Loading...
HomeMy WebLinkAboutB01-0253 Comments- - Au gust 13, 2001 O R GARY M Mr. Gary Goodell ADAMS -1016 Town of Vail Building Department 75 S. Frontage Road Vail, Co. 81657 ARCN $lot Re: Phase III — V Code Review Comments Vail Mountain Lodge Expansion and Renovation Dear Gary: Attached are responses for Architectural, Structural, Mechanical and Electrical to plan review comments dated May 14, 2001 on Full Phase III — V Permit Documents for Vail Mountain Lodge, Expansion and Renovation. Please see the Phase III Permit Documents ` Dated August 1, 2001 for reduced Phase III scope. Items which are no longer included as part of Phase III work, will be resolved in future phases. ARCHITECTURAL 1, la and lb We are approved to consider the building as a four story building with the two Health Club Levels defined as Basements. The grade exceeds 12' -0" along the south face only above the spa area. This area represents only 28 percent of the total building perimeter. Fires will not be fought from in spa area, therefore, the Upper Level Health Club on Sheet A3 -2, should be considered a basement level. Please see attached letter from Glenn Hoynoski, P.E. dated October 5, 2000. 2 On Sheet L2 -0, the wetlands and the park area to the south is deeded Town of Vail land and is dedicated open space 3 On Sheet L2 -0, The separation measured to centerline of road on the North side is 25 feet and on the East side is 31 feet. To the south, the public land is greater than 60 feet. 4 On Sheet A3 -2, property lines are correct as shown. The Existing parking garage does extend beyond the property line. 5 On Sheets A3 -3 through A3 -6, the renovated areas are provided with operable windows or doors which meet the egress requirements for Escape or Rescue windows in sleep rooms. The windows are accessible, by the fire department, from the garage roof. 6 N/A Sheets A3 -1 through A3 -7 have been revised and resubmitted to clarify scope of work for Phase III renovations, dated 08/01/01. Davis Partnership P.C., Architects Denver Office: 2301 Blake Street - Suite 100 Denver Colorado 80205 -2108 303.861 .8555 Fax 303.861.3027 Vail Office: 0137Main Street • Unit C106 P.O.Box 2711 Edwards Colorado 81632 970.926.8960 Fax 970.926.8961 Mr. Gary Goodell August 13, 2001 Page 2 Sheet A5 -1. Re- grading and window replacement are part of future phases. Existing windows less than 18" above grade, on the south fagade, will be replaced with tempered safety glass. Sheet S4.0. Architect will provide detail for weather proof seal at steel bearing assembly on top of existing concrete foundation wall to prevent moisture penetration. Sheets A5 -1 and A7 -10 have been revised per new phase three scope. Any walls with in 40 feet of the property line will be One -hour N/C per tables 5A and 6A of the UBC. Exterior finishes attached to the walls as defined in Phase III revisions are to be non - combustible siding. Please refer to Phase III Permit Drawings. 10 Siding above 35" on the North Elevation is non - combustible siding. 11 N/A Sheet L1.0. Ramp is not to be completed as part of Phase III work. It will be completed as part of future phases. 12 N/A Sheets A3 -1 and A64. Work is not to be completed as part of Phase III. The area is to remain unfinished space for Phase III. 13 N/A On Sheet A3 -2 and A6 -5. Work is not to be completed as part of Phase III. The Restaurant area will remain as unfinished space for Phase III. 14 N/A Sheet A3 -3. Work is not to be completed as part of Phase III work. Restaurant Construction, Stair 208 and Door 308C are part of future phases. The exiting through Stair 028 is no longer required. 15 Sheet A6 -5. The folding doors are not the main exit. Exiting is through door 200A which is 32" minimum clear wide and exits to grade. The Folding doors 200D — 200E open to balconies approximately 4 feet above grade. The restaurant space has been removed from Phase III scope. It will be left as unfinished space. 16 The doors are part of the existing exit vestibule. The work is not to be completed as part of Phase 111. The renovation to these doors will be part of phase Four. 17 N/A Sheet A3 -2. Work is not to be completed as part of Phase III work. Dishwashing Area will be resolved in future phases. 18 Division 08000, Door, Frame and Hardware Schedules, Division 09000, Finish Schedule, Division 10520, Fire Protection Specialties, Division 15 Fire Suppression and Division 16 Fire Detection were issued separately. 19 N/A Project Manual, Division 08960, will be revised to specify glazing material if sloped glazing is used in future phases. Phase III scope does not include sloped glazing. Mr. Gary Goodell August 13, 2001 Page 3 20 Sheet Al -1 and Specifications will be coordinated in regards to safety glazing at doors and windows subject to human impact. 21 Specification Section 06105: Wood sheathing and wood subflooring is not being used. 22 Specification section 06100 Equipment bases and support curbs will not be made of wood. 23 Specification Section 14420 refers to wheelchair lift located on A3 -3 in Entry, Rm. 334. The lift was completed in prior phases. STRUCTURAL: 24 The rooftop deck between grids 3 and 4, F and D is the only deck in the remaining in the scope which is exposed to snow loads. The following calculations indicate that this framing has been reviewed for 155 psf snow load including drift. 25 The general notes indicate 100 psf for roof slopes less than or equal to 3:12 and 80 psf for slopes greater than 3:12. Neither slope reduction nor live load reduction was used, as the Town of Vail requires 80 psf as the base snow load with a separate requirement of 100 psf for roof slopes less than or equal to 3:12. MECHANICAL: 26 N/A Work is not to be completed as part of Phase III work. 27 N/A Work is not to be completed as part of Phase III work. 28 A reduced pressure type backflow preventer will be provided to replace the double check type backflow preventer. This item will be addressed in Phase III Construction Documents. 29 N/A Work is not to be completed as part of Phase III work. 30 The gravity drainage portion of the discharge piping from pump P -1 will be changed to a 4" storm pipe. This item will be addressed in Phase III Construction Documents. 31 Sump pump P -1 serves as the building ground water dewatering system and is not connected to the sanitary sewer system. Therefore, per Chapter 11 of the UPC, a vent pipe shall not be required. This item will be addressed in Phase III Construction Documents. 32 N/A Work is not to be completed as part of Phase III work. Mr. Gary Goodell August 13, 2001 Page 4 33 N/A Work is not to be completed as part of Phase III work. 34 N/A Work is not to be completed as part of Phase III work. 35 N/A Work is not to be completed as part of Phase III work. 36 N/A Work is not to be completed as part of Phase III work. 37 N/A Work is not to be completed as part of Phase III work. 38 N/A Work is not to be completed as part of Phase III work. 39 N/A Work is not to be completed as part of Phase III work. 40 Clothes dryer exhaust ducts that exceed 14' will be provided with booster fans. This item will be addressed in Phase III Construction Documents. 41 N/A Work is not to be completed as part of Phase III work. 42 The make -up air for the guest room toilet exhaust will be provided by undercutting the bathroom doors. The guest room ventilation is provided by operable windows and doors. This item will be addressed in Phase III Construction Documents. 43 N/A Work is not to be completed as part of Phase III work. 44 Combustion air will be provided by Shaw Construction per manufactures requirements. 45 N/A Work is not to be completed as part of Phase III work. 46 Existing solid fuel fireplace chimney vent dampers and chimney construction shall be permanently opened and inspected by Shaw Construction. _ 47 N/A Work is not to be completed as part of Phase III work. 48 N/A Work is not to be completed as part of Phase III work. 49 N/A Work is not to be completed as part of Phase III work. 50 N/A Work is not to be completed as part of Phase III work. 51 It is noted on Sheet M4.3 to remove previously abandoned ductwork that is located above electrical equipment. Therefore, no abandoned ductwork will remain above electrical equipment. This item will be addressed in Phase III Construction Documents. Mr. Gary Goodell August 13, 2001 Page 5 52 A duct detector for unit shut down will be provided for relocated MUA -3. This item will be addressed in Phase III Construction Documents. 