HomeMy WebLinkAboutB07-0260 E07-0224: Entries for Item:190 - ELEC-Final 12:09 07/02/2013
Action Comments By Date Unique_
Ke
CR ABOVE COUNTER KITCHEN RECEPT TO SHAHN 12/17I2007 4880109
BE GFI.
RELOCATE SOUTH EXIT TO BE VISIBLE.
REPLACE DEFECTIVE EXIT IN KITCHEN.
AP shahn 12/1812007 A000109
566
Total Rows:2
Page 1
. i
P07-0169: Entries for Item:290 - PLMB-Final 12:10 07/02/2013
Action Comments By Date Unique_
Ke
PA CAULK ALL FIXTURES IN KITCHEN GCD 12/17/2007 4900109
AP GCD 12/20/2007 A000109
995
Total Rows: 2
Page 1
TOWN OF VAIL DEPARTMENT OF COMMUNITY DEVELOPMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2138
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
ADD/ALT COMM BUILD PERMT Permit # B07-0260
Project# PRJ07-0365
Job Address: 675 LIONSHEAD PL VAIL Status . . . : ISSUED
Location.......: ARRABELLE HOTEL Applied .. . : 08/07/2007
Parcel No....: 210106325001 Issued . . . : 09/07/2007
Expires.....: 03/OS/2008
OWNER ARRABELLE AT VAIL SQUARE LLC08/07/2007 �J�_` �^C� �V UL{ -�3C�J
PO BOX 7 --� 1
VAIL
CO 81658
APPLICANT TCD, INC. OS/07/2007 Phone: (970) 453-3959
PO BOX 4564
BRECKENRIDGE �� �J 3
COLORADO 80424 S--c(
License: 353-A �``� 4
CONTR.ACTOR TCD, INC. 08/07/2007 Phone: (970) 453-3959 ` M��`�
PO BOX 4564 �� `
BRECKENRIDGE
COLORADO 80424
License: 353-A
! v� �c�d��--�
Desciption:
TENANT FINISH WORK FOR THE BLUE MOOSE AT ARRABELLE
Occupancy: A-2
Type Construction: I-B
Valuation: $491,510.00 Revision Valuation: $0.00 Total Sq Ft Added: 0
******�*****:r***x*r*►*****+*►�*t**r**r******sr*****r*****s�s**r*�*�* FEE SUMMARY *****r*r***************r*a**�*�****��**+**�***t**tt**��****+
Building------> $3,18B.95 Restuarant Plan Review--> $�5.oo Total Calculated Fees--> $5,339.77
Plan Check---> $2,o�2.8 z Recreation Fee--------------> $o.o o Additional Fees----------> $o.o 0
Investigation-> $o.o o T07'AL FEES-------------> $5,3 3 9.�7 Total Permit Fee---------> $5,3 3 9.��
Will CaII-----> $3.0 0 Payments-------------------> $5,3 3 9.7 7
BALANCE DUE---------> $o.o 0
***�*�►*a+**stsx***r*e****t�tt**:+t*****�r*�***s*�***�:+s**«ts«��**�****a►+►r****r***r�**�*******�*�**►�*****�sss**�:vsx*r**+****t***►*r**�*►**�*�*
Approvals:
Item: 05100 BUILDING DEPARTMENT
08/30/2007 cgunion Action: CR plan review
comments sent
F: \cdev\CHRIS\PERMIT.COMMENTS\B07-0260\B07-026U .DOC
09/05/2007 cgunion Action: AP approved
resubmitted plans addressing code comments.
Item: 05400 PLANNING DEPARTMENT
09/06/2007 George Action: AP
Item: 05600 FIRE DEPARTMENT
08/17/2007 JJR Action: AP Approved as noted:
Exititng plan conflicts with E300.
Furniture is shown blocking claimed exit doors .
Provide adequate exit signage.
Item: 05500 PUBLIC WORKS
09/05/2007 tk Action: NA �
*:*****,��,......::.:*******.*.«*►.*�.�:*..�..*�*:**.*.+�**..*.�+.*.�+..**�.****+:*,»:*s*.***+*:*�**.****.�.*�*�.*..*.*.�*.*.*****.�:.�.*�.:...+�
See the Conditions section of this Document for any conditions that may apply to this permit.
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan,to comply with all
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordinances of the Town applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY-FOUR HOURS IN A VANCE BY T PHON T 479-2149 OR AT OUR OFFICE FROM 8:00 AM�
4 PM.
r
7 S��'' O�—
S TURE OF WNER OR CONTRACTOR FOR HIMSELF AND OWNER
********************************************************************************************************
CONDITIONS OF APPROVAL
Permit#: B07-0260 as of 09-07-2007 Status: ISSUED
********************************************************************************************************
Permit Type: ADD/ALT COMM BUILD PERMT Applied: 08/07/2007
Applicant: TCD, INC. Issued: 09/07/2007
(970)453-3959 To Expire: 03/OS/2008
Job Address: 675 LIONSHEAD PL VAIL
Location: ARRABELLE HOTEL
Parcel No: 210106325001
Description:
TENANT FINISH WORK FOR THE BLUE MOOSE AT ARRABELLE
***********************************************Conditions:************************************************
Cond: 1
(FIRE): FIRE DEPARTMENT APPROVAL IS REQUIRED BEFORE ANY
WORK CAN BE STARTED.
Cond: 12
(BLDG.): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE
COMPLIANCE.
***********************************************+***********+********************************
TOWN OF VAIL, COLORADOCopy Reprinted on 09-07-2007 at 10:39:11 09/07/2007
Statement
**+********�***+****�******+***********�****++*****��*******************************+*****�*
Statement Number: R070001786 Amount: $2, 864.77 09/07/200709:44 AM
Payment Method: Check Init: DDG
Notation: Catskill Place
Restaurant Co. 1501
-----------------------------------------------------------------------------
Permit No: B07-0260 Type: ADD/ALT COMM BUILD PERMT
Parcel No: 2101-063-2500-1
Site Address: 675 LIONSHEAD PL VAIL
Location: ARRABELLE HOTEL
Total Fees: $5, 339.77
This Payment: $2, 864.77 Total ALL Pmts: $5,339.77
Balance: $0. 00
*********************************************+******************************************++**
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------------- ------------------------------ ------------
BP 00100003111100 BUILDING PERMIT FEES 2, 861.77
WC 00100003112800 WILL CALL INSPECTION FEE 3 .00
-----------------------------------------------------------------------------
� t ` �
APPI.fi;AT10N WILL NOT BE ACCEPTED IF INCOMPLETE NSIGI ��
,,,\ Pr t�� ,����-_ �
� Bu g 1�erm�#; _r' � �
�' 97 � -2149 (Inspe tions) �
'�4�iV 0�'Y�'I.' ` Q . v ' �I !'t�,G�C��.
Fronta e Rd. � I
75 S. g ,,,��
Vail, Colorado 81657
TOWN OF VAIL BUILDING PERMIT A �1D1'm�� i/AIL
Separate Permits are required for electrical, plumbing, mechanica , e c..
CONTRACTOR INFORMATION
General Contractor: Town of Vail Reg. No.: Contact Person and Phone#'s:
TCD, Inc. 352-A Jim Anderson, 970.445.7245
Email address: janderson@tcdsummit.com Fax#: 970.453.3980
Contractor ignature j
�' 2 Aug 2007
COMPLETE VALUATIONS FOR BUILDING PERMIT Labor& Materials
ILDING: $ N/A ELECTRICAL: $ 92,225 OTHER: $ 209,260
PLUMBING: $ 55,225 MECHANICAL: $ 134,800 TOTAL: $ 491,510
For Parcel# Contact Ea le Count Assessors Office at 970-328-8640 or visit www.ea le-count .com
Parcel #
Job Name: Blue Moose Job Address: 675 Lionshead Place #P170, Vail, CO
Legal Description Lot: Block: Filing: Subdivision:
Owners Name: Vail Blue Moose, Address: PO Box 5549, Beaver Creek, CO 81620 Phone: 970.845.0545
Brian Nolan
Architect/Designer: Cahen Address: 7535 E. Hampden Ave#425, Denver, Phone: 303.743.0002
Architecture Group PC CO 80231
Engineer: KVA Consulting Address: 1100 W. Littleton Blvd #400, Littleton, Phone: 720.283.3018
CO 80120
Detailed description of work: Tenant Finish - Restaurant
Work Class: New( X ) Addition ( ) Remodel ( ) Repair( ) Demo ( ) Other( )
Work Type: Interior(X ) Exterior( ) Both ( ) Does an EHU exist at this location: Yes ( ) No ( X )
Type of Bldg.: Single-family( ) Two-family( ) Multi-family(X ) Commercial(X ) Restaurant( X) Other( )
No. of Existing Dwelling Units in this building: No. of Accommodation Units in this building:
No/T e of Fire laces Existin : Gas A liances Gas Lo s Wood/Pellet Wood Burnin
No/T e of Fire laces Pro osed: Gas A liances Gas Lo s Wood/Pellet Wood Burnin NOT ALLOWED
Does a Fire Alarm Exist: Yes ( ) No ( X ) Does a Fire Sprinkler System Exist: Yes ( X ) No ( )
***********************�:�*******************FOR OF FIC E US E ON LY�:��`*******'�'`�"`�"'"r�*'�`�"'`��*****'��**�'�"��
Date Received:
Received By:
C:\!TCD\Vail\building_permit_4-17-2007 moose.doc Page 1 of 4 04/17/2007
. - , � . 0
.'
TOWNOF YAII,`.
ASBESTOS TESTING REQUIREMENTS
THE TOWN OF VAIL AND STATE OF COLORADO DEPARTMENT OF PUBLIC HEALTH REQUIRE ASBESTOS
TESTING ANY TIME WHEN MORE THAN 160 S.F. OF MATERIAL WILL BE DISTURBED OR REMOVED.
AN ASBESTOS TEST AND REPORT IS REQUIRED TO BE SUBMITTED WITH YOUR BUILDING PERMIT
APPLICATION FOR ALL REMODEL, ADDITION OR OTHER PROJECTS INVOLVING ANY DEMOLITION OR
REMOVAL OF BUILDING MATERIALS THAT MAY CONTAIN ASBESTOS. BUILDINGS CONSTRUCTED AFTER
OCTOBER 12, 1988 THAT HAVE NO ASBESTOS CONTAINING MATERIALS ARE EXEMPT.
A COPY OF THE REPORT MUST BE SUBMITTED WITH YOUR BUILDING PERMIT APPLICATION
• I have included the asbestos test and report with my building permit application
applicant signature date
OR
• I certify my project will not disturb or remove more than 160 s.f. of building material. The construction
plans submitted with my application clearly indicate this information. (This will be verified during plan
review, and will delay your project if found to be inaccurate)
applicant signature date
OR
• The building as con tructe after October 12, 1988. The date of construction was _
to be com lete Dece er 00
original construction date
2 2007
applicant signature date
C:\!TCD\Vail\building_permit_4-17-2007 moose.doc Page 3 of 4 04/17/2007
424o Architecture Inc chicago denver
4240
July 31, 2007
Mr. Charlie Davis
Town of Vail Chief Building Official
Department of Community Development
75 South Frontage Road
Vail, CO 81657
Re: The Arrabelle Building - Retail Tenant Improvements: "Blue Moose Pizza". Produced by Cahen
Architectural Group P.C., 7535 East Hampton Ave., Suite 425, Denver, CO, and dated July 20,
2007.
