HomeMy WebLinkAboutPRJ07-0327 B07-0231.PDF � f � ■ i / � � I I � i January 16, 2008 � � Chris Gunion � TOV Building Plans Examiner Department of Community Development Building Safety and inspection Services 75 South Frontage Road Vail, CO 81657 Re Response to Plan Review Comments dated 08/17/07— Permit#607-0231 Chris, Please find responses to comments below Architectural Comments 1. See sheet A/A-10 for means of egress plan 2 There will not be any changes made to the ceiling layout, lightmg, sprmkler etc Per phone notes dated 08/29/07, there wdl not be a need for an RCP. 3 See sheet A-00 for building construction type 4 See C/A-10 for new wall construction detail 5. See B/A-10 for note regarding wall to be removed 6 IBC Section 1016 2 is in reference to Corridors The area between the lockers and benches would be considered an aisle, therefore the applicable IBC Section 1013 4 1 exception states that, Nonpubl�c a►sles serving less than 50 people, and not required to be accessible by Chapter 11 need nof exceed 28 mches Please see A/A-10 for aisle dimensions 7. See A/A-10 for notes and dimensions for ADA bench 8 See sheet A-10 for Finish Notes 9 See A/A-10 for existing door sizes 10 Per phone notes dated 08/29/07, item#7, it was stated that the existing double doors into the space could be utilized as part of the accessible route and therefore the 18" on the pull side of the single door would not be required. Electrical Comments 11 No changes to existing electrical are anticipated. An electrical subcontractor will provide lighting ComCheck calculations as required See item #4 of phone notes dated 08/29/07 attached � Mechanical Comments - 12 See attached letter by C&C Mechanical ti Enclosures (3) �r � � i Fax 970 926.2169 �;uQ-17-07 10:31am From-TOWN OF VAII CO�NIUNITY DEVELOPMENT 9T04T92452 T-830 P 002/002 F-506 : . s P{an review comments are based on limited infor om��teCOlans a�e re�eived�e�and plan sheet A- 10. Additional comments may be required once c p P Architectural C mm�n� �. Include a complete means of egress plan showin he exp d'scha ge e IBC �06.12 IBC ch 10 mon 4 path of egress travel and total travel distance to t 2 Inciude a reflected ceiling plan IBC 106.1.1 =� 3 In clude the buiiding construction tYpe per IBC ch. 6. on the pians. Town of Vai1 records show this building as type II-A 4 Inctude a construction detail for new walis. IBC ch. 6 5 Clarify if portion of wall proposed to be removed is a fire resistive or structural wall. Provide structural plans as necessary. 6 provide a minimum 36"clear exit width belween lockers and bench per IBC 10�.6.2 � 7 Show accessible bench and turning space per ANSI 117.1 1998 section 803 �' lude a complete list of proposed interior finish materials and flamespread index per TBC ch. 8 8 Inc g Show ali door sizes. XBC ch. 10 ' 10 Provide a minimum la"x_�P��� side clearance at door into the corridor area. ANSI J.17.1 1998 section �404.2.4 • Ele�ical _ on m�nts; ��n� panei schedule and load calculations. Plans must be � 1]. Include an electri�al power and fighting p stamped and signed