Loading...
HomeMy WebLinkAboutVail Village Filing 7 Block 1 Lot A B C Unit 330.PDF , . Revised by Zehren and Associates Apnl 8,2008 . BUILDING DEPARTMENT COMMENTS: 1 The memorandum of understandmg dated October 16, 2006 indicates the existing floor/ceiling � assemblies do not meet a one hour assembly Based on the extent of these re-models the existing floor/ceiling assemblies are required to meet one hour requirements Provide a listed one hour floor ceiling assembly that these floor/cedmgs will be constructed to (IBC Table 601 and 711 3) Ali of the units except for unit 145 will not require ceiling replacement Unit 145 is adding significant lighting that will require the maJority of that ceiling to be removed The ceiling will be replaced utilizing detail B/2 607 (attached) All other units wili oniy require minor cutting and patching to fish wire or ductwork Trenching for sprinkler and alarm runs will also be utilized so as not to require significant ceiling work Units that previously were top floor in the existing buiidings do not require ceiling replacement because their ceilings are not fire rated The fire separation occurs at the new structural floor for the new units above thereby making the existing roof act as a suspended non-rated ceiling 2 Provide ceilmg radiation dampers at all the new bath fan penetrations of the rated floor/ceiling assembly The exception quoted on the plans does not apply to the situation presented (IBC 716 6 2) Please reference the revised plans Exhaust fans with integral louvers shall be provided for all existing units except for those at what was the previous top level (below the new structural floor for the new units) Since the fire separation occurs at this new structural floor and the existing building old roof structure now acts as only a non rated drop ceiling, duct runs, fans and lights into this ceiling need not be rated and openings need not be protected 3 Provide a method of protecting the floor/ceiling membrane at the incandescent lights (IBC 712 4 2) Please reference the revised plans Lights shall be protected with 1-hour drywall enclosures in the same fashion that the new units are currently being protected and using the same detail 4 Provide fire-stopping details for the new tub drains, plumbing pipes and electrical wiring (IBC 712 4 2) The items mentioned and any other observed penetrations shall be protected and firestopped per specification section 07841 (attached) of the Manor Vail specification and by a qualified installer 5 Show location of all dryer vents on the drawings Some are entirely new, some are re-routed and some are remaining the same (IMC 504 6 2) Please reference the revised plans Dryer vent routing is shown for units with existing or new dryers 6 Provide 100 square inches of make-up air for the dryers in the closets (IMC 504 5) Please reference the revised plans Doors to closets or rooms housing dryers shall be replaced with doors containing a 100 square inch louver Please refer to the cover sheet for information and instructions for resubmitting plans. In order to avoid delays please check all requested information is included with the resubmitted plans. Plan Review Comments Contact Person• John Plano Plans Examiner/Senior Plans Examiner SAFEbuilt , lohn.planoCcilsafebuilt.com Page 2 of 2 SAFEbuilt Colorado Eagle Office✓P O Box 1618✓ 1286 Chambers Avenue,Unit 101 ✓Eagle,Colorado 81631 Phone (970)328-1790✓Toll Free (877)428-6412✓Fax (970)328-1791✓Z\2007\071776\III Permrts&Approvals\080317 TOV Review Comments doc ' 2" GONC tOPPINCz • SLAB ��2" MIN lUD � SHEATHINCs �XIS71NCs SOLID UJD • �XIS71NCs JOISTS CROSS BRIDCzINC� MIN 1X3 OR 2Xlm BLOGKINC�s ��z" RESILIENT CHANEL � 2 L�41'�RS �i2" FIRE � RAT�D Csl'P REF UL ASS�MBLI' �OR RE� UL ,4SSEMBLI' � FOR A�'PLIGAtION ADDITION,4L CONStRUCTION N07ES FULL D�PTH N�� INSULATION WHER� IND ICATED ON RGP � C� IL INC� ,4SS�1„rBL� T1'fi�� C��4 3" = 1'-m�� 2" CONC 70PPINCz SLAB ��z" MIN UJD � SH�ATHINCs EXISTINCs OP�N WEB WD JOISTS �XISTINCz NOT�: I� OPEN, PROVID� UPRICxHT � SPRINKLER H�,4DS a INTO THE SPAGE N p R�F. �LS N 0 DOGUMENTS 1/I F. °, ��z" RESILIENT � CNAN�L � . � 2 L,41'�RS ��z�� FIRE r R4TED C�YP R�� � UL ASS�MBLY FOR � RE� UL ,4SSEMBLI' L518 FOR APPLICATION s „ ADDITION,4L GONSTRUGTION NOTES FULL D�PTH � N��,J INSULATION UJI�ER� ° INDIGAT�D ON RGP � � C� IL INC� �4SS�1"f�L� T�P� C�1� � 3�� = 1'-m�� 0 E Z E H � E N PROJEGT NAME PROJEGT NO 1588 DRAWN B7 o AND ASSOCIATES, INC. 1"I�4NOR V�41L CONDOMINIUMS SSUE 280 BY � ARCHITECTURE•PLANNING•INTERIORS Vcl I I, CO I OPd G�O � P O Box 1976-Avon,Colora�o 81620 DRAWING TITLE SHE�T��� � (970)949-0257 FAX(970)949-1080 CEILINCs ASSEMBLI' T`fPE C� � 233 E Canon Perdi�Eo St-Santa Barbara,CA 93101 SGALE 3" = I'-0" DATE 9/18/0� g (605)963-6890 FAX(805)963-8102 n�l ' Nutone Model RDA - J-CAN HOUSING W/RADIATION DMPR-Radiation Dampers Page 1 of 2 Search Srte �'t' • - - Model# �—� BROWSE BY CATEGORIES HOME ABOUT US CUSTOMER SERVICE DEALER LOCATOR SHOP fOR PARTS CONTACT US BATH FANS Fans ]-CAN HOUSING � r�r,ceHOOOS ^ Rad�ation Dampers W/RADIATION DMPR CEILINGFANS ~�~��^��xVwM� ------- __..e.____ _ Model RDA CENTRALVACUUM SYSTEMS - � � � Housngs and flnishes(motor assembly and DECORATIVE BACKSVLASHES THV�� I',��, gnlle)sold separately in unrts of four per l-. '.,, �,� - - carton-purchase housings for rough-in and 000e cHintes � �`__ _____ __ ,�t , k�.,t � - blower assembhes/grdles later for finishing HEATERS �� µW ~� � � �'. ' � � �° = • UL classified(UL standard SSSC)for use in 1- ; - s ,�� � %" �;;' ,2-,or 3-hour fire-rated floor-ceiling and iN�oortntRQunurr ��v �� T'��yy4�, � ,���' roof-ceilfng designs i' *c�,� INTERCOM SYSTEMS �f� N�_ry < < '` `� ''`� �' . • Warnock Hersey Listing allows use in r ��- iROniHC ceHreRS �� m'��r�-�` �.;:;•� "�,y - j combustible cedings wdh ducted fans ' �f a�°' t,i'r:;., � - � • High temperature,non-asbestos,reinforced MEDICINECABINETS��PV�µ.YY�. *�v -�'••js':'� .'t� �* k � ysf��r�'���. � � fiberthermal fabric SECURITYCABINETS �~� r 1J'l,'� .,, _ - _� i �����s�.r.;.r� , • Galvanized steel frame TRASH COMPACTORS A_`�_ � �'f�� ' ' _t • 165°F fusble link WHOLE HOUSE AUDIO � '� • Stamless steel ne gator-t y pe closure sprin g � _w 4 ..,� • Available from 50 CFM to S10 CFM NSTOMER RESOURCES `-�=�--_. .