HomeMy WebLinkAboutB07-0023 PlansKRMCONSULTANTS, INC. [9701949-9391
P.O. Box 4572 FAX 949-1 577
Vail, Colorado B1 B5B
RECORD
TO: Lawrence Rogers Architect
DATE. 1/30/2007
PROJECT. O'Shaugnnessy Remodel, L@L #220
❑ RFI ❑ MEETING NOTES ® RESPONSE
JOB NUMBER: 0612-11
❑ CLARIFICATION/CHANGE
This record is in regards to a request to add stone veneer to a fireplace, located in the Lodge at Lionshead
Phase II unit #220 in Vail, CO. Full height 4" stone veneer (9'-0 max. height) will be added to the face of the
fireplace, as well as a stone mantel and hearth. The existing floor structure consists of precast concrete double
tee's which span the width of the building. A continuous L4x4xl/4 steel angle (approximately 6-6" long) should
be added to support the stone veneer above the mantel. This angle should be fastened to a C4x5.4 header
supporting the stud wall behind the veneer with 1/2" diameter through bolts @ 24" o.c. The header shall span
the width of the fireplace and be supported by (2) studs at each end. Otherwise it appears the existing structure
is adequate to support the anticipated design loads.
Please call with any questions or concerns.
S/GNE COPY TO:
ael P. Strumph
REVIEWED:
Tim D. Hennum, PE
x
m ~n~Ytk a~
D 1/3~f ~U `7
BXUV.U419 - Fire Resistance Ratings - ANSI/UL 263
Page 1 of 4
BXUV.U419
Fire Resistance Ratings - ANSI/UL 263
Page Bottom
Fire Resistance Ratings - ANSI/UL 263
See General Information for Fire Resistance Ratings - ANSI UL 263
Design No. 0419
November 28, 2006
Nonbearing Wall Ratings - 1, 2, 3 or 4 Hr (See Items 3 & 4)
For Nurtiber of I«vers
and Hourly [atiil ti
See Rem 4
- vie
` _
3 2
. '3k
~l
i
i
' 4.~'.
.
:
,
i.......,.........._.
I
4
1. Floor and Ceiling Runners - (Not shown) - For use with Item 2 - Channel shaped, fabricated from min 25 MSG
corrosion-protected steel, min width to accommodate stud size, with min 1 in. long legs, attached to floor and ceiling with
fasteners 24 in. OC max.
1A. Floor and Ceiling Runners* - Not shown - In lieu of Item 1 - For use with Item 2A, proprietary channel shaped, min. 3-
5/8 in. wide with 1 in. long legs, fabricated from min. 0.0150 in. (0.0146 in., min bare metal thickness) galvanized steel,
attached to floor and ceiling with fasteners 24 in. OC max.
DIETRICH INDUSTRIES INC - UltraSTEEL@.
16. Floor and Ceiling Runners - (Not shown - In lieu of Item 1) - For use with Item 2A, proprietary channel shaped, min.
2-9/16 in. wide with 1-3/16 in. wide flanges, fabricated from min. 0.0150 in. galvanized steel, attached to floor and ceiling
fasteners 24 in. OC. max.
DIETRICH INDUSTRIES INC - UltraSTEEL®.
2. Steel Studs - Channel shaped, fabricated from min 25 MSG corrosion-protected steel, min width as indicated under Item 4,
min 1-1/4 in. flanges and 1/4 in. return, spaced a max of 24 in. OC. Studs to be cut 3/8 to 3/4 in. less than assembly height.
http://database.ul.com/cgi-binIXYV/template/LISEXT/ 1 FRAME/showpage.html?name=BXUV.U419&c... 1/21/2007
BXUV.U419 - Fire Resistance Ratings - ANSI/UL 263
Page 2 of 4
2A. Steel Studs* - In lieu of Item 2 - Proprietary channel shaped studs, min. width as indicated under Item 4, min. 1-1/4 in.
long legs and 1/4 in. long folded back return flange legs, fabricated from min. 0.0155 in. (0.0149 in., min bare metal thickness)
galvanized steel, spaced a max of 24 in. OC. Studs to be cut 3/8 to 3/4 in. less than assembly height. Allowable use of studs is
shown in the table below. For direct attachment of gypsum board only.
DIETRICH INDUSTRIES INC - UltraSTEEL@.
3. Batts and Blankets* - (Required as indicated under Item 4) - Mineral wool batts, friction fitted between studs and
runners. Min nom thickness as indicated under Item 4. See Batts and Blankets (BKNV or BZ]Z) Categories for names of
Classified companies.
3A. Batts and Blankets* - (Optional) - Placed in stud cavities, any glass fiber or mineral wool insulation bearing the UL
Classification Marking as to Surface Burning Characteristics and/or Fire Resistance. See Batts and Blankets (BKNV or B7-]Z)
Categories for names of Classified companies.
4. Gypsum Board* - Gypsum panels with beveled, square or tapered edges, applied vertically or horizontally. Vertical joints
centered over studs and staggered one stud cavity on opposite sides of studs. Vertical joints in adjacent layers (multilayer
systems) staggered one stud cavity. Horizontal joints need not be backed by steel framing. Horizontal edge joints and
horizontal butt joints on opposite sides of studs need not be staggered. Horizontal edge joints and horizontal butt joints in
adjacent layers (multilayer systems) staggered a min of 12 in. The thickness and number of layers for the 1 hr, 2 hr, 3 hr and 4
hr ratings are as follows:
CANADIAN GYPSUM COMPANY - 1/2 in. thick Type C, IP-X2 or IPC-AR; WRC, 5/8 in. thick Type AR, C, IP-AR, IP-X1, IP-X2,
IPC-AR, SCX, SHX, WRX or WRC; 3/4 in. thick Types IP-X3 or ULTRACODE
UNITED STATES GYPSUM CO - 1/2 in. thick Type C, IP-X2, IPC-AR or WRC; 5/8 in. thick Type SCX, SHX, WRX, IP-X3, AR,
C, WRC, FRX-G, IP-AR, IP-X2, IPC-AR ; 3/4 in. thick Types IP-X3 or ULTRACODE
USG MEXICO S A DE C V - 1/2 in. thick Type C, IP-X2, IPC-AR or WRC; 5/8 in. thick Type AR, C, IP-AR, IP-X1, IP-X2, IPC-
- AR, SCX, SHX, WRX, WRC or; 3/4 in. thick Types IP-X3 or ULTRACODE
When Item 6B, Steel Framing Members*, is used, Nonbearing Wall Rating is limited to 1 Hr. Min. stud depth is 3-1/2 in., min.
thickness of insulation (Item 3) is 3 in., and two layers of gypsum board panels (1/2 in. or 5/8 in. thick) shall be attached to
http://database.ul.com/cgi-binIXYVItemplatelLISEXTI1 FRAMElshowpage.html?name=BXUV.U419&c... 1/21/2007
Wallboard Protection on Each Side of Wall
BXU V. U419 - Fire Resistance Ratings - ANSI/UL 263
Page 3 of 4
furring channels as described in Item 5. One layer of gypsum board panels (1/2 in. or 5/8 in. thick) attached to opposite side of
stud without furring channels as described in Item 5.
4A. Gypsum Board* - (As an alternate to Item 4) - 5/8 in. thick, 24 to 54 in. wide, applied horizontally as the outer layer to
one side of the assembly. Secured as described in Item 5.
CANADIAN GYPSUM COMPANY - Type SHX.
UNITED STATES GYPSUM CO - Type FRX-G, SHX.
USG MEXICO S A DE C V - Type SHX.
5. Fasteners - (Not shown) - For use with Item 2 - Type S or S-12 steel screws used to attach panels to studs (Item 2) or
furring channels (Item 6). Single layer systems: 1 in. long for 1/2 and 5/8 in. thick panels or 1-1/4 in. long for 3/4 in. thick
panels, spaced 8 in. OC when panels are applied horizontally, or 8 in. OC along vertical and bottom edges and 12 in. OC in the
field when panels are applied vertically. Two layer systems: First layer- 1 in. long for 1/2 and 5/8 in. thick panels or 1-1/4 in.
long for 3/4 in. thick panels, spaced 16 in. OC. Second layer- 1-5/8 in. long for 1/2 in., 5/8 in. thick panels or 2-1/4 in. long for
3/4 in. thick panels, spaced 16 in. OC with screws offset 8 in. from first layer. Three-layer systems: First layer- 1 in. long for
1/2 in., 5/8 in. thick panels, spaced 24 in. OC. Second layer- 1-5/8 in. long for 1/2 in., 5/8 in. thick panels, spaced 24 in. OC.