by a Colorado St�te L�censed Engineer ech nical Comm nts: osed locker room complying with IMC table 403.3 � 12 provide a mechartical ventilatio� system for the prop ' ulation of air is not permitted in locker rooms. Inciude �omplete mechanical plans. Plans must Rec�rc be stamped and signed by a Colorado State Licensed �ng ne please refer to the cover sheet for information on resubmittin9 p lans. I�order to avoid deiays in issuanoe of a Perm��►P�e���eck a_1 requested infermn resubmittals wi I�not he eviewed ed plans. Please submit revised plans as a complete set. Partial pla ��,,,,�v\C RIS\ ERMLT CO.�E�IBQL?�t�B�1.DOC ., Page 1 of 1 , 4 1 Shana W i dmer ���,,,�,_.,..�..,,W...._._..�..�-.-.--- From: Shana Widmer Sent: Wednesday, August 29, 2007 3 01 PM To: 'cgunion@vadgov com' � Cc: 'Jeff Babb', Jeff Metheney - Subject: Golden Peak Lockers-Phone Notes_Correction � Please note corrected items in red belaw: � Phone conversation between Chris Gunion TOc Comme DS artment and Shana Widmer Atlantis on Auqust 28t!' and 29th 2007 re ardin Plan Che 1. Chris stated that an RCP by the architesto ala�rmsly be required if there were going to be any changes to the ceding layout, lightmg,fire sprinkler , 2. Chris stated that if the lockers were within �8t of the seace� that sprinkler heads woutd need to be relocated in order to accommodate the layou P Mike was under the 3. Chris stated that per a phone cali with Mike McGhee of the Fire Department, impression from the client theStWere made oethe I ght fixtures orrreceptacleslthat no electrical drawings 4. Chris stated that if no chang stamped by an engineer would be required 5. Chris cianfied that the areas between the lockers ed on n lans whendresubm ttedred aisles and therefore only 28"would be required This should be indicat p 6. Shana stated that he revised layout would provid n�the ADA belnchers meet ADA and that 36"would be provided at these locations between the lockers a 7. Chris stated that the double doors into the Locker door int the bocker Rooms wouldtnot be equ red.oute and therefore the 18" on the pull side of the singie $. Chris stated that per code Locker Rooms cce would have to berrecionflgured by a Me han cal Eng neer return air vents currently located in the spa Shana Widmer @tlanti� 97 Main Street Suite W10� Edwards, CQ Fi1632 1/15/2008 GENERAL NOTES : 1 1.01 COORDINATION A. REVIEW THE ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONS AND CEILING COORDINATION. D. ALL MECHANICAL PENETRATIONS OF FlRE RATED WALLS, CEILINGS, AND FLOORS SHALL HAVE THE DO NOT SCALE THE MECHAI�ICAL DRAWINGS. ANNULAR SPACE AROUND PENETRAl10NS SEALED WITH A FlRE BARRIER SEALANT MEETING THE REQUIREMENTS OF UL STANDARD 1479 AND ASTM-E 814. INSTALL SEALANT IN FULL B. COORDINATE THE ROUTING DF ALL MECHANICAL SYSTEMS WITH THE OTHER TRADES IN ORDER TO COMPLIANCE WITH MANUFACTURER'S STANDARD INSTALLATION INSTRUC110NS. AVOID CONFLICTS WITH DUCTS, PIPES, ETC. E. :INSTALL ALL PIPING AND DUCTWORK TRUE AND PLUMB, PARALLEL OR PERPENDICULAR TO C. COORDINATE THE SUPPLY AND INSTALLAl10N OF EQUIPMENT REQUIRING