Dear Charlie:
Pursuant to 2003 IBC Section 106.3.4, this is to inform you that 4240 Architecture, as the registered
architectural design professional in responsible charge for the Arrabelle Project, has reviewed the above
referenced proposed retail tenant improvement construction documents. To the best of our knowiedge,
we find these documents compatible with the approved construction documents for the Arrabeile Project,
with the exception of several issues requiring additional documentation by the tenant's architect as
follows:
• A 3"thick floor topping is required to meet finish grade at the entrance doors. The allowable
load of the topping is limited to approximately 25 psf. The retail tenant architect should provide
an addendum to the drawings providing a description of the proposed topping that falls within
the load requirement. Options for this topping include, but are not limited to:: 1.) 3" `gyperete' or
light weight concrete; or, 2.) 1 '/z" normal weight concrete on 1 �/2" rigid insulation.
• Plumbing fixtures must be shown in Toilet Room 110.
• Compliance with the minimum plumbing fixture count and fixture accessibility should be verified.
Please do not hesitate to call should you have any questions.
Sincerely, �.:°� ��,�
'�J"� ���,S �i`:�'f ~�"�� .
�;'� . 'k.,,"�„y'^°°r�++���Y! ��.� `.;.
/�G.... ,y-'9'� � '�
i ,�
� � , � � �P ��ry.�� `
; � 4..�. / ��..
`, 1 e;
? a. tr i,.�t `�.`�r+�'� �
' � �t� � �=-� :�
E..:.� y;....' i
E. Randal Johnson, AIA �'�;�'�?,ay
Principal �,n:�`� ".°� .,` .s�'
� r t ''"� Y �`:.
� '� 4°��.1 ��j � ��
� . -
t62i Eighteenth Street Suite 20o Denver,Colorado 8ozoz T 303 29z 33$$ F 303 zgz 3ii3 W 4z4oarchitecture.corri
**************************************************************�**************+**************
TOWN OF VAIL, COLORADO Statement
***********+*************************************************************************�******
Statement Number: R070001456 Amount: $2,400.00 08/07/200703:06 PM
Payment Method: Check Init: JS
Notation: 1475/CATSKILL
PLACE RESTAURANT CO LLC
-----------------------------------------------------------------------------
Permit No: B07-0260 Type: ADD/ALT CONIM BUILD PERMT
Parcel No: 2101-063-2500-1
Site Address: 675 LIONSHEAD PL VAIL
Location: ARRABELLE HOTEL
Total Fees: $5,264.77
This Payment: $2,400.00 Total ALL Pmts: $2,400.00
Balance: $2,864.7'7
********************************************************************************************
ACCOLJNT ITEM LIST:
Account Code Description Current Pmts
-------------------- ------------------------------ ------------
BP 00100003111100 BUILDING PERMIT FEES 327.18
PF 00100003112300 PLAN CHECK FEES 2,072.82
-----------------------------------------------------------------------------
�
COMcheck Software Version 3.4.1
Lighting Compliance Certificate
2003 IECC
Report Date:07/12/07
Data filename:\\Kvafs\kVA Consulting\Projects�2007-139Wdmin\Schedules\20031ECC-BlueMoose07-139.cck
Section 1: Project Information
Project Title: Blue Moose Pizza
Construction Site: Owner/Agent: Designer/Contractor:
The Arrabelle at Vail Square Carl Fretwell
Vail,CO 81657 kVA Consulting
19590 East Main Street
Parker,CO 80138
(303)646-4770
ca rf @ kva cons u Iti ng.net
Section 2: General Information
Building Use Description by:
Project Type: New Construction
Buildinq Tvne Floor Area
Restaurant 4515
Section 3: Requirements Checklist
Interior Lighting:
� 1. Total actual watts must be less than or equal to total allowed watts.
Allowed Watts Actual Watts Complies
7224 7184 YES
� 2. Exit signs 5 Watts or less per side.
Exterior Lighting:
� 3. Efficacy greater than 45 lumens/W.
Exceptions:
Specialized lighting highlighting features of historic buildings;signage;safety or security lighting;low-voltage landscape
lighting.
Controls, Switching, and Wiring:
� 4. Independent controls for each space(switch/occupancy sensor). O
Exceptions: Q•••••' . s�
Areas designated as security or emergency areas that must be continuously illuminated. �;��• �'' F
(�':'Q
Lighting in stairways or corridors that are elements of the means of egress. r Q ��-m
� 5. Master switch at entry to hotel/motel guest room.
c�. 34235 r: v
� 6. Individual dwelling units separately metered. � �� /�
��'... 1�(�;���c/
� 7. Each space provided with a manual control to provide uniform light reduction by at least 50%. .(��:.,�'1 ;G�1
Exceptions: s ���""""'���J
S��IVA�E
Only one luminaire in space;
An occupant-sensing device controls the area;
The area is a corridor,storeroom,restroom,public lobby or guest room;
Page 1 of 3
COMcheck Software Version 3.4.1
� Lighting Application Worksheet
2003 IECC
Report Date:
Data filename:\\Kvafs\kVA Consulting\Projects�2007-139Wdmin\Schedules\20031ECC-BlueMoose07-139.cck
Section 1: Allowed Lighting Power Calculation
A B C D
Floor Area Allowed Allowed Watts
Watts I ft2
Restaurant 4515 1.6 7224
Total Allowed Watts= 7224
Section 2: Actual Lighting Power Calculation
A B C D E
Fixture ID:Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Restaurant(4515 sq.ft.)
Linear Fluorescent 1:A:2x4/48"T8 32W/Electronic 3 15 96 1440
Linear Fluorescent 2:A1:2x2/24"TS 17W/Electronic 3 1 54 54
Compact Fluorescent 1:D,D1:CF Downlight/Triple 4-pin 32W/Electronic 1 82 32 2624
Incandescent 1 copy 6:C:Decorative Pendant/Incandescent 150W 1 2 150 300
Incandescent 1 copy 1:F:Decorative Pendant/Incandescent 100W 1 12 100 1200
Incandescent 1 copy 2:P1:Decorative Pendant/Incandescent 100W 1 4 100 400
Incandescent 1 copy 2:P2:Decorative Pendant/Incandescent 50W 1 7 50 350
Incandescent 1 copy 3:T:Decorative Pendant/Incandescent 150W 1 4 150 600
Compact Fluorescent 2:WS:Decorative Wall Sconce/Triple 4-pin 18W/ 1 12 18 216
Electronic
Total Actual Watts= 7184
Section 3: Compliance Calculation
If the Total Allowed Watts minus the Total Actual Watts is greater than or equal to zero,the building complies.
Total Allowed Watts= 7224
Total Actual Watts= 7184
Project Compliance= 40
. ^
p0 R
..FR /s►�F
��:m
�'•� 34235 �' v
�►��:. �`,��.:�
�SS��V/VAI.ENG�
Page 3 of 3
� �
(�. ,� t�-- � ,�v�
�,� �
� ��
��
� .
�
���� '��
�, �"
August 14,2007 �
�
Cahen Architecturai Group ;
7076 South Alton Way, Bviiding A ��'��
Centenniat, Coiorado,80112
Phone: 303.743.0002
Ft�x: 3�i.996A640 �"7� Q C��Q V
Atht: Chad Wo�icrnorf
Re: aiue Moos+e Pizza ���
The�IRCibeMe Bu�tg
Qeor Chctd,
Please note the following responses ta fihe review comments provided by the
base building MEP engineer.
�MIECHANICAL
l,t Fhe make-up a�tiow rate in ttre ve�nti�rtiorr Schedule on FS 1 A tofic�ts 4152
CFM. The Mechonicarl Numbered nates on M2.0 totaf arnother�50 CFM
of make-up aA►: The to#oi from both sheei�is 7.202 C�M. fi�base bu�ding
de�gn a!located 6,200 CFM of mcike-�p a�to#his space. The makeup air
unit serving 81ve Moose Pizua►also served oi`her tenantx in the builatFng,. It is
nc�t accep�able to reduce c�flow fio it�e ofher#enon#s. fi+e rnc�keup
oufffow Pate to the Bive M�Pizacr spc�ce sho�nc�t exc�d tttg attocc�ted
6,200 CFM. /ssue an crddendum ta adjust the moke-up c�f/ow rarte
occardrngty►.
Response: The venfiiatit�n schedule on sh�et FS i A is inctxrect and witl be
modified to matd�the mechcynical drawings. The tota!rnake-up air tha#
wiN be used for the sp(ace is 5.900 GFM.
1.2 Sheet fS6 strows f+��o up-E�ast fons and a m�ulce-up c�unit �e kitchen
exhac�st fans ond marke-up a�unit a�e pravicied in ft�e base bu�ding
systems Qnd do not need to be fumished by fhe tenvnt.
Response:'fhe exhoust#ons and make-up air unit witl be removed from the
kitchen a�ipmen#su�lier dre�wing s+�t.
1.3 Sheet M 1.t7 shaws o wart�r coofed conderuing vr�t prpiryg ctetc� The
detoii indicates thot the piping to the conden�sing uniis wr�rvn wr�cl. Th�s is
ncst accepi�a#�e. !�wa�teesr ccxrled candensing ur�fs ryre us�d d solenoid
vc�lve confrol�ed by ffie condensing ur�t shall be installed to regulote flow
to ecrch conder�ing unit. if the t�nant connec�s to the bas+e bui�ding
1l590 E�st AA�S�t.+l209 : Px�t�.Cc�tc�r,�r�o a0'i 3� : MMO�343.613.47Ta : �iR�t 3i13.4it.�Sb2�
chilled woter system he shalt fwnish BFU meters on fhe chr�Ied water pipir�
serving the condensing units. The food service plaru indicate that the
watk in co+olers anri ice machines conder�sing urriis are o�-cooled. The
discreperncy between fhe food service drawings and mechanical plans
needs to be resolved. issve an addendum to m�fy the pla!ns
acc+�rdingiy.
Response: The sofenoid vc�tve to control the water flow to the condensing
vni#s has been added to#he pfans. Sheet M1.0 dated 7-3i-07 shows this
volve. The Icitchen equipmen#supplier clrawings w�t be reviseti#o mQtch
the mecha�ical plans.
1.4 Sheet P2.0 has o note sfc�ting i�hot o i" 140 deg F domest�c�t woter iine
wr11 be�xovided by the landtord. According to fhe Vai1 Resoris
Development Compony the tandtord/tenont agreement does not state
thQt i 40 deg F hof wvter wn7�be fumished to the sperce. The tenant shatt
provide a boosfer hectter for the dishwasher to roise �lU deg F water to
I�dsg F. �sue an cyddendum to adjust the pions vccor�aling�y.
Response: A iarger baoster heater v�rt'N be specfied for th�c�shwa�her,
and o ta�kiess electric water heater v�n't!be c�dded fcx the 3-compartment
si�k#o accommodate the e�asting cond'rtions.
Et,ECTRiCAL
].�4 E I OO:Indicc�te cvnduif and conductor s'rzes raeqv�ed fc�r the prim�y Qnd
secondcay feeds of the tran�ormers.