53 Make -up air to EF -4, located in the elevator equipment room, will be provided with fire smoke damper. This item will be addressed in Phase III Construction Documents. 54 Architectural Drawings will be revised to show Elevator Equipment room 210 meeting 2 hour rating. 55 N/A Work is not to be completed as part of Phase III work. 56 A fire smoke damper will be provided at the 24" x 48" supply air duct outlet from the fire rated shaft. This item will be addressed in Phase III Construction Documents. 57 N/A Work is not to be completed as part of Phase III work. 58 All valving associated with PUMP P -1 is accessible via a removable top of the approximate 4' -0" diameter dewatering pit. This item will be addressed in Phase III Construction Documents. 59 N/A Work is not to be completed as part of Phase III work. 60 N/A Work is not to be completed as part of Phase III work. 61 Design Build Fire Protection Sub Contractor will submit answer. 62 The pipe sizing is hydraulically calculated per NFPA 13. Pipe Scheduling per NFPA 13, 8 -5 is no longer an acceptable manner for sizing piping in new projects. 63 A 6" reduced pressure back flow prevention is installed in the riser room (Sheet FP -2). This backflow prevention device services the entire sprinkler system. 63 The piping at column line 3/M is in the garage, all of the piping in the garage is existing and will remain in place. 64 N/A Work is not to be completed as part of Phase III work. 65 N/A Work is not to be completed as part of Phase III work. ELECTRICAL: 66(a) A one line diagram and typical FFU circuit documentation will be provided. This item will be addressed in Phase III Construction Documents. 66(b) N/A Work is not to be completed as part of Phase III work. Mr. Gary Goodell • August 13, 2001 Page 6 66(c) Short circuit documentation will be provided. This item will be addressed in Phase III Construction Documents. 66(d) N/A Work is not to be completed as part of Phase III work. 66(e) N/A Work is not to be completed as part of Phase III work. 67 Street lighting circuit requirements will be coordinate with the T.O.V. This item will be addressed in Phase III Construction Documents. 68 (a), (b) Panel GH2 and H2 circuit documentation will be provided and weatherproof GFCI receptacles will be used. This item will be addressed in Phase III Construction Documents. 69 N/A Work is not to be completed as part of Phase III work. 70(a) A one -line diagram will be provided to clarify requirements for the future condominium units powered from the future MMS. This item will be addressed in Phase III Construction Documents. 70(b) A one -line diagram will be provided to indicate the power source of the existing club elevator. This item will be addressed in Phase III Construction Documents. 70(c) Elevator pit lighting and receptacle circuit will be document. This item will be addressed in Phase III Construction Documents. 71 Elevator pit lighting is not connected downstream of GFCI receptacle. A note will be added to clarify this. This item will be addressed in Phase III Construction Documents. 72 72(a) — 72(f) N/A Work is not to be completed as part of Phase III work. 73 See comment #70 (c) above. 74 See comment #70 (c) above. 75 Clarification of circuits 38, 40, 42 will be provided. This item will be addressed in Phase III Construction Documents. 76 Clarification of Panel HG2 loading will be provided. This item will be addressed in Phase III Construction Documents. 77 Clarification of Panel H2 loading will be provided. This item will be addressed in Phase III Construction Documents. 78 N/A Work is not to be completed as part of Phase III work. Mr. Gary Goodell August 13, 2001 Page 7 79 N/A Work is not to be completed as part of Phase III work. 80 N/A Work is not to be completed as part of Phase III work. 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 N/A Work is not to be completed as part of Phase III work. N/A Work is not to be completed as part of Phase III work. N/A Work is not to be completed as part of Phase III work. N/A Work is not to be completed as part of Phase III work. N/A Work is not to be completed as part of Phase III work. Panel FF1 location. NEC 110 -26 does not say panelboards cannot be located behind a door. N/A Work is not to be completed as part of Phase III work. N/A Work is not to be completed as part of Phase III work. N/A Work is not to be completed as part of Phase III work. N/A Work is not to be completed as part of Phase III work. N/A Work is not to be completed as part of Phase III work. N/A Work is not to be completed as part of Phase III work. N/A Work is not to be completed as part of Phase III work. N/A Work is not to be completed as part of Phase III work. N/A Work is not to be completed as part of Phase III work. Clarification of elevator equipment room circuit will be provided. This item will be addressed in Phase III Construction Documents. N/A Work is not to be completed as part of Phase III work. N/A Work is not to be completed as part of Phase III work. N/A Work is not to be completed as part of Phase III work. N/A Work is not to be completed as part of Phase III work. N/A Work is not to be completed as part of Phase III work. N/A Work is not to be completed as part of Phase III work. Mr. Gary Goodell August 13, 2001 Page 8 103 N/A Work is not to be completed as part of Phase III work. 104 N/A Work is not to be completed as part of Phase III work. 105 N/A Work is not to be completed as part of Phase III work. FIRE PROTECTION 106 Fire alarm manual pull stations will be provided at all exits at each level and will be reflected on the revised fire alarm plans. 107 Automatic heat and smoke detection will be provided in elevator shafts and will be reflected on the revised fire alarm plans. 108 Duct detectors will be provided for AHU Unit in Mech. 209 and MAU -I and will be reflected on the revised fire alarm plans. 109 If the door(s) in question is installed and is a fire door and is required to be held open, then it will be held open with a magnetic door holder and will be reflected on the revised fire alarm plans. 110 See Item 109. 111 See Item 109. 112 Design Build Fire Detection Sub Contractor will submit answer. 113 Automatic smoke detection will be provided in accordance with NFPA standards and will be reflected on the revised fire alarm plans. 114 Audio /visual appliances will be provided in accordance with NFPA standards and will be reflected on the revised fire alarm plans. 115 See Item 114. Please call if you have any questions or concerns. cc: Jay Peterson - Bailey & Peterson Ray Story - Ray Story Architect Keith Oxenreider - Shaw Construction Clark Atkinson - Shaw Construction Brad Staver - Beaudin Ganze Scott Wasson - Monroe & Newell v \vml\ 0022000 \adminUetter \tov080201. doc XT rir�7ti>lz °1�lt>;�it1t'i'.lil1� Fire PrOU -Cticn and Building Codn 972 Hwvy. 46, Suite 300. Golden. CO 80403 -8880 (Golden Gat(: Canyon Road) Pllcne: (303)' 642 -0635 G Fa:�: (303) 582-3855 OCTOBER 5, 2000 MR. GARY R. GOODELL, C.B.O. TOWN OF VAIL BUILDING DEPT. 75 S FRONTAGE RD VAIL, CO 81657 RE: CODE ISSUES VAIL MOUNTAIN RESORT Gary: project. This letter is to respond to issues raised during the Town of Vail review process of the subject The first issue of concern is the classification of the first story and the impact upon the required Type of Construction. The plan review indicates that the Upper Health Club level of the project must qualify as a basement. The expressed concern is that the distance above grade for the first floor exceeds 12' along a relatively small portion of the south elevation. We agree that the UBC is clear in the definition of a applicable story, however, this interpretation for this building seems impractical. The UBC Handbook suggests that each case should be judged individually based on characteristics of the site and construction. One of the more significant concerns is the issue of emergency access to the building and fire fighting operations. According to our review only 28% of the overall building perimeter exceeds the 12' Provision exclusively on the south elevation. It should be pointed out that the building is primarily accessed