Third layer- 2-1/4 in. long for 1/2 in., 5/8 in. thick panels or 2-5/8 in. long for 5/8 in. thick panels, spaced 12 in. OC. Screws
offset min 6 in. from layer below. Four-layer systems: First layer- 1 in. long for 1/2 in., 5/8 in. thick panels, spaced 24 in.
OC. Second layer- 1-5/8 in. long for 1/2 in., 5/8 in. thick panels, spaced 24 in. OC. Third layer- 2-1/4 in. long for 1/2 in. thick
panels or 2-5/8 in. long for 5/8 in. thick panels, spaced 24 in. OC. Fourth layer- 2-5/8 in. long for 1/2 in. thick panels or 3 in.
long for 5/8 in. thick panels, spaced 12 in. OC. Screws offset min 6 in. from layer below.
5A. Fasteners - (Not shown) -For use with Item 2A - Type S or S-12 steel screws used to attach panels to studs (Item 2).
Single layer systems: 1 in. long for 1/2 and 5/8 in. thick panels or 1-1/4 in. long for 3/4 in. thick panels, spaced 8-1/2 in. OC
with additional screws 1 in. and 2-1/2 in. from edges of the board when panels are horizontally. or 8 in. OC along vertical and
bottom edges and 12 in. OC in the field when panels are applied vertically. Two layer systems applied vertically: First layer-
1 in. long for 1/2 and 5/8 in. thick panels or 1-1/4 in. long for 3/4 in. thick panels, spaced 16 in. OC. Second layer- 1-5/8 in.
long for 1/2 in., 5/8 in. thick panels or 2-1/4 in. long for 3/4 in. thick panels, spaced 16 in. OC with screws offset 8 in. from first
layer. Two layer systems applied horizontally: First layer- 1 in. long for 1/2 and 5/8 in. thick panels or 1-1/4 in. long for
3/4 in. thick panels, spaced 16 in. OC starting 8 in. from each edge of the board with an additional screw placed 1-1/4 in. from
each edge of the board. Second layer- 1-5/8 in. long for 1/2 in., 5/8 in. thick panels or 2-1/4 in. long for 3/4 in. thick panels,
spaced 16 in. OC starting 8 in. from each edge of the board with an additional screw placed 1-1/4 in. from each edge of the
board with screws offset 8 in. from first layer. Three-layer systems: First layer- 1 in. long for 1/2 in., 5/8 in. thick panels,
spaced 24 in. OC. Second layer- 1-5/8 in. long for 1/2 in., 5/8 in. thick panels, spaced 24 in. OC. Third layer- 2-1/4 in. long for
1/2 in., 5/8 in. thick panels or 2-5/8 in. long for 5/8 in. thick panels, spaced 12 in. OC. Screws offset min 6 in. from layer
below. For all layers, an additional screw shall be placed 1-1/4 in. from each edge of the board. Four-layer systems: First
layer- 1 in. long for 1/2 in., 5/8 in. thick panels, spaced 24 in. OC. Second layer- 1-5/8 in. long for 1/2 in., 5/8 in. thick panels,
spaced 24 in. OC. Third layer- 2-1/4 in. long for 1/2 in. thick panels or 2-5/8 in. long for 5/8 in. thick panels, spaced 24 in. OC.
Fourth layer- 2-5/8 in. long for 1/2 in. thick panels or 3 in. long for 5/8 in. thick panels, spaced 12 in. OC. Screws offset min 6
in. from layer below. For all layers, an additional screw shall be placed 1-1/4 in. from each edge of the board.
6. Furring Channels - (Optional, not shown, for single or double layer systems) - Resilient furring channels fabricated from
min 25 MSG corrosion-protected steel, spaced vertically a max of 24 in. OC. Flange portion attached to each intersecting stud
with 1/2 in. long Type S-12 steel screws. Not for use with Item 4A.
6A. Steel Framing Members (Not Shown)* - (Optional on one or both sides, not shown, for single or double layer systems)
- As an alternate to Item 6, furring channels and Steel Framing Members as described below:
a. Furring Channels - Formed of No. 25 MSG galv steel. 2-3/8 in. wide by 7/8 in. deep, spaced max.
24 in. OC perpendicular to studs. Channels secured to studs as described in Item b. Gypsum board
attached to furring channels as described in Item 5. Not for use with Item 4A.
b. Steel Framing Members* - Used to attach furring channels (Item 6Aa) to studs (Item 2). Clips
_ spaced max. 48 in. OC., and secured to studs with No. 8 x 1-1/2 in. minimum self-drilling, S-12 steel
screw through the center grommet. Furring channels are friction fitted into clips.
PAC INTERNATIONAL INC - Type RSIC-1.
6B. Steel Framing Members (Optional, Not Shown)* - As an alternate to Item 6, furring channels and Steel Framing
Members on only one side of studs as described below:
http://database.ul.com/cgi-binIXYV/template/LISEXT/ 1 FRAME/showpage.html?name=BXUV.U419&c... 1/21/2007
BXU V.U419 - Fire Resistance Ratings - ANSI/UL 263
a. Furring Channels - Formed of No. 25 MSG galv steel, spaced 24 in. OC perpendicular to studs.
Channels secured to studs as described in Item b. Batts and Blankets placed in stud cavity as described
in Item 4. Two layers of gypsum board attached to furring channels as described in Item 4. Not for use
with Item 4A.
b. Steel Framing Members* - Used to attach furring channels (Item 6Ba) to one side of studs (Item
2) only. Clips spaced 48 in. OC., and secured to studs with two No. 8 x 2-1/2 in. coarse drywall screws,
one through the hole at each end of the clip. Furring channels are friction fitted into clips.
KINETICS NOISE CONTROL INC - Type Isomax
Page 4 of 4
7. Joint Tape and Compound - Vinyl or casein, dry or premixed joint compound applied in two coats to joints and screw
heads of outer layers. Paper tape, nom 2 in. wide, embedded in first layer of compound over all joints of outer layer panels.
Paper tape and joint compound may be omitted when gypsum panels are supplied with a square edge.
8. Siding, Brick or Stucco - (Optional, not shown) - Aluminum, vinyl or steel siding, brick veneer or stucco, meeting the
requirements of local code agencies, installed over gypsum panels. Brick veneer attached to studs with corrugated metal wall
ties attached to each stud with steel screws, not more than each sixth course of brick.
9. Caulking and Sealants* - (Optional, not shown) - A bead of acoustical sealant applied around the partition perimeter for
sound control.
UNITED STATES GYPSUM CO - Type AS
*Bearing the UL Classification Mark
Last Updated on 2006-11-28
Questions? Notice of Disclaimer
Page Top
Copyright n 2007 Underwriters Laboratories Inc .@
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under
UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always
look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information,
Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings).
2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the
extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright © 2007 Underwriters
Laboratories Inc.®"
tin 'ndere IC1 erganizaiion ~<<orkifl g for a safer vv orld tn infegrit,. Precision and knn~tiledge
0
http://database.ul.comlcgi-binIXYV/templatelLISEXTI1 FRAMElshowpage.html?name=BXUV.U419&c... 1/21/2007
XHEZ.C-AJ-2282 - Through-penetration Firestop Systems
Pagel of 3
XHEZ.C-AJ-2282
Through-penetration Firestop Systems
Page Bottom
Through-penetration Firestop Systems
See General Information for Through -penetration Firesto Systems
System No. C-AJ-2282
November 29, 2005
F Rating - 2 Hr
T Rating - 1 Hr
L Rating At Ambient - Less Than 1 CFM/sq ft
L Rating At 400 F - Less Than i CFM/sq ft
W Rating - Class 1 (See Item 4B)
4A
I
1
r3
f
Section A-A
i
~I
1. Floor Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400
kg/m3 ) concrete floor or min 5 in. (127 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3 )
concrete wall. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 5 in. (127 mm).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
< a
http://database.ul.com/cgi-binIXYV/templatelLISEXT/1 FRAMElshowpage.html?name=XHEZ.C-AJ-228... 1/24/2007
SAW-
s
A
i
XHEZ.C-AJ-2282 - Through-penetration Firestop Systems
Page 2 of 3
2. Steel Sleeve - (Optional) -Nom 5 in. (127 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe or nom 5 in. (127
mm) diam (or smaller) No. 26 GA (0.022 in. or 0.56 mm thick) sheet metal sleeve with square flange spot welded to the sleeve
at approx mid-height and sized to be a min of 2 in. larger than the sleeve diam cast or grouted into floor or wall assembly,
flush with floor or wall surfaces.
