HomeMy WebLinkAbout352 E Meadow Dr #BTOWN OF VAIL FIRE DEPARTMENT VAIL FIRE DEPARTMENT
75 S.FRONTAGEROAD
VAIL, CO 81657
970-479-2t35
NOTE: THIS PERMIT MUST BE POSTED ON IOBSITE AT ALL TIMES
SPRINKLER PERMIT Permit #: F04-0052
Job Address: 352 E MEADOW DR VAIL Status . . . : ISSUEDLocation.....: 352 E. MEADOW DR., LJNIT B Applied . . : l0lt3l200r'.
Parcel No...: 210108255007 Issued. . : 01/10/2005
Project No , -pR tO I -o0Ytf Expires . .:
om{ER VAZQVEZ, NYL,SA M. n/a3/2oo4 phone:
BOX 50
MAUAGI'AZ
PI'ERTO RIEO OO7O9
I_,icense:
CoNTRACTOR ALIr STATE FrRE PROTECTIOII, IL0/t3/2004 phone: 303-288-3901
5045 E 76TH #L2
COMMERCE CITY CO
40022
License: 370-S
APPIIICAI{IT AJ-,L STATE FIRE PROTECTION, ITO/LT/2004 PhONE: 303-288-3901
6045 E 75TH #L2
COMMERCE CITY CO
aoo22
Lricense: 370-S
Descipion: INSTALL FIRE SPRINKLER SYSTEM
Valuation: $6,500.00
**tl't+***************t**+,|.{i+:}++*,rrl*t't *'r,*tt*t.**r.*********'t **i.***{.*d.t*** FEE SIJtMMARY********t,t++,1**i.++t*++**{.******,1'l't:l***,i*!t*********)t***'t +t+**
M€chanical-- > 90.00 Reshnrant Plan Review- >
Plan check--> $3 50. 00 DRB Fee-------------- >
Investigation- >
Will Call--- >
$0.00 TOTAL FEES-------> S629.2s Toral Pemit Fee-----> $626.2s
PaynEnts--------------- > $626 -25$3 .00
rJa'-.-\ U;tt-ft-\9"
3(\Ls, a^..J g
Uti'tAu
$0. o0 Totsl Calculated Fees--> i629.2550.00 Additional Fees-----> ($3.00)
BALANCE DTJE---._ >$0. 0o
Item: 05100 BUIIJDING DEPARII{EIIIItem: 05600 FfRE DEPARTIiIE:NI
to/L4/2o04 mcgee Action: Ap
CONDITION OF APPROVAL
Cond: 12(BIJDG.); FIEI-,D IITSPBCTIONS ARE REQUIRED TO CIIECK FOR CODE COMPLIAIICE.
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in fulI the information required, completed an accurate plot
plan, and state that all the information as required is correct. I agree to comply with the information and plot plan, to comply
with all Town ordinances and state laws, and to build this stnrcture according to the towns zoning and subdivision codes, design
review approved, Uniform Building Code and other ordinances of the Town applicable thereto.
REQIIESTS IOR INSPECTION SHALL BE MADE TWENTY-FOUR EOURS IN ADVAI\CE BY TELf,PHONE AT 479-2135
FROM 8:00 AM - 5PM.
Vail,qi!;B1657
FT
********f,********|t**********'********|t**,o*o,,,8gt.k#-
APPLICATION WILL NOT BE ACCEPTEO IF INCOMPLETE OR UNSI
Projeet #;- ooV
LF LICATION
Fire Sprinkler shop drawings are required at time of permit submittal andmust include the following. Permit application will not be acceptedithout -this irformation :
.E.T. Level lll (min) stamp.
bA
o Pla tion Contractor.