Response: The conduit and canductcx sizes wiN be ctec�rly identified in the
Feeder and Transfc�rmer Schedules.
l.5 F 1 U0:On the fe$der schedule, indicote oMy#he feeders being used. lt
oppears only the new transfcxrner feeders wc71 be u�ed_
Response: Only fi�ansformer feeders ore�uRently used,th�s wiU be noted
on the plans.
l.6 E I.UO: Indicate only ths firansformer sizes t�ing used on fhe plar�s.
Response: C?niy transfarmer used wiif be noted on the plans.
1.7 E2.U0: Fenant's con.sultant/eontracta�shcY/1 provide connecfion fvr(41 tan
cor7 uniis per#he base bu+k�ing ele��ricoi documenfs. 7he fan coA units
were installed by the base bviiding mechaRical confractor.. Refer to
attached pian.
i 4S9Q Ensr M�St�.#�Q9 : Pn�u�e,Cotot�oo 8t113Q: P�3Q3.+646.47T0 : F�ut 3�.6AdYS62S
Response: �rowing will be revised to indicafe new connections as
required once attached plan is received.Attoched pian was not
included.lf possibie can you please send the missing attachment directly
to cari@kvaconsultin .c� net.Thank you.
1959'0 E�sr IIM�Sn�#209 : P�t�Caow►oo s013a : Px�3ti3.blb.47T0 : F�c 303.br16.56?.3
i
+ CATOR,RU]VIA �7 ASSOC IATES, CO.
ra�NC,PnLS CONSULTING MECHANICAL�ELECTRICAL ENGINEERS
MICHAELA.MEINTS
JouN A.HuctiFs
BRUCEE.APPEL
JAMES R.L�IZZERI
MARCUSA.VAL[RIUS
SENIOR AStiOCtATE
MARK V.JELINSKE August 1�GOO/
ASSOCIATES
SEAN I�.CONVERI'
GER.4RD W.O'BRII;N
DENNIS F.RUDKO
W.�IYNEA.�I�RADER Mr. Charlie Davis
Town of Vail Chief Building Official
Department of Community Development
75 South Frontage Road
Vail, CO 81657
RE: The Arrabelle Building: Blue Moose Pizza
Cahen Architectural Group P.C. Permit Set dated 7/20/07
Mechanical/ElectricaUPlumbing Infrastructure Coordination Review
CRA Project No. 2006-276
Dear Mr. Davis:
Pursuant to 2003 IBC Section 106.3.4, this is to inform you that Cator, Ruma and
Associates, as the registered design professional in responsible charge of the Mechanical,
Electrical, and Plumbing design for the base building at Arrabelle, has reviewed the
proposed remodeling of Unit 484/584 being submitted for a revision to the approved
construction documents. To the best of our knowledge, we find the proposed revisions
compatible with the approved construction documents with the exception of the items listed
in the mechanical and electrical review comments attached to this letter.
Please call if you have any questions or concerns.
������i,�;...,,,
`��� "'•-.
�• QO RE(ajs,'� Sincerely,
`��� ��,, ...U,�. �'�'•.
��` � �.�� �y�' ATOR RUMA&ASSOCIATES, CO.
�
;v0 t� �rs.�=�:_ ���� �E��s� ,
_ � 8 �_ ���.�,o��GLAS j°"F'QF�
- �� 'w; ��' � 1�^
� • � • �.� ����
��%��t���' �.�... '���� .s ,��,��,,����'
ss•• ,
���''� ��NAL��`'� �����•'�
�ii������i� ���`1����` o,�.�,�, ,. ,\� A. Hughes, P.E. Hal Yoder, P.E.
ELECTf�iICAL �'S;; , ' 'ncipal Mechanical Engineer
M L
HDY
P:�.Amabelle�2007-146 Retail Tenan[Review Proposal\Sup\Docs\blue moose btdg dept ltr 080107.doc
Cc: Steve Roberts—42/40 Architecture
1550 DOVER STREET•SUITE 2�LAKEWOOD,COLORADO 80215-3132
� PHONE(303)232-6200�FAX(303)233-3701 •E-MAIL:cra@catorruma.com
Arabelle—Blue Moose Pizza
Mechanical Peer Review Report
CRA#2007-146
August 1, 2007
Cator, Ruma&Associates performed a peer review of the mechanical drawings completed by the
owner's MEP engineer who will be providing their PE stamp on the drawings. The following
review comments are intended to notify the owner of possible base building conflicts and impacts,
as well as provide the Tenant Finish Engineer with a general review of their design. Note that the
building deparhnent should review the drawings for code conformance.
MECHANICAL
l.l The make-up air flow rate in the Ventilation Schedule on FSIA totals 4152 CFM. The
Mechanical Numbered Notes on M2.0 total another 3050 CFM of make-up air. The total
from both sheets is 7202 CFM. The base building design allocated 6200 CFM of make-up
air to this space. The makeup air unit serving Blue Moose Pizza also served other tenants
in the building. It is not acceptable to reduce the airflow to the other tenants. The makeup
airflow rate to Blue Moose Pizza shall not exceed the allocated 6200 CFM. Issue an
addendum to adjust the makeup airflow rate accordingly.
1.2 Sheet FS6 shows two up-blast exhaust fans and a makeup air unit. The kitchen exhaust
fans and makeup air unit are provided in the base building systems and do not need to be
furnished by the tenant.
1.3 Sheet M1.0 shows a water cooled condensing unit piping detail. The detail indicates that
the piping to the condensing units will run wild. This is not acceptable. If water cooled
condensing units are used a solenoid valve controlled by the condensing unit shall be
installed to regulate water flow to each condensing unit. If the tenant connects to the base
building chilled water system he shall furnish and install BTU meters on the chilled water
piping serving the condensing units. The food service plans indicate that the walk in
coolers and ice machine condensing units are air cooled. The discrepancy between the
food service and mechanical plans needs to be resolved. Issue an addendum to modify the
plans accordingly
1.4 Sheet P2.0 has a note stating that a 1" 140 deg F domestic hot water line will be provided
by the landlord. According to Vail Resorts Development Company the landlord/tenant
agreement does not state that 140 deg F water will be furnished to the space. The tenant
shall provide a booster heater for the dishwasher to raise 110 deg F water to 180 deg F.
Issue an addendum to adjust the plans accordingly.
HDY
P:\Arrabelle�2007-146 Retail Tenant Review Proposal\Sup\Docs\Arrabelle blue moose PeerReview-mech 0801]07.doc
Arabelle—Blue Moose Piza
Electrical Peer Review Report
CRA#2007-146
August l, 2007
Cator, Ruma&Associates performed a peer review of the electrical drawings completed by the
owner's MEP engineer who will be providing their PE stamp on the drawings. The following
review comments are intended to notify the owner of possible base building conflicts and impacts,
as well as provide the Tenant Finish Engineer with a general review of their design. Note that the
building department should review the drawings for code conformance.
GENERAL:
1.1 In general, it appears there is a substantial amount of information missing that would be
required by the building department. We have indicated some but not all missing
information or required clarification on the electrical drawings, sheets E100, E200, and
E300.
1.2 The drawings were reviewed for impacts on the base building electrical distribution system.
1.3 Refer to most current base building documents for requirements.
ELECTRICAL
1.4 E 100: Indicate conduit and conductor sizes required for the primary and secondary feeds
of the transformers.
1.5 E 100: On the feeder schedule, indicate only the feeders being used. It appears only the
new transformer feeders will be used(see item#1.3).
1.6 E100: Indicate only the transformer sizes being used on the plans.
1.7 E200: Tenant's consultant/contractor shall provide connection for(4) fan coil units per the
base building electrical documents. The fan coil units were installed by the base building
mechanical contractor. Refer to attached plan.
JAH/jah
P:�Arrabelle�2007-146 Retail Tenant Review Proposal\Sup�Docs�Arrabelle blue moose PeerReview-Elec.0801.07.doc
C:HRiSTOPHEf�1��ENG�S 17(l0 W. LittEeton Blvd.,su�te aQ�
LiYtleton, Cotorado 80120
ENGINEEl��,INC. Ph(72D}283-3U18
Fax(720)283-5253
www.mengeseng.com
�
,���,��,�;�..,.�..-'���.:
Decemb�r 21,2007 ;-- .
�
Ntr.Sil!Ga�ison .��L_�;��. � ,°
Envi�nmer�ta!Heaith C3tiicer, Planner
TQwn of Vail : . .
Vail,CO 81657 -�
�ear Mr.Garison:
T1ne purpose of this leiter is to verify ihe waier i�ea�er sizing f�r the alue Mc3ose an€�Cf�op Hause Restaurants aE ihe
Arrabelte Buifding in Vail,CO.
Each space is suppfied �vith water at 110 c�egrees �, therefore, the items that require 'i40 d2gree F �va�er
(dishwashin�operations}are supplied thraug�an eiec;tric wafer heatcr t�at raises the temper�ut'e 3Q degr�e.s F_
The ca�culated�o�water i�ad��the Chap Ho�se restaurar�t dishwashing operatic�n is'I6t7.5 GPH,ca[culafed per the
Golorada Re[ail Foad Establishment Ruies ar� Regulatiqns. The power reqr�ireci tc� r�ise the tem��rat�sre 30
ciegrees of tt�s flow rate of water is 40;091 Btu;hr. The specified electric water F�eater is Rhees�rr�odel E�-50-12-G;
uvt�ich has a recovery capacity of 4�;944 Btu/t�r('f2 kW}. The derr�anci is g8% Qf the water heater capa��#y, so the
specified tivater hea#er is suffieient f�r this ap�aEicat"ran.
The calcutated hot water€oad forihe 81ue Moose restaurar�t disf�washing aperaiian is 12Q.5�PN, calc�lated per the
Col�rada Retaii Foed Estabtishmenf Rules an� REgulatians. The power required to €ai5e the temperature 30
dQgre�s far this fl�w rate of water is 30,094�tu/hr. The speeifte�i electric water heater is Rh�ecn model ES-5(?-12-G,
�,vhi�h ha5 a recovery capaaty of 40,944 Btu/hr(�2 kW). The derriand is 74%4f the water heater capacity, so the
speci�ied water heater is sufficier�t for this ap�lication.
Sincerely,
f��"�`---'" Z''�� o
G . �.
Ch�is#apiter Menges
Pr�sident
TOWN OF VAIL FIRE DEPARTMENT VAIL FIRE DEPARTMENT
?5 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2135
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
ALARM PERMIT Permit #: A07-Ol 14
Job Address: 675 LIONSHEAD PL VAIL Status . . . : ISSUED
Location.....: ARRABELLE HOTEL-Blue Moose Applied . . : 10/OS/2007
Parcel No...: 210106325001 Issued . . . 10/11/2007
Project No : Expires . .: 04/08/2008
OWNER ARRABELLE AT VAIL SQUARE LLC10/05/2007
PO BOX 7
VAIL
CO 81658
APPLICANT COMMERCIAL SPECIALISTS OF 10/05/2007 Phone: 970-513-'7100
WESTERN COLORADO, LLC
P.O. BOX 1572
SILVERTHORNE
CO 80498
License: 161-5
CONTRACTOR COMMERCIAL SPECIALISTS OF 10/05/2007 Phone: 970-513-'7100
WESTERN COLORADO, LLC
P.O. BOX 1572
SILVERTHORNE
CO 80498
License: 161-5
Desciption: BLUE MOOSE AT ARRABELLE- Installation of smoke detectors,
heat detectors, strobes and speakers strobes
Valuation: $12,201.00
+**+��+***��**+►+*�*��*►��***��:+*►**a***s*�*►r*:r+*��*+*******��***** FEE S UMMARY ****�*+as***�x��«�:******rts*r*r***+*****�►*+*****r*+►**+r�*+
Electrical---------> $0.0 0 Totai Calculated Fees--> $6 8 9.54
DRB Fee---------> $o.00 Additional Fees----------> $0.00
lnvestigation----> $o.oo Total Permit Fee--------> $689.54
W ill Call---------> $o.0 0 Payments------------------> $6 8 9.5 4
TOTAL FEES--> $6 8 9.54 BALANCE DUE--------> $o.o 0
.r**r+rs+r******++**+++*+sr****+►►*►*�**►*►�**s��.�r*.�*�s►r*:**++**�+*r*r***�*►*r+***+**r*�*�*►+��+*�*�***s**+�*s**«r�r*+*****�+*�+�:*a***.***rxas
Approvals:
Item: 05600 FIRE DEPARTMENT
10/08/2007 mcgee Action: AP Add manual pull station in kitchen.
