HomeMy WebLinkAboutB07-0172 B07-0172: Entries for Item:90 - BLDG-Final 10:55 07/02/2013
Action Comments By Date Unique_
PI 1.REINSPECT WHEN STORE IS SET UP GCD 12/14/2007 A000109
2.SEAL PENETRATIONS IN SMOKE WALL 395
3.DUCT DETECTOR IS OPERATIONAL
AP ALL BUILDING ITEMS APPR. GCD 12/19/2007 A000109
STILL NEED PLANNING AND FIRE 667
APPROVAL
Total Rows:2
Page 1
E07-0209: Entries for Item:190 - ELEC-Final 10:55 07/02/2013
Action Comments By Date Unique_
Ke
CR EXIT LIGHTS ARE NOT WORKING. shahn 11/27/2007 A000108
529
CR EXIT SIGNS HAVE BEEN CORRECTED. SHAHN 11/30/2007 A000108
IT WAS NOTICED THAT APPROX 200 720
FLUORESCENT FIXTURES HAVE BEEN
INSTALLED BY TENANT INCLUDING 50
OBSOLETE T12 FLUORESCENTS.
PROVIDE REVISED COMCHECK REPORT
TO INCLUDE DISPLAY LIGHTING.
AP REVISEDCOMCHECKAPPROVED. SHAHN 12/11/2007 A000109
168
Total Rows:3
I
Page 1
I
TOWN OF VAIL DEPARTMENT OF COMMUNITY DEVELOPMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2138
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
ADD/ALT COMM BUILD PERMT Permit # B07-0172; ��� �� � ���
Project# PRJ07-0138
Job Address: 675 LIONSHEAD PL VAIL Status . . . : ISSUED
Location.......: QUIKSILVER @ ARRABELLE Applied .. . : 06/14/2007
Parcel No....: 210106308007 � Issued . . . : 08/21/2007
Expires.....: 02/17/2008
OWNER VAIL CORP 06/14/2007
PO BOX 7
VAIL, CO
81658
CONTRACTOR BLACK DUCK BUILDERS 06/14/2007 Phone: 970-262-:1430
PO BOX 593
DILLON
CO 80435
License: 678-B
APPLICANT FRICKE DESIGN/BUILD, INC. 06/14/2007 Phone: 303-917-8001
3829 RALEIGH ST.
DENVER
CO 80212-2129
Desciption:
QUIKSILVER TENANT FINISH
Occupancy: M
Type Construction: I-B
Valuation: $216,000.00 Revision Valuation: $0.00 Total Sq Ft Added: 0
****s*�+*s.�***r***�***+***********�►�r��****a*s*+**�*�*���r*xa*t*r* FEE S UMMARY r*******s***�*r�***+a****�:*************r***�:�**�****►r******
Building------> $1,643.35 Restuarant Plan Review--> $o.00 Total Calculated Fees--> $z,714.53
Plan Check---> $i,0 6 8.1 e Recreation Fee--------------> $o.0 0 Additional Fees----��-----> $o.0 0
Investigation-> $o.0 0 TOTAL FEES-------------> $2,�14.53 Total Permit Fee---��-----> $2,714.53
Will Call-----> $3.0 0 Payments-------------°-----> $2,7 1 4.5 3
BALANCE DUE---�------> $o.0 0
*�*s�r**+�sss***�*++**+a*+*+•r.s*��*+*�******r*�*�**�e***s++*s**«*.�**�*+s**s►x*s*as*r*s**���*�****�*******+*�****s�s****+****+�*►++*+�+**s*.*++:
Approvals:
Item: 05100 BUILDING DEPARTMENT
07/03/2007 cgunion Action: AP
Item: 05400 PLANNING DEPARTMENT
Item: 05600 FIRE DEPARTMENT
07/02/2007 mvaughan Action: AP fire and sprinkler
plan submittal requred to reflect changes.
Item: 05500 PUBLIC WORKS
07/03/2007 TK Action: AP Tenant
Finish-Quicksilver-No PW Issues
�#**#*M####*##fi####*#*#**MM####*#��►#rt###*#*#*#####4�4t##4*#*4*t*##f�*##*#*#####k###*#*4#M##4#*#**#####k#*###*##*t###�#*t##*fk*4###4**#*##*#***f•
See the Conditions section of this Document for any conditions that may apply to this permlt.
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, connpleted an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan, to comply with all
Town ardinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordinances of the Town applicable;thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY-FOUR HOURS IN ADVANCE BY TELEP NE 479-2149 OR AT OUR OFFICE FROM 8:00 AM•
4 PM.
SI A OF OWNER OR CONTRACTOR FOR HIMSELF AND OWNER
********************************************************************************************************
CONDITIONS OF APPROVAL
Permit#: B07-0172 as of 08-21-2007 Status: ISSUED
********************************************************************************************************
Permit Type: ADD/ALT COMM BUILD PERMT Applied: 06/14/2007
Applicant: FRICKE DESIGNBUILD, INC. Issued: 08/21/2007
303-917-8001 To Expire: 02/17/2008
Job Address: 675 LIONSHEAD PL VAIL
Location: QUIKSILVER @ ARRABELLE
Parcel No: 210106308007
Description:
QUIKSILVER TENANT FINISH
***********************************************Conditions:************************************************
Cond: 1
(FIRE): FIRE DEPARTMENT APPROVAL IS REQUIRED BEFORE ANY
WORK CAN BE STARTED.
Cond: 12
(BLDG.): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE
COMPLIANCE.
Cond: 14
(BLDG.): ALL PENETRATIONS IN WALLS, CEILINGS, AND FLOORS TO
BE SEALED WITH AN APPROVED FIRE MATERIAL.
Cond: CON0009135
1) SMOKE RESISTANT WALL PARTITIONS TO FLOOR DECK AND SMOKE
DOOR REQUIRED AROUND STORAGE ROOM PER IBC.
2) ANY MATERIAL IN PLENUM CEILING MUST BE LISTED FOR USE IN
THE CEILING PER IMC.
****####*#****#*#***#####**rt#***#**#####***##****#****###***#*##*#**#*#**##*****�k##****###**
TOWN OF VAIL, COLORADO Statement
#***####*#*######*�****##**####*#*##*#***#***#*****#*#**#*###*****#**#***#***###:k*##*##****#
Statement Number: R070001626 Amount: $1,646.35 08/21/200703 :C16 PM
Payment Method: Check Init: DDG
Notation: Fricke
Design/Build INc. 1600
-----------------------------------------------------------------------------
Permit No: B07-0172 Type: ADD/ALT COMM BUILD PER]yT
Parcel No: 2101-063-0800-7
Site Address: 675 LIONSHEAD PL VAIL
Location: QUIKSILVER @ ARRABELLE
Total Fees: $2, 714 .53
This Payment: $1, 646.35 Total ALL Pmts: $2,714 .53
Balance: $0.00
**************************+*****************************+*********************************�*
ACCOUNT ITEM LIST:
Account Code Description Cu.rrent Pmts
-------------------- ------------------------------ ------------
BP 00100003111100 BUILDING PERMIT FEES 1, 643 .35
WC 00100003112800 WILL CALL INSPECTION FEE 3 .00
-----------------------------------------------------------------------------
u
APPLICATION WILL NOT BE ACCEPTED IF INCOMPLETE OR UNSI . � � �
Project#: � (�"� �
Bu�ldmg Permrt# ' l7�
�' • O ��"t�'�4'��������'�tt��p�e��+4 ���
� � �,�y�
� �
�p �
7�!�����ge Rd. 1 ,(I� u1� , � ��y �,t"'`�'-�" ��!,D
Vail Colorado 81657 1 `� ~� '`� U�
� � ,
TOWN OF VAIL BUILDING P RI�IT APPLICAI'ION f
Separate Permits are required for electrical, plumbing, mechanical, �tc.! � ��/ ��
CONTRACTOR INFORMATION
General Contractor: Town of Vail Reg. No.: Contact Person and Phone#'s:
L SGOiT —6�►C.1C,� 303 a1� 90�1
[3L►�cK DV K t3v�L.U�KS �o�� �� � -�03 2�iq. 330�
Email address: S�ot��{r�ck¢,des� nbwld•c.ow� Fax#: �20 2q.(, qo�8
Contractor Signature:
COMPLETE VALUATIONS FOR BUILDING PERMIT Labor 8� Materials)
BUILDING: $ ELECTRICAL: $ OTHER: $
PLUMBING: $ MECHANICAL: $ TOTAL: $ 2;��,00�,o0
For Parcel# Contact Ea !e Coun Assessors Office at 970-328-8640 or visif wwiv.eaple-countv.com
��r��� �
z �o c��3 c� 8�v �
Tri� q �3 ar a��. va .
Job Name: Job Address:��s '-;or'"c'°"' Y'^°c�
QU�KSILv�� pUrLPIN�i � LE�'$�- Z RETq�L P21'�
� �� c.o 91G;S"7
Legal Description Lot: Block: Filing: Subdivision:
OwA e�rs Name� ���� Go Address: r Phone:
L
Architect/Designer: Address: r Phone:
Topp rr�Rc tr�.c v E 15Z3 �S�'" SS p�NV+�R G� 8o2v 2- (, 303 4��o�o
Engineer: N►u�rtvu�, sE6 ca�rErC�+7 Address: rPhone:
L
Detailed description of work:
I N"i'Et2i,o2 1�.Nr��tT ��iy)5�-) �� f�.Tt41 L, S?Ac.E
Work Class: New( ) Addition ( ) Remodel (X) Repair( ) Demo ( ) Other( )
Work Type: Interior(� Exterior( ) Both ( ) Does an EHU exist at this location: Yes ( ) No ( )
Type of Bldg.: Single-family( ) Two-family( ) Multi-family( ) Commercial(� Restaurant( ) Other( )
No. of Existing Dwelling Units in this building: No. of Accommodation Units in this building:
No/Type of Fireplaces Existing: Gas Appliances ( ) Gas Logs ( ) Wood/Pellet( ) Wood Burning ( )
No/Type of Fireplaces Proposed: Gas Appliances ( ) Gas Logs( ) Wood/Pellet( ) Wood Burning (NOT ALLOWED)
Does a Fire Alarm Exist: Yes No( ) Does a Fire Sprinkler System Exist: Yes (�() No( )
FOR OFFICE USE ONLY*'"�''`***��''���
�-----�--�— � _
�Date�ece�v�d � ; ' -� � �� � [� � � �
�Re,ce�ved,By';. . .. �
�����` ��'� !� �E�J�! �6 2�07
i
F:\cdev\FORMS\Permits\Building\building�ermit_4-17-2007.DOC P��/�1 OF VAI L 04/1 /2007
�z¢o Architecture Inc chicago denver
4240
June 4, 2007
Mr. Charlie Davis
Town of Vail Chief Building Officia�
Department of Community Development
75 South Frontage Road
Vail, CO 81657
Re: The Arrabelle Building - Retail Tenant Improvements: Burton; Quicksilver; Pa�tagonia; Sunglass
Shop. All four(4) construction document sets produced by Todd Architecture, 1523 15th Street,
Denver, CO, and dated May 8, 2007.