CONTRACTOR INFORMATION
VALUATIONS FOR ALARM PERMTT (Labor & Materiats)
Fire Sprinkler: $
Bullding Permit #:
Sprlnkler Permit #:
mvry0FYtn
75 S. Frontage Rd.
r's
||al
Fire Sprinkler Contractor:
At\-Sto\e Frrp Prntec\n
Town of Vail Reg. No.:r 3-to(Contact and Phone #'s:[Ai\€ ( aca)aqs.3qol
E-Mail Address:
Contractor Signature:_fr ,_O o *_ Jr^"l6r)(_
PLETE
Contact Assessors Office at 970-32A-A640 or visit for Parcel #Parcel# StOtC>54-\O-l
'oo
t""'Vozrruf z \.)n\l JobAddress:4Fl E Me-ac\o\Ars.. f
Lesat Description ll r_ot: ll ebcr:lri3Oll ririns:subdivision:\l6il M+ I mhfo*n"tt ruame:NtFrr Vo- y]
Engineer: Mi W Address:Ltl4E! E -?h*- A\F Phon'12.13p9q -19al
Detailed Location of work: (i.e., floor, unit #, bldgr #)
Detailed description of work:lffsjal\ r€ Sr'rirrV \ec S.rs-\ern
ti/ork Class: New ( ) Addition ( , Remodel {} |!EA
No. of Existing Dwelling Units in this buitding:Y .EfiAA ibfitiii"iiirnii 6litdins :
Does a Fir6 Alarm Exist: Ves ( ) No t I IlIbo
-COM.DE
07t24i200)
ALL-STATn FIRE PROTECTTON. TNC.
6045 E. 76t" AVE. #12, Commerce Cify, CO 80022
Phone (303) 288-3901 * Fax (303) 288-1936
FIRE SPRINKLER
PLANS
AND
EQUIPMENT SUBMITTAL
FOR
Z-,,z;10 '*fn/- ..,/
v,es fi_ rfi *;# s)npApT,rtf NI
Approuod er tiubrnl$ed Elz-
Yazqrtgz
Ysilugfrnl" 'o"t-to,u .
T;JJ F uhhy
MICHAEL KRZASTEK
NICET LEVEL III, # 93492
I I I I
EXISTING T_I/?'
I III
O AO - TYCI LFII RESIDENTIAL
196 SQUARE FTET PER
I I
CUNCEALER (K=4.2, 155F)
HEAD MAXIMUM SPACING
r
TXISTING I-I/?'
t-1h 4-th -
LIVING RONM
I
(E) BALCONY
3RD LtVtL PLAN
SCALT I/B'=I'0'
(E) BALCONY
?tq I ?r--
SCALE l/8'=['-0'
4TN LTVEL PLAN
SCALT I/B'=I'0'
VASAUIZ UNiTVAIL M!UNTAIN LIDGI352 T. MIADIV DR
VAIL, C[.
ALL_STATf FIRf PRTTtCTi[N, INC.
6045 t. 75TH AVt #1e
CIMMIRCI CITY, Ct] 8OOA2
ILL-STATC
NORTH CA
ttvEt ||lItl4ta
DESTC|{[8 VsK
scrtt NTS
o{cK aY MsKI IF|FE PRorEcrroN. rNc
STATE REGISTRATION
#008
F[t NullasR 2,10065
DlrE lO/7/O4
DR^TNTNG No. t-1O|B
-a,r,\ irilI | ;1""1
\o
E
--J
Ll-,
LLJ
-J
Z.{
L
M.EnI
Lr-
,,---'\ LJ-J
IU<rr,/r )
,v)_l
tr----,
-tl<-M
LrJ p-)r
=2.
Fzl
N
L,rJlG(/)
EB ll
rF
E.
f^t
Z.
IIIII
I
I
I
I
I
I
I
I
I
I
I
I
I
I
-L (JZ-Znacu.) cu-oi" cu c::: I-COu -{+-cl (v-u o-uF-la <L-J
, tr'\)J z4,-z> o4->-
t_t ./f L_) | |"":z a ,,"r LI- + F-_-lz- l_ F--1 Frl) z { r,rrD --L-,.J f Fr''N->E; iltr-
=> .rl-t,rM) l,t (,/\ - t,l
-J I IUt>\/) 4 a\t r---1 ' <-<<)x<--ix=>>b>au-
ulcl-l; =4:F
hli En
,i{lF : +Jttr t!'