*�.*.**.******.*.*.***.*...***.**.�...�..*...�.«*:***�*****.*.**....*.**�.*..*.*.*.*...*.*:.�..*...�.*.***.*.*�*,:.*.*.��.*.*s.*.�.*��..�*.*,*.�,:*
CONDITIONS OF APPROVAL
.���****.*�**.*�.�,.*.��*.*......�.........*.*.*.*.*.***..*****,...�.*.*.**.*.*,:�*�*«*�******.*.�*.*.*.***.*.��*,:.**.,*,**�*****.*.**.�.******.*.
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan,to comply with all
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordinances of the Town applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY-FOUR HOURS IN ADVANCE BY TELEPHONE AT 479-Z135 FROM 8:00 AM-5 PM.
\��"vJ �\�-�-�---�-_ .`_ C-C��'`% � .
� �
*+*****************************************+**************************************+*********
TOWN OF VAIL, COLORADO Statement
*****************************+***********************************+**************�***********
Statement Number: R070002175 Amount: $689.54 10/11/200708:37 .AM
Payment Method: Check Init: DDG
Notation: Commercial
Specialists 10825
-----------------------------------------------------------------------------
Permit No: A07-0114 Type: ALARM PERMIT
Parcel No: 2101-063-2500-1
Site Address: 675 LIONSHEAD PL VAIL
Location: ARRABELLE HOTEL - Blue Moose
Total Fees: $689.54
This Payment: $689.54 Total ALL Pmts: $689.54
Balance: $0.00
******************+*************************************************************************
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------------- ------------------------------ ------------
BP 00100003111100 FIRE ALARM PERMIT FEES 457.54
PF 00100003112300 PLAN CHECK FEES 232.00
-----------------------------------------------------------------------------
TOWN OF VAIL DEPARTMENT OF COMMUNITY DEVELOPMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2138
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
ELECTRICAL PERMIT Permit #: E07-0224
�; �1 -02� U
Job Address: 675 LIONSHEAD PL VAIL Status . . . : ISSUED
Location.....: BLUE MOOSE @ ARRABELLE HOTEL Applied . . : 09/14/2007
Parcel No...: 210106325001 Issued . . . 09/14/2007
Legal Description: S.�-s.�S� � _v �J Expires . .: 03/12/2008
Project No :
OWNER ARRABELLE AT VAIL SQUARE LLC09/14/2007
PO BOX 7
VAIL
CO 81658
APPLICANT DESIGN ELECTRICAL CONTR.ACTOR09/14/2007 Phone: (970) 468-5330
7193 S. DILLON COURT
ENGLEWOOD
CO 80112
License: 352-E
CONTR.ACTOR DESIGN ELECTRICAL CONTR.ACTOR09/14/2007 Phone: (970) 468-5330
7193 S. DILLON COURT '
ENGLEWOOD
CO 80112
License: 352-E
- --�..,'�
Desciption: ELECTRICAL F R BLUE MOOSE AT A ABELLE
Valuation: $80,000.00 --� quare feet: 0
******************************************************************* FEE SUMMARY ******************�*******************s********************�
Electrical---------> $1,713.50 Tota1 Calculated Fees--> $1,717.50
Invesdgation----> $0.00 Additional Fees----------> $0.00
Will Call---------> $4.00 Total Permit Fee--------> $1,�17.50
TOTAL FEES--> $1,717.50 Payments------------------> $1,717.50
BALANCE DUE--------> $o.o0
***�****************************�*a:*�***�*************************�**********s****************************�**�:***********************************
Approvals:
Item: 06000 ELECTRICAL DEPARTMENT
09/14/2007 shahn Action: AP
******�:****************************************�******�*«************��:*�***�*****************************************�*************************
CONDITIONS OF APPROVAL
Cond: 12
(BLDG. ) : FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
*********************************************************************�***********************************************************************�***
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot
plan, and state that all the information as required is correct. I agree to comply with the information and plot plan, to comply
with all Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design
review approved, International Building and Residential Codes and other ordinances of the Town applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY-FOUR HOURS IN ADVANCE BY TELEPHONE AT 479-2149 OR AT OUR OFFICE FROM 8:00 AM-4
PM. ' .
� ��, , ,, � � .
SIGN T OF OWN R ONTRACTOR FOR HIMSELF AND OWNEF
**************************************�*****************************************************
TOWN OF VAIL, COLORADOCopy Reprinted on 03-23-2009 at 13:23:35 03/23/2009
Statement
********************************************************************************************
Statement Number: R070001864 Amount: $1,717.50 09/14/200702:37 PM
Payment Method: Check Init: JS
Notation: 28816/DEC
-----------------------------------------------------------------------------
Permit No: E07-0224 Type: ELECTRICAL PERMIT
Parcel No: 2101-063-2500-1
Site Address: 675 LIONSHEAD PL VAIL
Location: BLUE MOOSE @ ARRABELLE HOTEL
Total Fees: $1,717.50
This Payment: $1,717.50 Total ALL Pmts: $1,717.50
Balance: $0.00
******************************************************************************�x*************
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------------- ------------------------------ ------------
EP 00100003111100 ELECTRICAL PERMIT FEES 1,713 .50
WC 00100003112800 WILL CALL INSPECTION FEE 4.00
-----------------------------------------------------------------------------
APPLICATION WILL NOT BE ACCEPTED IF INCOMPLETE OR UN �� _ V �� �
Project#:
Building Permit � � � � 7
� _ � ��i" ��� � �"� Electrical Permit#: � - " �
���'�'"'��� ' 970-479-2149 (Inspe �ons
75 S.Frontage Rd.
Vail,Colorado 81657
�T WN OF VAIL ELECTRICAL PERMIT APPLICATION
� � � �
l � � CONTRACTOR INFORMATION
�lectrical Contrs� or:_. Town of Vail Reg. No.: Contact Per n and Phone #'s: :
'��I�d � ��' ��,�y-- � �' / ' � � ! I` �,�► )
E-Ma Address: Fax#: �
Co tra�c�c�r Signatu�e: �' �� _
�i �
� � / �� /
O�PLETE SQ. FOOTAGE FOR AREA OF WORK AND VALUATION OF WORK (Labor&Materials)
AMOUNT OF SQ Ff IN STRUCTURE: ELECTRICAL VALUATION: $ �} } 1 � ��(�
Contact Ea /e Coun Assessors O�ce at 970-328-8640 or visit www,ea le-coun ,com fo�Parce/#
Parcel #
Job Name: �' �/ ���'�f�' �� Job Address:
!1� f�.,��� ^�,
Legal Description Lot: Block: Filing: � Subdivision:
Owners Name: Address: Phone:
Engineer: Address: Phone: �
Detailed description o�work:
� ��,�`i f��`���"�°v������'� TI'
Work Class: Ne Addition ( ) Remodel ( ) Repair( ) Temp Power( ) Other( ) •
Work Type: Interio Exterior( ) Both ( ) Does an EHU exist at this location: Yes ( ) No ( )
Type of Bldg.: Single-family( ) Duple�c( ) Multi-family( ) Commercial( ) Restaura Other( )
No. of Existing Dwelling Units in this building: No. of Accommodation Units in this building:
Is this ermit for a hot tub: Yes No
Does a Fire Alarm Exist: Yes ( ) No ( ) Does a Fire Sprinkler System Exist: Yes( ) No( )
(� �G �:,r, �u� r_ �l
� �� . ��
�*��������**�*��������*���***��**����**FOR OFFICE USE ONLY��� �*�*���*���*�*������r�r �r��*�*�
SEP 13 2007
�.�iier..Fe�»..��. �s _Da�Received .—
E�RB$ "'� ' ,: AaG� �B
� Rg- :�� �>�s. ' � Al�.
�►ar�n+en,�i rt-o�F. ..a_.._r
�
F:\cdev\FORMS\PERMITS\Building\electical�ermit 11-23-2005.DOC Page 1 of 2 11/23/2005
TOWN OF VAIL FIRE DEPARTMENT VAIL FIRE DEPARTMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2135
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
SPRINKLER PERMIT Permit #: F07-0139
Job Address: 675 LIONSHEAD PL VAIL Status . . . : ISSUED
Location.....: ARRABELLE HOTEL Applied . . : 10/18/2007
Parcel No...: 210106325001 Issued . . . 12/06/2007
Project No : Expires . .:
OWNER ARRABELLE AT VAIL SQUARE LLC10/18/2007
PO BOX 7
VAIL
CO 81658
APPLICANT TRI COUNTY FIRE PROTECTION 10/18/2007 Phone: cell 303-591-3111
PO BOX 309
RIFLE
CO 81650
License: 727-S
CONTRACTOR TRI COUNTY FIRE PROTECTION 10/18/2007 Phone: cell 303-591-3111
PO BOX 309
RIFLE
CO 81650
License: 727-5
Desciption: INSTALLATION OF KITCHEN HOOD FIRE SUPPRESSION SYSTEM FOR
THE BLUE MOOSE AT ARRABELLE
Valuation: $2,650.00
s*s**rr*a�*�+******�*++����*���*+**+*�******«*r*t+*►r►*+«**+**�+*r*• FEE S UMMARY **:t*rs*s*r�****�********sx**v***s*****+r+r*****+****��sr�**a
Mechanical---> $0.oo Restuarant Plan Review--> $o.00 Total Calculated Fees---> $462.63
Pian Check---> $3 5 0.o o DRB Fee---------------------> $o.0 0 Additional Fees-----------> $o.0 0
Investigation-> $o.oo TOTAL FEES--------------> $462.63 Total Permit Fee----------> $462.63
Will Call-----> $0.D 0 Payments-------------------> $4 6 2.6 3
BALANCE DUE---------> $o.o 0
+***.**�**►+�*�+.�.**++r:«*.**r■***.*�.*.***s.s**��+.»»*�*s**.*■.■.*:*.�:.***.*..*.■��.s*�►.***s.►**«�*�s��r*■�*s*+*+**.*.*.*.**►+►*�st�+�++*s***+�
Item: 05100 BUILDING DEPARTMENT
Item: 05600 FIRE DEPARTMENT
10/25/2007 mvaughan Action: AP
CONDITION OF APPROVAL
Cond: 12
(BLDG. ) : FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
*.**.**��.****���********:.****r�***�.**��..*.:►*«*:�******.+.�,:.**+*.*...«�*�►***��*.,*+«�*.**�*.*���*+*�*.�*�....+�*.**�.*.*****«**+*:�....*�.*
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan, to comply with all
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordinances of the Town applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY-FO, fJU S I ADVANCE BY TELEPHONE AT 479-2135
FROM 8:00 AM-5 PM. ' `
� G
SIGNATURE OF OWNER OR CONTRACTOR FOR HIMSELF AND OWNER
********************************************++*************************************+********
TOWN OF VAIL, COLORADO Statement
**************++**�**********************�**�*********************+*****+*********+*********
Statement Number: R070002659 Amount: $462 .63 12/06/200709:50 AN[
Payment Method: Check Init: DDG
Notation: Tri County Fire
Protection 505
-----------------------------------------------------------------------------
Permit No: F07-0139 Type: SPRINKLER PERMIT
Parcel No: 2101-063-2500-1
Site Address: 675 LIONSHEAD PL VAIL
Location: ARRABELLE HOTEL
Total Fees: $462 .63
This Payment: $462 .63 Total ALL Pmts: $462 .63
Balance: $0.00
************************************************�******�+�******�*�***************�*********
ACCOUNT ITEM LIST:
Account Code Description Curi-ent Pmts
-------------------- ------------------------------ --�--�--------
BP 00100003111100 SPRINKLER PERMIT FEES 112.63
PF 00100003112300 PLAN CHECK FEES 350.00
-----------------------------------------------------------------------------
.