Dear Charlie:
Pursuant to 2003 IBC Section 106.3.4, this is to inform you that 4240 Architecture, as the registered
architectural design professional in responsible charge for the Arrabelle Project, has reviewed the above
referenced proposed retail tenant improvement construction documents. To the best of our knowledge,
we find these documents compatible with the approved construction documents for the Arrabelle Project.
Please do not hesitate to call should you have any questions.
Sincerely,
Robert Fitzgerald
Principal
��` � ����94
�...'�P ,
ALD
2081
�
`/��ti \���
sE0 A R��
i6zi Eighteenth Street Suite zoo Denver,Colorado 8ozo2 T 303 z92 33$$ F 3�3 292 3>>3 W 424oarchitecture.com
CATOR,RuMA�J ASSOC IATES, CO.
PRINCIPALS CONSULTING MECHANICAL�ELECT'RICAL ENGINEERS
MICHAEL A.MEINTS
]OHN A.HUGHES
BRUCEE.APPEL
]AMES R.I,AZZERI
MARCIIS A.V,4I.F.RIUS
SENIOR ASSOCIATE
MARK V.�ELINSKE June 4�GOO/
nssoc�n�res
SEAN�1�.CONVBRY
GF.RARD W.O'BRIfiN
DF;NNIS F.RUDKO
4VAYNE A.TRADER Mr. Charlie Davis
Town of Vail Chief Building Official
Deparhnent of Community Development
75 South Frontage Road
Vail, CO 81657
RE: The Arrabelle Building
Tenant Finishes for Burton,Patagonia, Quicksilver, and Sunglass Shop
Todd Architecture Tenant Finish drawings dated May 8,2007
Mechanical/ElectricaUPlumbing Infrastructure Coordination Re`�iew
CRA Project No. 2007-146
Dear Mr. Davis:
Pursuant to 2003 IBC Section 106.3.4, this is to inform you tha1; Cator, Ruma and
Associates, as the registered design professional in responsible charge of the Mechanical,
Electrical, and Plumbing design for the base building at Arrabelle, has reviewed the
proposed above referenced tenant finish packages being submitted fi�r a revision to the
approved construction documents. To the best of our knowledge, we find the proposed
revisions compatible with the approved construction documents.
Please call if you have any questions or concerns.
\`���,,,,,,.,.: Sincerely,
e�'� P�o RE���`.
\�.��`\Q� H• S'�r�'E, CATOR, RUMA&ASSOCIAT, �REG/Sl
\ U • ,�N.. ����.�cr ,��;:'o�U�s yo F��o
_� , � ; c� - ��' 96 �:
. . ��
_ : � ; .
.o•
�, ,�':JUN 4 20J?�'�<v:, . � ��
'�%�s�''•• ..,. •••°'�,\'�;' John A. Hughes,P.E. H . •P: e��,��
�''�i��ah1�L E�,.�`�`, Principal Mf,c �` eer
�t�rr��������� � �1
HDY/
P:�2007�2007-146 Tenant Finish Review\Sup\Docs\Reports�2007-146 burton pat quick sun 060407.doc
Cc: Steve Roberts—42/40 Architecture
1550 DOVER STREET�SU[TE 2�LAKEWOOD,COLORADO 80215-3132
PHONE(303)232-6200�FAX(303)233-3701 �E-MAIL:cra@catorruma.rom
######**##**#**##*#*#**###************###**�##*##*#****#*#*##**#*#*#****##****�k*###**#######
TOWN OF VAIL, COLORADO Statement
� #*****###*#***#**********##*#****#***###*****##*****#****#####******##***#***#�k**##*****#**#
Statement Number: R070000957 Amount: $1,068.18 06/14/200709:28 AM
Payment Method: Check Init: JS
Notation: 1570/FRICKE
DESIGN/BUILD, INC.
-----------------------------------------------------------------------------
Permit No: B07-0172 Type: ADD/ALT COMM BUILD PE:RMT
Parcel No: 2101-063-0800-7
Site Address: 675 LIONSHEAD PL VAIL
Location: QUIKSILVER @ ARRABELLE
Total Fees: $2,714.53
This Payment: $1, 068.18 Total ALL Pmts: $1,068.18
Balance: $1,646.35
***********************************************************:x�x*************�x***�*************
� ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------------- ------------------------------ ------------
PF 00100003112300 PLAN CHECK FEES 1, 068.18
------------------------------------------------------------------------------
I
--— -- --- --_ _._
�(07/25/2007) Charhe Davis- B07-0172.... -� Page 1 '
._mm �_ _-_ ---�.... _ _..._
From: George Ruther
To: Building_Division
Date: 07/25/2007 10:51 AM
Subject: B07-0172....
Quiksilver has been approved.
George Ruther, AICP
Director of Community Development
Town of Vail
(970) 479-2145 office
(970) 376-2675 cell
(970) 479-2452 fax
gruther@vailgov.com
, .. ,.
COMcheck Software Version 3.4.2
Lighting Applic tion Works et
}-�� C�� �� f�-r'r�-� ,���
2003 IECC -�P� � ^��_ �l�Z
Report Date:
Data filename:NKvafslkVA ConsultinglProjects\2007-085�AdminlSchedules120031ECC07-085QSilver.cck
Section 1: Allowed Lighting Power Calculation
A B C D
Area Category Floor Area Allowed Allowed Watts
(tt2) Watts/ft2 (B x C)
Retail Sales,Wholesate Showroom 3870 1.7 6579
Aliowance:Merchandise Display!Fix.ID:D and T 2250(a) 1,6 3600(b)
Aliowance:Merchandise Display/Fix.ID:Light Boxes 500(a) 1.6 800(b)
Allowance:Merchandise Display/Fix.ID:LLitebox 1500(a) 1.6 2400(b)
Office 55 1.1 61
Storage,I�dustrial and Commercial 375 0.8 300
Total Allowed Watts= 13740
(a)Area claimed must not exceed the illuminated area permitted for this ailowance type.
(b) Allowance is(B x C)or the actual wattage of the fixtures given i�Section 2,whichever is less.
Section 2: Actual Lighting Power Calculation
A B C D E
Flxture ID:Description/Lamp/Wattage Per Lamp/Ballast Lamps/ �of Fixture (C X D)
Fixture Flxtures Watt.
Retail Sales,Wholesale Showroom(3870 sq.ft)
HID 1:D and T:CF InductioN Integrated MH/Other/Electronic 1 190 23 4370
Linear Fluorescent 3:light Boxes:Tenant Light Fixture!24"T8 17W/Electronic 1 160 17 2720
Linear Fluorescent 4:WS:Fitting Rm Mirror Light/Other/Electronic 2 8 42 336
Incandescent 1:P1:Decorative Pendant/Incandescent 50W 3 2 150 300
Incandescent 1 copy 1:P2:Decorative Pendant/Incandescent 60W 2 3 120 360
Incandescent 1 copy 1:P3:Decorative Pendant/Incandescent 25W 1 30 25 750
Linear Fluorescent 5:LLitebox:Large Light Box!48"T12 40W/Electronic 1 100 38 3800
linear Fluorescent 6:S1:Surfboard Uplight/48"T8 32W/Electronic 2 6 65 390
Office(55 sq.ft.)
Linear Fluorescent 1:A:2x4/48"T8 32W/Electronic 3 1 96 96
Storage,Industrlal and Commercial(375 sq.ft)
Linear Fluorescent 2:S:Strip Light/48"TS 32W/Electronic 2 8 65 520
Total Actual Watts= 13642
Section 3: Compliance Calculation
If the Total Allowed Watts minus the Total Actual Watts is greater than or equal to zero,the building complies.
Total Allowed Watts= 13740
Total Actual Watts= 13642
Project Compliance= 98
i------'--=',.�., V_ .
�'r=- a
� � (� ��� �! ���'� � ' �,,�i
�;���. '�.� I— 1� 1
�i��
'�34235 r' v D �� I
. _
_ _ : ._ _ ��-� � � '',�
�•�ti ����� Page 3 of 3 �-`
�•�:?�...�••• ,
�`��,.� Tow� �� v���.. _
� . �.
The area is a corridor,storeroom,restroom,public lobby or guest room;
Areas that use less tha�0.6 Watts/sq.ft.
� 8. Automatic lighting shutoff«�ntrol in buildings larger than 5,000 sq.ft.
Exceptions:
Areas with only one luminaire,corridors,storerooms,restrooms,or public lobbies.
� 9. Photocefl/astronomical time switch on exterior lights.
Exceptions:
Lighting intended for 24 hour use.
� 10.Tandem wired one-lamp and three-lamp ballasted luminaires(No singie-lamp ballasts).
Exceptions:
Electronic high-frequency ballasts;Luminaires on emergency circuits or with no available pair.
Section 4: Compliance Statement
Compliance Statement: The proposed lighting design represented in this document is�nsistent with the building plans,specifications
and other calculations submitted with this permit applicatio�.The proposed lighting system has been designed 6�meet the 2003 IECC,
Chapter 8,requirements in COMcheck Version 3.4.2 and to comply with the mandatory requirements in the Requirements Checklist.