IFMoZ
|-.-Otu
I
LJ
LJJ
Z.{J
O-
v.En)
L-
:LJ
,- -JT{vg
, ('/)_l I r----<;u
"' F)n.Z
F
zl
N
LrJl
f--x,
(A
{
I
T
I
I
I Series LFII Besidential
Concealed Pendent Sprinklers, FIat Plate4.2 K-factor
Ittlco lFire&Buitdins- | Products ffi-
Technical Services: Tel: (800) 381-93.12 / Fax: (800) 791-5500
C ustomer Servic€/Sa les:
Tel: (414) 570-5000 / (800) 558-5236
Fa:<: (4141 570-5010 / (800) 877-1295
I
I
I
I
I
I
I
T
I
I
I
I
I
I
General
Description
The Series LFll (TY2596) Residential
Concealed Pendent Sorin klers are
decorative, fast response. fusible sol-der sprinklers designed for use in resi-
dential occupancies such as homes,
apartments, dormitories, and hotels.
The cover plate assemblv conceals lhe
sprinkler ope rating comf onents abovethe ceiling. The flat profile of the coverplate provides the optimum aestheti-
cally appealing sprinkler design. In ad-dition, the concealed desion of the Se-ries LFll (TY2596) providles 1/2 inch(12,7 mm) verlical adjustment. This
adjustmenl r€duces the accuracv lo
which the fixed pipe drops to the sfrin-klers must be cul to help assure a
Derfect fit installation.
The Series LFll are to be used in wetpipe residential sprinkler syslems for
one- and two-famrly dwellings and mo-bile homes per NFPA 13D; wet pipe
residential sprinkler systems lor resi-dential occupancies up to and includ-ing four stories in height per NFPA
138; or, wet pipe sprinkler systems forthe residential portions of any occu-pancy per NFPA 13.
The Series LFll (TY2596) has a 4.2(60,5) KJactor that provides the re-
quired residential flow rates at reduced
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLEB
WARNING' that provides cautjons
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. lmproper handling and in-
stallation can permanently damagea sprinkler system or its compo-
nents and cause the sDrinkler to fail
to operate in a fhe situation or cause
it to operate prematurcly.
pressur€s, enabling smaller pipe sizes
and water supply requirements.
The Series LFll (TY2596) has beendesigned with heat sensitivily andwater distribution characleristics
proven to help in the control of residen-
tial fires and to improve the chance for
occupants lo escape or be evacuated.
The Series LFll (TY2596) Residential
Concealed Pendent Sprinklers are
shipped with a Disposable Protective
Cap. The Protective Cap is temporarily
removed tor inslallation, and then it
can be replaced to help protect the
sprinkler while the ceiling is being in-
slalled or f inished. The tiD of the Pro.
tective Cap can also be used to mark
the center of the ceiling hole into plas-ter board, ceiling tiles, etc. by gen y
pushing the ceiling product against the
Protective Cap. When the ceiling in-
stallation is comDlete the Protective
Cap is r€moved and the Cover Plate
Assembly installed.
WARNINGS
The Series LFll (TY2596) Residential
Concealed Pendent Sprinklers de-
suibed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Fallure to do so may
impafu the pertormance of these de-
vlces.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinklermanufacturer should be contacted
with any questions.
Sprinkler/Model
ldentification
Number
srN TY2596
Technical
Data
Approvals:
UL and C-UL Listed. NYC Aporoved
under MEA 44-03-E.
Maximum Wotking Pressure:
175 psi (12,1 bao
Discharge Coetflcient:
K = 4.2 GPM/psit/2 (60,5 LPM/bar1/2)
Temperalure Raling:
1 60"F/7 1 "C Sprinkler wilh
135"F/57"C Cov€r Plate
Verlical Adjustmenl:
1/2 inch (12,7 mm)
Finishes:
Cover Plate;
Flat White, Bright White, Chrome, or
Cuslom
Physical Characteristica:
Body . . BrassCap. . . BronzeSaddle Brass
Sealing Assembly ......... Beryllium Nickel w/ Teflont
Soldered Link Halves ..... NickelLever Bronze
Compression Screw . BrassDeflector Copper
Page I of 4 APB|L,2OO4 TFP44O
t
I
I
I
I
I
t
I
I
I
I
t
I
t
I
I
I
I
I
Page 2 ol 4
Guide Pin Housing . Bronze
Guide Pins Stainless Steel
Support Cup ... Steel
Cover Plate CooperRetainer ...... Brass
Cover Plate Eiection Spring . . .
