUND OPENING
MTL. DRIP EDGE
STOREFRONT
4"
EXTEND METAL FLASHING
INTO NEW SAWCUT REGLET
PAINTED 5/8" GYP.
BOARD. SUSPENDED ON
3/4" HAT CHANNELS ON 1
1/2" CROSS FURRING
COLD ROLLED CHANNELS
SEAL & SECURE AIR BARRIER TO
WALL WITH SELF- ADHERED
WEATHER/AIR BARRIER
R30 FOIL FACED BATT
INSULATION. FULLY TAPE
SEAMS AND PERIMITER.
20
000 3" 6" 9"
SCALE:
N
This document is the property of Heery International, Inc. and Heery International Inc. retains all
rights therein, including copyrights. It may only be used in a manner consistent with Heery
International Inc.'s rights while Heery International, Inc. is providing services for the specific project
identified or referred to herein or extensions thereto. It may not be used for any other purpose
except with the express written agreement of, and compensation to, Heery International Inc.
Copyright © 2013 by Heery International, Inc. all rights reserved.
WHEN PLOTTED AT FULL SIZE THIS SHEET MEASURES 30"x42"
drawn by checked by
sheet number
sheet title
item date
date
issued for
seal/signature
consultants/construction managers
owner's project number
project number
3" = 1'-0"
Heery International
555 17th Street, Suite 500
Denver, CO 80202
720.946.0276
OWNER'S PROJECT NUMBER
TOV:
C&S PRJ14-0157 B15-0185 (ADD#5)
TI PRJ14-0157 B15-0461 E15-0043 (ADD#6)
DFPC:
C&S 9667 (ADD#5)
TI TBD
6/15/2016
2:45:38 PM
A502.1A
Checker
Author
EXTERIOR ENVELOPE
DETAILS - FIBER
CEMENT BD & BRICK
02/06/2016
CONSTRUCTION
DOCUMENTS
VAIL VALLEY
MEDICAL CENTER
PHASE 1 - WEST WING
181 WEST MEADOW DRIVE
VAIL, CO
HII-1302604
INTERIOR DESIGN:
Gallun Snow
1920 Market Street,
Suite 240,
Denver, CO 80202 720.407.6002
MECHANICAL, ELECTRICAL,PLUMBING, LOW
VOLTAGE:
Cator Ruma & Associates,Co.
896 Tabor Street,
Lakewood, CO 80401-4700 303.232.6200
CIVIL:
Martin/Martin
225 Main Street,
Unit C101,
Edwards, CO 81632 970.926.6007
LANDSCAPE:
Lime Green Design, Inc.
900 East Louisiana Avenue,
Suite 209,
Denver, CO 80210 303.733.7558
STRUCTURAL:
Structural Consultants Inc.
3400 East Bayaud Avenue,
Suite 300,
Denver, CO 80209 303.399.5154
3" = 1'-0"
3
CEMENT BOARD @ MANSARD COPING
3" = 1'-0"
4
CEMENT BOARD @ WINDOW HEAD
3" = 1'-0" 6
CEMENT BOARD @ MECHANICAL SCREEN
3" = 1'-0"
8
CEMENT BOARD @
PARAPET
3" = 1'-0" 7
CEMENT BOARD @ NEW BRICK SILL
3" = 1'-0"
1
TOP OF MANSARD
3" = 1'-0"
2
MTL PANEL SYSTEM @ MANSARD BASE
3" = 1'-0"
5
CEMENT BOARD @ WINDOW JAMB_PLAN
3" = 1'-0"
9
CEMENT BOARD SOFFIT @ CURTAIN WALL
2 ADD #2 07.16.2015
5 ADD #5 TOV, DFPC 10.20.2015
20 ASI #12 02.03.2016
23 ASI #15 TBD
37 ASI #28 06.15.2016
01/04/17