TOWN OF VAIL FIRE DEPARTMENT VAIL FIRE DEPARTMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2135
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMF;S
SPRINKLER PERMIT Permit #: F07-0116
�G � - C�.�taU
Job Address: 675 LIONSHEAD PL VAIL Status . . . : ISSUED
Location.....: ARRABELLE HOTEL Applied . . : 09/26/2007
Parcel No...: 210106325001 Issued . . . 10/08/2007
Project No : �-��j� -G;j�� Expires . .:
OWNER ARRABELLE AT VAIL SQUARE LLC09/26/2007
PO BOX 7
VAIL
CO 81658
APPLICANT ALL STATE FIRE PROTECTION, I09/26/2007 Phone: 303-288-3901
6045 E 76TH #12
COMMERCE CITY
CO 80022
License: 370-S
CONTRACTOR ALL STATE FIRE PROTECTION, I09/26/2007 Phone: 303-288-3��01
6045 E 76TH #12
COMMERCE CITY
CO 80022
License: 370-5
Desciption: BLUE MOOSE AT ARRABELLE-INSTALL FIRE SPRINKLER SYSTEM
Valuation: $13,000.00
****��*****�***��:*******s*a***�**********+*+�****+�*****a***�****+*■ FEE SUMMARY �*�*�***«****�*r****t***t***,�************�****+***r*�***t***
Mechanical---> $0.00 Restuarant Plan Review--> $0.0 0 Total Calculated Fees---> $902.5 0
Plan Check---> $3 50.o o DRB Fee---------------------> $0.0 0 Additional Fees-----------> $0.0 0
Investigation-> $0.00 TOTAL FEES--------------> $902.50 Total Permit Fee----•----->
$902.50
WiIlCall-----> $0.00 Payments-------------------> $902.50
BALANCE DUE---------> S o.o 0
+***�:+**trr**�*r*****t***�***»�*►**�**�**t***s►*t*�*t*�*t*��r******v**rt**+**+****s+**�+r******«**+*********�***+****�:**�+*rx�*r********�s**�+***
Item: 05100 BUILDING DEPARTMENT
Item: 05600 FIRE DEPARTMENT
10/04/2007 DRhoades Action: AP Approved as noted:
1 . Location tor control valve tor this space must be approved by Vail Fire prior 1
installation.
CONDITION OF APPROVAL
Cond: 12
(BLDG. ) : FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE;.
***■**■*.****.***«**......:*«.«*.*,�+*.**.*.*■�.*■*.*:*.*.+*..:..*********»**.****..*.*■*■*■:■**■*.s*.*�******�.*.*.*..*�...***..**.*.*�■*.*.*■*:�
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, com��leted an accurate plot plan,
and state that all the infarmation as required is correct. I agree to comply with the information and plot plan,to comply with all
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordinances of the Town applicable tlhereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY-FOUR HOURS IN ADV NCE B T �EPHONE AT 479-2135
FROM 8:00 AM-5 PM.
. ��' �, -...'
SIG ATURE OF OWNER O ' ONTRACTOR.FOR HIMSELF AND OWNER
********************************************************************************************
TOWN OF VAIL, COLORADO Statement
*******************************************************************************�************
Statement Number: R070002126 Amount: $902 .50 10/08/200712 :45 Pb1
Payment Method: Check Init: LT
Notation: All State / ck
15825
----------------------------------------------------------------�-- -----------
Permit No: F07-0116 Type: SPRINKLER PERMIT
Parcel No: 2101-063-2500-1
Site Address: 675 LIONSHEAD PL VAIL
Location: ARRABELLE HOTEL
Total Fees: $902 .50
This Payment: $902.50 Total ALL Pmts: $902 .50
salance: $0.00
***************************************+***************************************�************
ACCOUNT ITEM LIST:
Account Code Description Cur��ent Pmts
-------------------- ------------------------------ -�--�---------
BP 00100003111100 SPRINKLER PERMIT FEES 552 .50
PF 00100003112300 PLAN CHECK FEES 350.00
------------------------------------------------------------------ -----------
APPLICATION WILL NOT BE ACCEPT D IF INCOMPLETE OR UNSI ���_`,�,�� �
Project#:
Building Permit#: _
� Sprinkler Permit;�:
,� 970-479-213 !ns tio s
`' TOWN OF VAIL FIRE SPRINKLER PERMIT APPLJCATION
TUWNOFYAIL Fire Sprinkler shop drawings are required at time of permit siabmittal and
75 S. Frontage Rd. must include the followi�g. Permit application will not be ac�;epted
Vail, Colorado 81 without this information:
• A Colorado Registered Engineer's stamp or N.I.C.E.T.. Level Iil (min) stamp,
• Equipment cut sheets of materials.
)%� • Hydraulic calculations.
� • A State of Colorado Plan Registration form.
• Plans must be submitted by a Registered Fire Proxecl:ion Contractor.
CONTRACTOR INFORMATION �„
�ire Sprinkler Contractor: Town of Vail Reg. No.: Contact and Phone#'s:� � �
�1°��; ._� ��i�—�'. �i'�Li:�Tr�! ti<-`': `�C��?'Y.�>�'->F'e �4
E-Mail Address: i'1���1�� �l 1 S+e:�-��r�`"ro�trCfr�c;�'� �'`�"� -----------��_W..��
7�
Contractor Signature: r ,(� �f�,� ,
i '�� ,�-1C,t�2,�d�< ��C2���:��l.a� __�_.�J
COMPLETE VALUA710NS FOR ALARM PERMIT (Labor& Materials)
Fire Sprinkler:$ �,� ���• �.�J
Contact Ea le Count Assessors Office at 970-328-8640 or visit www.ea !e-counf .com for Parcel#
€�arcel # �
Job Name:;� }^ t � y /� /�� Job Address �,���' a�,,/� j/�7�:,�t)� `�!`• ��� ¢�' ' �
�Z��ti+C���C. � �LZ�� �� �•^�rG(�JC�Iy� 1Y/' tl� f ...�✓,. S/ � ' �
_��-__'_ __��A`
Legal Description Lot: Biock: Filing: Subdivisior: T�__ � _M_.__�_.��-�i
�wners Name: i�,, �� Address:�� �: � ��, � CO �;t��� Phane:...����' � l�� _G�.j�-`'_V_.�..�i
-± �.CY � '" _�
Engineer: Address: Phnne:
�._...�. _ ---�-=�-—��
Detailed Location of work: (i.e.,floor, unit#, bldg.#) ��
1�"- � f ls5 . . —_—_. .. - .-.;-�i
Detailed description of work: � ��
�'���tid d �1i� e �J`J6'�a:'?���+'r _ e �j
� --- -----._._------''-,:�i
a�
�Nork Ciass: New( ) Addition ( ) Remodel ( ) Repair( ) Retro-fit( ) Other( ) � ___ ^ �j
7ype of Bldg.: Single-family( ) Two-family( ) Multi-family( ) Commercial ( } Restaurant( ) Other( }� ��
No. of Existing Dwefling Units in this building: No.of Accommodation Units in this building: 1
Does a Fire Alarm Exist: Yes( ) No ( ) Does a Fire Sprinkler System Ex�st: Yes ( ) No( )
*::**********�***�*****,�***�************FOR OFFICE USE ONLY*****************�k******��*�x*:r�*�***
�.Other F�es, ' � k ���
F,ub�cr . ����er .�ft��e���s� � �:;:�� � �
, F , �w.
. � n�:,
�O�ct� anc ��ou �' � �'s ��� �� � ,��= ` � �
P Y` P�
\��'ait\data\cdev\FORMS\PERMITS\SPRKPERM.DOC --_ ����4�7iI�'lLV"L,����xY��
'�'�C .��.(�'��.�.1�,�:�.�r'��.o...�a.....n,_.e..e.a....._�..�._,.
D�te: _�.�fl-DY-D'7 �...�.�.�.�v..�:�..
TOWN OF VAIL DEPARTMENT OF COMMUNITY DEVELOPMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2138
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
MECHANICAL PERMIT Permit #: M07-0256
Job Address: 675 LIONSHEAD PL VAIL Status . . . : ISSUED
Location.....: ARRABELLE HOTEL Applied . . : 10/02/2007
Parcel No...: 210106325001 Issued . . . 10/04/2007
Legal Description: Expires . .: 04/O1/2008
Project No :
OWNER ARRABELLE AT VAIL SQUARE LLC10/02/2007
PO BOX 7
VAIL
CO 81658
APPLICANT COMMERCIAL DESIGN ENGINEERINIO/02/2007 Phone: 970-245-0595
PO BOX 2440
COLORADO SPRINGS
CO 80901
License: 192-M
CONTRACTOR COMMERCIAL DESIGN ENGINEERINIO/02/2007 Phone: 970-245-0595
PO BOX 2440
COLORADO SPRINGS
CO 80901
License: 192-M
Desciption: BLUE MOOSE AT ARRABELLE TENANT FINISH
Valuation: $9,750.00
Fireplace Information:Restricted: #of Gas Appliances: 0 #of Gas Logs: 0 #of Wood Pellet: 0
���*�s******r**►*****a�+****�*�**r**+�*+*r*+*a****�+*+*�**�**t***r*r FEE S UMMARY •*�***swt*�**************►***�*�**v**+***+****►***�:++�***r�+
Mechanical---> $200.00 Restuarant Plan Review--> $o.00 Total Calculated Fees---> $254.00
Plan Check---> $5 0.o o TOTAL FEES--------------> $2 s 4.o o Additional Fees-----------> S o.o 0
Investigation-> $o.o o Total Permit Fee----------> $2 5 e.o 0
W ill Call-----> $4.0 0 Payments-------------------> $2 5 4.o 0
BALANCE DUE---------> $0.00
*�*v*s+*«►*******s***►s*******r****+****r***�*s**�r*�*****■**«****r►+�r*t+►w+****r*►+**��►****��**r*sr+*«�*+**a**„.*+*�*r**�*******s*s++�*****��*+
Item: 05100 BUILDING DEPARTMENT
10/02/2007 cgunion Action: AP
Item: 05600 FIRE DEPARTMENT
CONDITION OF APPROVAL
Cond: 12
(BLDG. ) : FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
Cond: 22
(BLDG. ) : COMBUSTION AIR IS REQUIRED PER CHAPTER 7 OF THE 2003 IMC AN:D SECTION
304 OF THE 2003 IFGC AS MODIFIED BY TOWN OF VAIL. �
Cond: 23
(BLDG. ) : BOIILER INSTALLATION MUST CONFORM TO MANUFACTURER'S INSTRUCI'IONS AND
CHAPTER 10 OF THE 2003 IMC.