Stainless Steel
tDuPont Registered Trademark
Operation
When exposed to heat trom a f ire, the
Cover Plate, which is normallv sol-
dered to the Support Cup at -three
points, falls away to expose the Sprin-
kler Assembly. At this point the Deflec-
tor supported by the Arms drops down
to its operated oosition.The fusible linkof the Sprinkler Assembly is com-prised of two link halves that are sot-
dered together with a thin layer of sol-
der. When the rated temDerature is
reached, the solder melts and lhe two
link halves separate allowing the sprin-
kler to activate and flow water.
Design
Criteria
The Series LFll (TY2596) Residential
Concealed Pendent Sprinklers are UL
and C-UL Listed for installation in ac-
cordance with the following criteria.
NOTE
When conditions exist that are outside
the scope ot the provided criteria, referto the Residential Sprinkler Design
Guide TFP49O for the manufacturer's
recommendations that may be accept-
able to the Authotity Having Jurisdic-
tion.
System Type. Only wel pipe syslems
may be utilized.
Hydraulic Design. The minimum re-quired sprinkler flow rate for systems
designed to NFPA 13D or NFPA 13R
are given in Table A as a function of
temperature rating and the maximum
allowable coverage areas. The sprin-
kler flow rate is the minimum required
discharge from each of the total
number of "design sprinklers" as speci-
fied in NFPA 13D or NFPA 13R.
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is to be the greater of the following:
. The flow rates given in Table A for
NFPA 13D and 13R as a lunction of
temperature rating and the maxi-
mum allowable coverage area.
e A minimum discharge of 0.1 gpm/sq.
ft. over the "design area" comprisedof the four most hydraulically de-
manding sprinklers tor the aclual
coverage areas being protected by
the four sprinklers.
Obstruction To Water Distrlbution.
Locations of sprinklers ara to be in
accordance with tha obstruction rules
of NFPA 13lor residential sprinklers.
Operatlonal S€nsltivity. The sprin-
klers are to be installed relative to the
ceiling mounting surface as shown in
Figure 3.
Sprinkler Spacing. The minimum
spacing between sprinkl€rs is 8 feet(2,4 m). The maximum spacing be-
tween sprinklers cannol exceed the
length ofthe coverage area (Ref. Table
A) being hydraulically calcuiated (e.9.,
maximum 12 feel for a 12 lI. x 12 11.
coverage area, or 20 feet tor a 20 fi. x
20 ft. coverage atea).
lnstallation
The Series LFll (TY2596) must be in-
stalled in accordance with the follow-
ing instructions:
NOTES
Damage to lhe tusible Link Assembly
during installation can be avoided by
handling the sprinkler by the frame
arms only (i.e., do not apply pressure
to the tusible link Assembly).
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs, (9,5 to 19,0 Nm). A maxL
TFP44O
Maximum
Covsrage
Area (a)
Fl. x Ft.
(mxm)
Maxlmum
Spacing
Ft.
(m)
Minimum Flo,v (b) and
Rssidual Pressui€
For Horizontal Cslllng
(Max. 2 Inch Rise
lor 12Inch Run)
Minlmum Flow (b) and
R€sldual Pressure
For Sloped Celllng
(Gr€alsr Than 2 Inch
Rlse Up To
Max. 4 Inch Rls€
for 12 Inch Run)
Mlnlmum fl6y (b) 3nil
R€sldual P|asgure
For Sloped Cslllng
(Graater Than 4 lnch
Rlse Up To
Max. I Inch Rlse
for 12 Inch Run)
1@'Fn1'C
Sprlnkler
160'Frf1"C
Sprinkler
160'F 1'C
Spdnkler
12x12
(3,7 x 3,7)(3,7)
13 GPt\4 (49,2 LPM)
9.6 psi (0,66 bar)
18 GPM (68,1 LPM)
18.4 psi (1,27 bar)
18 GPM (68, t LPM)
18.4 psi (1,27 bar)
14 x'14
(4,3 x 4,3)
14
(4,3)
14 GPM (53,0 LPM)
1 1.1 psi (0,Z7 bar)
18 GPM (68,1 LPM)
18,4 psi (1,27 bao
18 GPM (68,1 LPM)
18,4 psi (1,27 bar)
16x16
(4,9 x 4,9i
16
(4,9)
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
18 GPM (68,1 LPM)
18.4 psi (1,27 bar)
18 GPM (68,1 LPM)
18.a psi (1,27 bar)
18 x 18
(5,5 x 5,5)
18
tc,c,
20 GPM (75,7 LPM)
22.7 psi (1 ,57 bar)
20 GPM (7s,7 LPM)
22.7 psi (1,57 bar)
t\UA
20x20
(6,1 x 6,1)
20
(6,1)
24 GPM (90,8 LPM)
32.7 psi (2,25 bar)
26 GPM (98,4 LPM)
38.3 psi (2,64 bar)
N/A
(a) For coverage area dimensions less than or between those indicated, it is necessary lo use the minimum required llow tor thenext highest coverage area for which hydraulic design criteria are stated.