__ _ _ �.__�__�.k..._._y • Radiation damper comes attached to housing "' `�"' Spec�ficat�on Sheet• . Registeryonr 4� elower assembly will fit into housing without Nu7pnepraduct ��f �`+ the removal of the radiation damper-one �,n11r�kaday?�} ��=��� "°� less step m mstallation process ���� � NOTE Specification Sheets and Installation MBn IoC01 COdeS r2 uire that exhaust fans NuTr�ne• � " Guldes are provided In Adobe Atrobat Y q �,� �� (Pdq rormat Chck here to download mstalled in fire-reted ceihngs must be protected ���ags � ndobe Acrobat for�ree by dampers,which,m case of fire,protect avadab}e for��� �� agamst the spread of heat and flame downioad �� �.'�.� Being fire-rated means the abdity of a wall, floor/ceiling,or roof/ceiling to withstand the effects of fire for a specified period of time � ,r � NuTone ceihng radiation dampers are desgned i : �° to protect the openmgs in 1-,2-,or 3-hour fire- .. �._.:. . k'�:,p� rated Floor-ceding and roof-ceihng desfgns Broam�NuTone I�nuo�duces� Nev+r'Corpo�ratelJlerchandise Program When the temperature of the air pass(ng through � � the damper exceeds 165°F,the fusible link meits > Readyur Faqs and the thermal fabnc across the damper cioses > Locate a serv_ice Center automatically to�nterrupt the airflow by > upcommg_events&shows becommg a flame and heat barner,prevenUng rapid spread of fire to other areas NuTone NEWS ,� NuTone Ultra Silent Fan Contact your local dealer for pncmg Commeraal mformatwn on all NuTone products except � NuTone now offers 2D&3D range hoods files for_desyners ' Ultra Sil_ent""Series Qwetest Additional Models Avadable. Fans Now Feature Nevq Gnlles RDA J CAN HOUSING W/RADIATION DMPR � Powerful NuTone�Centr_al 80RDB BOCFM BLOWER W/METALGRILLE VdCUUm P_rOyideS Deep- 110RD6 110CFM BLOWER W/METAL GRILLE Cleanin�Power HDSORDB HEAVY DUN SOCFM BLOWER W/METAL GRL � Upcoming Events&Trade HD80RD8 HEAVY DUN 80CFM BLOWER W/METAL GRL Shows � News and Events Archive PARTS ASSISTANT >Part#K5509000 Non Duct IndicatingFilter Used on models LL6200 Series(All) RL6200 Series(Before 2000) SL6200 Series(Befare 2000) LL62F(Replacement For Thls Filter Model Number) >Part#$9852000 Grille_&LQns Asse_m_b� Used on models 660 Series,665 Series,668 In U S A Call 3ES 336 3?4S Pnvacy Technical Support SS3 33E 6151 In Canada Call S°&S62 7626 c 2007 Broan NuTOne LLC Customer Service S£9-336 3948 , VISIC nutone ca Contact us http://www.nutone com/product-detail asp�ProductID=10698 4/2/2008 N uTo n e� Architectural & Engineering Specifications July 2005 • DESCRIPTION Ve n t i I at i n g Fa n s HOUSING , • Rugged,26-gauge galvanized steel construction W;t h R a d i at i o n • Key-holed mounting brackets span up to 24"and are ad�ustable horizontally and vertically • Reversible knockout bracket allows wiring from top or side Da m pe rs • 4"round duct fitting with budt-in backdraft damper for easy duct connection BLOWER • Plug-in,permanently lubricated motor MODEL • Totally enclosed motor with long life bearings designed for RDA r.,:p, ;` continuous operation(HD80RD6, HD50RD6 only) ;, • Centrifugal blowerwheel -�d���e'- RADIATION DAMPER ,:�i ' • For use in 1, 2 and 3 hour rated floor-ceihng and roof-ceding o "° : ' �`iy' RDB constructions r'r;�;;��'�''� ��\ MODELS • Galvanized steel frame ���� � � • High temperature,non-asbestos,remforced fiber thermal fabric ���,�,°o0 • Stainless steel closure sprmgs ���° ��Po�� � � • 165°F fusible Imk �������°�,� GRILLE ° �� • Attractive steel grille painted white • Low profile blends well with any decor INSTALLATION (1)ROUGH-IN KIT&(1)FINISH KIT MAKE A Complete installation mstructions are included with each Ventdating COMPLETE UN/T.PURCHASE EACH SEPARATELY. Fan Kit Rough-In Kit Model RDA•Contains housmg and radiation damper ARCHITECT'S SPECIFICATION (packed 4 per carton) Ventdator with Radiation Damper shall be NuTone Model RDA Finish Kits with 110RDB(RDA with 80RDB)(RDA with HD80RDB)(RDA with Models 110RDB,80RDB, HDSORDB and HD50RD6• HD50RDB) Contain blower and grdle(packed 4 per carton) Housing shall be made of galvanized steel and have ad�ustable mountmg brackets It shall have a built-in backdraft damper and be ducted to a roof or wall cap SPECIFICATIONS Blower shall be removable and have a centrifugal blower wheel Motor shall be permanently lubricated RDA with VOLTS AMPS CFM SONES DUCT Air delivery shall be no less than and sound level shall be no 110RDB 120 1 3 110 4 0 4" greater than values listed in the chart to the left Air and sound ROUND ratings shall be certified by HVI 80RD6 120 0 5 80 2 5 4" Radiation damper shall be rated for use in up to three hour ceiling ROUND constructions It shall be UL Classified and Warnock Hersey Listed (see other side for installation details) HD8oRD6 120 0 5 80 2 5 ROUND 0 � � . CLASSIFIED Warnock Hersey . HD50RDB 120 0 4 50 1 5 4" �V' /� �` US ."�' � ROUND CERTIFIED u � WARNOCKHERSEYLISTED NuTone,Inc.,4820 Red Bank Road,Cincinnati,Ohio 45227(1-800-543-8687) REFERENCE QTY REMARKS Pro�ect Location Architect Engineer Contractor Submitted by Date 99043057C Ventilating Fans N uTone� W�th Radiation Dampers ' 8 $4 � / oa � 8� 3 %� %� �� 3 8 � � �i s �� �/ �i �- �o� �L Warnock Herse WARNOCK HERSEY LISTING y INCLUDES DAMPER ONLY IT CLASSIFIED SEE DETAILS ON UL DOES NOT INCLUDE EXHAUST CLASSIFICATION � FAN DAMPERS MAY BE USED u MARKING ON F�� WITH UL LISTED FAN MODELS C � L US PRODUCT WpRNOCKHERSEYLISTED NOTED 16"OR 24"ON CENTER �WIRE MOUNTING BRACKET FASTENER FAN FAN � ------� �---- DAMPER MOUNTING • BRACKET DAMPER I - I- - - - -- I � CEILING WOOD � GRILLE FRAMING ' � CEILING GRILLE MEMBER GRILLE SCREW SCREW OR JOIST GRILLE MANOR VAIL CONDOMINIUMS Pro�ect No 1588 00 Vail,Colorado • SECTION 07841 -THROUGH-PENETRATION FIRESTOP SYSTEMS • PART 1 - GENERAL 1 1 RELATED DOCUMENTS A. Drawmgs and general provisions of the Contract, mcludmg General and Supplementary Condrtions and Division 1 Specification Sections,apply to this Section. 