ATTEN110N BY MORE BUILDING CONSTRUCTION. THAN ONE TRADE WITH THE AFFECTED TRADES. F. PROVIDE ACCESS PANELS IN CEILINGS AND WALLS WHERE REQUIRED TO SERVICE DAMPERS, ,, D. FlELD VERIFY LOCAl10N AN) ELEVATION OF ALL EXISTING U11UT1ES. ANY DISCREPENCIES SHALL VALVES, SMOKE DETECTORS AND OTHER CONCEALED MECHANICAL EQUIPMENT. BE RELAYED TO THE ENGIN[ER FOR COMMENT AND CORRECTIVE AC110N AS NEEDED. SECTION 2 - AIR DISTRIBUTION 1.02 CODES AND STANDARDS 2.01 GENERAL A. INSTALL ALL WORK IN ACCO2DANCE WITH SMACNA STANDARDS AND SPECIFlCATIONS; NFPA 90A, � 90B, AND 91; 2006 INTERNATIONAL BUILDING CODES AND THE LOCAL AUTHORITY HAVING A. DUCT SIZES SHOWN ON DRAWINGS ARE THE ACTUAL DUCT SHEETMETAL DIMENSIONS. � JURISDICTION AND CODE ANENDMENTS IN PLACE. B. PROVIDE VOLUME DAMPERS AT ALL NEW DIFFUSER TAKEOFFS. 1.03 EXISTING CONDITIONS C. ALL TAKEOFFS, RUNOUTS, AND FLEX DUCTWORK TO DIFFUSERS SHALL BE THE SAME SIZE AS � A. THE DRAWINGS ARE DIAGRAMMAl1C IN NATURE AND ARE NOT INTENDED TO SHOW ALL THE DIFFUSER INLET UNLESS OTHERWISE NOTED. TRANSITIONS, OFFSETS, ETC FlELD VERIFY EXISTING CONDITIONS AND PROVIDE ALL NECESSARY FlTTiNGS TO COMPLETE THE INTENT OF THE DRAWINGS. INSTALLER MAY LOCATE MECHANICAL 2.02 DUCT SPECIFlCATIONS EQUIPMENT DIFFERENTLY THAN SHOWN ON DRAWINGS DUE TO CONFLICTS, AS LONG AS FUNCTION AND/OR APPEARANCE IS NDT AFFECTED. A. ALL NEW SEAMS, JOINTS, ETC., IN EXHAUST AND SUPPLY DUCTWORK SHALL BE SEALED AIRIIGHT. ' B. CLEAN AND CHECK OPERAION AND CONDITION OF ALL EXISTING MECHANICAL EQUIPMENT WITHIN B. ALL NEW NON-GREASE EXHAUST DUCT SHALL BE UNINSULATED GALVANIZED SHEET METAL DUCT THE CONFlNES OF THE SPA�E. PREPARE A WRITTEN LIST OF ANY DEFICIENCIES IN EQUIPMENT WORK. OPERATION OR CONDITION. SUBMITLIST TO THE PROPERTY MANAGER PRIOR TO COMPLETION OF THE PROJECT. DRAWING INDEX 1.04 NEW CONSTRUCTION � DRAWING NUMBER DESCRIPTION A. MAINTAIN A MARKED-UP SEf OF DRAWINGS, WHICH INDICATE VARIATIONS IN THE ACTUAL INSTALLATION FROM THE OP,IGINAL DESIGN. DELIVER THE DRAWINGS TO OWNER UPON M1.0 MECHANICAL COVER SHEET COMPLETION. M2.0 DEMO/EXISIING HVAC PLANS - PARTIAL LEVEL 194 B. ALL CAPACITIES ARE SCHE)ULED AT JOBSITE ALIITUDE. M2.1 NEW HVAC PLANS - PARTIAL LEVEL 194 C. NT AND PIPING SUPPORTS SUSPENDED FROM ROOF JOISTS SHALL BE SUSPENDED � � HORD OF THE JOIST. O;•�,�•�(4���,°•�c�` �v� ����' LEGEND OF SYMBOLS AND ABBREVIATIONS 3 '• . GENERAL CONTRACTOR G.C. MANUAL VOLUME DAMPER M� � CONCENTRIC REDUCER EF � �i� O��v MECHANICAL CONTRACTOR M.C. (E) DUCTWORK & CEILING TO BE REMOVED ����� --�- � �S' •.....••`��iG� NEW CONNECTION TO EXISIING O ROUND FLEX DUCT ►�t� � GOLD PEAK BASE LODGE �N� CONICAL BRANCH TAKE-OFF FOR CHANGING ROOM RENOVATION NEW 4-WAY THROW SUPPLY DIFFUSER � ROUND DUCT W/DIFFUSER c \ VAIL, COLORADO EXISIING �E� EXHAUST AIR GRILLE � STRAIGHT BRANCH TAKE-OF FOR RELOCATED �R) ROUND DUCT W/DIFFUSER � ��\ � nZ SHEET FLAG NOTE O3 SUPPLY FAN SF / �/MECHANICI�L ENG\E\ERS/CONSULTPVTS O�/LJ/�008 ,,1111,,, � E N G 1 N E E R I N G � AS NOTED VANED ELBOW , -� � �n,�. MECHANICAL COVER SHEET t032 60ULDER RD SUiTE 200 VIL�E COLORnDO 8002) D�w