2A. Nonmetallic Sleeve - (Optional) - Nom 5 in. (127 mm) diam (or smaller) polyvinyl chloride (PVC) sleeve cast into floor at
time of concrete placement.
3. Through Penetrant - One nonmetallic pipe, conduit or tube to be centered within the firestop system. The annular space
between the pipe or conduit and the periphery of the opening shall be nom 1/4 in. (6 mm). Pipe to be rigidly supported on both
sides of the floor or wall assembly. The following types and sizes of nonmetallic pipes, conduits and tubes may be used:
A. Polyvinyl Chloride (PVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 cellular or
solid core polyvinyl chloride (PVC) pipe for use in vented (drain, waste or vent) or closed (process or
supply) piping systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) SDR 13.5
chlorinated polyvinyl chloride (CPVC) pipe for use in closed (process or supply) piping systems.
C. Rigid Nonmetallic Conduit+ - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 PVC conduit
installed in accordance with Article 347 of the National Electrical Code (NFPA No. 70).
D. Electrical Nonmetallic Conduit+ - Nom 4 in. (102 mm) diam (or smaller) PVC tubing installed in
accordance with Article 331 of the National Electrical Code (NFPA No. 70).
E. Acrylonitrile Butadiene Styrene (ABS) - Pipe Nom 4 in. (102 mm) diam (or smaller) Schedule
40 cellular or solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent)
piping systems.
4. Firestop System - The firestop system shall consist of the following:
A. Fill, Void or Cavity Material* -Wrap Strip - Nom 1/8 in. (3.2 mm) or 3/16 in. (4.8 mm) thick
intumescent material faced on both sides with a plastic film, supplied in 2 in. (51 mm) wide strips. For
nom 2-1/2 in. (64 mm) through 4 in. (102 mm) diam through penetrants, two stacks of wrap strip,
each consisting of one wrap strip layer are individually wrapped around the through penetrant with the
ends butted and held in place with a layer of aluminum foil tape. For nom 2 in. (51 mm) diam or smaller
through penetrants, one layer of wrap strip wrapped around the through penetrant with the ends butted
and held in place with a layer of aluminum foil tape. For nom 2-1/2 in. (64 mm) through 4 in. (102 mm)
diam through penetrants, the wrap strips are installed such that the bottom edge is flush with the
bottom surface of the floor. For nom 2 in. (51 mm) diam through penetrants, the wrap strips are
installed such that the bottom edge is recessed 2 in. (51 mm) from the bottom of the floor. In walls, the
wrap strips are installed with the exposed edges recessed 1/2 in. (13 mm) from each surface.
SPECIFIED TECHNOLOGIES INC - SpecSeal BLU Wrap Strip or SpecSeal BLU2 Wrap Strip.
B. Fill, Void or Cavity Material *-Sealant - In floors, min 1/2 in. (13 mm) thickness of fill material
applied within the annulus on top surface of wrap strip. In walls, min 1/2 in. (13 mm) thickness of fill
material applied within the annulus, flush with each surface of the wall. When required as specified in
Item 4A, min 1/2 in. (13 mm) thickness of fill material applied within the annulus flush with both
surfaces of floor. As an option in floors, generous bead of sealant applied to leading edge of wrap strip
prior to insertion into annular space. Sufficient sealant shall be applied to cover lead edge of wrap strip
and to fill annular space between the wrap strip and the concrete.
SPECIFIED TECHNOLOGIES INC - SpecSeal 100 , 101, 102, 105, 120 or 129 Sealant, SpecSeal LCI
Sealant, Pensil 300 Silicone Sealant, or Pensil 300 SL Silicone Sealant.
W Ratings apply when min 1/2 in. (13 mm) thickness of Pensil 300 or Pensil 300 SL is applied flush with
top surface of floor.
*Bearing the UL Classification Mark
+Bearing the UL Listing Mark
http://database.ul.com/cgi-binIXYV/template/LISEXT/ 1 FRAME/showpage.html?name=XHEZ.C-AJ-228... 1/24/2007
XHEZ.C-AJ-2282 - Through-penetration Firestop Systems
Last Updated on 2005-11-29
Questions? Notice of Disclaimer
Page Too
Page 3 of 3
Copyright n 2007 Underwriters Laboratories Inc
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under
UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always
look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information,
Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings).
2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the
extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright © 2007 Underwriters
Laboratories Inc.@"
An independent organization working for a safer world vv ith integrity, precision and knowledoe.
(Ir~
http://database.ul.com/cgi-binIXYVItemplatelLISEXT/1 FRAMElshowpage.html?name=XHEZ.C-AJ-228... 1/24/2007
XHEZ.W-J-1030 - Through-penetration Firestop Systems
Pagel of 2
XHEZ.W-3-1030
Through-penetration Firestop Systems
Page Bottom
Through-penetration Firestop Systems
See General Information for Through -penetration Firesto S stems
System No. W-3-1030
December 17, 1996
F Rating - 2 Hr.
T Rating - 0 Hr.
.r
SECTION A-A
1. Wall Assembly - Min 6 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Wall may also be constructed
of any UL Classified Concrete Blocks*. Max diam of opening is 25 in.
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for the names of manufacturers.
2. Through Penetrant - One metallic pipe, tubing or conduit to be installed either concentrically or eccentrically within the
firestop system. The annular space between pipes, tubing or conduits and periphery of opening is dependent upon the type and
max diam of the through penetrant as tabulated below. Pipe, tubing or conduit to be rigidly supported on both sides of wall
assembly. The following types and sizes of metallic pipes, tubing or conduits may be used:
A. Steel Pipe - Nom 24 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1 FRAME/showpage.html?name=XHEZ. W-J-1030... 1/21/2007
XHEZ.W-J-1030 - Through-penetration Firestop Systems
Page 2 of 2
B. Iron Pipe - Nom 24 in. diam (or smaller) cast or ductile iron pipe.
C. Copper Tubing - Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
D. Copper Pipe - Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe.
E. Conduit - Nom 4 in. diam (or smaller) steel electrical metallic tubing, nom 6 in. diam galv steel conduit
or nom 1 in. diam flexible steel conduit.
Type of Max Diam of
Through Min & Max
Through Penetrant Annular Space
Penetrant In.
In.
Steel or Iron Pipe 4
0, 1-1/2
Steel Tubing or Conduit 4
0, 1-1/2
Steel Conduit 6
1/8, 1/2
Steel or Iron Pipe 24
1/8, 1/2
Copper Tubing or Pipe 6 1/8, 1/2
3. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. thickness of fill material applied within annulus, flush with both
surfaces of wall. At the point contact location between through penetrant and concrete, a min 3/8 in. diam bead of fill material
shall be applied at the concrete/through penetrant interface on both surfaces of wall.
SPECIFIED TECHNOLOGIES INC - LC 150, 151 152 and 155 Sealant
*Bearing the UL Classification Mark
Last Updated on 1996-12-17
Questions? Notice of Disclaimer
Page Top
Copyright n 2007 Underwriters Laboratories Inc .@
The Follow-Up appearance Service. of a Only those company's name products .or bearing product the in UL this Mark database should be does not in considered itself assure that products so identified have been manufactured
under UL's
the Mark on the product.
to be Listed and covered under UL's Follow-Up Service. Always look for
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: of The Guide Information,
Designs and/or Listings (files) must be presented in their entirety and in anon-misleading manner, without any manipulation of the data e drawings). 2.