Cart Fretwell,P.E.
Name-Title Signature t)ate
O RE
'• �
O'�' � ��'��tn
c.�: � �r;v
��� ....,.��,lo�(��
���..f
_ ___ _
Page 2 of 3
, . _
COMcheck Software Version 3.4.2
Lighting Compliance Certificate
2003 IECC
Report Date:12/06/07
Data filename:NKvafslkVA Consulting\Projects12007-085Wdmin\Schedules�20031ECC07-085QSilver.cdc
Section 1: Project Information
Project Title:Quicksilver
Construction Site: OwnedAgent: DesignerlContractor:
The Arrabelle at Vail Square Carl Frehvell
Vail,CO 81657 kVA Consulting
19590 East Main Street
Parker,CO 80138
(303)646-4770
carlQkvaconsulting.net
Section 2: General Information
Building Use Description by: Activity Type
Project Type: New Construction
Activtri Tvoelsl Floor Area
Retail Saies,Wholesale Showroom 3870 �
Office 55
Storage,Industrial and Commercial 375 •�
O •'' T tt`�
Section 3: Requirements Checklist O�;='�
:� �,q� v
Interior Lighting: �� �Z����
� 1. Total actual watts must be less than or equal to total albwed watts. ti,�..�
Allowed Watts Actual Watts Complies
13740 13642 YES
� 2. Exit signs 5 Watts or less per side.
Exterior Lighting:
� 3. Efficacy greater than 45 lumenslW.
Exceptions:
Specialized lighting highlighting features of historic buildings;signage;safery or security lighting;low-�roltage landscape
lighting.
Controls,Switching,and Wiring:
� 4. Independent controls for each space(switch/occupancy sensor).
Exceptions:
Areas designated as security or emergency areas that must be continuously illuminated.
Lighting in stairways or corridors that are elements of the means of egress.
� 5. Master switch at entry to hotellmotel guest room.
� 6. Individual dwelling units separately metered.
� 7. Each space provided with a manual control to provide uniform light reduction by at least 50%.
Exceptions:
Only one luminaire in space;
An occupant-sensing device controls the area;
_. ...._._ _..... ....._.. _ ..._.. . . _.. ... _ _ _ _ _..... _. .. _ _ . _.. .. _
Page 1 of 3
Town of Vail
Building Department
To Whom it May Concern:
This letter authorizes the transfer of the rights and responsibilities of the Bu�ilding Permit
for the Quiksilver store from Black Duck Builders to McBoyd Constructiori. ?7�, -r3
L "
Chris Steinlce
President
Black Duck Builders
',�p"7 - Ut i �
TOWN C'1F VAIL FIRE DEPARTMENT VAIL FIRE DEPARTMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2]35
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIluIES
ALARM PERMIT Permit #: �07-0110
Job Address: 675 LIONSHEAD PL VAIL Status . . . : ISSUED
Location.....: QUIKSILVER @ ARRABELLE Applied . . : 10/OS/2007
Parcel No...: 210106308007 Issued . . : 10/11/2007
Project No : Expires . .: 04/08/2008
OWNER VAIL CORP 10/05/2007
PO BOX 7
VAIL, CO
81658
APPLICANT COMMERCIAL SPECIALISTS OF 10/05/2007 Phone: 970-513-7100
WESTERN COLORADO, LLC
P.O. BOX 1572
SILVERTHORNE
CO 80498
License: 161-5
CONTRACTOR COMMERCIAL SPECIALISTS OF 10/05/2007 Phone: 970-513-7100
WESTERN COLORADO, LLC
P.O. BOX 1572
SILVERTHORNE
CO 80498
License: 161-5
Desciption: QUIKSILVER TENANT FINISH-INSTALLATION OF SMOKE DETECTORS,
HEAT DETECTORS STROBES AND SPEAKERS STROBES
Valuation: $6,863.00
*****���+a�*s*»*+*******�******��***********�**�*r�**+*r+*►***+►**** FEE S UMMARY +******�*��svxr+�s***r***a��+a*s*+�***+*�*****s�**+**��**�*+
Electrical---------> $o.o o Total Calcuiated Fees--> $4 a 9.3 6
DRB Fee---------> $0.0 0 Additional Fees----------> $o.o 0
Investigation----> $o.o o Total Permit Fee--------> $4 8 9.3 6
W ill Call---------> $o.o o Payments------------------> $4 8 9.3 6
TOTAL FEES--> $4 8 9.3 6 BALANCE DUE--------> $0.o 0
�*�****sr:..■■**.***«***x►**+►*►�►*+*��r►.****:�**s*■**+:*s***�+**+*���*x****+*►****a��*s****�****+*+*s»+*r*s*s***■**«►**s+***�+*»wr**►sr*■.+■*■+
Approvals:
Item: 05600 FIRE DEPARTMENT
10/08/2007 mcgee Action: AP
�**.�+**.*....,*.*,*�**.*.*.�:...«*.:***.*.**.:,:+::.*»+*.*.*..*...**+..*.*,:�..,**...*+*.***..�*..+.*.,�*��:**.*.*.**«*.***+....*:****..+�..►.+.*.*
CONDITIONS OF APPROVAL
.*..*.*.*.*.�*.*..�.*.*****�..�*.**�*�*�►.��*...**.****.�*�.*..**..*.*.,�.*.*�.,..**.**.**�**,.�*.*��*�:*.****.*.*.*�«.«.....*....*�*.*.*.*.*.*�..�
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan,to comply with all
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordinances of the Town applicabl�e thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY-FOUR HOURS IN ADVANCE BY TELEPHONE AT 479-2135 FROM 8;00 AM-5 PM.
� �S`�`��
, �, �
**********************************+********************************************�:************
TOWN OF VAIL, COLORADO Statement
***************************************************************+++***++******�*�r:****++*****+
Statement Number: R070002168 Amount: $489.36 10/il/200708:31 AM
Payment Method: Check Init: DDG
Notation: Commercial
Special 10825
-----------------------------------------------------------------------------
Permit No: A07-0110 Type: ALARM PERMIT
Parcel No: 2101-063-0800-7
Site Address: 675 LIONSHEAD PL VAIL
Location: QUIKSILVER @ ARRABELLE
Total Fees: $489.36
This Payment: $489.36 Total ALL Pmts: $489.36
Balance: $0.00
*************************************+*****************************************�************
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------------- ------------------------------ -- ----------
BP 00100003111100 FIRE ALARM PERMIT FEES 257.36
PF 00100003112300 PLAN CHECK FEES 232.00
-----------------------------------------------------------------------------
TOWN OF VAIL DEPARTMENT OF COMMUNITY DEVELOPMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2138
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
ELECTRICAL PERMIT Permit #: L07-0209
'�,U1 - O 1-1 �
Job Address: 675 LIONSHEAD PL VAIL Status . . . : ISSUED
Location.....: QUIKSILVER @ ARRABELLE Applied . . : 09/OS/2007
Parcel No...: 210106308007 Issued . . . 09/06/2007
Legal Description: ���� -C��� Expires . .: 03/04/2008
Project No :
OWNER VAIL CORP 09/05/2007
PO BOX 7
VAIL, CO
81658
APPLICANT A-PHASE ELECTRIC, LLC 09/05/2007 Phone: 970-845-0188
PO BOX 1564
AVON
CO 81620
License: 313-E
CONTRACTOR A-PHASE ELECTRIC, LLC 09/05/2007 Phone: 970-845-0188
PO BOX 1564
AVON
CO 81620
License: 313-E
Desciption: PROVIDE POWER AND LLIGHTING, LIGHT FIXTURES,
VOICE/DATANIDEO CONDUIT, CONDUIT RACEWAY FOR FIRE ALARM
SYSTEM FOR THE QUIKSILVER TENANT FINISH
Valuation: $59,600.00 Square feet: 0
�**�»�*****t*t***+**s**********�+s*��****�**s*********�****++**+*+* FEE S UMMARY *****�x**►*�*******+*te****rvs*r�**+******+�*�+***s**x******
Electrical---------> $i,2 9 9.5 0 Total Calculated Fees--> S 1,3 0 3.5 0
Investigation----> $o.o o Additional Fees----------> $o.0 0
W il I Call---------> $t.0 0 Total Permit Fee--------> $1,3 0 3.5 0
TOTAL FEES--> $1,3 0 3.5 0 Payments------------------> $1,3 0 3.5 0
BALANCE DUE--------> $o,o 0
.*:�*r***r.*****+*■*:*■**.**r■***�:*►+*+***+*ae**+***ase+**t****.rs*�*..****a**�***rr*r*r**■*:**+***a�r******�:******s****►*►a:**�+��*+*rwrr**e*r*
Approvals:
Item: 06000 ELECTRICAL DEPARTMENT
09/06/2007 SHAHN Action: AP PER APPROVED PLANS
Item: 05600 FIRE DEPARTMENT
****�.**.*.**.*�*.�+�**�:..�***+****:+****�*.*.***.*:*s***.**...****+**.*s*..*«*«*+*,*.*.*,�*�****+.***•***:*,:*.�*:***.s*..........:..►��,�.,.*+*
CONDITIONS OF APPROVAL
Cond: 12
(BLDG. ) : FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIAN�CE.
*+.*s*s�:,:**.+*�***.«***.**��**.+***.*.,*�*.**s*.*.*.*�*...:...+*:.*•+***s.:.*.*►**.*.*,:*.*�*s***.+v:++�***.**,*.*v****.***.*.:.:.*«...+**�**�*...
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan,to comply with all
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordinances of wn applicabl.e thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY-FOUR HOURS I A ANCE BY TELEP AT 479-2 R AT OUR OFFICE FROM 8:00 AM-4 PM.