by both the public, as well as emergency services on the north, east and west sides. The south side adjoining Gore Creek is not generally considered as accessible. The 12' height is exceeded slightly (16') and does not exceed 50% of the perimeter. In order to minimize this condition, the grade elevation will be increased lo satisfy the 12' criteria along the south side except in the area of the outdoor whirlpool, refer to Addendum #2. Since the building is not readily accessible on the south side; the provision for determination for classification of the first story should be waived allowing the building to be renovated as Type 11 - 1 hour construction. The second issue concerns the 3 -story communicating space which exists between the Lower Health Club, Upper Health Club, and the first floor. It is recognized that the UBC limits the number of communicating levels to two (2). The principal basis for the code restriction is to limit the potential for fire spread through a building, as well as minimize the impact of smoke travel and the impact on the evacuation capability of the building occupants. T MR. GARY R. GOODELL, C.B.O. TOWN OF VAIL BUILDING DEPT. CDDE ISSUES VAIL MOUNTAIN RESORT OCTOBER 5, 2000 PAGE 2 The design element in question is a 6' diameter circular opening (28 ft.2) located between the Lower H ealth Club level and the Upper Health Club level. Refer to the partial building section attached. Due to the limited size of the opening, it does not qualify as an atrium per Table 4 -A of the UBC. Based upon the above, we propose to provide the following safeguards to mitigate the safety risks associated with the installation of the opening between floors: • The installation of a draft stop located at the ceiling level of the Lower Health Club level with the installation of closely spaced 6' o.c. quick response sprinklers around the perimeter. 2. The installation of passive smoke vents at the ceiling /roof level at the first floor level. These vents would be activated by either of the following: a. Smoke detectors located at ceiling of the bar on the first floor level. b. Manual switching located at the proposed fire command center to be controlled by the fire department personnel. We believe that the installation of the above safeguards will provide an acceptable equivalency to permit the above mentioned opening between floors and provide an acceptable level of occupant safety. Please advise if you have any additional questions on !he proposed alternatives. GTH :gj,,ty cc: JASON OLINEK SINCERELY, GLENN T. HOYNOSKI, P.E. PRINCIPAL FIRE PROTECTION ENGR. w a f it i • C '�-�Y s 47 e 6t O lEF�L11t1E'eIFC`t�6 /' i S tv~ --- | � | / /| } � r--'+-i�--'---'-----'-T-- fro ' / /~ 8175' '77 BLDG. 5E7 ELD( / ., ( '-'----------------'-- '------------------'--' `` i |_--'- -------------- ------------------------' VAIL MOUNTAIN LODGE Town of Vail Phase III - V: Expansion & Renovation C -West 201084 East Meadow Drive & Vail Valley Drive Code Review May 14, 2001 Pg. 1 of 15 Applicable Codes: 1997 Uniform Building Code (UBC) 1994 Uniform Plumbing Code (UPC) (97 IPC OK) 1998 International Mech Code (IMC) (97 UMC OK) 1999 National Electrical Code (NEC) CABO /ANSI A117.1 Accessibility Standards (C /A) (Per Town of Vail Adoption) Drawings dated 02/26/01 Manual dated 02/05/01 Structural Calcs 04/04/01 Architect : Davis Partnership B -1016 Mech. & Elec.: Beaudin Ganze No Stamp Contractor : Shaw Construction Structural: Monroe & Newell PE -12082 Civil : Marcin Engineering No Stamp Fire Protection : All -State No Stamp Code Consultant: High Country Engineering PE 22147 A. Occupancy Groups: R -1 Apartments Units & Dwelling Units S -3 Parking Garage (Underground) A -3 Restaurant, Bar, Health Club, Lockers B Offices & Kitchen S -1 Storage B. Type of Construction : II - 1 HR Fully Sprinklered C. Location on Property North : Frontage on East Meadow Drive South : Faces Wetlands & Park East: Frontage on Vail Valley Drive West: Mountain Haus Parcel D. Summary of Floor Areas : These numbers have been calculated from the floor plans provided. Note that floor areas are larger than the entries provided in the Code Analysis on the Index Cover Sheet of the review sets. Floor Area (sf) Floor Elevation Basement Lower Level 15,167 8155.33' Health Club Upper Level 12,953 8164.83' Parking Garage 4,257 8164.83' Restaurant & Kitchen 2,500 8166.33' Main Floor 16,654 8177.33' 2nd Floor 16,474 8186.83' 3rd Floor 16,318 8196.33' Penthouse Level 7,316 8207.33' Total Building 91,609 VAIL MOUNTAIN LODGE Town of Vail Phase III - V: Expansion & Renovation C -West 201084 East Meadow Drive & Vail Valley Drive Code Review May 14, 2001 Pg. 2 of 15 E. Height & Number of Stories: See Review Comment No. 1 Architectural Review L 2 -0 : The height of the building needs to be resolved with regard to total number of stories above grade as altered by the new penthouse units added to the top floor. UBC 506 & 3403 a) A 5 -1 & L 2-0: Area to be re- graded at the exterior spa pool will leave this portion of the south yard at Water Elevation = 8160', which is more than 12 ft. below the main floor at Elevation 8177.33'; thereby disqualifying the contiguous floor level as a basement. UBC 220 & 208, Definitions of "Story" and "Grade. b) The Penthouse additions thereby cause the building to exceed the maximum allowable 4 story height for an R -1 occupancy in a Type II - 1 HR building. UBC 506 & Table 5 -B. 2. L 2 -0 : Verify that wetlands and park area on adjacent property south of the building is public space usable as an open yard greater than 60' applicable to floor area increase and fire department approach. Otherwise building has no usable yard clearance to the property line on this side. UBC 505. 1.1 3. L 2 -0 : Building requires sufficient open yards on 3 sides to justify allowable floor area on no more than 4 stories above grade. The parking garage and Health Club Lower Level are considered below grade. UBC 505.1.2 4. A 3 -2 : The existing underground Garage is shown extending beyond the North property line into the street ROW at East Meadow Drive. Are property lines correct as shown? UBC 106.3.1 5. A 3-3: New Bedroom windows on north side open onto yard supported by the Garage roof underground. Verify existing roof is adequate for emergency rescue by Fire Department to all new windows on this side of the building, including the new penthouse units. UBC 310.4 6. A 3 -1 thru A 3.7 : The keynotes and general notes are the same on each sheet. Since keynotes are not flagged on the plan; the new work of Phases III - V is difficult to separate from existing areas outside of the scope. 2 VAIL MOUNTAIN LODGE Town of Vail Phase III - V : Expansion & Renovation C -West 201084 East Meadow Drive & Vail Valley Drive Code Review May 14, 2001 Pg. 3 of 15 7. A 5 -1 : South Elevation : Existing windows in South exterior wall of Health Club Upper Level will require tempered safety glass if less than 18" above new grade and panels unsupported greater than 9 sq. ft. UBC 2406.4 8. S 4.0: Sec. 3 : Provide weather proof seal at steel bearing assembly on top of existing concrete foundation wall to prevent moisture penetration into building through areawell. UBC 1402 9. A 5 -1 & A 7-10: Wood siding is not permitted on the West Elevation on exterior walls less than 40 ft. from property line. UBC 603.3.1 & Table 5 -A 10. A 5 -2 & A 7-12: Wood siding on North Elevation at new dormers not permitted more than 35' above grade. UBC 601.5.4 & Table 5 -A 11. L 1.0 : New exterior 1:12 slope ramp will require a handrail on both sides. UBC 1003.3.4.5 12. A 3 -1 & A 6-4: Two exits from Basement between Grids 11 -12 are not adequately separated. 