Cond: 25
(BLDG. ) : GAS APPLIANCES SHALL BE VENTED ACCORDING TO CHAPTER 5 OF �HE 2003 IFGC.
Cond: 29
(BLDG. ) : ACCESS TO MECHANICAL EQUIPMENT MUST COMPLY WITH CHAPTER 3 OF THE 2003
IMC AND CHAPTER 3 OF THE 2003 IFGC. .
Cond: 31
(BLDG. ) : BOILERS SHALL BE MOUNTED ON FLOORS OF NONCOMBUSTIBLE CONS�. UNLESS
LISTED FOR MOUNTING ON COMBUSTIBLE FLOORING.
Cond: 32
(BLDG. ) : PERMIT, PLANS AND CODE ANALYSIS MUST BE POSTED IN MECHANICAL ROOM PRIOR
TO AN INSPECTION REQUEST.
Cond: 30
(BLDG. ) : BOILER ROOMS SHALL BE EQUIPPPED WITH A FLOOR DRAIN OR OTHE3R APPROVED
MEANS FOR DISPOSING OF LIQUID WASTE PER SECTION 1004 . 6 .
*+*».*+�.+s...*.***:**.*.*.*►**.*.*+*+.**...+..►*.*.*�+*..«...*.*.***.*.��.*.*�*�**.***.****►*.*�.*++.+*..*.*.».*.�+s.******.*rs***:+�.*.�*:.**.*
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, connpleted an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan,to comply with all
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordi nces of the Town applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY-FOUR HOURS IN ADVA E B TELEP AT 79-2149 OR A7 OUR OFFICE FROM 8:00 AM-4 PM.
SIGNATURE OF OWNER OR CONTRACTOR FOR HIMSELF AND OWNER
*++****+************************�***********************************************************
T0�1VN OF VAIL, COLORADO Statement
***************************************+*+**************************************************
Statement Number: R070002079 Amount: $254 .00 10/04/200708 : 18 .AM
Payment Method: Check Init: DDG
Notation: Commercial
Design Engineering 095470
-----------------------------------------------------------------------------
Permit No: M07-0256 Type: MECHANICAL PERMIT
Parcel No: 2101-063-2500-1
Site Address: 675 LIONSHEAD PL VAIL
Location: ARRABELLE HOTEL
Total Fees: $254.00
This Payment: $254 .00 Total ALL Pmts: $254 .00
Balance: $0.00
********************************************************************************************
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------------- ------------------------------ ------------
MP 00100003111100 MECHANICAL PERMIT FEES 200.00
PF 00100003112300 PLAN CHECK FEES 50.00
WC 00100003112800 WILL CALL INSPECTION FEE 4 .00
-----------------------------------------------------------------------------
10/Ol/2007 11:35 FAT 9702451015 �006/006
APPLICATION WILL NdT BE ACCEPTED IF INCOMPLETE OR UNSIG �f ��? �3��
TOV Project#: "V
Building Permit #:
Y ;• � b Mechanical Permit#:
� � � � 970-479-21�49 Ins ections
����� ( P )
TOWN OF VAIL MECHANICAL PERMIT APPLICATION
�5 s. Frontage Rd. Permit will not be accepted without the following:
vaiy Colorado 81657
Provide Mechanital Room Layout drawn to scale to include:
/ o Mechanical Room Dimensions
❑ Combustion Air Duct Size and Location
❑ Flue,Vent and Gas Line Size and Location
� o Heat Loss Calcs.
o Equipment Cut/Spec Sheets
CONTRACTOR INFORMATION
Mechanical Contractor: Town of Vail Reg: No.: Contact Person and Phone#'s:
co — �9 z � c �9 4qz-
E-Mai1 Address: Fa�c#:
Contractor Sigr�ture:
COMPLETE VALUATION FOR MECHANICAL PERMIT Labor&Materials
MECHANICAL: � SD
Contact Ea /e Coun Asse�sors�Ce at 7 -328- 640 or visit www,ea le-coun ,com fnr Parrce/�#
Parcel # 210/O
Job Name: Job Address:
�t !.0 E Mao.s�. �0 7 �.io he l% ���
Legal Description Lot: Block: Filing: Subdivision:
owners Name• �G�k / Addrass:b�5 L�onsfic lQ . P/3 Pf1On�'7o 32 I�
Engineer: Address: Phone:
Detailed description of work:
rENR�r.►-l' �/1�3{�
work Class: New ( ) Addition ( ) Alteration�[) Repair( ) Other( )
Boiler Location: Interior( ) Exterior( ) Other( ) Does an EHU exist at this location: Yes ( ) No( )
Type of Bldg: Single-family( ) Duplex( ) Multi-family( ) Commercial( ) Restaurant( ) Other( )
No. of Fxisting Dwelling Units in this building: No.of Accommodation Units in this building:
No of Fire aces Existin : Gas A liances Gas L s Wood Pellet Wood Burnin
No/Type of Fireplaces Proposed: Gas Appliances( ) Gas Logs( ) Wood/Pellet( ) Wood Burning(NOTALLOWED)
Ls this a conversion from a wood buming fireplace to an EPA Phase II device? Yes ( ) No ( )
************************FOR OFFICE USE ONLY*********************'�
: ...._...... ........... .. .. ...._......._:::.�::;:�� �p I�
�O e+.:.. ; . � -.. .Cy�iai?:Rec�iVi�::�::�:i�;�:����:�:::'-=?:�:: !s
..:#h:..:�r:_�ees;;>;;�_<:�:::'=>'�:�';;::=:_:::::�:................._........._........._................_......__-............. '��'::: G, � � \v�
_........:....:.�,:..._..................................................::::::-_:::.::r:�.::::��.._...
L.
::::::�::::::::::.::::::::::�-_,_-:,,�:::�:::-.::�... ......._............_.................................
.............._....,._........,... :,::,., ::.:: :.,::.-:,.-.
_...:..:::::::.::::::.-:.:.:::.:....:......_..............._...,., , .. ........._.;.....:.: ...._._:..::::.
.::::::::...::.:.:..::...::..:::::::::.::::.::::::��:::�,:.Ac�� ,�,it;B. ._::-�:::s:�'::;:;;:;;:;::�::�:::::::;:.;:;,::;.s::
.. ,. . .
::.�::::;::�;�;.:.:..:.::::::: .:::."=°''�:::t;:s;:;::s;:::_:::-;:'::.::-s�:-::::�:�a:;::::-:.�:�.::-:t�:;;:;;::::;;::;�;;;t::':::> -:_.:
��� �� 1 Z�fl�
F:\cdev\FORMS�Permits\Building\mechanical_permit_il-Z3-2Q�5.DOC � 11/23/2005
S
TOWN OF VAIL
TEST, ADJIJST A►ND BALANCE REPORT
PROJECT
BLUE MOOSE PIZZA
ELLE
VAIL, CO
PREPA�RED FOR
CDE MEC�:[��.NICAL
REPORT ISSIJE DATE
12/27/2007
PREPA►_R.ED B�
H-VAC
P O. BOX �123
VAIL, CO 81658
PHONE: 970-331-1095
FAX: 970-926-9406
� H-VAC
TEST.ADJUST AND BALAN�E REPaRT
THE DATA PRESENTED IN THIS REPORT LS AN EXACT RECORD OF
S�STEM PERI�ORMANCE AND WAS OB'I`AINED IN COMPLIANCE WITH
NEBB PROCEDURAL STANDARDS. ANY VARIANCES FROM THE DESIGN
REQUIREMENTS ARE NOTED THRQUGHOUT THIS REPORT.
THE RESULTS SHOWN AND INFORMATION PRESENTEU IN THIS
REPORT LS CERTIFIED TO BE ACCURATE AND COMPLETE,TO THE
EXTENT POSSIBLE BY EQUIPMENT AND PR4CEDURES USED THR4UGH-
OUT THIS SURVEY.
THE FINAL AIIt DISTRIBUTION SYSTEM MEASUREMENTS ARE IN
COMPLIANCE WITH NEBB PROCEDURAL STANDARDS FOR TESTING,
A.DdiJSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS AND THE
PROJECT SPECIFICATIONS.
CERTIFIED BY: _ DATE: �—���
THE FINAL HYDROI�IIC DISTRIBUTION SYSTEM MEASUREMEIV'TS
ARE Il�T COMPLIANCE WITH NEBB PRUCEDURAL STANDARUS FOR
TESTII�tG,ADUSTIl�TG AND BALANCIl�tG OF ENVIKONMENTAL SYSTEMS
AND THE PROJECT SPECIFICATIONS.
CERTIFIED BY• DATE•
H-VAC WARRNATS THAT TI-�AIR AND HyDROAIIC SYSTEM
EVALUATED DURING THIS SURVEY IS OPERATIl+iG AT THE SPECIFIED LEVELS
AS SHOWN WITHIN THIS REPORT,AT AND ONLY AT THIS TIME. H-VAC
MAKES NO OTI�R WARitANTIES,STATED�R IMPLIED,CONCERNiNG THE
CONfIUED PERFORMANCE,OPERATION OR SAFETY IN THE USE OF THIS
EQIJIPMENT PASS THIS TIME.
�.�/4�
T•A•�• Page: I
co��a
a
.
�'�iqa �.,t,a4Q
H-\/AC nvs�xvMErrr
CALIBRATION REPORT
PROJECT: �v�a�3F1...
INSTRUMENT/SERIAL# APPLICATIQN DATE OF USE CALIBRATION
DATE
SHORTRIDGE ADM-870/M91519 AIR FLOW READINGS 12/27/0� 4-27-07
SHORTRIDGE I�M-300/WO1115 WATER PRES.READTNGS 427-07
SHORTRID('E FLOW HOOD AIF FLOW READINGS 12/27/07 *
PITOT TUBE 18" PRES.READiNt3S NA
PITOT TUBE 24" PRE�.READINGS NA
PITOT TUBE 36" PRES.READINGS NA
SHIMPO TACHOMET'ER/B54139Q 18 RPM READINGS 12/Z7107 4/18/07
FLiJKE 32/52t01005 VOLT/AMP i2/27/07 4-25-07
DAVIS LCA 6000 AIItFL.OW READINGS 12l2710? 425-2007
TEST GAGE 0-S LBS WATER PRES.READINGS *
TEST GAGE 0-20 LBS WATER PRES.READINGS *
TEST GAGE 0-68 LBS WATER PRES.READINGS *
FLLlKE 62 INFARED TI�RM. TEMP.READINGS 3-20-07
'CHECK6D TO CAWBRATED METER
REMARKS: ALL READIIJGS WITH SHORTRIDGE INSTRUMEIVTS ARE CORR�GTED F�R
TEMPERATURE AND ALTiTUDE.