SIGNATURE OF OWNER OR CONTRACTOR FOR HIMSELF AND OWNER
********************+***************************+******************************��************
TOWN OF VAIL, COLORADO Statement
*******************************************************************************��************
Statement Number: R070001784 Amount: $1, 303 .50 09/06/200703 :38 PM
Payment Method: Check Init: DDG
Notation: A-Phase 2525
---------------------------------------------------------------- -------------
Permit No: E07-0209 Type: ELECTRICAL PERMIT
Parcel No: 2101-063-0800-7
Site Address: 675 LIONSHEAD PL VAIL
Location: QUIKSILVER @ ARRABELLE
Total Fees: $1, 303 .50
This Payment: $1, 303.50 Total ALL Pmts: $1,303 .50
salance: $0. 00
*******************************************************************************��************
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------------- ------------------------------ -�-----------
EP 00100003111100 ELECTRICAL PERMIT FEES 1,299.50
WC 00100003112800 WILL CALL INSPECTION FEE 4 .00
---------------------------------------------------------------- -------------
' ' ' • APPLICATION WILL NOT BE ACCEPTED IF 3NCOMPLETE OR UNSIGNED
Pr�ject#: r�-�a'1 —0238
Building Permit#; $a� O t?2�
� ElectrECal Permit#:
r�y����yr�"� � 970-479-2149{Inspections)
!U Y'
75 S.Frontage Rd.
Vail, Colorado 8i657
TOWN OF VAIL LECTRICAL PERMIT APPLICATIOIY
CONT CTOR INFORMAIION
E ectrical Contractor: Town oP ail Reg. No.: Cantad Person and �hone #'s;
� P� �t '?�13 J�Il�I D(L ��c,t� ���1�a
E-Mail Address. i � Fax#: ?O � S �
Contra r Slgnature:
CflMPLETE SQ. FOOTAGE FOR AREA OF ORK AND VALUATION OF WORK(Labar & Materials)
AMOUNT OF SQ FT IN STRUCTURE: ELECTRICAL VALUATION: $ � (pQQ �
Contact Ea /e toun As�essars Offrce at 9 0-328-8640 or visit wwvw,ea /e-coun .com for Parce/#
Parcel # Z(D p(d 30 800'/
3ob Name: Q�IG�Git �� ��i1�l�t�� !`�(.�.f Job Address: ��s j�D,��t9� T L ' V�L
Legal Descripdon I.o� Block: F ling: Subdivision:
Owr�ers Name: v�� (�j� Address: � Phone:
Engineer: Address: Phone;
Detailed description o�work: ����Ci "� � l�lC��'[�N � (�(C��,�' :�1 yc�7� �Pg1
�IGG� D� ��1 p� �c�t�u i T, �1��1 T ��`1?-�1n/�1 � �c � ��r�n� S�S�Z_n�
Work Ctass: New( ) Addit]on ( ) RemodeE . Repair ( ) Temp Power( } Other( ) •
Work Type: Interior( Exterior� ) Both ( ) Does an EHl! ex9st at this loc�tion: Yes( ) No( )
Type of Bldg.: Single-famijy( ) Duplex( ) Muiti-famil ( ) Commercial ) Restaurant( ) Other( ) �
No. af Existing Dwelling Units in this building: No. of Accommadation Units �n this building:
Is this ermit for a h�ot tub: Yes No
Does a Fire Alarm Exist: Yes( ) No( ) Does a Fire Sprinkler SysEem E�cist: Yes( ) No( )
' e�s ��� _ ��--,
�*��r*�*�**��,a*�'* ***�**,��*�*�**�**�**��FOR OFFICE USE QNLY*X�*�,�� ��*��� � * �*�
��
:;�:ather;�ee��;�'�_��_�::�= ,.._ _-�,;`:: Dat �:I�eceived:=`. -:;: - ,:
� ;;..:
,
..:: ,;;:�
.. .
2�
�7
:�; :.: _�:�.y.-�=_: ;x - .-:Acce ted�'.::.:. �;�
..DRB�Eees.:' �,k`:� -
•� �� -
-......
....>.
.....� . �.._,. - �.
.
, :. .: __ _
,, �,..,,,..,a.� ,: r
'�.' '-
.;
_ . ::.;
�P anne.r.'S'i n-off.:.:::,: :.. : .:.:,::. - - � -
. . . .
�� TOWN OF VAIL
r
F:l�devl�RMS�PERMI�Building�electical�ermf�.11-23-20o5.D0 Page i of 2 /2005
�•d stn7.�GtA0l6 ���!2� uuof' �LO�LO LO �0 d8S
� � .� r
�
. � � �
T�O�N OF PA1� '
Amendrnent�o the 2002 N.E.C. Town of Vail Ordinance 4, Series of Z005
a Ovefiead services are not allowed in ifie Tawn of Vail. .
a Underground serviees sha!!be in cflnduit (PVC) from the util►ity trans�ormer to the electric meter, ma'tn
disconnect switch, and tio the first electrical disfribution circui�breaker panef.
a The main d'�onnec�switch shall be re�adilyacciessibl�aedlocated next to the meter on the exterior wall of
the str�cfiare A!I underground oondu�ts are required to be inspected before back�,fiiling the trench.
v In�nulb-family dw�llir�g un�ts, no�iectrical wiring o�fieeder cables shatl pass from o.ne unit to another. Common
waffs and s�aces are exempt
a �iM Cable (Rornex) can fae �sed only in sing/e and mu/ti fami/y dvlretlings net exceeding 3 st+vrie�.
TypeNlNcannatberrsedinanybai/ding�nixe�d with Tjrpe.�B.�F,H,I,M&Soccupancies.
o Alrrr�intrm c�vnductorssmaller than size#8 are not perrni�:ed with the Town of Vail.
TOWN �F VAIL ELECTRICAL PERMIT GUIDELIN�S
❑ All instailatians af exterior hot tubs or spa's requi�-e a DRB approvaE from plar�ning.This application wi�l
no� be accepted witJ�out a copy of t�e DR8 approval €orm a�.tached (if appNicable).
� If this permi��s foc inst�ilat+on of an extenor hot tub or spa on a new elevated platform ar deck over
30" above grade, you must also obtain a bu�lding permit. .
❑ �f this permit is for installation of an exteripr hot#ub or spa on any exis4�g deck or elevated platform,
a structural engineer must rev�ew tl�e existing condition and verify that i� will support the added
cancentrated 1oad. Please provide a copy;of the s�uctural engineers wet�tarnped letter or drawing
with �h�s applacation. !
n If this is a nernodel in a rnulti-family building with a homeowners associa�ion, a letter o� perrnissior�
fror� tfie a�saciation is required. i
n if�his permit is �or a cort�meraal space, two (�) sets of s�mped drawings are required.�Electrica/
one-Iine ar�d panelscltedu/es�re required ifload is added or distribution is altered.
1
!
I hav read an derstand the abave. ;
. � I
� � � -
5ignature i Da#e igned
If you have any questions regarding the ai�ove iefonrativn or have additional questions,
please contact�he Town of Ya�l Electric�! Inspector a�97�-479-2147. The inspecfior can be
reached on Monday thru Friday rnornm�s befinreen the hours of Sam and 9am, You may also
leave a voice n�ail and the inspecfior wif� call you �ack.
,
�
i
�
i
�
�:�cdev�FORMSIPERMITS18udc�ng�electiml�ermit 31-Zi-2005.DOC Pag+e 2 of 2 1f/73/2005
�•d Qn�nc+�aniF ec�oi� uyo� �80�L0 LO ti0 deS
TOWN OF VAIL FIRE DEPARTMENT VAIL FIRE DEPARTMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2135
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
SPRINKLER PERMIT Permit #: F07-0097
Job Address: 675 LIONSHEAD PL VAIL Status . . . : ISSUED
Location.....: QUIKSILVER @ ARRABELLE Applied . . : 09/14/2007
Parcel No...: 210106308007 Issued . . : 10/03/2007
Project No : Expires . .:
OWNER VAIL CORP 09/14/2007
PO BOX 7
VAIL, CO
81658
APPLICANT ALL STATE FIRE PROTECTION, I09/14/2007 Phone: 303-288-3901
6045 E 76TH #12
COMMERCE CITY
CO 80022
License: 370-5
CONTRACTOR ALL STATE FIRE PROTECTION, I09/14/2007 Phone: 303-288-3901
6045 E 76TH #12
COMMERCE CITY
CO 80022
License: 370-5
Desciption: INSTALL FIRE SPRINKLER SYSTEM FOR QUIKSILVER TENANT FINISH
Valuation: $12,100.00
*s+*+**�*++t*******+*++**�s*�*r******r******►�►v*�*r�******a+*a**tr* FEE S UMMARY *****a***s+**��r**+r****+f+s�»�***�****�****t�*******a*�**r*
Mechanical---> $o.o o Restuarant Plan Review--> $o.0 o Total Calculated Fe;es---> $8 64.2 5
Plan Check---> $3 5 0.o o DRB Fee---------------------> $0.0 o Additional Fees-----------> $116.o 0
Investigation-> $0.0o TOTALFEES--------------> $864.25 TotalPermitFee----------> $960.25
W ill Call-----> $o.o o Payments-------------------> $9 8 0.2 5
BALANCE DUE---------> $o.o 0
****�*t********�**r*r*s*****************xr*+*+********r******r********+****«�*************a*******���::r*******�:*****aM****+*********►*►*t***�*+*++
Item: 05100 BUILDING DEPARTMENT
Item: 05600 FIRE DEPARTMENT
09/19/2007 JJR Action: DN Incomplete applicatian.
Incomplete plan registration form.
09/28/2007 JJR Action: AP
11/19/2007 McGee Action: AP Quicksiler surt board. plan approved on rev:
11/16/07 .
CONDITION OF APPROVAL
Cond: 12
(BLDG. ) : FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
«**...**..*�*::.�**:*....**.*.*+��.+:.****..*****.*«+...�..�*.**..,:+�.***.*..***...*.*+*+*.....+...�,�.**..:s,:*..*,:.*►*.***.»....***.+.*,�*.......