1/2 the major diagonal of the basement area served is approximately 98'; requiring 49' separation between the exit - access doors at 101 & 102. UBC 1004.2.3 & 1004.2.4 13. A 3 -2 & A 6 -5 : New Elevator opens into the egress route from the Restaurant (Dining) area to Stair 208. The Elevator opening must be equipped with a smoke and draft seal; or be separated from the Dining Room by a Lobby. UBC 1004.3.3.5 & 711.4 14. A 6 -6 : Door 308C appears to be a non - conforming required exit for the new Restaurant occupants from the lower level. Address door width at top of stair, minimum width of exit discharge into courtyard between retaining walls; and the unidentified gate at the end of the walkway. UBC 1003.3.1.3, 1003.3.1.5, 1003.3.1.8, 1006.3.5.2 15. A 6 -5 : The main exit from the Restaurant may be considered the doors opening onto the Patio. Folding doors are not considered safe for orderly evacuation during an emergency. UBC 1003.3.1.5 16. A 6 -6 : Door 308B does not provide an adequate landing at the foot of Stair 308. UBC 1003.3.1.7 & 1003.3.3.5 - 17. A 3 -2 : Dishwashing area is not permitted under enclosed Stair 308 above. UBC 1005.3.3.6 3 VAIL MOUNTAIN LODGE Town of Vail Phase III - V : Expansion & Renovation C -West 201084 East Meadow Drive & Vail Valley Drive Code Review May 14, 2001 Pg. 4 of 15 18. Specs Table of Contents : The following Sections are noted as not included in the project manual. 08000 Door, Frame, Hardware Schedules. 09000 Finish Schedule 10520 Fire Protection Specialties Div. 15 Fire Suppression & Standpipe Specifications Div. 16 Fire Alarm 19. Specs 08960 : Refers to Div. 8, Section for "Glazing "; not provided. Identify whether glass or plastic to be used at sloped glazing. UBC 2409 & 2603.7 20. A 1 -1 : Coordinate specifications and safety glazing requirements at doors and windows subject to human impact. UBC 2406 21. Specs 06105: Part 1.2. A 4 & 5 : Sheathing and subflooring may not be of wood in Type 11 - 1 HR building. UBC 603 22. Specs 06100 : Part 1.2. A 1 & 5 : Equipment bases and support curbs may not be of wood in Type II - 1 HR building. UMC 308.3 23. Specs 14420 : Calls for wheelchair lifts; not located on drawings. Use as an egress component is limited by UBC 1104.1.4 Structural Review 24. Structural calculations use 40 psf LL for Residential balconies; same as interior floors. Minimum 60 psf required by Table 16 -A; greater with snow drifting based on area snow loads. This includes the rooftop balconies shown on Sheet A 5 -1. UBC 1608 25. S 4.0 : General Notes : Snow loads call for 100 psf at roof slopes less than or equal to 3 : 12; and 80 psf at slopes > 3 : 12. Reductions may not be applied for slopes less than 4.36 : 12; i.e. 200 from horizontal. UBC 1614 Mechanical Review 26. M1.1. Provide trip lever on wide side of handicapped water closet stall (CABO /ANSI A117.1 -1992, 4- 17.5). 27. M2.3, M2.4, M2.5. Required fire rating of rated corridors and floor to floor separation shall be maintained at all times during construction within occupied building (UBC 710.11, 713.10). 4 VAIL MOUNTAIN LODGE Town of Vail Phase III - V : Expansion & Renovation C -West 201084 East Meadow Drive & Vail Valley Drive Code Review May 14, 2001 Pg. 5 of 15 28. M3.1. Provide reduced pressure backflow preventer in lieu of double check valve shown on domestic water service (UPC 602.3). 29. M3.1. 2" vent serving 4" P -10 floor drain is undersized and should be increased one pipe diameter. 4" waste outlet normally requires minimum 2" vent. However, excessive length of 2" vent shown requires pipe upsizing to next recognized diameter (UPC Table 7 -5). 30. M3.1. P -1 discharge piping is too small to be considered gravity drainage piping. Specified 39 gpm equals 78 fixture units, requiring a 4" gravity drain by UPC Table 7 -5. All 2" PST piping from P -1 shall be rated for anticipated flow and pressure (UPC 703.2, 710.5, 710.7). 31. M3.1. Sump for P -1 shall be vented (UPC 710.10). 32. M3.1. 2" vent may not be reduced in size to 1 -1/2" V (UPC 311.5). 33. M3.1. Provide cleanout on two 2 vents originating from grease interceptor, following vent rise through grade (UPC 905.3). 34. M3.2, M3.3. 1 -1/4" MG is undersized for gas load and length of piping to kitchen and should be increased in size (UPC Table 12 -4). 35. M3.3. Clarify gas flow rate at Hors Dourves Range (UPC 103.2.3). 36. M3.3. Minimum vent size at 4" P -9 and 4" P -10 equals 2" diameter (UPC Table 7 -5). 37. M3.3. Length of horizontal 1 -1/2" V originating from P -8 at column lines L/11 exceeds allowable maximum length (UPC Table 7 -5). 38. M3.3. Provide cleanout at Bath 114 waste branch (UPC 707.4). 39. M4.3, M4.5, M4.6, M4.8. Provide smoke detector within 5'0" of all fire smoke dampers (UBC 713.10, 713.11). 40. M4.3, M4.4. Clothes dryer exhaust duct limited to 14' length with (2) two 900 elbows (UMC 504.3.2). 41. M4.3, M4.4. Clarify outside air quantity to CUH -4 (UBC 1202.2.1). 42. M4.3, M4.4, M4.5. Clarify source of make up air to guestroom toilet exhaust system (UMC 402.4). 5 VAIL MOUNTAIN LODGE Town of Vail Phase 111 - V : Expansion & Renovation C -West 201084 East Meadow Drive & Vail Valley Drive Code Review May 14, 2001 Pg. 6 of 15 43. M4.3, M4.4, M45, M6.1, M6.2. Sanitary vent below fixture flood rim level not allowed unless required due to structural conditions (UPC 905.3). 44. M4.3, M4.4, M4.5, M4.6. Provide combustion air to gas fireplaces (UMC 901.2, 901.3). 45. M4.3, M4.4, M4.5. All ductwork penetrations of fire rated occupancy separation shall be provided with fire smoke dampers (UBC 713. 10, 713.11). 46. M4.3, M4.4, M4.5. Existing solid fuel fireplace chimney vent dampers and chimney construction shall be permanently opened and inspected prior to conversion to gas use (UMC 813.2, 901.2). 47. M4.3, M4.4, M4.5. Clarify all natural gas pipe loading to fireplaces and miscellaneous gas appliances such as ranges and boilers and total gas loads such that gas pipe sizes may be reviewed for code compliance (UPC 1217.0). 48. M4.6. 2" horizontal storm drain is not a recognized size. Increase horizontal storm drain to minimum 3" diameter (UPC Table 11 -2). 49. M4.6. Length of 1 -1/2" vent above Bedroom 610A exceeds allowable horizontal length and must be increased in diameter one pipe size (UPC Table 7 -5). 50. M4.6. Outlet of grease exhaust fans shall be located 24" above all building construction within 10' (UMC 507.11). 51. M4.8. Ductwork may not remain abandoned above electric panels (NEC). 52. M4.8. Provide smoke detector in S.A. duct of relocated MAU -3 (UMC 608.0). 53. M4.9. Provide make up air to EF -4 in elevator equipment room (UMC 402.4). 54. M4.9. Elevator equipment room shall have fire rating at least equal to elevator shaft served (ASM E A17.1, 10 1. 1 a). 55. M4.9. Provide fire rated duct cleanouts in grease exhaust duct systems (UMC 507.5, 507.7). 56. M4.9. Provide fire smoke damper at 24" x 48" S.A. exit from duct shaft (UBC 713.10, 713.11). Ll VAIL MOUNTAIN LODGE Town of Vail Phase III - V : Expansion & Renovation C -West 201084 East Meadow Drive & Vail Valley Drive Code Review May 14, 2001 Pg. 7 of 15 57. M4.9. Provide minimum 3" high pad below condensing unit CU -1 (UMC 1105.2.1). 58. M5.1. Check valves and gate valves at P -1 should be accessible (UPC 710.4). 59. M6.2. Clarify size of vent from P /13 into riser P/14 (UPC 103.2.3). 60. Not Used. 61. FP -2. Pipe sizes shown are too small for pipe size schedule compliance. Provide hydraulic calculations to justify pipe sizing (NFPA 13, 8 -5). 62. FP -3. Provide reduced pressure backflow preventer on sprinkler piping with glycol (UPC 603.4.18.3). 63. FP -3. Clarify missing piping at approximately column lines 3/M (UPC 103.2.3). 64. F3 -0.1. Plumbing notes, number 11 indicates the need for gas pressure regulator for each piece of kitchen gas equipment. Plumbing drawings should be revised to show location of each regulator with appropriate venting to atmosphere. (UPC 1218.0). 65. FS -1.2, FS1.3, FS -1 PP. Food service drawings appear incomplete. Clarify description of keynotes used on plans (UMC 113.5, UPC 103.2.3). Electrical Review 66. General Comments (E2.1 through E3.5): a) Document the complete electrical system one -line diagram and load summary from the load panelboards back to the main service to demonstrate compliance with NEC Article 220 and NEC 215 -5. Show wire and conduit sizes, equipment ratings and the loads at each panelboard, distribution panel and the main service. Document each component of load with the applicable demand, continuous, and largest motor factors. b) Document guest room panelboard loads and compliance with circuiting requirements per NEC Article 210 and 220. 