PAGE:
H-V�4►C
I�TCHEN HQUD T�EST REPUIt.T
REPORT: BT.T iF M CF pT7.7 A LOCATI�N: pT77 A nVFNS
DATE: _�'�����m , TYPE:
CLIENT: t�nF�,rFrI-iA�iICAL MFG: �APTLYF nTUF
ADDRESS'ARR AR�'T T F.—VAiT t''t� SERIAI.: C�E"i�4 ND-�
ATTN: EQUIP ID_
GREAS� FILTER INTAKE VELOCITY READINGS
143 220 148 165 i62 155 151
166
��IRFLOW DATA
AVERA(iE C3REASE FILTER VELOCITY 164
GREASE FILTER AREA FACTOR 10.7
MEASLTREI3 TOTAL EXHAUST CFM 1754
DESIGN T�TAL EXHAUST CFM �gpp
MEASURED TOTAL MAKE UP AIR CFM 917
DESIGN'ii0Tt1L MAKE UP AIlt CFM 9QQ
SMOKE TEST
RCSIILTS
PASSED
MANUFACTURER MODEL TEST'PROBE
SHORTRIDGE ADM 870 VELGRID
PAGE: I
�����
KITCHEN �I40D TEST REPUR�'
REPORT: Rt.{TF M['N)�F Pi77 A LOCATION: xi'rru�N t.TNF
DATE: ��?���� . TYPE:
CLIENT: .S'I�MEC.N�iIICAi MFG: CAPTIVE AIFtE
ADDRESS� ARRABET LF SERIAL: �4�4 NU-�
ATTN: EQUIP ID:
GREASE FILTER INTAKE VELOCITY READINGS
216 193 202 192 1'I8 186 202
188 201 194
ow n Ta
AVERAGE GREASE FII,1ER VELOCiTY 196
GREASE FILTER AREA FACTOR 16A
MEASURED TOTAL EXHAUST CFM 3136
DESIGN TOTAL EXHAUST CFM 3200
MEASURED TOTAL MAKE UP AIR CFM 1577
DESIGN TOTAL MAKE UP AIR CFM 1600
SMOKE TEST
�..sUL1's
PASSED
MANUEACTURER MUDEL TEST PROBE
SHORTRIDC',�E ADM 870 VELGRID
PAGE:2
� H-�AC AIR APPARATUS
TEST REPORT
PRQJECT:BIUE MOOSE PIZZA ARRAREL.LE UNiT: D'!-01
AIR HANDLER UNtT DATA MUTOR NAMEPLATE DATA
MANUFACTURER IEC MANUFACTURER BALDt�R
MODEL HBC1200051645 HP R.P.M. 1/2 1725
SERIAI_ 961455-10-2 PHASE FRAME 1 56
FAN TYPE CENTRIFUGAL S.F. TYPE 1.25 NG
RI4TING 1000 CFM VOLTS AMPS 115 l 230 8.4/4.2
MIN OSA 700 CFM THERMALLY PROTECTED YES
STARTER DATA DRIVE DATA
MANUFACTURER NC1NE MOT�t ORNE '! VP 325"4D
MODEL MOTOR B4RE 1/2"
Sie!E/THERMAL NO. FAN DRtYE 1 AK 54
RANGE FAN BORE 3i4"
SET AT(AMPS} .BELTS�SIZE 1 �A25
REQ.THERMAL ROTATIt�N CORRECT
RATING(AMPSj DRNE CHANGE
AIRFLOW DATA TEST DATA lNIT1AL FINAL
SUPPLY CFM 107& FqN R,p�. g�
OSA CFM 721 VOLTAGE �2p
RETURN CFM 355 AMPERAGE 7.9
ATMOS FILTER COIL -0.41" r� �12„
NOTES:
PAGE: �
H-a/AC AIR APPARATUS
TEST REPORT
PROJECT:BLUE MOOSE PIZZA ARRABEILE UNIT: D1-03
, I41R HANDLER UNtT DATA MOTQR NAMEPWTE DATA
MANUFACTURER IEC MANUFACTURER BALDOR
MODEL HBC200005i648 HP R.P.M. 1 1725
SERIAL 961455-50-2 PHASE FRAME 1 56H
FAN TYPE CENTRIFUGAL S.F. TYPE 1.15 NG
RATING 20q0 CFM VOLTS AMPS 115/230 13.4/6.7
THERMAi.LY PROTECTED YES
STARTER DATA ORNE DATA
MANUFACTURER NONE INOTOR ORNE 1 VP 3.25"O�
MODEL MOTOR BORE 5/8" '
SIZEITHERMAL NO. FAN DRNE 9 AK 54
RANGE FAN BORE 3/4"
SET AT{AMPS} .BEi.TS 8�SIZE 1 �i A28
REQ.THERMAL ROTATlON CORRECT
RATING(AMPS) DRNE CHANGE
- I
AIRFLOW DATA TEST OATA INITIAi. FINAL
SUPPLY CFM 2Q47 FAN R.P.M. 897
OSA CFM 0 VOLTAGE 120
RETURN CFM 2047 AMPERAGE g.1
ATMOS FILTER COIL -0.48" rJ �09„
NOTES:
PAGE:2
H•VA►C A!R APPARATUS
TEST I�EPORT
PROJECT:BLUE M4QSE PIZZA ARRABELLE UNIT: D'!-05
AIR HANDLER UNtT DATA MOTOR NAMEPLATE DATA
MANUFACTURER IEC MANUFACTURER BALDC>R
MC)DEL HBC2000051648 HP R.P.M. 1 i 725
SERiAL 969455-50-3 PHASE FRAME 1 56/56H
FAN TYPE CEW7RIFUGAL S.F. TYPE 1.15 NG
RATING 1990 CFM VOLT3 AMPS 115/2'3p 13.4/6.7
THERMALLY PROTECTEO YES
STARTER DATA DRNE DATA
MANUFACTURER NONE MOTOR DRNE 1 VP 3_25"OD
MODEL MOTOR BORE 5/8"
SiZElTHERMAL NO. FAN DRNE i AK 54
RANGE FAN BQRE 314"
SET AT�AMPS) .�1TS 8 SLZE 1 �A28
REQ.THERMAL ROTAT10itl CORRECT
RATING(AMPS} DRNE CHANGE
AlRFlAW DATA TEST DATA INITIAL. F�NqL
SUPPLY CFM 2079 FAN R.P.M. 919
OSA CFM 0 VOLTAGE 121
RETURN CFM - 2079 q�pERq� 5$
ATMOS FtLTER COIL -Q.41" rJ 0.16"
NOTES:
PAGE:3
� H-VQG AIR APPARATUS
TEST REPURT
PROJECT:BLUE MOOSE PIZZA ARRABELLE UNIT: D1-13
AIR HANDL.ER UNlT DATA MOTOR NAMEPLATE DATA I
MANUFACTURER IEC MANUFACTURER BAt.D�R
MODEL HBC3400063261 HP R.P.M. 2 1725
SERIAL 199531-10-2 PHASE FRAME 3 56H
�AN TYPE CENTRIFUGAL S.F. iYPE 1.15 NG
RATING 3100 CFM VOLTS AMPS 208-23U/46fl 6.2-f�.0/3.0
THERlIAALLY PROTECTED YES
STARTER DATA DRIVE DATA �
MANU�ACTURER NONE MOTOR ORNE 1 VP 4.A"OD �
MODEL MOTOR BORE 518" �
SIZE/THERNIAL NO. FAN DRIVE 1 FP 5.U"OD
RaNGE FAN BORE 1"
SET AT tAMPSj .BELTS 8 S2E 1 �A32
REQ.THERMAI. ROTATION CORRECT
RATfNG{AMPSj DRIVE CH/�NGE
AiRFLt7W DATA TEST DATA INITIAL FlIVqL
SUPPLY CFM 3157 FAN R.P.M. 1380
OSA CFM Q VOLTAGE 483-485-482
RETURN CFM 3157 AMpERpGE 2.� _2_� _�.g
ATMOS FILTER COIL -0.33" fJ 0.07"
NOTES:
PAGE:4
. H-VAG AIR TERMINAL
TEST REPORT
PR4JECT: B�uE M4osE P¢zA-�R�� SYSTEM: FCU pi-��,as,os
SYSTEM TERMINAL DESIGN INiT1AL FlNAL NOTES
NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM
D1-01 1 CD 24x24 4pp 4g7
2 CD 24XZ4 4pp ,�p
3 CD 24X24 200 p�
�� 1076 TOTAL
D7-03 1 SL 48x6 254 257
2 SL 4sxs 250 --- ��
3 SL 48x6 250 Zg0
4 �- �� 2� 253
5 SL 48x6 250 260
6 SL 48x6 250 261
� s� asxs zsa 2s4
8 SL 48x6 250 251
� 2�47 TOTAL
D1-05 1 CD 24�Q4 7p 82
2 GD 24X24 40Q q.'p
3 CO 24x24 400 414
4 CD 24x24 40Q 423
5 CD 24x24 gp 94
6 CD 24X24 23p �g
7 CD 24x24 4pp q,1?
�'� 2479 TOTAL
N4TES
PAGE:�¢,�'
�H-VAC AiR TERMINAL
TEST REPI�RT
PROJECT: eu�MoosE P�a-aRRd��� F SYSTEM: FCU D1 13
SYSTEM TERMINAL DESIGN INiT1AL FtNAL NOTE�3�
ND TYPE SIZE AK VEL CFM VEL CFM VEl CFM
D1-13 ! SL 48x8 25Q 28p '
�
2 SL 48�c6 250 �7
3 SL 48x6 250 259
4 SL 48x6 250 �,5p
5 SL 48x6 175 180 '�
6 SL 48x6 175 173 —
7 SL 48x6 175 173 �
8 SL 48x6 175 178
9 SL 48x6 175 180 I
i
10 SL 48x6 175 185
�
11 SL 48x6 175 172 ;
12 S� 48x6 175 164 ,'
13 SL 48x6 175 173 i
� 14 SL 48�t6 9 75 184 l
15 Sl 48x6 175 189 �
16 SL 48x6 175 �gg
3140 3157 TQTAL '
�
�-�� OPEN 10x10 .69 797 5�0 811 559 '
�
(
. II�_. . _�
NOTES
PAGE:�6
TOWN OF VAIL DEPARTMENT OF COMMUNITY DEVELOPMENT
75 S. FRONTAGE ROAD
VAIL, CO 81657
970-479-2138
NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
PLUMBING PERMIT Permit #: P07-0169
Job Address: 675 LIONSHEAD PL VAIL Status . . . : ISSUED
Location.....: ARRABELLE HOTEL Applied . . : 10/02/2007
Parcel No...: 210106325001 Issued . . . 10/04/2007
Legal Description: Expires . .: 04/O1/2008
Project No :
OWNER ARRABELLE AT VAIL SQUARE LLC10/02/2007
PO BOX 7
VAIL
CO 81658
APPLICANT COMMERCIAL DESIGN ENGINEERINIO/02/2007 Phone: 970-245-0595
PO BOX 2440
COLORADO SPRINGS
CO 80901
License: 228-P
CONTRACTOR COMMERCIAL DESIGN ENGINEERINIO/02/2007 Phone: 970-245-0595
PO BOX 2440
COLORADO SPRINGS
CO 80901
License: 228-P
Desciption: BLUE MOOSE AT ARRABELLE TENANT FINISH
Valuation: $9,500.00
Fireplace lnformation:Restricted:?? #of Gas Appliances: ?? #of Gas Logs: ?? #of Wood Pallet: ??