The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the
extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright © 2007 Underwriters
Laboratories Inc.@"
Ar inrfependenf orya 1-1 ization working fc:r a safer Etorlr with ifl fegrity. precision and knoeiledge.
i
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1 FRAME/showpage.html?name=XHEZ. W-J-1030... 1/21/2007
BXUV.P905 - Fire Resistance Ratings - ANSI/UL 263
Page 1 of 5
BXUV.P905
Fire Resistance Ratings - ANSI/UL 263
Page Bottom
Fire Resistance Ratings - ANSI/UL 263
See General Information for Fire Resistance Ratings - ANSI UL 263
Design No. P905
April 06, 2006
Restrained Assembly Rating 1, 1-1/2 and - 2 Hr. + (See Item 4D).
Restrained Assembly Rating - 2 Hr.
Unrestrained Assembly Rating - 1/2 Hr.
+(Applicable only when stems are spaced 4 ft or less on centers)
Load Restricted for Canadian Applications - See Guide BXUV7
Kestroined
End Detail
Unrestroined
End Detoil
http://database.ul.com/cgi-binIXYV/templatelLISEXT/1 FRAMElshowpage.html?name=BXUV.P905&cc... 1/21/2007
BXUV.P905 - Fire Resistance Ratings - ANSI/UL 263
tI
Restrained
End Detcii
Page 2 of 5
Unrestrot ed
End Detail
1. Roof Covering* - Consisting of hot mopped or cold application materials compatible with insulation(s) described herein
which provide Class A, B Or C coverings. See Roofing Materials and Systems Directory-Roof Covering Materials (TEVT).
1A. In lieu of Item 1, roof covering consisting of single-ply Roofing Membrane* - that is either ballasted, adhered or
mechanically attached as permitted under the respective manufacturer's Classification. See Fire Resistance Directory - Roofing
Membranes (CHCI).
2. Joint - Precast units to be butted together.
3. Minimum Bearing - 3 in.
4. Insulating Concrete - Various types of insulating concrete applied in the thickness indicated below:
A. Perlite Concrete - Total thickness, min 2 in., max 6 in. 4 to 6-cu ft Perlite Aggregate* to 94-lb
Portland cement and 2 pt of air entraining agent.
See Perlite Aggregate (CFFX) category for names of manufacturers.
Al. Foamed Plastic* (Optional) - Foamed plastic insulation boards with holes and slots. For use
only with perlite concrete. Max thickness 4 in.
CELLOFOAM NORTH AMERICA INC
DYPLAST PRODUCTS L L C
B. Vermiculite Concrete - Total thickness, min 2 in., 6 to 8-cu ft Vermiculite Aggregate* to 94-lb
Portland cement and 0.125 lb air entraining agent.
GRACE CANADA INC
ELASTIZELL CORP OF AMERICA - Types MS16-U, MSV 200.
MANDOVAL LTD
MANDOVAL VERMICULITE PRODUCTS INC
PALMETTO VERMICULITE CO
http://database.ul.com/cgi-binIXYV/template/LISEXTI1 FRAMElshowpage.htmi?name=BXUV.P905 &cc... 1/21/2007
BXUV.P905 - Fire Resistance Ratings - ANSI/UL 263
Page 3 of 5
SIPLASTINC
STRONG CO INC
VERMICULITE PRODUCTS INC
131. Foamed Plastic* (Optional) - Foamed plastic insulation board with holes and slots for use only
with vermiculite concrete. Max thickness 8 in.
SIPLASTINC
VERMICULITE PRODUCTS INC
C. Cellular Concrete - Total thickness min 2 in.; 3.6 cu ft of stabilized preformed foam to 94 b
Portland cement premixed with 6-1/4 gal of water. Cellular concrete to have a dry density of 30 I
+or-
3.0 pcf and a 28-day compressive strength of 125 to 475 psi as determined in accordance with ASTM
C495-66.
C3. Cellular Concrete - Roof Topping Mixture* - Concentrate mixed with water and Portland
cement per manufacturer's specifications. Cast dry density and 28-day min compressive strength of min
190 psi as determined in accordance with ASTM C495-66. Thickness of cellular concrete shall be min 2
in.
CELCORE INC - Type Celcore with cast dry density of 31 or - 3.0) pcf or Type Celcore MF with cast
dry density of 29 or - 3.0) pcf.
CELLULAR CONCRETE L L C - Cast dry density 37 or 3.0 pcf.
ELASTIZELL CORP OF AMERICA - Type H. Mix #1 of cast dry density 39 or 3.0 pcf, Mix #2 of
cast dry density 40 or 3.0 pcf, Mix #3 of cast dry density 47 or 3.0 pcf.
LITE-CRETE INC - Cast dry density of 29 or 3.0 pcf,
SIPLAST INC - Mix #1. Cast dry density 32 or 3.0 pcf.
VERMICULITE PRODUCTS INC
C2. Foamed Plastic* - (Optional) - For use only with cellular concrete. Max thickness 8 in. with 1-
1/2 in. diam holes.
C3. Foamed Plastic* - (Optional) - For use with cellular concrete. Max thickness 8 in. and containing
both hole and slot configuration.
SIPLASTINC
VERMICULITE PRODUCTS INC
D. Vermiculite Concrete - Slurry coat 1/8 in. thickness, min 1 in. topping thickness, 3.5 cu ft. Type
NVC Concrete Aggregate* or Type NVS Vermiculite Aggregate* to 94 lb Portland cement.
SIPLASTINC
VERMICULITE PRODUCTS INC
Dl. Foamed Plastic* - Foamed plastic insulation board with holes and slots for use only with
vermiculite concrete. Min thickness 3- 1/8 in., for 2 hr rating. Foamed plastic is optional for 1 and 1-
112 hr rating.
http://database.ul. corn/cgi-binIXYV/templatelLISEXTI I FRAMElshowpage.html?name=BXUV.P905&cc... 1/21/2007
BXU V.P905 - Fire Resistance Ratings - ANSI/UL 263
SIPLASTINC
VERMICULITE PRODUCTS INC
E. Cellular Concrete - Roof Topping Mixture* - Foam Concentrate mixed with water, Portland
Cement and UL Classified Vermiculite Aggregate per manufacturer's application instructions. Cast dry
density of 33 or 3.0 pcf and 28-day compressive strength of min 250 psi as determined in
accordance with ASTM C495-86.
ENGLEHARD CORP EXAUST CONTROLS INC - Mix #3.
SIPLAST INC - Mix #3.
El. Foamed Plastic* - (Optional) - For use with cellular concrete. Max thickness 8 in. and containing
bother hole and slot configuration.
SIPLASTINC
VERMICULITE PRODUCTS INC
F. Roof Topping Mixture* - Approx 4.5 gal of water to 41 Ibs of NVS Premix floor topping mixture.
Slurry coat 1/8 in. thickness beneath foamed plastic, when used, 1 in. min topping thickness.
SIPLASTINC
Fl. Foamed Plastic* - Foamed plastic insulation board with holes and slots for use only with Roof
topping mixture, min thickness 3-1/8 in., for 2 hr rating. Foamed plastic is optional for 1 and 1-1/2 hr
ratings.
SIPLASTINC
5. Precast Concrete Units* - Single- or double stemmed, lightweight or normal weight aggregate.
See Precast Concrete Units category for names of manufacturers.
*Bearing the UL Classification Mark
Page 4 of 5
Last Updated on 2006-04-06
Questions? Notice of Disclaimer Page Top
Copyright n 2007 Underwriters Laboratories Inc .@
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under
UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always
look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information,
Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings).