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and��lot plan,to comply with all
Town ordinances and state laws, and to build this structure according to the towns zoning a subdivision codes, design review
approved, International Building and Residential Codes and other inances of the To n ap licable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY R HOUR ADV CE BY TELEPHONE AT 479-2135
FROM 5:00 AM-5 PM.
�
S T F ER R CONTRACT��R FOR HIMSELF AND OWNER
***+*******+**************************************++****************************************
. TOWN OF VAIL, COLORADO Statement
*******#*********�k+*+*****++�********************#*****************************��***t********
Statement Number: R070002592 Amount: $116. 00 11/27/200712:26 PM
Payment Method: Check Init: LC
Notation: #18706/ALL
STATE FIRE PROTECTION INC.
-----------------------------------------------------------------------------
Permit No: F07-0097 Type: SPRINKLER PERMIT
Parcel No: 2101-063-0800-7
Site Address: 675 LIONSHEAD PL VAIL
Location: QUIKSILVER @ ARRABELLE
Total Fees: $980.25
This Payment: $116.00 Total ALL Pmts: $980.25
Balance: $0.00
*******************************************************************************�:************
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------------- ------------------------------ -------------
BP 00100003111100 SPRINKLER PERMIT FEES 116.00
-----------------------------------------------------------------------------
,..- ��_ - -- _- ___� �_ __.- __ . — � �__. - �-- __�_
i (11/19/2007) Mike McGee- F07 0097 Quicksilver Surfboard Revision Page 1
From: Mike McGee
To: rgibler@allstatefireprotection.com
Date: 11/19/2007 9:39 AM
Subject: F07-0097 Quicksilver SurFboard Revision
CC: Building_Division; Dave Leiker; Fire_Inspectors
Approved
Additional Plan Check fee$116.00 assessed.
TOWN OF VAIL FIRE DEPARTMENT VAIL FIRE DEPARTMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2135
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIl�✓IES
SPRINKLER PERMIT Permit #: F07-0097
Job Address: 675 LIONSHEAD PL VAIL Status . . . : ISSUED
Location.....: QUIKSILVER @ ARRABELLE Applied . . : 09/14/2007
Parcel No...: 210106308007 Issued . . . 10/03/2007
Project No : Expires . .:
OWNER VAIL CORP 09/14/2007
PO BOX 7
VAIL, CO
81658
APPLICANT ALL STATE FIRE PROTECTION, I09/14/2007 Phone: 303-288-3901
6045 E 76TH #12
COMMERCE CITY
CO 80022
License: 370-5
CONTRACTOR ALL STATE FIRE PROTECTION, I09/14/2007 Phone: 303-288-3901
6045 E 76TH #12
COMMERCE CITY
CO 80022
License: 370-5
Desciption: INSTALL FIRE SPRINKLER SYSTEM FOR QUIKSILVER TENANT FINISH
Valuation: $12,100.00
«*��*t*�a*t*t*t**�r+r+�t****rr***�+t**+*r*******+++�«*+�x*�********* FEE SUMMARY *�**�s**�***************+a�**x*x+xr***r*���*�****�+�********+
Mechanical---> $o.o o Restuarant Plan Review--> $o.o o Total Calculated Fees---> $86 n.2 5
Plan Check---> $3 5 0.0 0 DRB Fee---------------------> $0.0 0 Additional Fees-----••-----> $0.0 0
Investigation-> $o.o o TOTAL FEES--------------> $8 6 4.2 5 Total Permit Fee----��-----> $s 54.2 5
Will Call-----> $0.00 Payments-------------••-----> $864.25
BALANCE DUE---��-----> $o.0 0
*�*****s***►********sa*r******�******************arrr********s****►****r*s*�****s********�***�:*�****xa***rr******►�x*******►�*****te+********�«**
Item: 05100 BUILDING DEPARTMENT
Item: 05600 FIRE DEPARTMENT
09/19/2007 JJR Action: DN Incomplete application.
Incomplete plan registration form.
09/28/2007 JJR Action: AP
CONDITION OF APPROVAL
Cond: 12
(BLDG. ) : FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
*�*�.*����*+*+*«*.*..***.*.*.*:*.*..,:.:...*�*.+,«�**:r*�*�:*****:..:.*�■*.*.�**.�.**.*►****+*�r****►*r.«**..****r*.**■**:r*.*+.+*...�.�r..***.*.****
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, cobnpleted an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan,to comply with all
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordinances of the Town applicabl��thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY-FOD URS IN A �LEPHONE AT 479-2135
FROM 8:00 AM-5 PM. �_
�
,� ,�(��� ��
SIGN URE OF OWNER OR ONTRACTOR FOR HIMSELF AND OWNER
************************+**�***+********************************+***************+***********
TOWN OF VAIL, COLORADO Statement
***************************+**++++++************************+**+*�**************************
Statement Number: R070002068 Amount: $864.25 10/03/200710:47 AM
Payment Method: Check Init: LT
Notation: All State Fire
Protection /#15816
-----------------------------------------------------------------------------
Permit No: F07-0097 Type: SPRINKLER PERMIT
Parcel No: 2101-063-0800-7
Site Address: 675 LIONSHEAD PL VAIL
Location: QUIKSILVER @ ARRABELLE
Total Fees: $864.25
This Payment: $864.25 Total ALL Pmts: $864.25
Balance: $0.00
********************************************************************************************
ACCOLINT ITEM LIST:
Account Code Description Current Pmts
-------------------- ------------------------------ ------------
BP 00100003111100 SPRINKLER PERMIT FEES 514.25
PF 00100003112300 PLAN CHECK FEES 350.00
-----------------------------------------------------------------------------
k�5!'19;`20b? E��: 44 3�32881935 �1LLST�rTE F'AGE �i2
APPLfCAT�#�N WILL NOT�E ACCEPT�D IF INCOMPL���OR LINSIGNE:D
P raJe ct #:
w . � � Building Permit#:_ _ ______
U� � Sprinkler Permit#:
9ro:��s-Z�as(�nsnecrl°ns)
TUA�N4FYAIL T��N OF VAiI� FfRE SPRINKLER P�RIV�IT A�PPLIGATfON
Fire Sprfnkter shap drawings are requ�red at t�me af permit s��bmittal and
75 S. Frontage Rd. must irtclud� the following.Permlt appllcatian wili not be acr�epted
Vail, Cvlorado 81657 wf#hout this Infiarmation:
� . A Colorado Registered Engineer's stamp or N.I,C.�,T. Level IEI (min) stamp.
• Equipment aut sheets af materlals.
. Hydr�ulic calculations.
• A State�f Colorado Plan Registrativrl form.
, + Pfans must be subrnitted by a Registered Flre Proxection Contractor.
CON'Y'RA.C'�O�t 1NFORMATION
Fire Sprinkl�r Cpntractor: Town of Vai!Reg. No.: Contact and Phone#'s:
'q� 3�7b � � I�l;l�. krtas-�ek 3�3�ZS° -3�D1
E-Ma�l Address: �n i k_e_k� all s�-ake 're, rp'Fee_�-ror� . co,-r�
GontrdCtar Slgnature: J']
JCQ C '�t o r1 t 4,�
� COMFL��T�VALUATIONS FOR A�,ARM PERMIT (Labor& Materlalls)
--�
�Ire Sprinkler:$ � � , �_�� •�Q
�.�
Co»tact�a !e Counf As�essors Dfflce at 970-328-8540 or vlslt www�.ea !�- co,�»for Parcel#
parcel# !O 1 Dlp 3C?SDD7
Job Name: Job Address: ��� ���n S�^�.ci.c� �1 �� �
��;�� s;l��,� � �-,�������� .,.
Le�al Description �ot: BIoCk� Fillrtg: Subdivisi�n;
�( Owners Name: �CJI�� �G� Address: �� �G � � ��` �0 �i(r�r� Phone: ���..5 i 7 - Gk�{�
�nginear; Address: Phone:
Detsfled l.oc�tion af work. (i.e.,floor,unit#, bldg. #)
u,n y k .zb _
Detailed descr(ptlon of wark:
ir����ll -�i�re. 5 r;nkl�,.�` � 5�'�rn
Work Glass: New� ) Additian ( } Remodel( ) Repair( ) Retro�fit( ) Other( )
`fype of Bldg., Singla-family( ) Two-iamily( ) Mult!-family{ ) Comm�rCial(�d? Restaurant( ) Other{ )
-�..
No. of Existing Dwelling Units In this building_ No.of Aacommadatian ltni.ts in thia building:
Do9s� Flre A{arm Ex1st: Y68( ) No{ ) Does a �ire Sprinkler System Exist: Y6s( } No( )
r���**,r�r�,r�*�k**,r***,o*,�,t*w,.****�,t,tfi***�*FOR�F ! *��'��`,� *��
`�M��� �
,�f �'r�y�"r�n �'p .rl�r;" '''" .�l� �
,� , .� y�� Y�; +��['f�f, ..
,:,. h �( y c r �i ,Y w1y � ,�@ r ' � 4�. .�,: {,e I.i�w �L P Itl/d art '
u 1 {� I� �i ,�,a� .}:T�i�S ;�t� .tJyn�y�-rv.'��4.� . .� �.e' 'i ''G F .h�,t1. 6.�. �un i -- — /�
I'. • .
,,. •.... . . �.r....... . . .. , ., .