MAIBET� �M1O 3�3 926 0020 I 303 926 6�0�� M� � 1N!DOD�OIf�UOIO NL E[Af ND RlWS l!M lRm11Cf fi]DIm���4 MG MO IW PIIP��ED A Rl6fllOWl OEl�I 11MfZ MD GMqf S Y!D Q WUfY�1E0 M MIDl Q M�NR YY NIY QIIEII►�RIT 101 PEfYf�Oq Q�N1ATM NIMD�I�Ot TO OI�M'/OTQ PRQlC�fMOUf 11�1RIM NITKIGTOI Q 20/]O Olv[EAK MG CmM101f 2001 t i� r� � FROM (E)SF-1 �E)�6»� � �E)�4"� •r - - (E)550 CFM _�� � q ' SHEET NOTES: � 1O RELOCATE EXISIING EXHAUST GRILLES AS SHOWN ON PLANS. G.C. TD REPAIR CEILING AS (E)14"� (E)10°� NECESSARY. (E)36"x18"� (E)10"� 3 2O PROVIDE DUCT TRAVERSE AT THIS LOCATION BEFORE ANY MECHANICAL SYSTEM RENOVATION , ``` (E)550 CFM � a WHEN EF-13 IS ON HIGH SPEED. ��` � (E)550 CFM N 3O G.C. TO REMOVE EXISTING CEILING IN THIS AREA. G.C. TO REPA�R CEILING AS NECESSARY. � N u u M 2 �� ��E�10�� W a � ❑X (E)12"x12" (E)VAV-1.5 ' � � i � - ' � (E)24°x14" . 0 � (E)10"� ��(E)10"0 (E)10"� 1 (E)14"� `� ,� ``���� (E)35"x26" (E)330 CFM, TYP. OF 6 �,��, , �/ D� �EG �........,.�s� 00;��p. PAq�,�;;�� TO (E)EF-13 —� c.�:� 7 �;v 't �';.1 ���. . , DEMO. EXISTING HVAC PLAN — PARTIAL LEVEL 194 �. .��� � �i;.h� M2.D SCALE.1/8 = 1 —0 ♦ ss'I� ��G NORTH GOLD PEAK BASE LODGE ' � � CHANGING ROOM RENOVATION c��� VAIL, COLORADO , � � ,^�`� � „ � Z MECHANICAL ENGINEERSICONSULTAR�S O�/�J/�OOS � � E N G I N E E R I N G AS NOTED s�r nnF. ,�,,, E Gc�r„ a���pF�, „ �17E 20A DEMO PLAN — PARTIAL LEVEL 194 . ����5����E ����RA�o a��z� owc.rxn� , ,�,3 4z6���zo � 30,�zs e,,,�, M2 0 na rowar�unw iu ow wo maa s nc nmuer a�o/m avEnsw xn Mo wa wawm�nivnsau�ocsw aw�wo�ar�u�u a anrwhn M wc ae x rowr rr wn onu�Mrr rat rad[mo a�tnuwnv�naro.v rv ne a rv onu r�atcT rmaur n�wnd wmnvua�o�oM wamsia��+wrt�ms � E� �� �� ��� � FROM (E)SF-1 (E)16"0 R 3 (R)160 CFM, TYPE 'E', TYP. OF 3 ,-Q S H E E T N 0 T E S: � 14° 1O CAP AND SEAL EXISTING DUCT. 2O PROVIDE NEW EXHAUST GRILLE, MATCH EXISTING TYPE "E" GRILL6. (E)14"0 � � 3O RELOCATE EXISTING EXHAUST GRILLE, CLEAN AS NECESSARY. (E)36"x18" (E��p"� $M�(E)10"� � 2 N 1 CFM E E ``� O4 (N)160 C , TYf�E II 4O RE—USE EXISTING EXHAUST GRILLE, CLEAN AS NECESSARY. ``� I I � $�� N 5O PROVIDE DUCT TRAVERSE AT THIS LOCATION AFTER SYSTEM IS B4LANCED. U U � 6O RE—PROGRAM EXISIING VAV-1.5 TO MAX COOL � 1200 CFM, MIN COOL � 700 CFM AND � 12„� � $p� � „ v HEAT � 700 CFM. (E)10 � 7O EF-13 ON ROOF EXIST1NG BALANCE (7/1/97) 9953 CFM � 490 RPM. N ❑ NEW CFM (9953-1500) = 8453 CFM � 416 RPM, —0.48 IN. WC. x � (E)12°x12" (E)VAV-1.5 , �r, � v (E)24°x14" 6O � � (E)14"� � E 10"0 1 E 10°� � `� �, ``````` (E)35"x26" (E)200 CFM, TYP. OF 6 �,�� ,� � -� � v �p0 REG� ' �:���•�M,q�':�J'F` . • �:� �''� 7 �;v O TO (E)EF-13 . �►n:,.. � i3I.p,�"� 2 NEW HVAC PLAN - PARTIAL LEVEL 194 j S ''• ...