12 SUMMARY A This Section mcludes through-penetration firestop systems for penetrations through fire- resistance-rated constructions, mcluding both empty openmgs and openmgs contammg penetratmg items 1 Floors 2 Roofs 3 Walls and partitions 4 Smoke barriers 5 Construction enclosmg compartmentahzed areas B Related Sechons mclude the followmg• 1 Division 7 Section"Fire-Resistive Jomt Systems " 2. Division 13 Sections specifymg fire-suppression pipmg penetrations 3. Division 15 Sections specifymg duct and pipmg penetrations 4. Division 16 Sections specifymg cable and conduit penetrations 1.3 PERFORMANCE REQUIREMENTS A. General For penetrations through the followmg fire-resistance-rated constructions, includmg both empty openmgs and openmgs contammg penetratmg rtems, provide through-penetration firestop systems that are produced and installed to resist spread of fire accordmg to requirements mdicated, resist passage of smoke and other gases, and mamtam origmal fire- resistance ratmg of construction penetrated. 1 Fire-resistance-rated walls mcluding firewalls, fire partrtions, fire barriers, and smoke barriers 2. Fire-resistance-rated honzontal assemblies mcludmg floors, floor/ceihng assembhes and ceilmg membranes of roof/ceiling assemblies B. Rated Systems• Provide through-penetration firestop systems wrth the followmg ratmgs determmed per ASTM E 814: THROUGH-PENETR.ATION FIRESTOP SYSTEMS 07841 - 1 MANOR VAIL CONDOMINIUMS Pro�ect No. 1588 00 Vail, Colorado 1 F-Rated Systems Provide through-penetration firestop systems with F-ratmgs mdicated, but not less than that equalmg or exceedmg fire-resistance ratmg of constructions penetrated 2 T-Rated Systems Far the followmg condrtions, provide through-penetration firestop systems wrth T-ratmgs mdicated, as well as F-ratmgs, where systems protect penetratmg items exposed to potential contact with ad�acent materials m occupiable floor areas a Penetrations located outside wall cavities b Penetrations located outside fire-resistance-rated shaft enclosures C For through-penetration firestop systems exposed to view, traffic, moisture, and physical damage,provide products that, after curing, do not deteriorate when exposed to these condrtions both durmg and after construchon l. For pipmg penetrations far plumbmg and wet-pipe sprinkler systems, provide moisture- resistant through-penetration firestop systems 2 For floor penetrahons wrth annular spaces exceedmg 4 �nches (]00 mm) in width and exposed to possible loading and traffic, provide firestop systems capable of supporting floor loads mvolved,either by mstallmg floor plates or by other means 3 Far penetrations mvolvmg msulated piping, provide through-penetration firestop systems not requirmg removal of msulation D For through-penetration firestop systems exposed to view, provide products with flame-spread and smoke-developed indexes of less than 25 and 450, respectively, as determined per ASTM E 84 1.4 SUBMITTALS A. Product Data For each type of product indicated B Shop Drawmgs For each through-penetration firestop system, show each type of construction condrtion penetrated, relationships to ad�ommg construchon, and type of penetratmg rtem. Include firestop design designation of quahfied testmg and mspectmg agency that evidences comphance with requirements for each condrtion mdicated 1 Submit documentahon, mcludmg illustrations, from a quahfied testmg and mspectmg agency that is applicable to each through-penetration firestop system configuration for construchon and penetratmg rtems. 2 Where Pro�ect condrtions require modification to a quahfied testmg and mspectmg agency's illustration far a particular through-penetrahon firestop condrtion, submit illustration, wrth modifications marked, approved by through-penetration firestop system manufacturer's fire-protection engmeer as an engmeermg �udgment or equivalent fire- resistance-rated assembly C Quahfication Data• For Installer • D Product Certificates. For through-penetration firestop system products, signed by product manufacturer THROUGH-PENETRATION FIRESTOP SYSTEMS 07841 -2 MANOR VAIL CONDOMINIUMS Pro�ect No 1588 00 Vail, Colorado E Product Test Reports From a qualified testmg agency mdicatmg through-penetration firestop ' system comphes wrth requirements,based on comprehensive teshng of current products. ' 1.5 QUALITY ASSURANCE A Installer Quahfications A firm experienced m mstalhng through-penetration firestop systems similar m material, design,and extent to that mdicated for this Pro�ect,whose work has resulted m construction with a record of successful performance B Installation Responsibility Assign mstallation of through-penetration firestop systems m Pro�ect to a smgle qualified mstaller. C. Source Limitations• Obtam through-penetration firestop systems, for each kmd of penetration and construction condition indicated,through one source from a smgle manufacturer D Fire-Test-Response Characteristics Provide through-penetration firestop systems that comply wrth the followmg requirements and those specified in Part 1 "Performance Requirements" Article 1. Firestopping tests are performed by a qualified testmg and mspecting agency. A qualified testmg and mspectmg agency is UL, or another agency performmg testmg and follow-up inspection services for firestop systems acceptable to authorities havmg �urisdiction 2 Through-penetration firestop systems are identical to those tested per testing standard referenced m "Part 1 Performance Requirements" Article. Provide rated systems complymg wrth the followmg requirements a Through-penetrahon firestop system products bear classificahon markmg of quahfied testmg and mspectmg agency b. Through-penetration firestop systems correspond to those mdicated by reference to through-penetration firestop system designations listed by the following. 1) UL m its "Fire Resistance Directory " E. Premstallation Conference Conduct conference at Pro�ect site to comply with requirements m Division 1 Section"Pro�ect Management and Coordination" F Installer Trammg Individuals performmg the mstallation of firestop systems shall be tramed by a direct representative of the firestop materials manufacturer,not a distributor or agent. 