�% ��j � ^ � . !����/—_
�,�Vailldn'nledevlFORMSlPER1�FlTStiSPRICPERh1.DOC � �,5.�---- �'���v �
� , Z�. G 7 •
�
TOWN OF VAIL DEPARTMENT OF COMMUNITY DEVELOPMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2138
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIPvIES
MECHANICAL PERMIT Permit #: M07-0183
'�G1 -c� c�t �
Job Address: 675 LIONSHEAD PL VAIL Status . . . : ISSUED
Location.....: QUIKSILVER @ ARRABELLE Applied . . : 08/28/2007
Parcel No...: 210106308007 Issued . . : 09/OS/2007
Legal Description: ���'l _ 6 � 3� Expires . .: 03/03/2008
Project No :
OWNER VAIL CORP 08/28/2007
PO BOX 7
VAIL, CO
81658
APPLICANT R & H MECHANICAL LLC 08/28/2007 Phone: (970) 328-2699
PO BOX 810
EAGLE
CO 81631
License: 184-M
CONTRACTOR R & H MECHANICAL LLC 08/28/2007 Phone: (970) 328-2699
PO BOX 810
EAGLE
CO 81631
License: 184-M
Desciption: QUIKSILVER TENANT FINISH-HVAC TENANT FINISH SYSTEM
Valuation: $25,000.00
Fireplace Information:Restricted: #of Gas Appliances: 0 #of Gas Logs: 0 #of Wood Pellet: 0
**+�a*****►*►x*****�*a**x��«**r+a►+r****+**«********++***►�**rr***** FEE S UMMARY *rr*******rs*+r****«****���***►*��**+***r�:�r*�+****«******+*•
Mechanical---> $5 0 0.o o Restuarant Plan Review--> $o.o o Total Calculated Fees---> $6 2 8.o 0
Plan Check---> $12 5.0 0 TOTAL FEES--------------> $62 s.o o Additional Fees-----------> $o.o 0
Investigation-> $0.0 0 Total Permit Fee----------> $62 8.o 0
W ill Call-----> $3.0 o Payments-------------------> $6 2 6.o 0
BALANCE DUE---------> $o.0 0
*a*t**��*�x**s►.**+srss*s******r****�*e*************�*x****�+**+�*�***��s�*��********+****+******�*�++�:��*****.�s*s**s**s+******+*►*+�*�**�**�a:�
Item: 05100 BUILDING DEPARTMENT
08/28/2007 cgunion Action: AP
Item: 05600 FIRE DEPARTMENT
CONDITION OF APPROVAL
Cond: 12
(BLDG. ) : FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
Cond: 22
(BLDG. ) : COMBUSTION AIR IS REQUIRED PER CHAPTER 7 OF THE 2003 IMC AND SECTION
304 OF THE 2003 IFGC AS MODIFIED BY TOWN OF VAIL.
Cond: 23
(BLDG. ) : BOIILER INSTALLATION MUST CONFORM TO MANUFACTURER' S INSTRUCTIONS AND
CHAPTER 10 OF THE 2003 IMC.
Cond: 25
(BLDG. ) : GAS APPLIANCES SHALL BE VENTED ACCORDING TO CHAPTER 5 OF THE 2003 IFGC.
Cond: 29
(BLDG. ) : ACCESS TO MECHANICAL EQUIPMENT MUST COMPLY WITH CHAPTER 3 OF THE 2003
IMC AND CHAPTER 3 OF THE 2003 IFGC. .
Cond: 31
(BLDG. ) : BOILERS SHALL BE MOUNTED ON FLOORS OF NONCOMBUSTIBLE CONST. UNLESS
LISTED FOR MOUNTING ON COMBUSTIBLE FLOORING.
Cond: 32
(BLDG. ) : PERMIT, PLANS AND CODE ANALYSIS MUST BE POSTED IN MECHANICAL ROOM PRIOR
TO AN INSPECTION REQUEST.
Cond: 30
(BLDG. ) : BOILER ROOMS SHALL BE EQUIPPPED WITH A FLOOR DR.AIN OR OTHER APPROVED
MEANS FOR DISPOSING OF LIQUID WASTE PER SECTION 1004 . 6 .
**..�*»,*s*,*.*s***.»*.*s.�.**»*.*�.*.»..*.�+.�.*:+.*.*�++*++***�*..**.+.**��.**.*:*.�.*...**..*�.**�*�.**�«*�*�.*+.*...��**.*.**�..*s*+++:�*�...
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and ��lot plan, to comply with all
Town ordinances and state laws, and to build this structure accordirt�;to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordinances of the Town applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY-FOUR HOURS INADVANCE BY TELEPH NEiAT 479-2149 OR AT OUR OFFICE FROM 8:00 AM-4 PM.
SIGNATURE OF O ER'DR CONTRACT��R FOR HIMSELF AND OWNER
; �
***######*##*###**********************#**#**##*#*##*########********#########*#MK**###*******
TOWN OF VAIL, COLORADO Statement
##*###*##*##*#####*########**#********##*****##**###*#**##***##***#*********###�k#******#*###
Statement Number: R070001757 Amount: $628. 00 09/05/200712 :36 PM
Payment Method: Check Init: LC
Notation: #12795/R & H
MECHANICAL
----------------------------------------------------------------�-------------
Permit No: M07-0183 Type: MECHANICAL PERMIT
Parcel No: 2101-063-0800-7
Site Address: 675 LIONSHEAD PL VAIL
Location: QUIKSILVER @ ARRABELLE
Total Fees: $628.00
This Payment: $628.00 Total ALL Pmts: $628. 00
Balance: $0. 00
�k�k�k*#:k#:k##+k�K�k�k**#+k*#*�k�k�k�k�k�k�k�K*�k�kok###�k#######�k�K#*#�k�k�k*�k�k:k:k�k�k#:k:k##*�k*�k�k�k�k�k�k�k�k�k�k-k*qk##�k�k:k*�k#�k�K�k�k
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------------- ------------------------------ -�-----------
MP 00100003111100 MECHANICAL PERMIT FEES 500.00
PF 00100003112300 PLAN CHECK FEES 125.00
WC 00100003112800 WILL CALL INSPECTION FEE 3 .00
----------------------------------------------------------------�-------------
� ^' ``+�'`i�jun ►�1�I��,NOT BE ACCEPTED I�TNCOMPLEI'E OR UNSI
. � z3 �
. . .
Projecfi#;, ��- Q
� d� , O � 8'3 Building Permit�:
� � Mechanical Permit#: • �
���F�� 970-479-214!�.(inspections)
TOW N QF VAIL NlECHqNTCAL PERMIT AppLIC,ATIpN
75 5. Frontage Rd, Permit wil( not be accepted without the following:
Vail, Colorado 81657 �
. Provide Niechanical Room LayQU�dr�wn to sca �
. o Mechanical Room Dimensions • � � �! S
� ❑ Comb�stion Air buct Size and Location D
� ���'"— o Flue,Vent and Gas Line S'rze and Loration . �
v Heat toss�at�s. AUG 27 1001;
o Equipment Cut/Spec Sheets � �
� CONTRACTpR INFpI��TXON T�VVN OF VAIL ..
Mechanieal Contractor: Town of Vaii Reg. No,; Contac�and Phone#°s: �
���� ' �°� � ��`-1 �. �q �
�-Mai) Address: � �, � � / �
� ignatuce: � ��'�`� C��'r . � .
CON�PLEl'�VALUA'�ON FOR M�CtiANACAL PERMTT Labo�& Materials �
MECHANICAL: $ o�� C��C?,C� �
Co�tact Ea /e Coun Assessors D�ce at 97�-328_8640 or vfsi t www,ea le-coun ,com for Pance/#
Parcel #
Job Name \ �� �ob�Address;
��' v�. z� � `� � .
Legal Des�ciption Lofi: � ��� � �\
Block: Fiiing: �, Subdivision: '
Owners Name: Address;
Phone: � . ,
Engineer; ' Address:
Phone:
Detaifed desq-iption of work:
�l� �cSc� i^.�, � C��,��,,�� , ,
t �\ _ ��,
.��7
Work Class: New ( ) Addition ( ) Alteration ( Repair. �
( ) Other(� )
Boiler�.oca�ion: Interior( ) Exterior( ) other
, ( ) Does an EhIU exist at this location: Yes ( ) .No ( )
Type of Bldg: Single-family( ) Duplex( ) Multi-famil
y( ) Commercial Restaurant( ) Other( )
No. of Existing Dwelling Units in this building: No..of Accommodation Units in rF�is building:
No e of Fire laces Existin ; Gas A liances Gas Lo s Wood Pellet Wood Bumin ,
NojType of Freplaces Proposed: Gas Appliances ( ) Gas l.ogs � ) Wood Pellet
/ ( ) Wood gurning (NOT ALLOWED)
Is this a conversion from a wood burning fireplace to an �PA Phase YI device? Yes ( ) No( ) .
. ' �
********��*�**�x*******�* ��� .
FOR OFFICE USE aNLY*********�****�**x�**�*****:��,�
�•Qtlier��ees•;:�°.,;�.r�,;p;;; ;:�..:`�=''j����Plann'sr�'Si ''� . �
DRB ���f, �-_ , n=offr, :;,; -��`�acce ted.'g �.-: ,�;,;,�;.::;,.,�,, .
��Fees.. .�;�: �'::" . ,.., . -�-, -�.•'.•:;.,
.Date Receivedr`:;ti��; '�,,:;:�:• � ..�r�;. . _,�� �.. ..,
.n%'c}r,",`,=l':+���'t.;.,;i;�
1\Vail\dala\cdcv�rori•M,�:RM1��8 9 ,�o N E,z�,,Doc 1 d�I N d H�3 W H'9� W d C ti�O l L O O Z 'L Z '��d
, �
`" ' PROPOSAL
R&H MEC�caL
RADIANT HEAT SPECIALIST
PO BOX 810,045 EnGLE Pa�tK EAST DRNE,r•,�►c�t,E,CO 81631
VOrC�: (97U);28-2699 F,�c: (970)328-0234
Proposal Submitted to bato Prepared by
McBoyd Construction Solutions Yun�4,2007 Terry Hine, P.E.
Street ]ob Name
I'.0. Bo�c 238 Quicksil�+er Store
City, Scate and Zip Code rob Location
Eagle, Colorado 8I631 Tk�e Arabelle at V'ail Square
Phone Fax Contact Mobile
970-328-3007 970-328-6527 Steve Boyd, Jr., P.E. 970-�90-1497
Payment to �e made as follows: DRAVV rJPON COMp�.�7'lON o�'�AC�I P�TAS�.