2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must appear adjacent to the
extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright © 2007 Underwriters
Laboratories Inc.@"
w
N
http://database.ul.comlcgi-binIXYV/templatelLISEXTI1 FRAMElshowpage.html?name=BXUV.P905&cc... 1/21/2007
I ~ ~ ~ J
, , ~ ~e r~ -
, ~ ~ r~rc~h~t~ct,
{j ~ ~ p,a. bax 421
UNIT #224- O'SHAUGNN~S~Y ~ ~J LY ~ ~ Y ~ ~ esdwcarda, ca blb~2
FINAL KITGHEN/GABINET ~ ~ PA?€'~GH WALL AT ENTRY GL05ET ~ ► DE51GN PER KITGHEN F ~ ~ f L
GONSULTANT t ~ DELETED DOOR {TYP ~ T W GP/T EX EX p ago-ate--tlbs
iA I '1/ IA f' a7a-x{26-"fl6'7
aA FLOOR 4 IrAY'G}ll';t'IGt~GaY71Ga0~J1C~ PENETRATION
Rig ~ e~opuE ~ ias G~ 01 ~ FULL TILE SURROUND I
_ ~ _ AT TUB WITH DUROGK 0 o O~ 4' I%" 5 -I" 6AGKER BOARD
BATH ° WH BATH ~ GL RaaM RaaM ~ GLOSET ~ ~ S~~ ~ DW REF _ N- I
~ 4'-10'is", ~ -II I ~ ti ~ ~ I I W q
m BATHROOM ~ T T GP/T EX EX
~ i I ~ ~ FF(- - 3 - Q ~'~..d i _'h FLOOR
FULL TILE SURROUND ~ - KITGHEN AT SHOWER ENGLDSURE - ~ N-- i i _I_ W _ i ~ i ~ 5~2~~ Z~_S~~ I ~ 2A ENETRPtTION _ 1 ~ t - ~ ~a W/D u ~
WITH DUROGIC BAGKER m m I I ~ KITGHEN ~ ~ I BATHROt7M #2
~ BOARD _ ~n ~n WER T T GP EX=EX I ~ -J ~ ~ T T CAP/T EX EX
~ ° ~ d r IA ~ ~ r IA _ ~ ~-2' 6'-S~" 3'!~2° 03 ~ 11 "T°1 ' RELOGATED
1~ m 7/ ~ ~ _ WATER HEATER m - 15LAND W/ GERAMIG TILE FLOOR,
_ Rg5 ! I I I`\ - RCS ~ VERIFY FINAL DOOR 51EE
_ `i Oq i i / dT 4 ply„ S~~ 5~y~f~~~ WH ~ ~ IA
~ ~ GL~ d~ GL _ cv N (i1 _ cv GL05E ~ ii m i I I I I ~ BENG W/ BBIES ABV. GLOSET ~ '
.~1C1 ~Ql~IL#I~Q_._ ~ ~ _ ~ ~ ~ ` ~ ~ m
08
NOTE: LINE OF 50FFIT ~ 05 O6 TO BE REMOVED ~ ~ ~
C.DNTRAGTDR SHALL PREPARE ALL SUBFLaaR A55EMBLlES FDR FINAL TYP DELETED ~ ~
FLDORINC~ INSTALLATION, FINAL FLaa REMOVE EXISTING ~
FINISHES Ta BE IN5TALLED WITH EVEN 4'~" TRANSITIONS BETWEEN MATERIALS
Il'-b" 13'..la~~ ~~_5~~
~
~
BEDRaaM DINING/LIVINa 6EDRaaM
HALGaNY
I ~ D~?R P~~ I5T
a 1 2 4 Feet
~'-a.' v
ALIGN W/ TaP G~NE~241. NC7T~5 : ~?DOi~S
DF DaaR GASE
- I. SEE FLaaR PLANS FOR DDDR LDGATIOP
2. ALL SWINGING, DOORS TD RECEIVE STDi" 5TORAGE GUBBIES- _
ALDER 3. SUISMIT HARDWARE SCHEDULE AND DDOE a
~ ~ 4, INTERIaR ODORS AND Fi~AMES SHALL B WINDOW TREATMENT WINDOW TREATMENT i' i ~ ~ 1
AND VALANCE N.I,G. AND VALANCE N.I,G, II E ; GDNTRAGTaR TD VERIFY ALL ROUGH DG ~ ~ 1
I ~ I ~ ~ ~ CLEARANCE FOR FINISH TRIM, IN CASE C ! ~ ~ {
3' " x ~f4' ~ ( , ~I , 6, CONTRACTOR TO VERIFY ALL EXISTING ! ~ ' t
j I ~ _ REPLACE WITH SAME 51ZE DaaR UNLES°_ 3~" x ~i~' _ _ ~ ~ I~ tY ____I BEAD BaARD PANELING , I i ~ ~n CONFLICT CONTRACTOR Ta NOTIFY ARCI
I____________ i - INSIDE RECESS, 3 SIDES i I ~ , i V' i
~ ~ i - "I. ALL ODORS Ta BE HUNG iN SUCH A MANI ! ~ SHALL ALIGN WITH WINDOW HEAD TRiM ,
I I ~ $ENGH AT +1 -6 i I ( ,
3i~' X~ia" TRIM i 1 ! j „ 2a s," BOARD ~ ~ 1
~i~" X ~/a a j E ~ I
i " ~ 9r 2i2' X 3/a" TYP WALL BASE 3~Z a
HASEHOARD, 45° MITER SKIRT HOARD N D METAL ~fP ~ (NDOW AT ROU DE BA a W I
CORNER SEAR SILL BOARD
T`(PICAL INTERIOR DaaR TYPICAL BEDRaOM1LIVING Tl`PIGAL BEDRaaM WINDaW `i
ROOM DaaR } j
GU~B I ~ ~~NG~ ~~.~V~T10N
A C 1~' 3
,i,1V1' ~ ~1"'l:J I I'+<4"~ fi~~"i"'~~4 SCALE: r2, : I'_a„ ~ I~C~c~i2 ~N~ W I N TYPI~ L a I 2 4 feet
NDT Ta SCALE
50LiD GC~R~
WD 2 P>4N~L
L~40i~ ~
NaTE: ALL INTERIOR TRIM IN THIS UNIT Ta BE ALDER
~C~4~ 5G#~~I~UL~
L7C,~C?1~. ~R>~M~
_ -
TYPE WInTH HEIGHT TH1GK" M{~T'L SIN M,~T'L SIN N4. RDaM
~ OI MAIN ENTRY A 3'-0° b'-S" $EE REMARKS WOOD STAIN
02 ENTRY CLOSET A 2'-O" 6'-8" I WOOD STAIN WOOD STAIN
03 BEDROOM #2 A 2'-b" b'-8" i ~a" WOOD STAIN WOOD STAIN
04 BATHROOM ~2 A ~'-4" 6'-&" I WOOD STAIN WOOD STAIN O5 GI.C>5ET #2 A 2'-~" 6'-&" I ~a' WOOD STAIN WOOD STAIN
Ob WATER HEATER CLOSET A ~'-4" b'-8" I ~/4" WOOD STAIN WOOD STAIN-
0't $EDROOM 44 A 21-61 V-8" I WOOD STAIN WOOD STAIN 5TAIN Ml\/ACY PLATE5, 51LLS $ 5LEEPERS IN CONTACT WITH CONCRETE 5LA55 ON SRAU ANU >=OUNUATION YS^LL.S
08 OLOSET *4 S 4'-0` 91-POLD 1 -5/4" WOOD STAIN WOOD STAIN 5TAIN PA55A&E SHALL BE TREATED A5 REOUIRED 5Y CODE
O9 HATHROOM M A 2'-4" 6'-8"' I v WOOD STAIN WOOD STAIN 10 TOILET A 2'-4°POCKET `/4" WOOD STAIN WOOD STAIN STAIN PRIVACY
II GL05E7 A 2'-4" I WOOD STAIN WOOD STAIN
A L- 12 SHOWER G 21-4" V.LP. PER MANUP. GLASS
IB TUB ENCLOSURE-EWWOOM #2 - V.I V.f F. PER MANUF. GLASS METAL
t
3
A2.1 ~C,~Yd I^~d'1 ~iPs
EXISTING GE EXISTING CEILING ~ O~erS
ASSY. ASSY. -~~,1~ A~^"~~"`~--~XI5TIN6 CEILING ~~~a~~~a f .