1 6 DELIVERY, STORAGE,AND HANDLING A Dehver through-penetration firestop system products to Pro�ect srte m origmal, unopened contamers or packages with mtact and legible manufacturers' labels identifymg product and manufacturer, date of manufacture, lot number, shelf life if apphcable, qualified testmg and . mspectmg agency's classificahon marking applicable to Pro�ect, curmg hme, and mixmg instructions for multicomponent materials THROUGH-PENETRATION FIRESTOP SYSTEMS 07841 -3 MANOR VAIL CONDOMINIUMS Pro�ect No 1588 00 Vail, Colorado B. Store and handle materials for through-penetration firestop systems to prevent their • deterioration or damage due to moisture,temperature changes,contammants,or other causes 1 7 PROJECT CONDITIONS A Environmental Limitahons Do not mstall through-penetration firestop systems when ambient or substrate temperatures are outside limrts permitted by through-penetration firestop system manufacturers or when substrates are wet due to ram,frost,condensation,or other causes B Ventilate through-penetration firestop systems per manufacturer's wntten mstructions by natural means or,where this is madequate,forced-air circulation 1.8 COORDINATION A Coordmate construchon of opemngs and penetratmg items to ensure that through-penetration firestop systems are mstalled accordmg to specified requirements. B Coordmate size and location of cast-m-place firestop devices to accommodate planned pipe and cable runs Ensure proper placement of devices before placement of concrete C. Coordmate sizmg of sleeves, opemngs, core-drilled holes, or cut opemngs to accommodate through-penetration firestop systems D Nohfy Owner's inspechng agency at least seven days m advance of through-penetrahon firestop system mstallations, confirm dates and times on days preceding each series of mstallations E Do not cover up through-penetration firestop system mstallations that will become concealed behmd other construction until each mstallation has been exammed by Owner's inspectmg agency and buildmg mspector, if required by authorrties havmg�urisdiction PART 2-PRODUCTS 21 MANUFACTURERS A. Products Subject to comphance with requirements, provide one of the through-penetration firestop systems mdicated for each application that are produced by one of the followmg manufacturers. 1 Hilti,Inc 2 3M,Fire Protection Products Division 3 Tremco; Sealant/Weatherproofing Division 2 2 FIRESTOPPING,GENERAL A Compatibility Provide through-penetration firestop systems that are compatible with one another, wrth the substrates forming openmgs, and with the rtems, if any, penetratmg through- THROUGH-PENETRATION FIRESTOP SYSTEMS 07841 -4 MANOR VAIL CONDOMINIUMS Pro�ect No 1588 00 Vail, Colorado penetration firestop systems, under conditions of service and application, as demonstrated by ' through-penetration firestop system manufacturer based on testmg and field experience. B Accessories Provide components for each through-penetration firestop system that are needed � to mstall fill materials and to comply wrth Part 1 "Performance Requirements" Article Use only components specified by through-penetration firestop system manufacturer and approved by quahfied testmg and mspectmg agency for firestop systems mdicated. Accessones mclude, but are not hmrted to,the followmg items 1 Permanent formmg/dammmg/backing materials,mcludmg the followmg. a Slag-/rock-wool-fiber msulation b Sealants used m combmation with other formmg/dammmg/backing materials to prevent leakage of fill materials m liquid state. c. Fire-rated form board. d Fillers for sealants 2 Temporary formmg materials 3 Substrate primers 4 Collars. 5 Steel sleeves 2.3 FILL MATERIALS A. General Provide through-penetration firestop systems contammg the types of fill materials required by Authorities Havmg Jurisdiction and by referencmg the types of matenals described m this Article Fill materials are those referred to m directaries of referenced testing and mspectmg agencies as"fill," "void," or"cavrty" matenals B. Cast-in-Place Firestop Devices Factory-assembled devices for use m cast-m-place concrete floors and consistmg of an outer metalhc or plastic casmg hned with an mtumescent strip, a radial extended flange attached to one end of the sleeve for fastemng to concrete formwork, and a neoprene gasket C Latex Sealants• Single-component latex formulations that after cure do not re-emulsify during exposure to moisture D Firestop Devices Factory-assembled collars formed from galvamzed steel and hned wrth intumescent material sized to fit specific diameter of penetrant E. Intumescent Composite Sheets Rigid panels consistmg of alummum-foil-faced elastomenc sheet bonded to galvamzed steel sheet. F Intumescent Putties Nonhardemng dielectric, water-resistant putties contammg no solvents, morganic fibers,or silicone compounds , G Intumescent Wrap Strips. Smgle-component mtumescent elastomeric sheets wrth alummum foil on one side. THROUGH-PENETRATION FIRESTOP SYSTEMS 07841 -5 MANOR VAIL CONDOMINNMS Pro�ect No 1588 00 Vail, Colorado H Mortars Prepackaged dry mixes consistmg of a blend of inorgamc bmders, hydraulic cement, • fillers, and lightweight aggregate formulated for mixing wrth water at ProJect site to form a nonshrmkmg,homogeneous mortar ' I PillowsBags Reusable heat-expandmg pillows/bags consistmg of glass-fiber cloth cases filled wrth a combmation of mmeral-fiber, water-msoluble expansion agents, and fire-retardant additives J. Sihcone Foams Multicomponent, sihcone-based liquid elastomers that, when mixed, expand and cure in place to produce a flexible,nonshrmking foam. K. Silicone Sealants Smgle-component, silicone-based, neutral-curmg elastomeric sealants of grade mdicated below. 