7 VAIL MOUNTAIN LODGE Town of Vail Phase III - V: Expansion & Renovation C -West 201084 East Meadow Drive & Vail Valley Drive Code Review May 14, 2001 Pg. 8 of 15 c) Document the available short circuit current and equipment short circuit ratings for new panelboards and feeder replacements per NEC 110 -9 and 110 -10. d) The drawings are difficult to read, the background line weights do not appear to be any different than the device line weights. Also, the symbols in the legend on sheet E1.1 are heavy line weights that make is difficult (at best) to distinguish the differences. In addition, the symbol size in the legend is very small. For example, the difference between GFI, isolated ground and other receptacles is not distinguishable. e) Fire alarm and detection system division 16 specifications are not included with the construction documents. Document that fire alarm system shop drawings will be provided per UFC 1007.3.1. Also, document acceptance testing of the fire alarm system in the presence of the chief and certifying to the chief that the system has been installed in accordance with the approved drawings and specifications. 67. E1.2. Reference notes 3 and 4 for street lighting. Document the power source, load and feeder sizes to demonstrate compliance with NEC Article 210 and 220. 68. E1.2 and E2.3. Reference note 6 on E1.2 and notes 19 and 20 on E2.3 regarding X -MAS lighting circuits. a) Document panelboard GH2 and H2 branch circuits and loads per NEC Articles 210 and 220; reference the above general comments. b) Document that weatherproof receptacles will be provided in compliance with NEC 410- 57(b); notes only call for termination of circuits. 69. E1.2 and E2.7. Document panelboard SPA branch circuits and loads per NEC Articles 210 and 220; reference the above general comments. 70. E2.1. Reference flag notes 2, 4, 5, 6, and 7 and plan notes. a) Document the one -line diagram, branch circuits and loads for future MMS (multiple meter stack), panel W (panel schedule only shown on sheet E2.1K), relocated H.C.E pad mounted transformer, panel K1 and K2 (panel schedules only shown on E:3 VAIL MOUNTAIN LODGE Phase III - V: Expansion & Renovation East Meadow Drive & Vail Valley Drive May 14, 2001 sheet E2.1 K), and downstream feeders from condominiums GS -5, GS -6, C5 -1 and C5 -2; general comments. Town of Vail C -West 201084 Code Review Pg. 9 of 15 MMS to reference the above b) Document the one -line diagram and load for the elevator connections to the club switchboard; reference the above general comments. c) Document the circuit and load for the elevator pit lighting and receptacle per NEC Article 220 and NEC 620 -24. 71. E2.1. Document that the elevator pit light is not connected downstream of the GFCI receptacle per NEC 620- 24(a). 72. E2.1 K. Reference kitchen detail 2, food service equipment load schedule and panelboard schedules: a) Document the minimum circuit ampacity and maximum overcurrent device for item number 2, freezer refrigerator system (circuit K1- 9,11), per NEC 440 -35 and 440- 22(c); 40A breaker is shown for #10 conductors and load is 21.4A. b) Document the feeder conductors for item 19, cook & hold oven (circuit K1 -23, 24), per NEC 240 -3; a load of 38.5A (8 kW at 208V, 1- phase) with 50A circuit breaker. c) Document that the feeder to item 37, booster heater (circuit K1- 20, 22, 24), complies with NEC 422 -10; 40A circuit shown and equipment is rated for 33.3A (12 kW, at 208V, 3- phase, 33.3 x 1.25 = 41.6A). d) Document that the feeder to item 41, ice machine (circuit K1 -26, 28), complies with NEC 240 -3(d); 25A circuit breaker shown for #12 conductors and load is 12.8A. e) Document that the feeder to item 45, coffee brewer (circuit K2 -5 ,7), complies with NEC 240 -3(d); 40A circuit breaker shown for #10 conductors and load is 28A. f) Document that the feeder to item 46, ice tea dispenser (circuit K2 -9), complies with NEC 240 -3(d); a 25A circuit breaker is shown for #12 conductors and the load is 1.7 kW. f7 VAIL MOUNTAIN LODGE Town of Vail Phase III - V : Expansion & Renovation C -West 201084 East Meadow Drive & Vail Valley Drive Code Review May 14, 2001 Pg. 10 of 15 73. E2.2. Document the feeder source and load for the elevator pit lighting and receptacle per NEC Article 220; only nearest 120V circuit indicated. Nearest suitable 120V circuit should be identified by the design engineer. 74. E2.2. Document the feeder for the elevator machine room 210 receptacle and lighting per NEC Article 220 for compliance with NEC 620- 23(a). 75. E2.2. Reference EF -1 (stair 202). The 15A/3 pole circuit breaker shown panel W -3, circuits 38, 40, and 42, does not comply with NEC Article 430; 17.5A shown per phase. 76. E2.2. Reference flag notes 1, 6, 7, and 8. Load is shown added to panel HG2 and the panel schedule with branch loads and load summary is not shown; reference the general comments above. 77. E2.2. Reference flag note 2. Reference the area enclosed by flag note 2. New circuits are shown to panel H2; however, they are not identified in the panel schedule on sheet E2.8. 78. E2.3. Document new panelboards A and G1A branch circuits and loads per NEC Articles 210 and 220; reference the above general comments. 79. E2.3. Document panelboard H3 (flag note 6) and G2 (flag note 15) branch circuits and loads per NEC Article 210 and 220; reference the above general comments. 80. E2.3, E2.4, E2.5, E2.6 and E2.7. Reference egress path lighting. Document that the wiring for the emergency egress lighting and exit signs in corridors and other egress paths complies with NEC 700 -12(e) for unit equipment wired to the same circuit as the normal lighting, and NEC 700 -16 for two lamps so that the failure of any individual lighting element will not leave the area in total darkness. a) E2.3. The F5 emergency cove fixtures in corridor 300 only have one lamp. b) E2.3. The emergency lighting and exit sign circuiting is not shown in corridor 300; the normal lighting circuiting is also not shown. c) E2.3. Document emergency egress lighting in vestibule 344 and stairs 308 per UBC 1003.2.9.2; nothing shown. 10 VAIL MOUNTAIN LODGE Town of Vail Phase III - V : Expansion & Renovation C -West 201084 East Meadow Drive & Vail Valley Drive Code Review May 14, 2001 Pg. 11 of 15 d) E2.3. Document emergency egress lighting over the exterior stairs, outside of vestibule 344 at column lines F, G and 13, per UBC 1003.2.9.2; nothing shown. e) E2.3. Document emergency egress lighting in elevator lobby; see flag note 6. f) E2.4. Document emergency egress lighting in elevator lobby; see flag note 6. g) E2.4 The F5 emergency cove fixtures in corridor 400 only have one lamp. h) E2.4. The emergency lighting and exit sign circuiting is not shown in corridor 300; the normal lighting circuiting is also not shown. i) E2.5. The F5 emergency cove fixture in corridor 500 only have one lamp. j) E2.5. The emergency lighting and exit sign circuiting is not shown in corridor 500; the normal lighting circuiting is also not shown. k) E2.5. Document emergency egress lighting in elevator lobby; see flag note 4. 1) E2.6. The F5 emergency cove fixture in corridor 600 and hall 622 only have one lamp. m) E2.6. The emergency lighting and exit sign circuiting is not shown in corridor 600 and hall 622, the normal lighting circuiting is also not shown. 81. E2.3. Reference flag note 16. The feeder noted from H3 to A does not comply with NEC 240 -3; #1 conductor (rated for 130A at 75 degrees C) shown protected by 150A breaker. 82. E2.3. Reference panels H2 and H2A, flag note 17. Document the one -line diagram per NEC 215 -5 (schedule shown on E2.8); reference the above general comments. 11 VAIL MOUNTAIN LODGE Town of Vail Phase III - V: Expansion & Renovation C -West 201084 East Meadow Drive & Vail Valley Drive Code Review May 14, 2001 Pg. 12 of 15 83. E2.3. Reference flag note 11. Document the branch circuit and load per NEC Articles 210 and 220; note indicates connection of lighting to existing circuit. 84. E2.4. Document panelboard G2, G2A, FF1, and FF2 branch circuits and loads per NEC Article 210 and 220; reference the above general comments. 85. E2.4. The location of new panelboard G2 does not comply with NEC 110- 26; the panel is located behind corridor doors to elevator. 86. E2.4. Further document the location of panel FF1 at column lines F -11 and document compliance with NEC 110 -26; the panelboard appears to be located behind a door. 87. E2.4. Document flag notes 13, 14 and 15 on plan; nothing shown. Also, document the panelboard branch circuits and load per NEC Articles 210 and 220; reference above general comments. 