(b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calc latedusing the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.
TABLE A
NFPA 13D ANO NFPA 13R HYDRAULIC DESIGN CRITERIA
FOR THE SEB/ES LFU (Ty2596) RESTDENTIAL CONCEALEO qENDENT SPRINKLER
lFP440
I
I
I
I
I
I
I
I
I
I
t
I
I
I
I
T
I
I
I
BODY
(1/2" NPT)
SUPPORT
CUP WITH
ROLL FORMEO
THREAOS
GUIOE
PIN
SPRINKLER
WRENCHING
AREA
COMPFESSION
SCREW
SEALING
ASSEMBLY
GUIDE PIN
HOUSING
SOLDER LINK
ELEMENT
OEFLECTOR
(OPEFATED
POSTT|ON)
RFTAINER
WITH THREAD
DIMPLES
EJECTION
SPRING
DEFLECTOR
THREAD INTO
SUPPOFIT CUP
UI.ITIL MOUNTING
SUFFACE IS
FLUSH wrrH
CEILING
COVER PLATE/RETAINEB
ASSEMBLY
FIGURE 1
SERiES LF" (TY2596) RESTDENZAL
CONCEALED PENDENT SPRINKLER
Page 3 of 4
mum of 21 ft.lbs. (28,5 Nm) ol torgueis to be used to install sDrinklers.
Higher levels of torque may distort the
sprinkler inlet wlth conseeuent teak-
age or impahment of the sprinkler.
Do not attempt to compensate tor in-
sufficient adjustment in an Escutcheon
Plate by under- or over-tightening tha
Sprinkler. Readjust the position of the
sprinkler fitting to suit.
Step 1, The sprinkler must only beinstalled in the pendent position and
with the centerline of the sprinkler per-
pendicular to the mounting surtace.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant ap-plied to the pipe threads, and using
the W-Type 18 Wrench shown in Figure
2, install and tighten lhe Sprinkler/Sup-port Cup Assembly into the fitting. The
W-Type 18 Wrench will accepl a 112
inch ratchet drive.
WRENCH
RECESS
(ffi'^t\t4 i \|v1I| | lJV"
PUSH WBENCH
IN TO ENSURE
ENGAGEMENT
WITH SPBINKLER
WRENCHING AREA
F'GUNE 2
W.TYPE 18
SPR'NKLERWNENCH
_ 2-1/2 DtA.SPRINKLEF.
SUPPORT CUP
ASSEMBLY
OPERATEO
SPRINKLER
COVEF
PLATE
RETAINER
senu.xr-en. IsuPPoRT CUP IASSEMBLY I
=r_112' (12,7 .r'r|,l
1" (25,4 mm)T--Ii.- s-vl o' DrA. -(81,0 mm)DISPOSABLETIP PROTECTIVE CAP
FIGURE 3
SERIES LFII (TY259q NESDENTIAL CONCEALED PENDENT SPRINKLER
INSTALLATION DIMENSIONS / PROTECTIVE CAP / ACTIVATED DEFLECTOR
DEFLECTOF IN
OPERATED POSITION
SPRINKLEF
FITTING
1/8" GAP
(3,2 mm)
I
I
I
I
I
I
I
I
T
I
I
I
I
I
I
T
I
I
Page 4 ol 4
Slep 4. Replace the Protective Cap bypushing it upwards until it bottoms out
against lhe Support Cup. The protec-
tive Cap helps prevent damage to the
Deflector and Arms during ceiling in-
stallation and/or during application ol
the finish coating of th6 ceiling. lt may
also be used to locate the center of the
clearance hole by gently pushing theceiling material against the center
ooinl of the Cao.
NOTE
As long as the prctective Cap remains
in place, the system is considered to
be 'Out Ot Service".