1 Grade Pourable (self-leveling) formulation for opemngs m floors and other horizontal surfaces, and nonsag formulation for openings in vertical and other surfaces requirmg a nonslumpmg, gunnable sealant, unless indicated firestop system limits use to nonsag grade for both opemng conditions 2 Grade for Horizontal Surfaces Pourable (self-levelmg) formulation for openmgs in floors and other horizontal surfaces 3 Grade for Vertical Surfaces Nonsag formulahon for openmgs m vertical and other surfaces L Intumescent Acrylic Sealant Firestop sealant that expands when exposed to heat Protects penetrations contammg combustible and non-combustible penetrants M Foam "sponge-like blocks Re-penetratable mtumescent blocks that may be friction fit, deformed,or cut to fit m through penetration opemngs 2 4 MIXING A. For those products requiring mixmg before application, comply wrth through-penetration firestop system manufacturer's wrrtten mstructions for accurate proportiomng of materials, water (if required), type of mixmg equipment, selection of mixer speeds, mixing containers, mixmg time, and other items or procedures needed to produce products of umform quahty wrth optimum performance characteristics for application mdicated. PART 3 -EXECUTION 31 EXAMINATION A Examme substrates and condrtions, wrth Installer present, for compliance wrth requirements for opemng configurations, penetratmg rtems, substrates, and other condrtions affectmg performance of work � 1 Proceed with installation only after unsatisfactory conditions have been corrected THROUGH-PENETRATION FIRESTOP SYSTEMS 07841 -6 MANOR VAIL CONDOMINIUMS ProJect No 1588 00 Vail, Colorado B Manufacturer's mtallation mstruchons shall be followed In situations where the requirements • of this section differ from those of the manufacturer, the more conservative requirements shall govern 3 2 PREPARATION A. Surface Cleamng Clean out opemngs immediately before mstallmg through-penetration firestop systems to comply with firestop system manufacturer's wrrtten instructions and with the followmg requirements 1 Remove from surfaces of openmg substrates and from penetratmg items foreign materials that could mterfere with adhesion of through-penetration firestop systems 2 Clean opemng substrates and penetrating rtems to produce clean, sound surfaces capable of developmg optimum bond wrth through-penetration firestop systems Remove loose particles remammg from cleanmg operation 3 Remove laitance and form-release agents from concrete B Pnmmg. Prime substrates where recommended m wrrtmg by through-penetration firestop system manufacturer usmg that manufacturer's recommended products and methods. Confine primers to areas of bond,do not allow spillage and migration onto exposed surfaces C Maskmg Tape Use maskmg tape to prevent through-penetration firestop systems from contactmg ad�oining surfaces that will remain exposed on completion of Work and that would otherwise be permanently stained or damaged by such contact or by cleamng methods used to remove smears from firestop system materials. Remove tape as soon as possible wrthout disturbmg firestop system's seal with substrates 3 3 THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLATION A General• Install through-penetration firestop systems to comply with Part 1 "Performance Requirements" Article and wrth firestop system manufacturer's written installation instructions and published drawmgs for products and applications mdicated B Install formmg/dammmg/backmg materials and other accessories of types required to support iiii materials during their application and in the position needed to produce cross-sectional shapes and depths required to achieve fire rahngs mdicated. 1. After mstallmg fill materials and allowmg them to fully cure, remove combustible formmg materials and other accessories not mdicated as permanent components of firestop systems C Install fill materials for firestop systems by proven techmques to produce the followmg results 1 Fill voids and cavrties farmed by openmgs, formmg materials, accessories, and penetratmg rtems as required to achieve fire-resistance ratmgs mdicated , 2 Apply materials so they contact and adhere to substrates formed by opemngs and penetratmg items 3 For fill materials that will remain exposed after completmg Work, fimsh to produce . smooth,umform surfaces that are flush wrth ad�ommg fimshes. THROUGH-PENETRATION FIRESTOP SYSTEMS 07841 -7 ' MANOR VAIL CONDOMINIUMS Project No 1588 00 Vail, Colorado 3 4 IDENTIFICATION A Identify through-penetration firestop systems with preprmted metal or plastic labels Attach labels permanently to surfaces ad�acent to and wrthm 6 inches (1�0 mm) of edge of the firestop ' systems so that labels will be visible to anyone seekmg to remove penetratmg rtems or firestop systems Use mechamcal fasteners for metal labels. For plastic labels, use self-adhermg type wrth adhesives capable of permanently bondmg labels to surfaces on which labels are placed and, in combmahon wrth label material, will result m partial destruction of label if removal is attempted Include the followmg mformation on labels. 1 The words "Warning - Through-Penetration Firestop System - Do Not Disturb Notify Buildmg Management of Any Damage " 2 Contractor's name, address, and phone number 3 Through-penetration firestop system designation of applicable testmg and inspectmg agency 4 Date of installation 5 Through-penetration firestop system manufacturer's name 6 Installer's name 3 5 FIELD QUALITY CONTROL A Inspectmg Agency Owner will engage a qualified, mdependent mspectmg agency to mspect through-penetration firestops Independent mspectmg agency shall comply with ASTM E 2174 requirements includmg those related to qualifications, conductmg mspections, and preparmg test reports. B Where deficiencies are found, repair or replace through-penetration firestop systems so they comply with requirements C Proceed with enclosing through-penetrahon firestop systems wrth other construction only after mspection reports are issued and firestop mstallations comply wrth requirements 3 6 CLEANING AND PROTECTING A Clean off excess fill materials ad�acent to opemngs as Work progresses by methods and with cleanmg matenals that are approved m wrrtmg by through-penetration firestop system manufacturers and that do not damage materials m which opemngs occur B. Provide final protection and mamtam condrtions durmg and after mstallation that ensure that through-penetration firestop systems are without damage or deterioration at time of Substantial Completion If, despite such protection, damage or deterioration occurs, cut out and remove damaged or deteriorated through-penetration firestop systems immediately and mstall new materials to produce systems complying wrth specified requirements . END OF SECTION 07841 THROUGH-PENETRATION FIRESTOP SYSTEMS 07841 -8 �L�CTRIC�L SYMBOLS: KEY NOt�S: C�ENERr4L NOtES: "1"�INI" COD� ,4N,4L't'SIS: KEYPL�4N: • Vo $ SINGsLE 8U11tCH O 1. ALL PARtItIONB ARE 5/8" �IRE RAtED CsWB UNIt AREA: 1369 SQ Ft oG '$ tNREE WAY SWItCH i BAtN AND/OR DRYER VEN7 GAP �OCAtED Z u,i IN SOFFit ABOVE. PROVIDE 36" MiN ON EAG4� SIDE OF WOOD S1'lJD FRAMER OCCUPANt LOAD: � F �, � w w D DIMMER 8lUItCN 2. ALL DOORS SHOUIN AS DEMO'D t0 BE 11369 SQ Ft/ 200 SQ Ft ■ 6.84) ' N = _ . ❑ �REStOP tNER ENETURAtION NP NE DRAFt ONE EXit REG2LIIRED �? O O �� 6" ,4PERTlJRE FIXED C,4N LIC:Ht W/ BLACK ALZAK tRIM StOP tHAt OGCURS A7 tNE EXtERIOR REPLACED WItN SOLID 1U00D StILE ,4ND E W V � �- �- �' BUILDINCs UJALL. RAIL PANEL DOORS UNLESS SPECI�IED tNiB llNit MODIFIC,4tION 1�OE8 NOt Z o � • OtNERWISE BY INtERIOR DESICsNER ENtRY CHANC�sE TNE OCCUP�4NGY OR OtHER � - C �" APER'I'URE CAN LICsNt U!