88. E2.5. Document new panelboard G3 and existing panelboard PG5 branch circuits and loads per NEC Article 210 and 220; reference the above general comments. 89. E2.6. Document new panelboard G4 branch circuits and loads per NEC Article 210 and 220; reference the above general comments. 90. E2.6. The location of new panelboard G4 does not comply with NEC 110- 26; the panel is located behind door. 91. E2.6. Reference flag note 10. Document the source panel for DC -5 and panelboard load calculations per NEC Articles 210 and 220. 92. E2.7. Reference detail 2, MAU -4. Document the branch circuit feeder and compliance with NEC Articles 220 and 430. 93. E2.7. Reference detail 2, AHU -1. Document the branch feeder breaker rating and compliance with NEC Article 430. 94. E2.7. Reference detail 2, emergency lighting circuit for dining room 200. Document the branch feeder and load of existing circuit for connection per NEC Article 220. Also, document compliance with NEC 700- 12(e), emergency lighting not shown connected to normal lighting circuit. 95. E2.7. Reference detail 1, emergency lighting circuit for wine cellar, passage and elevator lobby. Document the branch feeder and load per NEC Article 12 VAIL MOUNTAIN LODGE Town of Vail Phase III - V: Expansion & Renovation C -West 201084 East Meadow Drive & Vail Valley Drive Code Review May 14, 2001 Pg. 13 of 15 220; panel and circuit not shown. Also, document compliance with NEC 700- 12(e), emergency lighting not shown connected to normal lighting circuit. 96. E2.7. Reference detail 2. A separate circuit is not shown for elevator equipment room 210 per NEC 620- 33(a). 97. E2.7. Reference detail 1, equipment CU -1. Document the equipment load and feeder rating per NEC Article 424. 98. E2.8. Reference the "Partial Main Level Electrical Plan" detail. Emergency egress lighting is not shown for stairs 301 per UBC 1003.2.9.2. Even if the stairs are not part of the required egress system they are an occupied part of the building and may be in use; UBC 1001.1. 99. E2.8. Panel schedule 1-12A does not appear to be complete; document all loads and the load summary per NEC Article 220. For example, circuits H2A -19, 21 for equipment 101 is not shown. 100. E2.8. Reference the "Partial Main Level Electrical Plan" detail. Equipment mark numbers and circuiting for 86, 90, 93 and 119 -133 (with electrical loads) are not shown on the plan. Document the circuits and loads to demonstrate compliance with NEC Articles 210 and 220. 101. E11 through E3.5, and E1.1. Reference guest room details and lighting fixture C4 located above tubs and showers. Document that the fixture is "Suitable for Wet Locations" per NEC 410 -4(a); not indicated on fixture schedule sheet E1.1. 102. E3.1 through E3.5. Reference guest room details. Document the circuiting for all receptacles to demonstrate compliance with NEC 210 -60; some receptacles are not circuited. 103. E3.1 through E3.5. Document that the type C13 lighting fixture as used in the balcony is "Suitable for Damp Location" per NEC 410 -4(b); not indicated on fixture schedule sheet E1.1. Reference detail 1, unit 313a on sheet E3.1 for example. 104. E3.3. Reference panel FFU414, detail 1. The panel working space is obstructed by the laundry room door which does not comply with NEC 110 -26. 105. E3.5. Reference detail 1, unit 515B electrical plan. Nothing but background plan is shown; appears to be unfinished. 13 VAIL MOUNTAIN LODGE Town of Vail Phase III - V: Expansion & Renovation C -West 201084 East Meadow Drive & Vail Valley Drive Code Review May 14, 2001 Pg. 14 of 15 106. FP -2 through FP -7. Fire alarm system manual pull stations are not shown at all stairs and exits at each level per UFC 1007.3.3.1. 107. FP -2. Coordinate elevator #1 and #2 shaft detection with the chief; nothing shown. 108. FP -3. Document that the duct smoke detector in mechanical 209 is for the AHU -1; unit rated for 6850 cfm. Document duct smoke detector for MAU -1 per UMC 608; unit rated for 7600 cfm. 109. FP -4. Clarify and document the magnetic door hold open and smoke detector location shown at the bottom of stair 328; no door shown on architectural plan sheet A3 -3. Door schedule for project is not provided. 110. FP -4. Clarify and document the magnetic door hold open shown at column lines G -12; document what doors hold open is applied to. Also, no smoke detection shown. 111. FP -6. Coordinate and document the corridor double door at column lines G-4; the location does not match the architectural drawing A3 -4. Also, coordinate the additional magnetic door hold opens shown in corridor 500 at column lines G -5, G -7, and at the top of the stairs at approximately G -10. 112. FP -7. Coordinate and document the floor plan background between column lines G -2 to G -5; the floor plan does not match the architectural drawing A3 -6. 113. FP -7. The smoke detector at column lines F -5 in corridor 600 does not provide coverage all the way back to the door at column line G -4 per NFPA 72, 2- 3.4.5.1.2 & UFC STD. 10 -2; the distance to the door exceeds 21 feet from the detector. 114. FP -7. Fire alarm system visible notification devices are not located within 15' of the ends of corridor 600 (near column lines F -5 and F -9). C/A 4.26.3 115. FP -7. A fire alarm system visible notification device is not located in the elevator lobby 616 per UFC 1007.3.3.3.4 & C/A 4.26.3 C -West Code Consultants Tele : 303 205 -7860 2801 Youngfield Street, Suite 300 Fax: 303 237 -0023 Golden, Colorado 80401 E -Mail : steve @c- westcode.com www.c - westcode.com 14 VAIL MOUNTAIN LODGE Phase III - V: Expansion & Renovation East Meadow Drive & Vail Valley Drive May 14, 2001 lCB0 # 4495 Distribution : 15 Town of Vail C -West 201084 Code Review Pg. 15 of 15 Gary Goodell, CBO,TOV George Ruther, AICP Ron Drey, CW Gary Nickerson, CW PLAN REVIEW COMMENTS & CORRECTIONS, VAIL MOUNTAIN LODGE (FORMER VAIL ATHLETIC CLUB), PERMIT #1301 -02539 PHASE 1119 352 W. MEADOW DRIVE. 1. Reference Documents. Please refer to plan review report by C -West Code Consultants, Inc. dated 2/14/01, and Davis Partnership Architects response dated 7/20/01. All commitments made in the response to the C -West plan review report are considered to be conditions of approval for Permit #B01 -0253. Note that subsequent phases of the Vail Mountain Lodge project are also subject to the code requirements contained in the C -West Code Consultants, Inc. report and the requirements listed below. 2. Interpretations. Due to the facts that this is an existing building and this project has had various previous Town of Vail Design Review Board (DRB) and Planning and Environmental Commission (PEC) approvals which require a specific exterior appearance and the use of wood on the exterior, that the building has been the subject of a life safety analysis and fire protection engineering report by High Country Engineering, and for various other reasons, the following code interpretations have been made: a. Type II 1 -Hour Construction. The building will be considered as having two levels of basements and four stories, permitting the building to be classified as Type 1 1 1 -Hour construction. Much of the existing building meets the requirements for the next higher type of construction, Type II -F.R. Notable exceptions are that regular plywood roof sheathing is in place over much of the roof and most of the floor - ceiling assemblies cannot technically meet the Type II -F.R. requirements for a 2 -hour fire- resistive assembly primarily due to the webs of the existing steel open web floor joists being too light in gauge to achieve a 2 -hour rating. For practical purposes regarding emergency access, the fact that a portion of one side of the upper basement exceeds the height above grade of the UBC definitions for basements and stories has little, if any, effect, on emergency access. See also the High Country Engineering fire protection engineering report dated 10/5/2000 and the previous life safety issues analysis by High Country Engineering. b. Exterior Wood. A limited amount of certain types of wood will be permitted to be used on the exterior, as detailed below. 