*�***t*****+s****sr+*t***►*strvrt**t+*�*t***►++****�+**t*+r**+******* FEE S UMMARY **********�+****+*+******************+�******ar*******t***�*
Plumbing---> $150.0 0 Restuarant Plan Review--> $o.o o Total Calculated Fees---> $191.5 0
Plan Check---> $3 7.5 0 TOTAL FEES--------------> $191.5 0 Additional Fees-----------> $o.o 0
Investigation-> $o.o o Total Permit Fee----------> $191.5 0
Will Call-----> $4.oo Payments-------------------> $191.50
BALANCE DUE---------> $o.o 0
*r****a*s+****+*******************+*******�*****s�s********►**+�***+*�****�aa***�**���*�a***�:+***���**�:���*�►+��*►�**+«a*�*s*****+►**��+�r**+*r*
Item: 05100 BUILDING DEPARTMENT
10/02/2007 cgunion Action: AP
Item: 05600 FIRE DEPARTMENT
CONDITION OF APPROVAL
Cond: 12
(BLDG. ) : FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANC'E.
+�,:*...*.*.�**+***.*�*******�..*■*►��.*�++.*.�:++•+:�++.*.�.*�*+»*■��.*.��.+«*.*��.■***********�***********x**�*******.***.*.*■*.*****�..*.***..�
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan,
and state that all the information as required is correct. I agree to comply with the information and plot plan,to comply with all
Town ordinances and state laws, and to build this structure according to the towns zoning and subdivision codes, design review
approved, International Building and Residential Codes and other ordin nces of the Town applicable thereto.
REQUESTS FOR INSPECTION SHALL BE MADE TWENTY-FOUR HOURS IN ADV BY ELEPH A 79-2149 R AT'OUR OFFICE FROM 8:00 AM-4 PM.
SIGNAT RE OF OWNER OR CONTRACTOR FOR HIMSELF AND OWNER
****************************************************************************+***�***********
TOWN OF VAIL, COLORADO Statement
********�*******++*************************************************************************�
Statement Number: R070002078 Amount: $191.50 10/04/200708:17 :�M
Payment Method: Check Init: DDG
Notation: Commercial
Design Engineering 095470
-----------------------------------------------------------------------------
Permit No: P07-0169 Type: PLUMBING PERMIT
Parcel No: 2101-063-2500-1
Site Address: 675 LIONSHEAD PL VAIL
Location: ARRABELLE HOTEL
Total Fees: $191.50
This Payment: $191.50 Total ALL Pmts: $191.50
Balance: $0.00
***********�*****************************************************+*+************�k***********
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------------- ------------------------------ ------------
PF 00100003112300 PLAN CHECK FEES 37.50
PP 00100003111100 PLUMBING PERMIT FEES 150.00
WC 00100003112800 WILL CALL INSPECTION FEE 4.00
---------------------------------------------------------------- -------------
10/O1/2007 11:35 FA1 9702451015 �005/006
APPLICATION WILL NOT BE ACCEPTED IF INCOMPLETE OR UNS����6�
Project#:
Building Permit#:
� �" � Plumbing Permit#:
�'�'��`�' ' • 970-479-2149 (Inspections)
75 S. Frontage Rd.
Vail,Colorado 81657
TOWN OF VAIL PLUMBING PERMIT APPLICATION
q •
CONTRACTOR INFORMATION
Plumbing Contractor: Town of Vail R No.: Contact Person and Phone#'s:
� ' � ' 22� � �c�r �vbGu�.s �i9 �5/92-788�
E-Mail Address: '� ���Q Fax#:
Contractor Signature:
COMPLETE VALUATION FOR PLUMBING PERMIT(Labor&Materials)
PLUMBING: � 950�
Contac�t Ea /e Coun Assessors O�ce at 970 328 8640 or visit yvww ea /e-coun .com for Parc�e/#
Parce) # 2 �O�p� S O
Job Name:� Job Address: -
I hc luc�1on�� (o�5 L.ic�Sh� P,(ac� ��I3
Legal Description Lot: Block: Filing: Subdivision:
Owners Name: `� Address�?5� �/ '� � Phone'99a 3Z
Engineer: Address: Phone:
Detailed description of work:
�l nitSh
Work Class: New ( ) Addition( ) Alteration(X) Repair( ) Other( )
Type of Bldg.: Single-family( ) Duplex( ) Multi-family( ) Commerdal(�y Restaurant( ) Other( )
No.of Existing Dwelling Units in this building: No.of Accommodation Units in this building:
�**********�****�,��x***fi**************,�FOR OFFICE USE ONLY**�*********,�*��*******�****�*x******
......- - _ ,.:..... ..,.. ..:: .:.::.:
O�Iie;��F�e�s.:=::_:�;.: �:::;:::::;::_;.::�::s:::::;:.Da�e�Re±�eivei�::.:;:::::::;�:::=::::'::.'::;.:.:-
.. .
�C'c�!_. ......;;B-:"::>=�::::.::::.:::.``;';°,;;:;. ":..`:::;
I� � � � � �
D �
��;� o � 2007
F:�cdev\FORMS\PERMITS\Building\plumbing_permit_11-23-2005.dot Page 1 of 1 il/23/2005
TOWN OF VAIL
«......r
04-23-2008 Inspection Request Reporting / Page 15
4:10 pm Vail, CO - Ci�Of ���'U��'f'
Requested Inspect Date: Thursday,April 24, 2008
Inspection Area: CG
Site Address: 675 LIONSHEAD PL VAIL
ARRABELLE HOTEL
A/P/D Information
Activity: 607-0260 Type: A-COMM Sub Type: ACOM Status: ISSUED
Const Type: Occu�pancy: see plan Use: I-B Insp Area: CG
Owner: ARRABELLE AT VAIL SQUARE LLC
Contractor: TCD, INC. Phone: (970)453-3959
Description: TENANT FINISH WORK FOR THE BLUE MOOSE AT ARRABELLE
Requested Inspection(s) � �/l �� _O �
�,�F- �
Item: 540 BLDG-Final C/O Requested Tf'me: 04:0 PM
Requestor: TCD, INC. --JIM Phone: (970)453-3959
Comments: FINAL MECH/FINAL CO UNIT P111;REQUESTS 1 PM INSPECTION-HAS TO ARRANGE FOR
R EST. OP EN�970-445-7245
Assigned To: JMONDRAG�N Entered By: SBELLM K
Action: Time Exp:
�L/� 1� / i!'�Z%��
�
�-� �.� .U°�--�
,�v� �Z- z -� -a �
/ � �'��
�
Inspection Historv
Item: 501 PW-Temp.access/draina e
Item: 10 BLDG-Footings/Steel+ U�R grd
Item: 20 BLDG-Foundation/Steel
Item: 30 BLDG-Framing ""Approved""
10/19/07 Inspector: dplace Action: PA PARTIAL APPROVAL
Comment: blue moose-ok to drywall walls.
placed a hold on short wall w-3 for elec. inspection and bathroom w-5 for sound insulation.
11/15/07 Inspector: GCD Action: COND APPROVED/CONDITIONS
Comment:
12/14/07 Inspector: GCD Action: AP APPROVED
Comment:
Item: 50 BLDG-Insulation
Item: 60 BLDG-Sheetrock Nail **Approved"*
10/31/07 Inspector: dplace Action: APCR APPROVED/CORRECTION REQD
Comment: nail cdx backing so FRP can be applied.
11/21/07 Inspector: GCD Action: AP APPROVED
Comment:
Item: 70 BLDG-Misc.
Item: 90 BLDG-Final "*App roved""
12/20/07 Inspector: GCD Action: PA PARTIAL APPROVAL
Comment: OK FOR TCO
1.RAMP THREASHOLD AT MAIN ENTRY
2.PANIC HARDWARE REQD AT SECONDARY EXIT
3.PLUMBING CORRECTIONS APPR
Item: 532 PW-TEMP. C/O
Item: 533 PLAN-TEMP. C/O
Item: 530 BLDG-Temp. C/O `"Approved"`
12/20/07 Inspector: GCD Action: AP APPROVED
Comment:
Item: 539 PW-FINAL C/O
Item: 537 PLAN-FINAL C/O
REPT131 Run Id: 7906
� _ .
04-24-2008 Inspection Request Reporting Page 1
1:14 pm Vail, CO - Citv Of
Requested Inspect Date: Thursday,April 24, 2008
Assigned To: CGUNION
Inspection Type: MECH
Inspection Area: CG
Site Address: 675 LIONSHEAD PL VAIL
ARRABELLE HOTEL
A/P/D Information
Activity: M07-0256 Type: B-MECH Sub Type: NCOM Status: ISSUED
Const Type: Occu�pancy: Use: Insp Area: CG
Owner: ARRABELLE AT VAIL SQUARE LLC
Contractor: COMMERCIAL DESIGN ENGINEERING LTD Phone: 970-245-0595
Description: BLUE MOOSE AT ARRABELLE TENANT FINISH
Requested Inspection(s) /� /� '� L�-/�` �
C./ ( � o`_"
Item: 390 MECH-Final Requested Time: 11:30 AM
Requestor: COMMERCIAL DESIGN ENGINEERING LTD Phone: 970-245-0595
Assigned To: CGUNION Entered By: DGOLDEN K
Action: Time Exp:
Comment: CTIONS FOR WR . L ACCESS DOOR COVERS PFR INSTRUCTIONS.
Comment: canceled by contractor
Comment: 1.HOOD ABOVE CEILING REQD TO BE COVERED WITH DUCT WRAP.
2.LOCATE AND LABEL CLEANOUT AND LOW POINT ON CEILING.
3.PRELIMINARY BALANCE REPORT RECEIVED.
CAPTURE TEST APPR.
• �
Inspection Historv
Item: 200 MECH-Rough ""Approved""
11/07/OT Inspector: GCD Action: CR CORRECTION REQUIRED
Comment: 1.ADD 6"SUPPLY IN OFFICE AND RETURN OR DOOR UNDERCUT.
2.SUPPLY NEAR DISHWASHER REQD TO BE SEALED AND INSULATED.
GREASE DUCT CONNECTION TO HOOD AND AND MUA REQD
OSA AND MUA SUPPLY AND RETURN FOR FCU APPR.
11/20/07 Insp ector: GCD Action: PA PARTIAL APPROVAL
Comment: LIGHT TEST FOR GREAS DUCT CONNECTION TO HOOD.
Item: 310 MECH-Heating
Item: 315 PLMB-Gas Piping ""Approved""
11/02/07 lnspector: GCD Action: AP APPROVED
Comment: 27psi TEST
Item: 320 MECH-Exhaust Hoods
Item: 330 MECH-Supply Air "Approved"*
10/16/07 Inspector: dpsafe Action: PA PARTIAL APPROVAL
Comment: 4 feeds from four fan coils.
Item: 340 MECH-Misc. "`Approved*"
10/18/07 Inspector: SB Action: AP APPROVED
Comment: GREASE DUCK COMPLETE--LIGHT TEST APPROVED
11/20/07 Inspector: GCD Action: AP APPROVED
Comment: SEE ROUGH
Item: 390 MECH-Final ""A�pproved"'
11/30/07 Inspector: GCD Action: CR CORRECTION REQUIRED
REPT131 Run Id: 7910