•(�G� 112.1 SCALE:1/8" = 1' 0" o�lAL� NORTH GOLD PEAK BASE LODGE c CHANGING ROOM RENOVATION \ VAIL, COLORADO � �o � / / \ ot/zs/zzoa � / MECHANICAL ENGINEERS/CONSULTANS E N G 1 N E E R i N G AS NOTED ^ " s�+�r nne. 103z s��r„ a „�pER Rp s�„E 208 HVAC PLAN — PARTIAL LEVEL 194 � owsviue ao�oanoo sooz� py��ygQ� � 303 a26 002� f 3�13 926 6�00 ,I r� � M L TO OOL��OIf NIA�q NL KN ND OE10�3 4 M IIImULT V]0/70 UOmsq.MG W IW P110��EED A 11160lOIIL R1W lIIML[ND GNqf R 13D Q dR1CAllD N'MQL qt N�NR�'/Nf/OIIE11�NrtY fOt PF1Nf�q Q MlfALLAlqI IV�Ol.t IQt M!OI AMI 011Q IIIOFCf f11Wf M Mf1EM MIMpIQAI�I d 10�2D UI�EDIM4 NG t�O1f]OOl , � Construction Documentation for the Tenant I m rovement for .. p . , � ARCHITECTURE Golden Peak Base Facility INTERIOR DESIGN 458 Vail Valley Drive Vail Colorado 81657 GRAPHIC DESIGN , General Notes Architectural Abbreviations Reference S mbols Pro�ect Team Buildin Data Pro�ect Data Index to Drawings & Y J g 1 . m leted F� o� MATL Matenal Room Information Symbol Project Architect / Interior Designer Occupancy. Applicable Codes Construction Documents 19 Clean and provide maintenance on co p AFF Above Finished o B 1 CONTRACT DOCUMENTS � construction as frequently as necessary through ACOUS Acoustical MO Masonry Opening NAME�� Room Name TLANTIS Contract Documents forthis pro�ect are comprised of construction Ad�ust and lubricate operable ADD Addenda,Addendum MTL Metal @ Building. Cover Notes / Index / ProJect Information the Drawings,the Specifications and the Pro�ect Manual components to assure new and existing ADJ Ad acent MAX Maximum ��� Room Number 97 Main Street Unit W104 2 All work under this contract shall be in stnct accordance equipmentwill operate to manufacturer's requirements � ' S Foot Area of S ace � A10 Demolition Plan and Floor Plan atsubstantialcompletion AGGR Aggregate MECH Mechanical Edwards, CO 81632 a� p 03 International Building Code with applicable codes, local ordinances and public ALT Alternate MC Mechanical Contractor Section / Elevation Symbol Dressing Room. 1366 (with local amendments) agencies having�urisdiction over the work 20 Superwse construction operations to assure that no part of the construction, completed or in ro ress, ALUM Aluminum MED Medic�ine)(al) . -._..,�. 3 All matenals stored on site shall be properly p g APPD A roved MIN Minimum Contacts� Terry Carpenter, AIA Y�� is sub�ectto harmful, dangerous, damaging PP Drawin Number e ��� e'"�8� stacked and protected to prevent damage and exposure during construction APPROX Approximae MISC Miscellaneous A g Jeff Metheney Total: 1366 Mechanical. P�-`��,,, � '�� deterioration Failure to protect materials may be cause for re�ection of the work 21 Contractor shall replace,without cost to the Owner, ARCH Architect(u�al) NOM Nommal A10 �—Sheet Number '03 I nternational Mechanical �»� defective work or materials appearing within one ASAP As Soon A�Possible NIC Not In Contract " � � 4 The Contractor shall confine construction operations [1]year after completion of the pro�ect BBR BaseboardRadiation NA NotApplicable Detail Symbol Phone 970 926.2194 Occupant Load� Code � Y . �, t�N�EE� on site to areas permitted by these documents FaX� 970 926 2169 22 Contractor shall coordinate samples and matenals BM Beam NTS Not To Scale Dressin r001Y1S. 'rJ� er t `'�+'��(��0. 