3. Use of Wood on the Exterior: a. Siding. All wood siding used on the building, regardless of its location and height above grade, is to be factory fire - retardant - treated wood meeting the UBC definition and standard for "Fire- Retardant - Treated Wood" found under Section 207, 1997 UBC. Siding is to otherwise "...be placed either directly against noncombustible surfaces or furred out from such surfaces not to exceed 1- 5/8" with all concealed spaces fire blocked as provided in Section 708." One way that this requirement can be met is to apply fire - resistive exterior gypsum sheathing underneath the siding. b. Trim. All trim, including fascia boards, is to be at least "2 X" nominal in dimension. c. Ornamentation. Larger wooden ornamentation, i.e., corbels, "brackets," etc. are to be at least "4 X" nominal material and larger. d. Soffits. Any wooden horizontal soffits are to be backed by noncombustible materials or solid "2 X" wood blocking covered by 5/8" exterior fire - resistive gypsum sheathing with any wooden soffit materials to be either approved, factory fire- retardant - treated wood OR m treated with an approved, exterior flame retardant treatment to achieve a Class "A" (UBC Class I) flame spread rating. e. Eaves. All exterior walls are to be built "tight to the deck" to attempt to prevent the spread of an exterior fire into the eaves and roof structure. The underside of any existing plywood roof sheathing that is exposed during construction will be treated with an approved interior flame retardant treatment to obtain a Class "A" (UBC Class I) flame spread rating. Approved insulation materials will be blown into joist spaces to serve as fire blocking within the joist cavities of the roof assembly. In accordance with Section 707.3, 1997 UBC, kraft paper backing is not permitted to be used in Type II buildings. Any vapor retarders used must meet the flame spread and smoke developed rating requirements of Section 707. f. Guardrails. The proposed rough- sawn - cedar- covered balcony guard rails are EITHER to be constructed of approved factory fire- retardant - treated wood OR treated with an exterior flame retardant treatment to achieve a Class "A" (UBC Class I) flame spread rating. The flame retardant treatment is also to be protected from ultra- violet degradation by an approved finish treatment. The applicant is to follow up by submitting a proposal for the treatment of the guard rail materials to the building official for review and approval. g. Shutters. The proposed window shutters are subject to the same requirements as item "f' immediately above. 4. Miscellaneous. Any and all new wood installed as sheathing, backing, blocking, sleepers, etc., within assemblies must be approved fire- retardant - treated wood. See Section 603. 1, 1997 UBC. Gary R. oodell, Chief Building Official GRG: grg TRANSMITTAL Date: 12/5/2001 Project No.: 00220.00 Project Name: Vail Mountain Lodge — Expansion and Renovation To: The Town of Vail Attn: Charlie Davis We are sending you the following material: ❑ HEREWITH ❑ UNDER SEPARATE COVER ® BY MESSENGER ❑ VIA FEDERAL EXPRESS Copies I Sheet No. I Description 4 NT -1 & Addendum #1 — Phase III Permit Doc NT -2, O S2.5 -S2.7; Comments: Call with questions From: Tony Ricca Copy to: Gary Adams, Jay Peterson, Ray Story ❑ Approved ❑ Approved As Noted ❑ Disapproved/Resubmit M Other Davis Partnership P.C., Architects I Denver Office: 2301 Blake Street Suite 100 Denver Colorado 80205 -2108 303.861.8555 Fax 303.861.3027 Vail Office: 0737 Main Street Unit C7 06 P.O. Box 2711 Edwards Colorado 81632 970.926.8960 Fox 970.926 -8961 10/03/2801 09:57 0000000 M014ROE NEWELL PAGE 03/03 Monroe & Newell Engineers, inc. i' JOB L1 � I?" MEET NO. :5 t? . S- Of CALCULATEDBY CHEW:[) BY I - - - - - - - - - - ... ....... ........ . 4 L L7 5 15. IT6. 71m TAmI 4 114 P DATE 10 1 Z - 0 j DATE r y . ...... . ........ r 10/03/2001 09:57 0000000 Monroe & Newell Engbieem, Inc. MONROE NEWELL L SHEET 140. . e 52. (o OF CALCULATED CHECKED BY PAGE 02/03 [)ATE 10-3 -01 DATE SCALE 4.. ... . .... .. ----------- - ..... . ... . .......... 2-7t, Id IL ............ . . .. . .. !v F y IL _J 6 ......... A R .. ._4 4k 41 4 re ...... . ....... . -�-- 7-- et i 10/08/2002 0S: 36 jJ 0000000 A101-Iroe & Newell . Engiricers, Tnc. M014ROE NEWELL PAGE 02/02 JOB V n� SHEET NO. OF CALCULATED 8Y ter`~ J DATE _ CHECKEDBY 101103/2001 09:57 0000000 :3 Monroe & Newell Engineers, bac. M014ROE HDj.)ELL JOB SHEET NO. CALCULATEDBY PAGE 03'/63 OF DATE 10 ! 0 j CHMM BY DATE SCALE e. J. .. ... ... .... . . . 42 A- r 4 J. 10/03/2001 09:57 0000000 Monroe & Newell Engineers, Inc. MONROE NEWELL im-- \Lm L (/0 19 SHEET 140. 52- G OF CALCULATED sy--!�= CHECKED BY. PAGE 02/03 DATE 10-3-01 DATE SCALE ........ ... . -(ek10 . . .... . ...... .4E C1 !v . . ......... C rk -Nb J-e: r\ k, , i 4' - -------------- .............. .. I 10/08/2001 09:36 000000 MONROE NEWELL PAGE 02/02 r n�Io11z �e & Newell Engixieers, Inc. SMEET NO _ OF cnicuL.,aTEv sY K— �J DATE I 5 - E `D ) 10/03/2001 05:57 0000000 Monroe & Newell )Engineers, Inc. 1,1014ROE 14E(4ELL J { JOB V Nl (j SHEET NO. f 2 ' S7 - _ -- CALCULATEDBY c-- - CHECKED BY PAGE 03/03 OF - OATE 10 -3 -Di DATE SCALE ......... . ........ ... ... . ......... 7i: ....... . .... ..... ------ ; : w �i : t : : i : K .. y .. :... .. ..... . . r i ; 10,•'03,'2001 09:57 0000000 0i00 Monroe & Newell Engineers, inc. `H Y 1,9014ROE NEWELL JOB V N1 ( 7 SHEET NO. CALCULATEDBY 5n ' CHECKED eY PAGE 03r 03 OF OATE i 3 DATE SCAM a i t : .. .. i ... .. ..... ..... n _ ... .. .. _ _.. _ _» — __ .... .____ .. ....:......... - -- - _ - 2 114 T : : i t 10/03/2001 09:57 0000000 Monroe & Newell Englneers, Inc. MONROE NDi.)ELL JOB \1 pi L 10 SHEET 140._5_ -( OF CALCULATED CHECKED PAGE 02/03 DATE ) 0 - �3 - 0 1 DATE SCALE 10 .... ....... . . . . . . .... Cl F jNa�. Lo 12WL I ...... . ... .. . ...... j ... ...... L + . . were ----------- A I in 10/00',/2001 09: 36 0000000 Monroe & Neurell En.90-ril-ers, Inc. MONROE NEWELL JOB V -SHEET NO. OF_` PAGE F- CALCULATED BY--!=:- DATE PAGE 02/02 -t4- V. -I) Qtk�lc: IqT. 7 'NO R C30 10/03/2001 69:57 6OOO6 00 MONROE ND4ELL PAGE 02/03 Monroe & Newell EngIneers, Inc. JOB SHEET 140. OF CALCULATED CHECKED BY. DATF; / 0 .3 0 1 DATE SCALE . . ............. ....... .. ..... . . ...... --- -------- t ......... . ....... Lu J! C1 zu > . . . . . . . . . . . . . .. . ........ ...... . .... ... ... • .................... . 1T-O f . .......... . ........ . _4 . .. ... 10/0812001 09:36 0000000 .1 Onroe & Newell . E71 _91xicer$, Inc. M014k0E NEWELL JOB V rO y t4 0 1 SHEET WQ, ' OF CALCVLAJW 6Y. PAGE 02102 DATE ( f-' - 4-- _ t 7� .1 x.q. x. pGk ED(r L 019 YS A ..cr K.I.�1 - tVO U_Z�RfJ)tl.Zr. S NO2: kcoF: 1 t 7� .1 x.q. x. pGk ED(r L 019 YS A ..cr K.I.�1 - tVO U_Z�RfJ)tl.Zr. S NO2: kcoF: Town of Vail Building Safety and Inspection Services 75. South Frontage Rd. Vail, Colorado 81657 (970)479 -2138 Plan convection based on The 1997 Uniform Building Code Date: September 23, 2002 Project Number: B02 -0268 Project Name: Vail Mountain Lodge Phase IV Address: 352 E Meadow Dr Occupancy: R1 /A3 Construction: 11 1 -HR Report By: Charlie Davis Contractor: Shaw Construction Architect: Raymond E Story Jr. Engineer: Peter Donald Monroe Listed below are corrections that are required to be addressed. Responses listed in italics are responses to response from the Architect of record dated 9/6/02 NOTE: The code items listed in this report are not intended to be a complete listing of all possible code requirements in the 1997 UBC. It is a guide to selected sections of the code. # SHEET IDENTIFICATION CORRECTION REQUIRED 1. None Provided Provide a complete site plan showing all structures, dimensions, and public ways. Landscaping and all public improvements required for this project shall be submitted — Sec. 106.3.3. Site /Landscape plan has been received and approved by the Town of Vail Planning Department. 2. All Pages Glazing in a hazardous location is required to be glazed with safety material. -- Sec. 2406.3 & Sec. 2406.4 No window /door schedule provided. Still required, no door /window schedule received to date. 3. A4.1/4.2 Not Shown Provide attic ventilation that complies with Sec. 1505.3. Will be addressed in the Tenant Finish Package. See Architect of Record Response dated 916102 4. A1.4/3.1 Not Shown Provide an attic access (22X30 min) to each attic area. -- Sec. 1505.1 This will be addressed in the Tenant Finish Package. See Architect of Record Response dated 9/6102 5. All Pages Not Shown This area is required to have an automatic sprinkler system. -- Sec. 904.2.1 This will be addressed in the Tenant Finish Package. See Architect of Record Response dated 916102 6. A1.1 Provide a complete foundation design for this building based on the soils condition at this site for expanded portion of restaurant. -- Chapter 18. This foundation work was completed in a previous phase of construction. See Sheet S5 for detail. 