EXISTING CE EXISTING GEILINC~ FLUE PER ~ BEAM W/ CLADDING
BEAM W/ CL REMOVED BEAM W/ CLADDING F,P. MANUF. ~ ~ _e _ _ _ _ _ _ _ F2LM4 (ES7 p.o. bax 4291 REMOVED ~ I, ~ _ _ _ _ _ . edwdrdn, as 81692
42" PLASMA Wl MOUNTING 42" PLASMA SCREEN TV PLASMA I Wl MOUNTING BR4GKET -'a``~"`"~a~, p SCREEN TV WINDOW TREATMENT p q'tt~.-q,2b-768
AND BLOCKI AND BLOCKING ~9 ' AND VALANCE N.I.G. i ~ _4 P a"f0-alb-?I6't
GONT 4X~X}~ GONT 4X4X}/4" STL ANGLE i`! ~ ~ e ~rarchttx+ctwcamcc+etnet
STONE VENE STONE VENEER SUPPORT, NEW STONE MANTEL
FASTEN TO (N STUD WAL FASTEN TO G4X5.4 HEADER C„~ AND SUPPORTS (N STUD WALL W/%" DfA ~"f
BOLTS ~A C BOLTS ~4" O.G. I ~ IM
STONE MANT STONE MANTEL ~ ~
4° STONE V~ `'---t r .J~ " _ NEW STONE 4° STONE VENEER ~ _ - - - `7 Vl✓NEER
raWN a Gain TOWN ~ COUNTRY TG 36 ~ j ~ j L
GA5 FIREPL GA5 FIREPLACE 4NSERT ~ i / ~ NEW DECORATIVE ~ ~ i FP DOORS
~ ~ FIRE ~ I'~
STONE H>rA',~ FIN. FLOOR 1 STONE HEARTH AT PLACE FIN. FLOOR LEVEL ~ i ~ ~ ~,~---TYPICAL NWLL BASE
2 HR FLOOR 2 WR FLOORf ~ i I . GEiLING A55'Y ~ ~i, "`Y " }
~L~GTi21G,~L KEY V GELLING ASS PER DET ON PER DET ON A2.2
PUCK LIGHT, MONO-POINT, SIM C~, SMOKE DETECTOR s° ALL LIGHT FIXTURE, OUTLET, SWITCH, ETC. LaCATlaNS
ARE SUBJECT TO FIELD REVIEW BY OWNER AND ARCHITECT
SSED CEILING ADJ CAN HALOGEN LIGHT WALL SWITCH ~ AND MAY CHANGE A5 A RESULT OF SUCH FIELD REVIEW. R.ECE
" INSTALL ROUGH BOXES AND COORDINATE WITH OWNER FOR
R °S ED CEILING GAN LIGHT 8-WAY WALL SWITCH ~ REVIEW PRIOR TO HARD WIRING OF ALL DEViCE5. EGC S s
OUTLETS, TV, TELEPHONE, ETG., BOXES IN BEDROOMS SHALL 0 1 ~2 feet 5GALE: ~ I~_O„
RECE55ED CEILING GAN -WATER RE515T. DIMMER WALL SWITCH ~p NOT BE INSTALLED BACK TO BACK IN SAME WALL STUD CAVITY ~v
WITH DEVICES IN ADJACENT SPACES. ADJUST LOCATIONS AS REQ'D.
RECESSED CEILING ADJ GAN LIGHT 3-WAY DIMMER SWITCH ~ SWITGN FOR FIREPLACE TO BE LIGHTED TYPE THAT 15 LIT WHEN ~ FIREPLACE IS ON.
CEILING BEAM9~ i3EAM9
WALL/SURFACE MOUNT LIGHT ~ JAMB SWITCH ~ OUTLET BOX AT WASHER/DRYER Ta BE 'TYPE THAT 15 INTEGRAL WITH FIXTURE BY OWNER ~ WATER VALVES AND WASHER WASTE CONNECTION.
N ANT FIXTURE P OUTLET- DUPLEX ~ T N T INDICATED ON THIS PLAN TO BE INCLUDED PE D ELECTRICAL OUTLE S O
PER GODS REG2UIREMENTS,
FLOURESGENT LIGHT OUTLET- ONE SIDE SWITCHED ~ ELEGTRIGAL SUBCONTRACTOR TO VERIFY THAT OUTLET LOCATIONS 7
SHOWN MEET ALL APPLICABLE CODES. NOTIFY ARCHITECT IF ADDITIONAL
UNDER CABINET LIGHTING ~ aUTLET- GFI ~~PI OUTLETS ARE REC~UIRED.
ELECTRICAL SUBCONTRACTOR Ta COORDINATE WITH OTHER SUBCONTRACTORS
CLOSET LIGHT OUTLET- MOUNTING HT 4P~5, AND SUPPLIERS AND SHALL PROVIDE ELECTRICAL NOT SHDWN HERE AS MAY !
BE REQUIRED. _ _ _
' HT FIXTURES l___ OUTLET- WATERPROOF TYPE 4" B,S.TYP TRACK ~.IG I'-C~~..~ - l ~P n THESE PLANS ARE PROVIDED aNLY TO SHOW DESIGN INTENT AND SHOULD NOT
o BE CONSIDERED A5 ELECTRICAL GON5TRUGTION DOCUMENTS, o LOW LEVEL LANDSCAPE LIGHTINCo Q aUTLET- FLOOR U
SMOKE DETECTORS PER GODS. , D/W
STEP LIGHT OR ELEC PANEL OUTLET- SPECIAL (WASHER/DRYER} ~
IF LIGHTING CONTROL SYSTEM IS INSTALLED IT SHALL BE DESIGN BUILD.
JUNCTION BOX Q TELEPHONE JACK PROVIDE GUT SHEETS AND SYSTEM OVER-VIEW FOR OWNER REVIEW.
FIXIURE BY OWNER
~ FAN ~ TV JACK (ALWAYS INCLUDE PHONE) CURRENT ELECTRICAL PLAN TO BE USED FOR PRELIMINARY PRICING ONLY.
THIS PLAN fLLUSTRATES EXTENT OF LIGHTING REVI510N AND DOES n NOT INCLUDE ALL FINAL ELECTRICAL (SWITCHING, aUTLET, CONTROL)
A T M COMPUTER DATA LAN PROTECTED OUTLET) ' RMAT N. 1`"'t f MOTOR DEVICE (EXHAUST FAN, SP TUB, E C) ( ~ c it~FO 10 SCALE: ~e = I -O
,
KITCHEN ENTRY CLOSET
EXISTING LIGHT FIXTURE EXISTING CEILING HEIGHT TO i
TO BE REMOVED NEW TEXTURE AND PAINT, TYP
t r' Tvi I _ _ . q ~ ii BATIROOM ~q
BATHROOM ~N I P i r ~ ' ~ ~ r-
I ~ . I a _ ~t _ ~ ~
~ BATHROOM #2 FI ~ ~__=I _JI- _ YID
1 I NEW CEILING
'I ~,>t , ~ ~ i a I - FAN PER HVAG a
tl , ~ ~ '~~-L~
.I f __>rl I P P P ` ALL NEW ELEC FIXTURES,
I 1~ ti T-STATS DOOR CHIME ETG. a y ~ RELOCATE CEILING
~ ( ~ ~ - TO BE ROUGH-IN APPROVED FANS AS REO D
t~ ~ ~ NEW ELEC BASEBOARD ~ HEATER IN CABINET BASE .~f}~ ~ BEFORE FINAL INSTALLATION
PER MECH CONSULTANT, li f F = - ~ - ~ a _ _ - - ~ PEN >~NT LI a
KITCHEN AND BATHROOMS. - ii ~ FI S O R NEW T-STAYS AT ALL II , ~ j
ISLA ( I HEATER LOGS ii ~ , _ _
a EXISTIN IGHT~ 1 it 1 A
" FIXTURE ra BE ~'1 ~ f'" s y I I ~ If \ li ~ REMaV ~ ~ ~ I~ II
I I II \ it s
HARDWIRE FOR PLASMA N ELEC J HARDWIRE FOR PLASMA B EBOARD I SCREEN TV, PROVIDE BLOCKING
SCREEN N, PROVIDE BLOCKING H TER FOR WALL BRACKET, FINAL FOR WALL BRACKET, FINAL ~ LOCATION V.I.F. r
LOCATION V,I.F. j rvi FINAL LIGHTING r
LOCATIONS TO BE `-J 1 ~ ~ BEDROOM ~2 FEILD VERIFIED (TYP)
Ya. ~ BEDROOM ~ BEDROOM ~ I
NEW LIGHT 11 NEW LIGHT PROVIDE NEW BASEBOARD
FIXTURES IN 1 I FIXTURES IN HEATERS THROUGHOUT UNIT
EXIST CEILING ~ ' s>? EXIST EILING~ PER HVAG CONSULTANT I)
I ~ NEW BASEBOARD HEATERS TO BE 1 ~ a I (
f 3aa WATT'S PER FaOT. KICKSPACE HEATERS 1.5 KW AT BATHROOM, 1 ~
l ( ti 3 KW IN KITCHEN
II d NEW ELEC
ir- I ~ BASEBOARD ~u NEW ELEC NEW LIGHT HEATER, TYP ~
J ASEBOA FIXTURES l ~ I ( B ~v ~ , ,
HEATER,TY EXISTING I ~ CEILING I !.f C~
I + ~ _ - II
~='I PROVIDE POWER AND ~
DINING /LIVING RaOM CONTROLS FOR NEW ~
FIREPLACE INSERT AND FLAT SCREEN N
f ~I~ NE1H GEILINC~ CAN J-.16H75 r ~OF05EV ELEC"MICAL PLAN FR( I PROP05ED REFLECTED GEILIN& PLAN f;Mr-LECTEV GELLING PLAN NOTES
aG 7O BE HALO 3004YNW, 0 1 2 4 feet OR APPROVED EOUAL p I 2 feet EXISTING CEILINGS TO BE LEFT INTACT AND FAINTED ONLY,
THERe SHALL BE NO REMOVAL OF EXISTING CEILING MATERAL
OTHER THAN AREAS OF DEMOLITION WORK A2.1
ALL NEW CEILING HEIGHT5 TO BE SAME AS
EXISTING CEILING HEIGHTS AND IN NO CASES LOWER WITHOUT APPROVAL
~ ~.CiW!^~I'1G~
$~4~~~_~'S
GEiZ~M1G TILE >^LaaR Tile PER G,4RPET ~I"~t1~:~, ~.~i.