/ LENS .°rLIItABLE IN WEt ARE�45 UJ/ BLACK �4LZ,4K tRIM 1 OO B'4tN FAN AND DUCtUJORK At EXiStINCx tOP DOORS SNALL REMAIN UNCH,4NC�ED UN.O. LIFE SA�EtY FEAtUREB OF TNIS UNit. Q Z �i � a+ � � FLOOR UNItS SNALL BE ROUtED WItNIN tNE AS A �SULt tNERE IS NO ADDItIONAL � v� � o „ 3. D 1 5 7 U R B E D A R E A S O F G E I L I N C�s S N A L L B E L O A D t 0 t H E E X I 8 t i 1� E X I t I N G P G V � •- co 7 t INtERZtITiAL SPACE. tNE FIRE SEPARAtION REPI.AGED AND�oR REPAIRED t0 MAtCN SYSTEMB, FIRE RATED ASSEMBLIE3 OR D a �_ E .� Q 3" APER?URE DIREGTIONAL/ ADJUStABLE GAN LIC�sNt UJ/ BLACK ALX�G tRIM OCCURS At 7HE NEW UNI7 FLOOR StRUCtURE EXIStINGz ADJAGEMT CONSTRUGTION AND TO OtHER LIFE SAFEtY FE�4tURES A8 O W � � � 0 6" r4PERTURE SLOPED CEIl.INC� FIXED CAN LIGHT W/ BI.ACK ,4L2�4K TRIM ABOVE, tHERE�ORE NO R4DIAtION DAMPER IS REQUIRED. C O M P L Y W I t H t H E M A N O R V A I L P R O J E G t A P P R 0 1 I E D U N D E R t H E A G t I v E MA�l. BUILDINCs PERMIT FOR tNE 01/ERALL � � p �.� Q� �4" APERIURE SLOPED CEIL1NCx �IXED C,4N LICsHt UJ/ BLACK ,4LZAK tRIM �'� 3 DRYER EXHAUST SNALL RUN WItHIN 7NE MANOR VAIL CONTBTR�,tCtION PROJECT Q �j H „ �M � O WALL. PER SECtION 't16.62 OF 7NE 20fd3 �. INDICA7ED PLUMBINCx CHANCsES MAY tNAN tH08E NOtED ON TNIS SUBM1tT�L. O �, � -� � J Q �i APERTURE SLOPED C�C� DIREGt/ ADJLISt. CAN LICxH7 UJ/ BL.AGK �4LZAK TR �� � IBC, DRl'ER DUGtB GONtAINED U117NIN A REG�UIRE UJORK TO BE PE�ORMED BELOW A B � m � Q �� � TNE �LOOR AND MAY REQUIRE ACGESS = � Q �� 3" MINI LICxNT FOR DISPLAI' C,4BINE7 LICsHtiNCs U1/ BLACK tRiM U1ALL BE�ORE PENEtRAtINCs tHE GEILINC� Z (� M � � U V � MEMBRANE, DO NOT PASS tHROUCsH TNROUC�sN tHE GEILINCx OF UN175 BELOIU. ALL pC �„� c� Z � Q-I UJ,4LL MOUNtED LICxHT ,�� � � ANOtNER DWELLINCs UNIt AND IUItH ANNULAR ACCESg POINTS SNALL BE REPAIRED t0 � N , Q � ev v� ... = w V w � C'��� MAtGH EXIStINCs OR PROPOSED �E E D � WALL MOUNT FLUOREvGENt � ���� _ Y, �� SPAGE �IREStOPPINCs AT tNE GEILINCs �INE � U � �,�„� � � FLUORESCNEt STRIP LICxNt � SNALL NOt REG2UIRE RADIAtION DAMPERS. SURROLINDINCs CONStRUCt10N. W Q � Q � � DEMO W,4LL LEvEL TNREE � � Z w Z N ,4Nt ICsHT �� �� O REPLAGE DOOR, USING SAME OPENINCx AS 5. PROVIDE i/2" CEMENt BOARD AND FULL � NEW WALL CON3TR�.lCTION PE D L �� t� HEICsNt W,4tERPOOF MEMBR4NE At ALL EXIStINCx. I-�-1 EXIStINC, WALL t0 REMAIN N � SURFACE MOUNTED LICsH7 � � � SNOWER ENGLOSURES. �OLLOW tCNA M � o 5 WINDOUJS HAVE BEEN REPLACED UNDER StANDARD SPECS FOR INStALLAtION AND � «� � p � JLINCtION BOX �►�� O A S S E M B L I E S. S H O W E R S E A T S S H A L I. B E o � �� �� � BIN�OW M J E St �ON�R 4 Ct�u ElUrO�ERABLE .� � � DUPLEX REGEP'1'ACLE At 18 AFF UNA. � W D EE E RE REC RE I U A t ER t lCs N t A ND S LOP ED t 0 D R A I N. � �� a+ z z GONStR�.IGT SIMILAR t0 PLOOR REGEPtOR w w .�. A� NAL� SWItCNED DUPLEX REGEPt,4CLE At 18" AFF UNA. ��� O PROYIDE BOtH RC�6 AND CA7 Ve GABLES -� `o ^ O OO � EXNAI,ISt FAN t0 tHESE LOGAtIONS. 6. PROVIDE WATER RESISt,4Nt FIRE RAtED m �o� p„ p.. CxWB AT ALL OtHER WALLS IN BAtHROOMS, � THERMOSTAt �4t 6m" ,4FF UNA. O UNItS AT tNE tOP LEVEI. OF tNE EXISTINCs KITCNEN, LAUNDRI' ROOM AND ANY OtNER � � � � P tELEPHONE Ol1t�Et - GAt Ye BUILDINCx DO NOt REC.�UIRE TENts BECAUSE WEt AREAS. C. V � n 0 GABLE TELEviSION OUTLET tNE ExIStIN� RooP StRUCtURE IS NoT a� `° � PROVIDINCs A �IR� SEPARAtION. "1• DEMOLITION SNOWN REPRESENtB tNE � � � Q � MINIMUM NECESSARI' TO ALLOW FOR NEW '" O S PROYIDE OOOR UJITH 1m0 SG2UARE INCN G O N S t R U C t I O N. A D D I t I O N A L D E M O L I t I O N m � FREE AREA LOUVER At BOttOM FOR MA1' BE REQUIRED 70 ACHIEVE THE GONtRAGtOR'S PRE�ERRED MEANS AND � � � DR1'ER MAKE-UP AIR MEtNODS O� GONStRUCT►ON. � a °3 O9 RELOCAtE SHOWER NEAD AND YALVE 70 TNfS LOCATION. 8. NOT ALL EXIBTING POUJER AND/OR L.fC�sNTINCx Q MAY BE SHOIUN, ft IS tHE INtENt OF THESE 10 EXIStINCs BASEBOARD NEATER DOGUMENtS tNAt A�L APPLIANGES BE � COORDINATE SHOWER CxLA88 t0 PROVIDE POWERED t0 TNEIR REG�UIREMENtS AND U NECESSARI' CLEARANCE. tNA7 EXIS71NCs POWER, PHONE, 7V, AND j Q � Q � LIC�NtINCs REM,41N UNLESS NOtED OtHERWISE. U I Z tA Z N O t i F Y t N E A R G H I t E C t O F A N Y G O N F L I G t 5. 9. PROVIDE ALL REGtUIFCD RCCCF't,�GLES t0 MEEt GIIRRENt ELECtRIG,4L CODES. g�A , OF C� 0 10. REFERENCE INtERIOR DESICxN DOCUMENTS � �OR INTERIOR E1.EvA710NS. IAN �� P TRICK * SIPES � B-3196 V �tis� ��,�� o� D AR � � -_ � -==-�� -- �- W -�I _ � _ ` ___ �-- - — � i --- _ �� - - - _ -� - ---�-- n--- —�--- �— �� --�-� _--�!- ______- -- Z ______-__ �---_ �1N�4tE LOG�4tION OF OUtLEtS \ � � � AND 8WI7CNE8 ON BED WALL WItH � � � -- BUILt-IN HEQD BOARDS, YERIFY LOC�►tiON W/ ID, tYP -- - - - - � - - - - WALL �4B01/E - - - - - - - - -- - - -�� ----� ( J ' T` ��- � � a � � � � --. � � � - - p � I- - -- --I — 1-�\ � +� � , �� � ,. j� � I �i � � � � � � - 3 --� .� � / � � .� I � � �i I \� � � ��-m° 0 � 8 0 � � � �� DROOM �1 � .�+� I� I I ��I � � � > � � � \ q _ � _ ° � `�' M � � I B� � � � � � 1 °' p� / �,� �� 330 05 f0 �I I I EDROOM �'2 � j � ; � W � I �/ � �� �� � ^ �t 'I � �� I � � CLOSET �' I I 330-09 �� ,I � � I f.G� 0 � � �� � 6 � �' �� � / � I � � 330-06 � I I � ,� I � o I � � � � I i n � � I � `� i I B u 1 L t-I N, I O � / \� -� � � 8�^ � � � / I � � I� I I (R EP ID) �� �/ � � BUILt-IN �\ i V C '� -U r- � � � � � � � I \ I � HEADBOARD � � ' --'���G � � �- -, �,J .. =� .�� /�� i I � \ �� � ( SLOPED C�Ca � � � � IREF ID) BEDROOM � BEDROOM � � � � � � �� `�� � J�'�"! /� � � � I \ gLOPED GLCs , B/O StR1,ICt � ,� I � � � � � � i� •, �� �,; `-� � � � Bui�.t-iN I � Bio sTRUCr � , � Q � � ��� �� �- � I !