Step 5. After the ceiling has been com-pleled with Ihe 2-112 inch (63 mm)
diameter clearance hole and in Dreoa-
ralion for installing the Cover Plate As-
sembly, remove and discard lhe Pro-tective Cap, and verify that the
Deflector moves up and down f reely.
lf the Sprinkler has been damaged andthe De{lector does not move up and
down freely, replace the entire Sprin-
kler assembly. Do not attempt lo mod-
ify or repair a damaged sprinkler.
Step 6. Screw on the Cover Plate As-
sembly until its flange comes in con-
tact with the ceiling.
Do not continue to screw on the Cover
Plale Assembly such that it lifts a ceil-
ing panel out of its normal position.
lf the Cover Plate Assemblv cannot be
engaged with the Mountind Cup or the
Cover Plate Assemblv cannot be en-gaged sufficienily to boniact the ceiL
ing, the Sprinkler Fitting must be repo-
silioned.
Care and
Maintenance
The Series LFll (TY2596) must be
mainlained and serviced in accord-
ance with the following instructions:
/vo7Es
Absence of an Escutcheon Plate mav
deley the sprinkler operation in a tiie
siluetion.
Beforc closing a fire protection system
main control valve lor maintenance
work on the lire protection system
which it controls, permission to shut
down the atfected fire protaction sys-
tem must be obtained from the proper
authorities and all perconnel who may
be aftected by this action must be no-
tified.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be reolaced.
Automatrc sorinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied or over heated sprinklers must be
replaced.
Care musl be exercised to avoid dam-
age - before, during, and atter instal-
lation. Sprinklers damaged by drop-
ping. striking, wrench twisUslippage,
or the like, must be replaced.
The owner is resDonsible for the in-
spection, testing, and mainlenance oftheir tire protection syst€m and de-vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.9., NFPA 25), in
addition to the standards of anv other
authorities having jurisdiction. ihe in-
stalling conlraclor or sprinkler manu-
factursr should be conlacted relative to
any questions.
NOTE
The ownet must assurc that the sorin-
klers are not used lot hanging oi any
objects and that the sprinhlers are only
cleaned by means of gently dusting
with a leather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
It is recommended thal automalicsprinkler systems be inspected,
tssted, and maintained by a qualified
Inspection Service in accordance wilhlocal requirements and/or national
codes,
Limited
Warranty
Products manufactured by Tyco Fire
Producls are warranted solely to theoriginal Buyer for ten (10) years
against deiects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warrantv will ex-
pire ten (10) years lrom date o{ ship-
ment by Tyco Fire Products. No war-ranly is given for products or
components manufactured by compa-
nies not affiljated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with apolicable Standards oflhe National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate.
rials found by Tyco Fire Products to be
defective shall be either reoaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authoriz€s any person lo
assume for it, any other obligation in
TFF44O
connection with the sale of products orparts ol products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurale orincomplete information supplied by
Buyer or Buyer's representalives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON.
TBACT, TORT, STRICT LIABILITY OB
UNDEB ANY OTHER LEGAL THE.ORY FOR INCIDENTAL, INDIRECISPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOH CHARGES, RE.
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCHDAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS'LI.ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
Ordering
Procedure
When placing an order, indicatethe full
product name. Contacl your local dis-
tribulor for availability..
Sprinkler Assembly:
Series LFll (TY2596), K=4.2, Residen-
tial Concealed Pendent Sorinkler with-
out Cover Plate Assambly,
PiN 51-122-1-160.
Cover Plale Assembly:
Cover Plate Assembly having a (spec-
ify) finish for the Series LFll (TY2596),
K=4.2, Residential Concealed Pen-
dent Sprinkler, P/N (specify).
Chrome.................. P/N56-122-9-135
Otf While . . . . . . . . . . . . . . . . . P/N 56.122-0-135BrightWhile............... PN56.122-4-135
Flat Whlie .. P/N 5&122-5-135
v\hite {RAL90'10)'. ... ... .., P/N 56-122-3"135
Custo.n ...... P/N 56-122-X-135
'Easlern Hemisphsre sales only.
Sprlnkler Wrench:
Specify: W-Type 1 I Sprinkler Wrench,
P/N 56-000-1-265.
I
TYCO FIRE PRODUCTS,451 Norlh Cannon Av€nue, Lansdale, Pennsylvania 19446