a}NNER, 7HIN5e7 GARPE7 AND PAD ~fY PER aWNER p,o, box 431
_r SGHLUTER Di'CRA „ _ edward~, co 8163
i~4 ~r~,r_.ni n..•~.~r~ir~
. a, a. a. a.
a n a o a
c p n a o
A
`1 G ,
. D 4I
A
/
NOTE:
GONTRAGTOR SHALL PREPARE ALL SUBFLOOR ASSEMBLIES FOR FINAL
FLOORING INSTALLATION. FINAL FLOOR
FINISHES TO BE INSTALLED WITH EVEN
TRANSITIONS BETWEEN MAT)~RlALS
1j .
- ~ r
b
P TY IGAL EXTERIOR
WALL A55EM6LY AT ~ ~
~IREPLAGE- PREGAST 4 GONG PANEL c ~ '
fl~
7NROUGH WALL
PENETRANT
. {PIREPLAGE FLUE)
a D
PELL MATERIAL PER ~ G , UL t?)"TAiL
G C •
,y
G
U L DESIGN N0, W J 1030
i - E R,~TING
Tf~ROVGH-pENETR~4TI0N 1=1fi~E 5TG
. P > ~ P A i
G D S S r F G. Ya
N D D ~ ~ P ,
' Q ,
4
6
D
Q ,
D
P
D ,
D as
A
P P
' ~ ,
D
f?
SGALE : I ~2~~ ~ I ~ _O,a
UL DESIGN N0. p a03
- 2 ~fR RATING
r~Y k.
RESTRAINED EXITING FLOORIGE
L 3
r V-*% i.L. I I I- L. zo)
5r-,ALF 11/:2" P-O"
{NOT ALL SYMBOLS REQUIRED FOR THIS PROJECT}
~ LODGE AT LIONSHEAD UNIT Z2t} ( _ { PROJECT: LODGE ATLIONSHEADPHASEII Q RECESSED DR SURFACEDDWNLIGHT ABBREVIATIONS _ y~ k~ ~ . . ~_w_ _ _ _ _ CLIENT: LAWRENCERQGERS
O-I WALLMDUNTEDLIGHTFIX[URE AC -ABOVECDUNTER Deitlc'~t1(~ LOr'~C>S Calculations ~ _ _ _ _ _ . _ _ _ _ _ _ w_ _ AFF ABDVEFiN(SHEDFtDDR - _ - _ _ ~ _
REC6SSEDFLUDRLIGHrFIXTURE ~ _ _ (Per NEiC 220-3B Through 220-19) _ _ _ _ DESCRIPl10N: PANEL UN1T220 _ AFC -ABDVEFINf~iEDGRADE w----- _
suRFADEFLUOR,uGHTFlxruRE AL -ALUr~NUM January 2007 _ ..W ` _ - , MOUNTING RECESSED ! a - _ _ _ a_____.~.,__ Aa Du • co~rER _ - _ ______n. _ TYPE; QO RESIDENTIAL FikTUREDES(GNA110N5 DE51G. •DESIGNAIIDN ' - - ~ i_
UPPERCASE-FL`(TURETYPE EM •EMERGC'vCY ~ Quanii ~4~Y Afi11p5 C1e1'Yland TOtd1 VA PHASE LOWERCASE-SWITCHDESIGNATKNJ EMP E~.IdERGl'MAKAGEMEfVTPANEL ~Bnerai
SHADING ON FIXTUREINDICATESEMERG.BATFERYBACKUP EVVC L1.ECiRVCWRIERCDDLER _ _ _ _ DESCRIPTION A B
CND -crzauND {Dwelling unit Square footage l 950 ~ I • GROUND FAULT INTERRUPTER _ t _ . _ _ _ - FLUDRESCENTSTR(PFfXTURE I General & Li htin 1st 3 KVA ~ 950 SF X 3 X 100°I° 2$5p
Nf -NDTruSED g g ( ) _ _ _ L(GHT~1G&RECEPTACLES 1575 1-n-a-{ TRADKL+GHTASNDTEDORSOHEDUtco NIO •r;oi~i~eorarR,tcT Add'( Li htin after3WISF # 1 I-S X _ 150 _ _X _ _ 10O% _ € 150
NL • NicHr ual,r g g _ _ ~ - LIGHTNG & RECEPTACLES .1573 a WAUWASHER _ Remainder after 1st 3 KVA ; 1 LS X ~ 150 X 35% 53 Nrs • Nor?c SCALE . - . _ . _ _ _ .._._._t _ _ . _ _ . f _ SMALL APPLIANCE REC 1500
PoLE~MOUNrEDFIxruRE uG -urloER~aouno Kitchen I PosrlaatLARD>FaruRE w~ +n~rnr~+FRPRDOF _ , ° _ SMALLAPPLWNCE REG 1500
xFMR •ranusFOar~ER Small Appliances & Refrigerator 2 EA X 1500 X 3510 - 105p EXHAUST FANS 3 270 » srEPUGHr ~+a° -r"xwNrwcl+r~,HrrocENTERLINE Dishwasher 1 EA X 1000 X 75% 750. s+
ofL~Ew„E„s~DRAFG _ _ . _ - _ ELECTRIC WATER NEATER 2250 ~ CEIUNGDRWALLh4ouNTEDEXCfLIGHr Microwave 1 EA X _ 1004 X 75% - I 750
EMERGENCYBATTERYLEGHTS FiREALARM5~"STEM DISpOSaI ____1 EA X 1400 _X _ __.^~~75% _ i_..__- ! -_7750 2250 J
~ DUPLEXREGEPrADtE~tB"uNLESSNOTED Oven/Ran e Re_table22d.19 1 EA X 8000 _ X 104°!° _ ~ 8400 SPACE 0 M~`IYIFACP FlREALARMCDP:rRDI.PPNEI. g ( . w_._ _ _ _ _ SPACE 0 DDUBLEDUPLEXRECEPTACLE~iB"'UNLESSNOTED ANN FIREALARMANNUPlCInTORPM:0. L.aurldry 8< Spa A~LJIIanCes 1 1.