7. A1.3/1.4 East penthouse Include a complete framing plan for each floor. —Sec. 106.3.31 Will be addressed in the Tenant Finish Package. See Architect of Record Response dated 916102. The Tenant Finish package shall provide additional detail when submitted. 8. All Sheets Provide room finish schedules for all areas being renovated. Unable to determine extent of work being proposed. -- Sec. 106.3.3.1 Will be addressed in the Tenant Finish Package. See Architect of Record Response dated 916102 ALL Provide information of how existing hotel rooms are accessed and means of egress is maintained at north side of corridor. -- Sec. 1004.2.3.3. The area in question is an existing portion of the hotel and is not considered for construction at this time. See Architect of Record response dated 916102. 10. A1.4 Provide more information of upper level East Penthouse, Is employee unit under ownership of east penthouse? If not, a separation is required. -- Sec. 310.2.21 Will be addressed in the Tenant Finish Package. See Architect of Record Response dated 916102 11. All pages Provide a door schedule for all doors being added or replaced. -- Sec. 106.3.1 Door Schedule still required and shall be addressed with the Tenant Finish package. See Architect of Record response dated 916102. 12. A1.3/1.4/1.5 Provide information of type of shaft assembly proposed for relocated kitchen ductwork. -- Sec. 711, Table 6 -A & 1997 UMC. -- Sec. 507.6 Where is kitchen mechanical equipment being relocated to? Has DRB (Design Review Board) approval been obtained? If this equipment is to be relocated to an exterior location such as the rooftop, DRB approval is required. Show location of kitchen equipment on plans. See architect of Record response, Item 12, dated 916102. All mechanical assemblies and equipment shall comply with the 1997 Uniform Mechanical Code. 13. A1.3 Mechanical equipment not allowed within or accessed from exit enclosure. Provide more detail as to what type of equipment this is and how it is being accessed. -- Sec. 1005.3.3.1 & 1005.3.3.5 See Architect of Record response, Item 13, dated 916102. All mechanical assemblies and equipment shall comply with the 1997 Uniform Mechanical Code. 14. 15. S1 /S2 Provide information of what type of assembly will be used to protect structural elements of building. -- Sec. 704, Table 6 -A & 7 -A. See Architect of Record response dated 916102. If spray - applied fire proofing is installed, it shall be inspected by an independent special inspector. Provide reports of these inspections at time of a framing inspection. 16. A1.3/1.4 Provide information of assembly of stairs in east penthouse showing conformance of type of materials used -- Sec. 603.4, and showing conformance to - -Sec. 1003.3.3. Shall be submitted with the Tenant Finish package. See architect of Record response, item 15, dated 916102 17. A4.1/4.2 Details show that plywood being used for roof assemblies. This is not allowed. Provide revised details. — Sec. 603.5. Per Architect of Record response, item 16, existing plywood can be treated as discussed however, any new assemblies must conform to the type of construction requirements and plywood products is not allowed to be used in exterior assemblies. 18. All pages Provide information type and quantity of alarm devices being proposed. -- Sec. 310.10. See architect of Record response, Fire Alarm information shall be submitted at time of Tenant Finish package. This is not a complete list of corrections required. Field inspections shall be performed to check for code compliance. Any code non - conformities found during the course of construction and inspection shall be addressed in an approved manner. INTERNATIONAL September 3, 2002 Town of Vail Building Safety and Inspection Services 75 South Frontage Road Vail, Colorado 81657 Attn: Charlie Davis RE: Vail Mountain Lodge Project No. B02 -0267 352 E. Meadow Drive Vail, Colorado In response to your letter dated August 27, 2002, please accept the following: General: The permit application you are reviewing for this project is for "Core & Shell ". Therefore, some of the internal construction will be clarified with the "Tenant Finish" application drawings. Item 1: We have copied the Civil Engineering package and the new "current ", interim site plan. Shaw Construction will deliver 4 sets to you. The interim site plan is for work this fall. The original approval for the total project is still in effect & will need to be "accounted for" as we complete the various phases. Item 2: The current application has windows that are not hazardous locations. Also there are doors and sidelights that are hazardous. We will submit a schedule of windows and doors as soon as we receive compliance from "Built Best" the manufacturer. Item 3 & 4: We do not have attics in this phase "Core & Shell ". Attic ventilation and access shall be addressed with the "Tenant Finish" package. Item 5: The automatic sprinkling is "warehouse" design per current conditions. We will maintain the existing during the "Core & Shell" construction. The "Tenant finish" package shall be a design — build contract similar to the west penthouse "Lubin" now virtually complete. 3 8 8 Market Street, Suite Number 3 8 0, S a n F r a n c i s c o C A 9 4 1 1 1 phone: 415.392.4433 fax: 415.392.4454 email: info @Resortl) esign.com www.Resortl) esign.com Item 6: Concrete foundation for this area is existing. (M -N shall add a sheet S -5 for clarification of details in this area.) Item 7: Level 3 (third floor) is existing with minor in.fil at north wall. Level 4 (fourth floor) is existing with significant modification. See sheets S -1. Item 8: See general comment re: "Core & Shell" only for this application. Item 9: We are not sure what you are asking. The Hotel exiting shall remain as it is today per U.B.C. and approved plans. (Subject to Shaw furnishing the approved construction.) This work does not modify existing egress corridors or stairs. Item 10: If interior "Tenant Finish" plans take over the employee housing unit, then it will need to be replaced as a part of the P &Z, DRB and staff approvals. Our original approval moved all 4 employee units to the first floor. Our current interior preliminary plan leaves the employee unit as is. Item 11: Exterior doors to balconies are only doors in this phase "Core & Shell ". Schedule shall be provided with windows. Item 12: Roof top — chimney exhaust look and forms are on DRB approval. Shafts shall be extended and built to comply with current codes. We are not exactly sure what assembly was approved for the floor below, however, the new assembly must be compatible with the existing on below level. Item 13: We will provide all egress separations with "Tenant Finish' package. (Especially mech/attic /stair) Item 14: Fire protection shall be "spray on" as currently approved or gypsum board wrap - 2 layers '/2" type X — per existing conditions. Type II — 1 hour minimum standard. item 15: Inter stair shall be steel structure & pan with concrete fill — same as West Penthouse — Lubin. Details with "Tenant Finish' application. Item 16: Per our site meeting with T.O.V. Building Inspection & Vail Fire Dept: If we spray existing wood deck with fire retardant coating, fill the joist space with insulations and complete all exterior wall assemblies tight to underside of deck, then this would comply as approved mitigation for "exception to the rule ". This is the approved process from Phase III of this project. Also, we are placing Y2" exterior type X gypsum sheathing on top of the roof deck with fire rated shingles to complete the fire assembly. 2 Item 17: The fire alarm system shall be extended from the "main building" and shall be a "design building" submittal with the "Tenant Finish" applications. We are currently working to complete the "Tenant Finish" submittal. Hopefully, we may tore & Shell" so as to be enclosed for the winter. iciates cc: Stan Cope — Fax (970) 476 -4093 Keith Oxenreider — Fax (970) 241 -5618 3