9 p a (with local amendments) i���n 5 PRECEDENCE BRG Beann oc On Center A Detail Number � C-5233 � with Architect in order that Architect/Interior 9 A Generally, specifications take precedence over the Designer may review samples in a manner so as BFF Below Finished Floor OPG Opening Sheet Number drawings and large scale details or plans shall govern not to impede the progress of the work BET Between OPP Opposite A� Total Occu ar1C Load 27 �'�°, ��� over small scale drawin s In the event the p y Plumbing. �:�� ��°� 9 23 Contractor shall re are a construction schedule BLK Block ORN Ornimental �""�'E� �'�?���� Contractordiscovers discrepancies, orthe intent p p Ke ed Note S mbol 03 International Plumbing of the plans or s ecifications is not clear,the within five[5]days after the established start of BSMT Basement OPH Opposite Hand y }� '"�""` "� p construction This schedule is to be coordinated BTU British Th�mal Unit s OD Outside Diameter Owner / Tenant Egress required (1) Code � Contractor shall notify the Architect before proceeding � � Note Identification with Architect/Interior Designerto anticipate F Not required to open with (with local amendments) with the work BD Board PTN Partition lead/delivery times of items provided by Architect B All dimensions take precedence over scale to be installed by Contractor BS Both Sides d Penny(Nails, Ect) Vail Associates the path of travel as there are i Bo Bottom of PERF Perforated Finish Material Symbol ofdrawings 24 Contractorto provide the Architectwill all P� B�X 7 less than 50 occupants Fire BLDG Budding PLAST Plaster C All dimensions are to face of stud unless otherwise submittals and shop drawings and samples in CAB Cabinet PLAS Plastic W-� Finish Identification �/al�, CO 81658 � noted accordance with the Contract Documents c�, CenterLme PL Plate Room Wall Elevation Symbol Construction T pe. 03 International Fire o e D Ceding height dimensions are from finish floor to 25 Contractor shall prowde inspections, tests and other CLG Ceiling PLEX Plexiglass COC1taCt Jeff Babb y face of finish ceiling surface unless noted otherwise quality control serwces speafied here and elsewhere CER Ceramic PLMB Plumbing A Elevation Number ��-A in the Contract Documents and required by authorities C2��� 970 331 5959 Accessibility (ADA): 6 The Contractor shall acquire and pay for all permits having�unsdiction over the work The costs for CLR Clear PLY Plywood p A10 Sheet Number inspections and approvals connected with the these services are to be included in the final CLO Closet PROJ Pro�ect '03 International Building work as part of the cost of construction construction sum � � c�� Clothes Dryer PROP Property � Code & ANSI A117 1 7 The drawings and specifications shall serve as a guide 26 Coordinate the sequence of activities to accommodate CLW Clothes Washer QT Quarry Tile to the scope of this pro�ect The Contractor shall required services with a minimum of delay Coordinate COL Column QTY Quantity Door Number Symbol provide all necessary labor, matenals and equipment activities to avoid removin and re lacin construction Electric required for a complete pro�ect g p g CONC Concrete R Radius r to accommodate inspections and tests CJ Construction Joint RD Roof Drain ��� Door Number '05 