Q FLUSHFLODRDUPLEXRECEPTACLE ~ CiotheS Washer - - - 1 EA X 1400 X - 75% = j 750 SPACE 0 FIREAtARMPULlSTAihCN I
SPECIAtOUTtETASNOTEO ° _ _ .SPACE O ~ ALARMHORNDRSPEAKER _ Clothes Dryer I 1 EA X 5040 X _ 100 fo _ _ 50dO
~ DUPLEXRECEPTADLEHALF-S+MTCHED~18"uNLESSNOTED Steam Shower ~ 1 EA X 7500 X 75% _ 5625 SPACE 0 ~ TEI.E-POWERPDLE COMBINAriDNHDRPUSTRD6EORSPEAKER/STROBE
,~fi~gg •W TFIERMALHEATDEfECTDR McChdnIG11 EgUij?rnent _ ' SPACE 0 t•1I--9f1 Mutrl.DUrLErPLUCSrRiP el sMOKEfrDNIZArtoNDETECTOR Electric Baseboard Neat _ .Y 46i LF X ; 250 X~ _ _ .100°!° _ .._19500 SPACE 0
~ SUNCTION BDX IN FLOOR, CEILING DR IN WALL ~ ° ° _ n rtP PHDTDELECTRICSMDKEDErECTDR E}dlaustFans _ _ I ~ E:AX ~ ^9Q ,~X ~ m 104/o ` 270 SPACE 0
I~f T COMWJTERitELEPHDNEDUTLEfINFLDORORWALL ~r'- CHIP HEATlPHOTDBLECTRlCSMDKEDEiEGTOR Water{-leat~r ~ 1?~X I 4544 X 7rJ°lo ~~~rJ Q i_ ~ _ _ _ _ _ _
f-~ TELEVISION OUTLET ~ _ DUCl'DETECTOR ! _ o TELEPHDNEBACKBOARD _._.a._ d.._.
SRRINKLERSYSTEMFLDWS"MTCH TOTAL. ~ 4O$73 O CONDUITRUNCDNCERLEDINWALLDRABDVECBCLING ___v- _ _ eH- sPRiNKLERSYSfEMTAMPERSW~fCH For 208V, 1-Phase, 3 Wire Service 40873 (VA) / 208 = ^197jAMPS 0
-°---1►- CIRCUTf HOMERUN STROBE _ _ _ _ _ ~_a _
CDNDUITRUNB0.4WFLODRDRGRADE SMOKE1FtREDAtf2C0NNECTiON ~ DDNDUITSTUB•uP-DAPBMARK ~ Per optional talcs permitted per NEC 220,82 0 1
REMOTEiNDICATDR LiGHr ° _ . uGHTS~TDHATaa^uNLESSNOTED 100 of 1st 10 kva r 10400 _ _
suascRiPrs sEGURCfYSYSTEM 40% of rest _ t_______~....; _ I _ 1 d 188 L{7AD CALCULATION SUMMARY NCTE: PRO' 2=2-PDLE5SMTCH Lar estofld0%COOIin or 65°1o/4p°!°ofheati * i .____._______€P___.,___~____z 4600 _ _ _
8=3WAY5VeIrCH DC CDNTACTDDDRSMTCHINJAMBORHINGE g-..-___~____.__.__ ~ _ _ ~ FWA 4=A-WAY CH _I I__._...., .
~ INTRDSroNn~onoNr~:TEDr~ASSPECI~m,+~RRm~RDOM v__u _ --TfJTA~ s g 2476$ CALCULATED POWER FACTOR: 0.94 K=KEY•OPERATEDSWITCH ~ _ _ TD=THERMALOVERLOADSWITCH CGRR _ 'Far,'~0~`V, 1-P~'I~se, ~r Wire SeCrt~ce~_~_ ? _ 24768 (VA) / 208 _ , ' ~~'j1~~AMPS _ ____e_ _ ,
P=5WiTCH4MTHPILOTL(GHT 4 ~ KEr-oP€Pnrrotvccr~ss~~rrDH _ - CONNECTED LQAD
DlMMERStMTCH4WWAITAGE m° - ~ ~ suRVEtLLnR(,ECAMiRA _ _ (3#2 A~)9-114 C inaommg service, ampacrt~r aiiowed by node is: . _ '!26 AMPS______ APPLIANCES 8500 Q PUSHBUTTONCDNTRDLSTATION Main circuit breaker atmeterbank: ! 125~AMPS LIGHTING&RECEPT _ I 9670 b__
DISTRIBUTlDN EOU i~r, ki.T Sl`PnE3UE 3 4 - ~HOroEL€crR>GCELL MECHANICAL 15750 _
TS TlMESWITCH D6SCONNECT'3NAI"CH KITCHEN OVEN & DRYER13000
Q THERMDSTATAT~3"UNLESSNDTED -~,1~-^- FUu[S TOTALv 4~92Q
OMS1ON95EOUtPM~:T C~RCUIIGREAKER Q FDDDSERVICEEQUfF~WENT -4~- CURRE:NTTRANSFDRMER
~"A'A rRANSFORMER COMMUNIGATIONSYSfEM ltNJt
h METER V ~}S, i SAEAKER IN CE~I_iT!GOR WALL ~ MAGNEIYC MOTOR STARTER 8
~ vatuMECDNTROLAr YYVNLESSNDTED DISDONNECTSwrrcH REFERENCE BASE BUILDING ELECTRICAL
~ ONE-LINE DRAWINGS FOR METERBANK ~M A~ i MICRDPHDNEOUTLETINFLDDRBDXDRWNJ. i'~ PANE!.BDARD4RLpApCEMER,R.llSHORSURFACEt~1NiED
DALL-INuRMTCH swTCr~oARO ~aDrDRCONTRa~.cENratoeD~srR~ur~aNaDARD LOAD CALCULATIONS. PROGRAM BELL , a I
® ri~raasraRrraR 0 INTERCOM
--~-jp~ G,~ourlo CLOCK ~ H CIRCUITBREAItER
L:.I AMPLIFlER ,~y~ Q CUT.Er V7" M TOR I x
ATS ALi1'OMAT!CTRANSFERSWtTCt#
f~
BONDING JUMPER J if!
(#3I0 CU G}(3"G
#6 TO TELEPHONE
CONCRETE
ENCASED ELECTRODE
fN~.OMING WATER SERVICE
PIPE
WATER METER.
PANEL PANEL
UNIT 401 UNIT 401A BUILDING STEEL
(3j 3/4`"x10' 8012
- DRIVEN (3#2 CU, #8 CU G} PANEL PANEL PANEL GROUND ROD
UNfT 350 UNIT 360 UNIT 370
g.
PANEL PANEL UNIT 280 UNIT 290
NO SCALE
NOTE: CONFIRM CURRENT GROUNDING #3
MEETS CODE MINIMUM. PANEL PANEL PANEL PANEL PANEL PANEL PANEL PANEL {3#250 MCM AL~"C 1ST/2ND/3RD i '
OFFICE AREA UNIT 100 UNIT 110 UNIT 120 UNIT 130 UNIT 140 UNIT 150 UNIT 160 FLOOR
EXISTING
#3 #1 #2 DRIVEWAY #4 #6 p
UNMARKED UNMA~tKED SNOWMELT ELEVATOR UNMARKED H
HIGHEST DEMAND AT _ _ _ _ _ _ _ _
MOUSE METER: 30kW
12512 12512 125f2 10012 12512 125f2 125!2 12512 10012 10012 20012 20012 20012 200(
M ~
80013 ~ ~ ~
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 10013 100!3 17513 125!3 10013 10013
LEFT N[ETERBAN _
5[{4#500 MCM ALj4"C] 3 600A Bt~QA 120d~~8V ~P 4!x!1 ~
~ ~ ~ LPN-RK
~(4#35fl MCM cU~ 6°Ot3 _ _ _ _ _ _
HOUSE DISTRlBU7~ON CENTER
24#500 MCM AL ~V~~ ~G~~~~~V 3!'" ~Y1f (3~16QOA ~ ~ ) ~ ~ ~
KRP-C 1600!3
~rn~~x~n rtet+rtn r+r n
rRaNSFORMER'ITE SWITCHBOARD U t-,ALUN
PAD MOUNTED 1600A, 120/208V, 3P7 4W
EPLACE EXISTING RIGHT METERBANK PA NE AS SCHEDULED
ELECTRICAL ONE-LINE DIAGRAM 800AI 120120811 Y 3P, 4 AS EXTEND XIS TO FEEDER
NO SCALE PANEL. LOCATION
1 of 1
l+ CCPYRIGNT M ARCMTECTMAL ENptN;ERiNC WMLTANTS, N!