A.li material is�uaranued to be as Specified, A11 work to be eomplctcd in e workmanli�c mmmcr according to standard prac[icxs. Any ai�era[ion or deviation from
sper,iFCati�ns bdow involving extra costs will be eaecuted only upon�vritien orders,and witl becom�ar.ex�•ra.cl�acgG nver anA nbove�he es.�.ima[.e. All�greemencs ..
contingent upon SCril:es, eecidents or delAys bcyond our control. Thc concept of force majeure applies hereto. qw�et to curry fire tomado and other necessary
insurnnee. Our wnrker�ere�Ily covered by Workman's Compensation lnsurance.Thc partics aeree to deal wit[�oeE anoch�c ia good fai�h and fair dcaling.ln thc
event of any dispute,the prevailino parry sha0 be enritled ro all teasonablc costs includi�g attomey's fees.Maaimum interest permihed by law Shalt accrue upon thc l"
brcach of cliis agreement and any,judgment shall be enci[led to maximum imerest by)aw,
Note:we mAy withdruw this proposat if not acccpted witl�in 30 days.
We LiG(eby submil SpeCifics[i0ng 8nd�Stim1C�S fOr; HVAC TENANT FYN'YS� SYSTEM
Furnish and install(20) linear slat registers aild plenums with round duct tap, spin-in fittings and OBD.
(5) Ceiling retum grilles with insulated sound boot for plenum retum.
Tnsulated sheetnnetal ductwork and fittings (uninsulated vvhere exposed).
(1)4 kw electric ceiling heater.
(3) Wall mounted 7-day prograrnmable heat/cool thermostats and 24 volt wixing.
Duct sealant mastic, strap and scre�uvs.
All required tools, ladders, lifts, scaffolding as required for installation of a complete, operational s�stenca.
Labor,material, pertnit and tax.
Not Yncluded; Li,ne voltage't�v'iring,plumbing, gas pipix�g, dr�'vvall repair,painting, deck repair, access doors,
certified test and balance, fan coils,mixing bo�ces, equipment warranty, exk�aust fans, m��torized dampers, �re
darnpers, outside air duct. THANK YOY7.
Signature Date
Acceptance o� Proposal - n,� ahove (Client)
prices, Specifcations and condivons are satisfactory and
are herehy accepted. 'You are auchori2ed to do chc work as
specified.Payment will ba made as outlined above. Slgria'CUTe , Date
(1�&T�Mechanical)
. pa,ge 1 of X
� 'd 0�89 '�N lb'�INb'H�3W H'8� NdLti�Ol LOOZ 'LZ '�nd
SHT. N0. - MSK-01 (REV1 ) SCALE: 1 /4" = 1 '-0" DWG. REF. - M200
. .
�
The Arrabelle at Vail Square
Vail, Colorado 81657
REV N0. 1
DATE. 12-07-2007
CHRISTOPHER MENGES
�ENGINEERING, INC.�
Mechanlcal Consulting Engineera
1100 W.Littleton Boulevard,Suite 400
Littleton,Coloredo 80t20
Ph(720)283-3018 Fax(720)283-6253
www.mengeseng.com
� p � � � .v�
. �
'�'EST, ADJUST AND BALANCE +'PURT
PROJECT
QUICKSIL`TER
AR:RABELLE LIONSHEAD
PREPAR.ED FOR
R & H MECH��NICAL
I�PORT ISSUE DATE
11 / 20 / 2007
PREPARED BY
H-VAC
P.O. BOX 5123
VAIL, CO 81658
PHONE: 970-331-1095
FAX: 970-926-9406
, � H�VAC INSTRUMENT
CALIBRATION REPORT
PROJECT: __�{[� l�b�S."1 tr0%�--
INSTRUMENT!SERIAL# APPLICATION DATE OF USE CALIBRATION
DATE
SHORTRIDGE ADM-870/M41519 AIR FLOW READINGS I 1 /21/4? 427-07
SHORTRIDGE HDM-300/WO111 S WATER PRES.READINGS 4-27-d7
SHORTRIDGE FLOW HOOD AIF FLOW READINGS 11/21/07 *
PITOT TiJBE 18" PRES.READINGS 11/21 I 07 NA
PITOT TUBE 24" PRES.READINGS NA
PITOT TUBE 36" PRES.READINGS NA
SHI1�IP0 TACHOMETER/BS4139018 RPM READINGS 21 J 21 /07 4/18/07
FLtTKE 32/52101005 VOLT/AMP 11 /21/07 4-25-07
DAVIS LCA 6000 AIRFLOW READiNGS 4-25-2007
TEST GAGE 0-5 LBS WATER PRES.READINGS •
TEST GAGE 0-20 LBS 'WATER PRES.READINGS *
TEST GAGE 0-60 LBS WATER PRES.READINGS *
FLUKE 62 INFARED THERM. TEMP.REqDINGS 3-20-07
•CHECKED TO CALIBRATED METER
REMARKS: ALL READiNGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED�FOR
TEMPERATURE AND ALTITUDE_
PAGE:
� , H-VAC
TEST.ADJUST AND BALANCE REPOR'T
THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF
SYSTEM PERFORMANCE AND WAS OBTAII�TED IN COMPLIANCE WITH
NEBB PROCEDURAL STANDARDS. ANY VARIANCES FROM T'HE DESIGN
REQUIREMENTS ARE NOTED THROUGHOUT TffiS REPORT.
THE RESULTS SHOWN AND INFORMATION PRESENTED IN THIS
REPORT IS CERTIFIED TO BE ACCURATE AND COMPLETE, TU THE
EXTENT POSSIBLE BY EQUIPMENT AND PROCEDURES USED T'HROUGH-
OUT THIS SURVEY.
THE FINAL AIIt DISTRIBUTION SYSTEM MEASUREMENT'S ARE IN
COMPLIANCE WITH NEBB PROCEDURAL STANDARDS FOR TESTING,
ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS AND THE
PROJECT SPECIFICATIONS.
_____:
CERTIFIED B : ' DA�• ( l ��' C�
�
THE FINAL HYDRO1vIC DISTRIBUTION SYSTEM MEASUREMENTS
ARE IN COMPLIANCE WITH NEBB PROCEDURAL STANDARDS FOR
TESTING,ADUSTIl�TG AND BALANCIlVG OF ENVIItONMENTAL SYSTEMS
AND THE PROJECT SPECIFICATIONS.
CERTIFIED BY• DATE•
H-VAC WARRNATS THAT THE AIR AND HYDRp1vIC SYST:EM
EVALUATED DURING THIS SURVEY IS OPERATING AT THE SPECIFTED LEVELS
AS SHOWN WITHIN THIS REPORT,AT AND ONLY AT THIS TIME. H-VAC
MAKES NO OTHER WARRANTIES, STATED OR IMPLIED,CONCERNING THE
CONTIUED PERFOR�MANCE, OPERATION ,v �Ty IN TI�USE OF THIS
EQUIPMENT PASS THIS TIME. �
�-A•g`
GONtRp�t�R
2� Page: I
♦
eq�qN D.�oQQ
' �H-VAC AIR APPARATUS
TEST REPC�RT
PROJECT:QUICKSILVER -ARRABELLE UNIT: FCU D2-08
AIR HANDLER UMIT DATA MOTOR NAMEPLATE DATA
MANUFACTURER IEC MANUFACTURER BALDOF2
MODEL HBC2000051B48 HP R.P.M. 1 1725
SERIAL 961457-40-2 PHASE FRAME 1 56H
FAN TYPE CENTRIFUGAL S.F. TYPE 1.15 NG
RATING 2000 CFM VOLTS AMPS 115/23+D 13.4/6.7
MIN OSA 400 CFM THERMA�.LY PROTECTED YES
STARTER DATA ORIVE�ATA
MANUFACTURER FACTORY INSTALLED MOTOR DRIVE 1 VP 4.0"O.D.
MODEL MOTOR BORE 5/8"
SIZE/THERMAL N�. PAN DRIVE 1 AK 54
RANGE FAN BORE 1"
SET AT(AMPS) NO. BELTS�SIZE 1 �A28
REQ. THERMAL ROTATION CORREC;T
RATING(AMPS) DRfVE CHANGE
AIRFLOW DATA TEST DATA INIT�AL FINAL
SUPPLY CFM 2051 FAN R.P.M, g22
OSA CFM 411 VOLTAGE 119
RETURN CFM 1640 AMPERAGE 5,2
-0.15" FILTER -0.22" COIL -0.38" rJ 0.2:9"
NOTES:
PAGE: 01
� �H-VAC AIR APPARATUS
TEST REPORT
PROJECT:QUICKSILVER -ARRQBELLE UNIT: FCU D2-09
AIR HANDLER UNIT DATA MOTOR NAMEPLATE DATA
MANUFACTURER IEC MANUFACTURER BALDOR
MODEL HBC2000051648 HP R.P.M. 1 1725
SERIA� 961457-40-3 PHASE FRAME 1 56H
FAN TYPE CENTRIFUGAL 3.F. TYPE 1.15 NG
RATING 2000 CFM VOLTS AMPS 115/23�U 13.4/6.7
MIN OSA 400 CFM THERMALLY PROTECTED� YES
STARTER DATA DRIVE DATA
MANUFACTURER FACTORY INSTALLED MOTOR DRIVE 1 VP 4.(3"O.D.
MODEL MOTOR BORE SJ8°
SIZE/THERMAL NO. FAN DRIVE 1 AK 54
RANGE FAN B�RE 1"
SET AT(AMPS) NO.BELTS 8 SIZE 1 �AZft
REQ. THERMAL ROTATION CORRE+CT
RATING(AMPS) DRNE CHANGE
AIRFLOW DATA TEST DATA INIT'IAL FINAL
SUPPI.Y CFM 2875 FAN R.P.M. 831
OSA CFM 408 VOLTAGE 119
RETURN CFM 1867 AMPERAGE 4,7
-0.17" FILTER -Q.28" COIL -0.48" rJ 0.;26"
NOTES:
PAGE: 02
- � H-VAC AIR APPARATUS
TEST REPORT
PROJECT:QUICKSILVER -ARRABELLE UNiT: FCU D2-10
AIR HANDLER UNiT DATA MOTOR NAMEPLATE DATA
MANUFACTURER IEC MANUFACTURER BALDOf2
MODEL HBC2000051648 HP R.P.M. 1 1725
SERIAL 981457-40-4 PHASE FRAME 1 56H
FAN TYPE CENTRIFUGAL S.F. TYPE 1.15 NG
RATING 200Q CFM YOLTS AMPS 115 f 23�0 13.4/6.7
MIN OSA 400 CFM THERMALLY PRUTECTED YES
STARTER DATA DRtVE IDATA
MANUFACTURER FACTORY INSTALLED MOTOR DRIVE 1 VP 4.0�"O.D.