�i� ��� V NE�oeoaRU � I �� �\ �� � ; � � I �� � � i� � � \� \� �, � �� � � ��� � � j I j �� � _ I CLOS�T �� �� j I ' i Go /�-\� , 6 / � \ � I � BUILt IN, � ��� I � _ � � � / � � � (t� ID� � � 330-08 / �/ I � � V ��-m�� � _ � � � o; � I � i� �� _ � 3�--t�� � � �� � � .� �� ; � � ( V ° , 0 �\ \ / _ �B � I i i � 0 � � � �� �I ,,�..� , � i8��x���x�-3i8��, � �� � � � / I � I � I 10 / � � � LINEN DOORS I / � _ __ � r -...� m \ � I - - - - � / m � I \ \�- - - � L_�� _� � t0 MAtGH ---i'- - - - - 9 - �� _�-�= - — � - -- - / -�_ - — -�-�- BUILT-INS, TYP � _ _ �-i�i i � _ _ - _� � `� I I ,��-I�. COO�u(N,atE �� F �-� � � � _` B �__ I I tILE GPt �I I P1' TILE ' I � W/ INTERIOR � 1 � BAtI-{ROOM � � �� I I I I � BAtHROOM ( � �� � '� � -� B,4TN �1 _ z O �. P - 3 O _ +�� DESIC�ER ' I I � � � II I I i � �� '��� ���"- c I I ^ � II � ^ ' �� � � � � 330-m4 wm - - - I � B�4TN �"2 � � � � � r � � � � rr �� � � f � X �.� 0 - � - - -� � - - - N , � O I I �/ f F - II j \/ � � 1 • • � i i BENCH i � tILE �, 0 ��r � i �� 330-m� � J � C � � '�,,�r°-� `. i i ii �� � i C� W � — �° - � � � � �`_J � C =1- � - ,4LIGN -- - PROYIDE ,4 _ DISPOSAL 8 4� tl - - -Q- � 0 (-�- �-Jr^�r=�_l�.,L 22mv our�Et - - - rzECESSE� ENTR1' L�UNDRY � LE �- � MEDICINE -� � _ �+ W , � / E�ITRY _ _ _ J LC�- J � 18:3UED FOR: - - - - - -� � UNDER GABINEtB, RE� ,� �� 330-01 330 03 � -- �� -� � _ -� GABINEt � �� � � / / �� I-"--�^-TI� No. DAtE GoMMEhlt 8'-m" ,4FF � � I I / I I ���� l J��� ,q �,��� r-�a•nr aet ID POR SIZE / �� BENGN / ll � a LICsH71NCs ,4ND LOG,4tION8, � FLAT G�Cs �, KITC4-��1� O ,� � � � �- - -- --j J Klt N I I ^ I I g �msima �art cNEac RESPa,tbE ° --O� �O� tYP M U D fi�0 0 M —9 _ O _ 2'-83/��� � 3 3 0-1 m I _� - - �------ --� I��' �� / --- � � _ �L� � � \_-oB � �,_m�� 2� � ---- � 33(d-02 ,4NT �' vAULtED � � �r _ —^ _ _ � � - - ---� �- - -- - -----=------� f \ � - _ � �., � - \ � 9 � L���N�: ; , SYMBOL DEVICE � _ FACP Fire Alarm Control Panel � _ � � � �`� RPS �_ Remote Power Supply � � , g„ , g„ �� � � � AAanuai Pull Station ' il O � � J 2 � Accl;mate Photo Detector 1 — / -- — �SB Acclimate Photo Det SOUNDER BASE � g, v � � P , ti � ) ' — U g O � Heat Detector �l BEDROOM #2 � Fiorn/Strobe (wall mount) ' UP 330-09 �P - Q p � � � ' �� BEDROOM #� � g� � C Horn/Strobe(ce�i+ng mount) � Q +,. f 330-05 �,�`' � � O / � Strobe(wall mount) w �� � 1 `p p� C O � v U 1 ��� A � vP � � Strobe(ceding mount) � � � �� � Horn , �9 , " „ � . A S P 1 g L5D07 �WP Horn/Strabe(weatherproo� a � � � 1' S ,� „ „ 0 � " " 5 � � FROM ADJACENT ' ' � 2 ' " ' " TO ADJACENT �R � + U N I T S B S g U N I T Control Rela q r � Monitor Module BATH 1 g� c�' BATH 2 � - Dual Monitor Module � 330-0 330-07 � �� 0 � Control Module A • UND O H � � � 330-0 Door Holder 120V � ENTRY L5D0 � � Hea �u Rela � 330-01 2 g' �� O + , � � v Sprmkler Waterflow Switch � � � . KITCHEN MUDROOM --- ----- 330-10 � � I J � S nn�cler Valve Tam er Switch � � ,� � ----- ' T - ,� �� EOLR-�ND �F LINE RFSiSTOR � I , � 330-02 � ;��� I � L � , ---- � �'J L1 D1 -ADDRESS, L=LCOP, D=DETECTOR � Ir STOR � L1M1 -ADDRESS, L=LOOP, M=MODULE � � C304 �- - - --- II BA H L5D 4 ~�L �r N1-1 -NAC CIRCUIT, N=NAC, DEVICE NUMBER �_--- — -- -— --—� � � .�4 � ;�,�, , � " TO ADJACENT � � � � � i —� �_ .4��, , � �_� NIT � � � � �� — � _ �� S B � �, ; CLOSE�_; ' ° ;� � C� � � � � � � � � � � �� � 5 0 O �, � 330-1'�5 � �' ' � i D I N I N G � j , � � � � � 330-12 � � ,, �, � � 1 I 1�' A p � � � � �_ � ' �r � � � „ O � Q � � � w O � 5 m �. � � � � � � � � 2 � 33� ��'� � � ° � �� �N� -� w � � � �� � � � L5D05 � -� � � r� '� LIVING � �P " ROOM � � w O vP o 330-13 P v Q �' � Z� � / � v � � � � �P � P „ � v , 5„ 8� `� 11' �� _ S ��—- �� � � i I; , � � � � �� ! � � ' i � � � � � � � � � � � I i�==-=_��-�-__--_— — �_____--- ---==-�r— -- --- �— ---- -- -- � � p � � � � � � � � NORTH o . O � L��y�IyJ, � �i BUILDING C, UNIT 330 PLAN SCALE 1 4" = 1'-0" � +p�.�.• �EI �Ns�,a=f � � y � / `' � Z _ � C� � 0 352 3 � � � � � : � � ��; � � � � O ' ; � S � ��*.�+'�` � � � �.trr���AKZ �� ' � 2�s�� � � w ���r ���� � � � � ° F m � � � � � GE1�lERA�. Ri07'ES � � p E W -,�e � U � �, [�lo exce tion taken � � o ���� [ )Submit specified�tem j F 1 RE ALARM 1N1 RE TYPE [ ] Re�ected-Resubmit � �= � �= � 1. LOCATE UNIT SMOKE DETECTOR NO CLOSER THE 6 FEET FROM ANY BATHROOM AS TO PREVENT [ ] Revise& Resubmit I W � ; � ANY POTENTIAL FALSE ALARMS DUE TO STEAM. ID CIRCUI� SIZE COl.OR [ ] Make corrections as noted � PARKING � Q ; � -- 2• ALL RACEWAYS SHALL BE 3/4" CONDUIT MINIMUM. A SIGNALING LINE CIRCUIT(SLC) 2#16 SOLID RED OR LIGHT COLOR(+), B�K OR DARK COLOR(-) � GARAGE I p � � Q Checking is o�ly for general conformance w�th the desipn concept of the 3. ALL CABLING WILL BE PULLED THROUGH J—BOXES 1MTHOUT SPLICES. AC ANNUNCIATOR COM (EIA-485) 2#16 SOLID RED OR LIGHT COLOR(+), BLK OR DARK COLOR(-) pro�ect and g�neral rompl�ance w�th the infa�mation gi�ie�,�r, �he ' � 4. ALL CABLING WILL BE PULLED FROM DEVICE TYPE TO NEXT DEVICE TYPE LOCATION WITH NO C NOTIFICr1TION APPLIANCE CIRCUIT(NAC) 2#14 SOLID RED OR LIGHT COLOR(+), BLK OR DARK COLOR(-) contract documents ,�ny action shown is sub;ect+o tre r�q�ire�nents ' bf the Pfans&�reciflcahons SPUCES. WHEN CONDUIT SYSTEM IS BEING INSTALLED, ALL WIRES SHALL BE PULL THROUGH D INITIATING DEVICE CIRCUIT(ID�) 2#16 SOLID RED OR LIGHT COLOR(+), BLK OR DARK COLOR(-) Coritractor is responsible for dimensions which shall b�con�irmed ard � D�j�'jf D.L.S. + THE BOX OTHER THAN DEVICE TYPE BEING CONNECTED. P AUXILIARY POWER(24VDC) 2#14 SOLID RED OR LIGHT COLOR(+), BLK OR DARK COLOR(-) conelated at the;ob site,fabrication proce;s and lechr��.�u��s o( { 5. ANY DEVICES INSTALLED LESS THAN 96" StiALL HAVE A RACEWAY S SOUNDER BASE POWER(24VD:,) 2#14 SOLID RED OR LIGHT COLOR(+), BLK OR DARK COLOR(-) constr.icf�on,coerdmntion of his�^✓ork e��ith that of all cthe�tra�es and A B CHEC�fED �',M, �'�; } 6. ANY PENETRATIONS THROUGH FIRE RATED AlVD OR STRUCTURAL MEMBRANES WALL SHALL BE V STROBE CIRCUIT 2#14 SOLID RED OR LIGHT COLOR(+), BLK OR DARK COLOR(-) the sar�s a�tory�e�ior�r,ance of his work � i� SLEEVED AND FIRE STOPPED. This stemp doPs not rPlieve the contractor of his res�cnsib�lETies to DATE ,2����8 � T SMOKE DETECTOR TANDEM WRE 1#16 SOLID RED comply v��ith ali appli able codes&insNe tion organiz� on require;r�ents ,y + ' 7. ALL INSTALLATION SHALL COMPLY WITH T.O.V. INSTALLATION STANDARD GUIDELINES. NT NETWORK 2#16 SOLID RED OR LIGHT COLOR(+), BLK OR DARK COLOR(-) v/�� �p� e � �� o� ; ' � 8. REFER TO BASE BUILDING FIRE ALARM DRA1h"NGS FOR SYSTEM INFORMATION. Date I "') �' � . 