MODEL MOTOR BORE 5/8"
SIZE/THERMAL NO. FAN DRIVE 1 AK�4
RANGE FAN BORE 1"
SET AT(AMPS) NO. BELTS�SiZE 1@ A28�
REQ. THERMAL ROTAT{ON CORRE(:T
RATING(AMPS? DRtVE CHANGE
AIRFLOW DATA TEST DATA INITIAL FINAL
SUPPLY C�M 2028 FAN R.P.M. 833
OSA CFM 406 VOLTAGE 119
RETURN CFM 1622 AMPERAGE 5.4
-0.17" FILTER -0.22" COIL -0.41° rJ �.:?4„
NOTES:
PAGE: 03
. .H-VAC AIR TERMINAL
TES� REPORT
PROJECT: Qu�cKSt�vErt-ARRABELl.E SYSTEM: �CU D2-08� D2-tt9
, - --- --__.______.__--.._- ---- --------A� NOTES
SYSTEM TERMlNAL DESIGN tNIT1AL FiM
N� TYPE SIZE AK VEL CFM VEL CFM VEL � CFM
D2-08 1 SL 48x3 200 ,207
2 SL 48x3 200 210
3 SL 48x3 200 204
4 SL 48x3 200 2pg
5 SL 48x3 300 304
6 SL 48x3 300 301
7 SL 48x3 3Q0 31Q
8 SL 48x3 3QQ 347
20Q0 2051 TOTAL
D2-09 1 SL 48x3 250 2�7
2 SL 48x3 250 25g
3 SL 48x3 250 27�
4 SL 48x3 250 271
5 SL 48x3 300 307
6 SL 48x3 300 3�p
7 SL 48x3 200 204
8 SL 48x3 2pp �g7
2� 2075 TOTAL
NOTES
PAGE: 04
• v
, . H-VAC AtR TERMINAL
TEST REPORT
PROJECT: Qu1CKSI�VER-ARRABELLE SYSTEM: FCU D2-10
i SYSTEM TERMINAL DESiGN INITUIL FINAL NOTES
NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM
D2-10 1 SL 48x3 ?.25 22�
2 SL 48x3 225 230
3 SL 48x3 275 281
4 SL 48x3 275 270
5 SL 48x3 2�5 2g2
6 SL 48x3 275 2$1
7 SL 48x3 200 195
8 CD 24x24 80 ' 75
9 CD 10x10 30 30
10 CD 10x10 30 32
11 CD 10x10 30 35
12 CD 24x24 gp 70
1980 2028 TOTAL
�
NOTES
PAGE: 05
s
_�
._.- s.T � ��.
300
F%ISIiYC THERMOSiAi
RELGCAiED 0.S SHOwV,
ttP.(7)PVLES
MOL�M ON IN�
SUI
C
,C_9���
.�g v � F'
��_I—
f_�
iE 21 �—
24r�4 ACCESS PANEL,
Y F,,L�L
, t��r i��. ,
1;t. . '_
�
tE.9?_ __ _ _ _ _
��
v ✓ __
SIT SiT
3ca 300
� MECHANICAL SYMBOL
LEGEND
L Mt4NUP1 VOIWE DNAPER-PRONOE:N fAC�I NEM'SUPPLY AND E%44USf �l. VOIUME EMTFACTJR
WR RUNOUf. ��
dT- ROpA iNERNOSTAT(W2RPN P7qGTE5 RELOLA"N) �}..� RETURN AIR GRR�E-REfFR TO SCHEIXILE
VJ V
(J HVF.0 NUNBFFED NOiE �� RENRN GRILIE W/'.'NED SbUNL ATIENU4iMG BOOT
� �� E%STIMo DUC'WORN?0 ftEA!Alk �q
�---� •-I! F+SUPPLY NR DIFFUStR-FEiER ID SCMEDI.4E
� 1�I
NEW SHEE7)AEfrY DUC1N'OPo(-MWSfKALLY LINED �
L-� LIkFIA SLOT DIFNSEF-RCFOi TO SCHFDUIE,MROW INDILNES ROW
O � D'�RECTION
NEW SHEE�7AEfF1 DULIYGRK
#� �� AIR OUTLEf�MLEf TAG-BOT701A NUM�EA I�DICAiES AIR fLQN IN CM
�*Y EYJSiIAC DUC7WORN iG BE RE11QvED� /�&5
�� v PlWii OF CONNE'iqY TO E%IS71N�
RUNWT
� <5 DEGRFf INIRY FlRINC aF� ABO`�E iINISIfD F100R
d.0.0. BOTTOM OF DUCT
�- RWIA SP@l-IN�MR'FlRING �D) ���7�' �iEMS 1C ff OFYOl1SHEC
(E) IXISrING MECHPN'GL TO IEM4M
� SQIARF-iO-ROUND 77tAY5'�710N (R) RELOCAIE YECH4iICAL RENS
� RA RENRN AIH -
ELBOW Y7iH NRNING VANES 5.0. SUPPL7 PIR
,r!,I I
'�'
�����i
DEMD 8"0 DUCT�
PN�RE�IACE NTM NE11' �
70'O�FRESH!IR DUC� �
WRH WIUME Q4NPER 1
I/
so
l�ll
1
n MECHANICAL PLAM
� � %;%'NE1M'•t'a
`i
MECHANICAL NUtABEREG NOTrS:
01 UNDERCUi OOOR 5/8'FOR A�i1RFt<_FER OUT OF(100Y
\�
,,,��� �
\\
����.� -H� N� � ..�.�..
'L 23 r"�� '� L1___�
�I
��?
� /
Q _ --�
_ . .I . _ ..� _ . . . ..
� sir I ----'
�—
`�. �-�'__- I
✓ i
,
����o ----s � '
—��@.�.z.,� �
__ �
��I—--
-- :;�
i �
� j
� I I� __
�� -� (EJ u..g .
1000 .._. �—� ', I
�-� — (e)z<.r
I ���
._� � rcu oz-n wk�ac useo
� �--� FOR�,pIACE.YI i'Mt�
� % �, � -i. __i� \
I
! p_ FCU�. �-i [%IS11NG E%HAUSi VAN
�BKIB 7RANSFER GRNLE Z�
� AB(VE C9JUG �. �
'. WOS�SIQICU�E / � � _i��T�
� �_'--�—��
1---------------------1—� ,��d-
(e)io,io ----+_---- � ��
�-------------- �
� BACKSfOCK t-T �� �� ;�-�-
-- � �
—--
----—- � zs -r��-T ���y;.
--- y' —
---� ;�Eiw,zi _ ��
_ :.-�
--— �•� -_��__ , __��J ,,
OE110 8�1 WC1 � (G�J2e16 IXHUASI
AND XEPIA�WI7H NiW
10�I FRESFI AIR WCT (�)ifivlU 90WN THftU ROOR�
W(IH YOL:'NE DqMP[R .,
`l����01
�V �
�.
�
.J
' .
I �I
����
1959f�'ast Main St.#209�,Porker,CO 80)38
(303)�a6-4770 vo'�m(303)646-5623 focsimile
N P
m�
P
a'^
o.d
`o'O
o°0
U a
�.�
�
c
a�
�
mo
��
N�
1�
h O
.-M
� m
N.�
�i
�
.
I �
w
I �
0
�
0
`o
I —o
v
I O
>
y
.,
�
�
� O
�
.n
` �
-- F_
�
�
S
12-04-2007 inspection Request Reporting Page 48
4:05 pm Vail, G� . Gitv�f
Requested Inspect Date: Wednesday, December 05,2007
Inspection Area: CG
Site Address: 675 LIONSHEAD PL VAIL
QUIKSILVER @ ARRABELLE
A/P/D Information
Activity: M07-0183 Type: B-MECH Sub Type: NCOM Status: ISSUED
Const Type: Occupancy: Use: Insp Area: CG
Owner: VAIL CORP
Contractor: R&H MECHANICAL LLC Phone: (970)328-2699
Description: QUIKSILVER TENANT FINISH-HVAC TENANT FINISH SYSTEM
Reauested Insaection(s) q /� _ ��'-O�
Item: 390 MECH-Final Re ue�t d Time: 09:00 M
Requestor: R&H MECHANICAL LLC/DARCY Phone: (970)328-2699, -or-
970-471-5673,JE Y
Comments: REINSPECT-QUICKS �[ER-OTHER CONTqCT BRIAN 970-471-5661
Assigned To: JMONDRAGON p�, � Entered By: LCAMPBELL K
Action: ��rme Exp: �
Comment: CE EPORT
TRANSFER GRILLS REQ SMOKE DAMPER OR DUCTED RETURN
l� � � �
��:I�l.��f,�.C� .
a � .
�'�� �� /����' ��
� � �n
�
Inspection Historv
Item: 200 MECH-Rough "`Approved'"
09/27/OT Ins�pector: GCD Action: CR CORRECTION REQIIIRED
Comment: NQ PLANS
09/28/07 Inspector: GCD Action: AP APPROVED
Comment:
Item: 310 MECH-Heating
Item: 315 PLMB-Gas Pipin�g
Item: 320 MECH-Exhaust Noods
Item: 330 MECH-Supply Air
Item: 340 MECH-Misc.
Item: 390 MECH-Final
11/15/07 Inspector: GCD Action: CR CORRECTION REQIIIRED
Comment: PRDVIDE BALANCE REPORT
TRANSFER GRILLS REQ SMOKE DAMPER OR DUCTED RETURN
. G� p� �
.
,
�
REPT131 Run d: 7323