9. SCOPE OF WORK INCLUDES RELOGATION OF DE`dICES FROM BASE BUILDING DESIGN. SYSTEM �dgT�: y--r � SHEET ��.,�e�� � CALCULATIONS ARE NOT AFFECTED BY THIS UNIT REMODEL. 1 LABEUTAG ALL CIRCUIT � 2 NO T-TAPPING ON IDC, NAC, NETWQRK OR SOUNDER BASE 24VDC # OF � GENERAL NOTES WIRE SCHEDULE SHEETS � 3 — , _ ` ' y � -- _ `_ T l J � --- - '� '�."�' L� ; �' � �� � � . � ; � , � . � � , -�� � � . ; � , � � ��-, : _ ______ ; , � � �� ' � _.__ _- __ L___ .�_' _- ' ����..0 � -_' -_�_1 i g �_ �� , I �� � ` � `� G 0 S B d, � BEDR00 �1 : o ' € � ; _ 3 �— F � � Building A �,�� ; 3�0 05 BEDRC�aM �� , ; ,� � �'��' x �, � � � ��o-ag �P � � � ; � ��;. 1�� Tv SLOPED C�G � ' � � � i � � � � BIO TRUC � �� � 11�/� B 1 " <v ; Work Area ! � � 3 � c"::;::::=� �, , ; ��� 1 _ � g � � 3rd Level �'� 11 . �� BUILT—IN ; � � � � ; ►�. 9;� HEADBOARD ; ,� �, I RE � ❑ RE � ❑ � � � � � �9 ; �� � g �J �� , (REF ID) i SL�PED CLG � '` ; � � � ir , � 4 -1 � B/0 STRUCT T� � ����ET � �� ; -� 330—ag F ; � � oF � � - 10 �� � � � � )9 � 'f9 � �g B 9 g� S� ;�� � � � �� � o � �, , g , � � � `�� � � .� � � �_ � � � , 3 \ n � .�� � � i � l V � I t 4 ` _ --%i-- _�{--- _-1--�..� �' � _ - cr� � - - ------ -� ---- ., ; � �� � E ' �� , Z _��� �_ , � � ' � - � , W 1 , ;_____ � 1 ';- \R.► cr- ' i I ;----- --- ---r ---� --- � ' `' / --i-------- - R .--�7� �� I z i � i t i ; BATH �1 `��� _ ; �`.; � , --� c�' , , �no i � ; � ,I � ; ,c �� , -;, � i , . , � i _ , � 330—04 � , , � � .,� 3 „ � 3 � -- '=---- " � �t- - � ' 20 � ! � i I �j''T Y 1� - --- ��- �� -- - � � � �, -- - -- ��i i i� i r ,� i, ,�, �,� - -- - _ --- � -f ;�, � ; i B A TH �2 � � ; ---------- � ��J__.,'' �� ��� 4 8 �/ 3-7 f � - � �/ - 4 � - � ���� � __� ;�� � � � 33a- � _�, � � a J �' � ;, �: . I : , �BENCH ,, ,��__�;;� ��__ ,; 2 %, , � ,�__ %' �;,�^-°==�;;� ' � , ;, �;� ---- �.�� �A U �1 D R Y j ���� - --= s;� i ��--:� — i _.. r1 i � � ,--, �� � - - -- --- - ; E N T R Y , 3 3 0—0 3 � <<_,_____---------� �_:_;-N�� ^ , ---- D I S P Q S A L � �z � � � . , , � � � ti � ;; ; - - , � 33�---a1 „ � � �``^`�`��, 1 �2 — � I ,�� i W �� �------ - - � , , , o , � E , ; � � ; „ „ 11 - 11 ��—o}� AFF „ � „ 330 �-- - ----;, , , � � � FLAT CLG � — � ,'- ! ''i; � , � � uaROa - _ _ _ � _ � F ��-�` ' -'� � � . � 4 3 � 3 8 M � b 0 —� . ; , , _ � , i 3,�0—a2 B 3 �� ��. � {_ � `�- ; � o ; n d- � � ,\ �,=' _ � � 7 A D D VAU LTE � I , — � ��� w � I� I � __ _�_CEILING � � �0 7 �� - �0, �1 � 1rJ 0 - ----; V / j' ,,,� - %� i ` ' f » _' �� � � , ' 8 —0 A�F _ �_ -_-= --_-_----- -- ---- --_--_ G G � � FLAT CLG � SLI I N G GL,�SS;; � i '='����'''�,'-' � � '��3� � ' � � ' � .'���, � � -- -- --------- - ___ _ - - -- -� - - - � ��osET � ,:__�,�, ____� --, �,.�_. � _ � ; ��� ��+ ���_� 4 ��- .___ � SPRINKLER PROTECTION IS N�T PROVIDED IN BATHR❑OMS ; 33�-15 , � '`��.%�` � �T� �i D I I� I N G THSN 24ASQUARE�FEET FEET OR IN CLOSETS LESS -� X Q 1 SURFACE A j , o � \ � �� 0 11 330-12 MOUNTEQ ' `7j � � � Tf LE `� 6 — 5 FI XTU R E GENERAL NOTES � - -- --- � 1, PR❑VIDE SPRINKLER PR❑TECTI�N IN UNIT 145 AS SH�WN ' � � 3 3 3 _ �� � ��"` � �I SPRINKLER PR�TECTI�N SHALL BE PROVIDED AB�VE AND BELOW THE CEILING ' ' `� ��Z" CP� ~,- � �� � d— 2, MAXIMUM SPACING ❑F THE RESIDENTIAL PENDANT SPRINKLER HEADS IS 224 SQUARE I � � CPT � F�OT PER SPRINKLER, ; � q R EL Q� � _ _ R E � ❑ 4, ALLI PIPING T❑NBE�TYPEEMUCOPPER W TH KC❑P ERSFITTINGSARE FO❑T PER SPRINKLER ; � �..r� �: � 5, C�NNECT TO 2" C❑PPER SPRINKLER MAIN IN THE C❑RRID�R, � ' � w `p c�'�'-° \ - - , ; ~ �G , �O � � m �G r—, I � � I i � � o— c'`�`� � m � � � W � � � [ No exception taken � � ' � � � [ ] Submit specrfied item � � � ���� [ ] Re�ected-Resubmit � � [ ] Revise& Resubmit � ; � ~ ; � ,-� � cx� LI �/I f�l G � �'��' [ ] P✓iake corrections as noted � R C�0 M I Checking is only for general conformance�vith ihe des�gn concept of the � � x � pro�ect and gen�ral complianre wiih the informabon oiven in the � � � contract documents Any acUon shcwn is sub�ect to the requirements ' G w 3 3�-1 � �� bf ihe Plans&Specrf�catiom� I �,,� ; G �] � FP � Ceriracter�s responsible fo�dimensicns which shall be confirmed and I � � � �� correlate�at ine�cb s�tp, fab�icat�en process and techn,ques of � construction,coordinafion of his work with that nf alt other trades and � � the satisfactory performance of h�s v�rork � ' � This stamp uo_s net reheve the cor+ractor of his responsibiliUes to � A D� ~ comply with all applicable codes&inspe n organization requirements � � � i ' '� �� , � � � ,, �� - ( � � ' ' � �� � �� � Date � ` �8 By� T v{ i i i � � �� � � I � 4 � 1 �� , � ; � SLOPED GLG � 1 � I i ' �� � �� � ; ; B/0 STRUCT � - � i �-__� ; � �., � ; ' M i i ° • • �°5 L ! ' — - - - --- -- -- - ' Cl � O � � � ° o � � j � w , = i Gen�ral Notes 5 bols Number of S rinklers .� E� k �°"'� TENANT FINISH Job: � � � ` � � �,P �q s boi n68�� t�on Total This 3heet zz Total This Job 2z T��e Fishman Unit 330 Bldg C � ' � � r 4 ' ��G 5�,� 1. All Pi e Locations are to be Field Menaured Prior to Fabrlcation __ ctJ , P � Hydraulic Reference Points S bol Deacri tion Revisions: Date: ; � a n d I n s t a ll a t i o n b y S p r i n k l e r C o n t r a c t o r. [ers ed] IIev Below To of Steel . Con t rac t No. 2 7 C 0 3 0 1. Added ll htin 2/13/08 MANOR VAIL ' P � 6 Cl/2,K=4,9> TYC� LF II RESI C�NCEALED 155F 9 9 � � r 2. All Dimensiona Shown are Center to Center. C a-d] IIev Above FYnished Floor Supplied froM copper pipe In Mech chase 0 � 2" 3 � -!-cTOS 2o-w Elev of To oi Steel • �'°� �Y M• ��K V�L� C�. ' ; O LL STATE 3. High Temperature Heads are to be Field Locnted Where Required. P � il Ci/2 ,K=4.9> TYCO LF II RESI CONCEALED 155F � � FIRE PROTECTION, irvc 4. All Pipes and Hangers are !c be Iastalled per NFPA #13. � Ceiliag Height Supplled froM steel plpe In tnterstltlal space » Contraetor. �- Denotea Hanger Location � 5 Cl/2',K=4,2) QR BRASS UPRIGHT 200F 3cale 3/f = 1-0 o xtse u or aown ALL—STATE FIRE PROTECTION, INC. w ' ` 5. Hangers are to be U.L Liate1 and F.M. Approved. p Date i/28/08 STATE REGI5TRATION N I C E T 6045 E. 76TH AVE #12 W #OQ$ LEVEL IV x #9 3 4 9 2 App�� gy ��, � COMMERCE CITY, C0. 80022 