National Electric Code � 8 The Contractor shall do all cutting, fitting and 27 Contractor is responsible for scheduling inspections, CONT Contmuous RM Room patching such that all parts fit together properly tests and similar activities in a timel fashion Cutting and patching shall not endanger any other y COORD Coordinate RS Rough Sawn Window Number Symbol � so as not to impede the progress of the work CTR Counter RCB Resdient Cove Base work All patching, repainng and replacement � of surfaces or matenals damaged during cuttmg 28 All work shall be done by workers skilled in their C/S Counter Snk RW Retaining Wall �QQ Window Number and patching shall be repaired to match surroundmg respective trade All work shall be done in strict CF Cubic Fee1 REF Refer surfaces free from visible differentiation accordance with manufacturer's directions DP Damproofiig REFR Refrigerator Revision S mbol R where applicable Workmanship that does not comply y 9 The Contractor shall provide all necessary blocking, DEPT Department REINF Reinforce(d) n with the obvious intent of these documents shall Revision Number backing and framing for all store fixtures, all equipment be replaced at the Contractor's expense All matenals DTL Detail REBAR Remforcing Bar(s) 1 ,� shelving, electrical devices and equipment, mechanical shall be of the best of the their respective kinds DIA, Diameter RESIL Resdient devices and equipment, recessed items and other s eafied, new and free of defects Equipment Number Symbol items as required,whether indicated exactly on drawings p DIM Dimension REQD Required or not 29 Brands or names of manufacturers speafied herein DW Dishwasher R Riser ` i vvA Equipment Number reflect a measure of quality or a standard if the DN Down RO Rough Opening 10 Provide access panels as required by governing codes Contractor desires to use an other brand or Wall Type/Construction Symbol to all concealed spaces, equipment, and devices y DR Drain SAN Sanitary manufacturer, he shall request approval from the DWG Drawin SECT Section Venfy type required, location and size with Architect Architect�ustifying the equal substitution and shall g Wall Type Call Out prior to installation EA Each sEw Sewer O � Refer to Details P Q R S & T submit that information to the Architect for review in , , , , 11 Provide smoke detectors in accordance with such a time frame so as not to impact the pro�ect EW Each Way SHT Sheet Sheet A30 current applicable codes schedule ELECT Electncal SVF Sheet Vinyl Flooring 12 The General Contractor and all Contractors bidding on 30 FINAL ACCEPTANCE EC Electrical Contractor SHLV Shelv(es)(mg) Room Wall Elevation Symbol this pro�ect shall visit the�ob site to familianze them- Before requesting final acceptance certification, EL Elevation SIM Similar P 9 complete and prowde the following ENGR En ineer SL Slidin selves with the actual site conditions rior to buddin g g EQ Equal STC Sound-Transmission Class N E— Direction of Pro�ect North 13 Field verify all conditions and dimensions with A Submit specific warranties,workmanship bonds, EXG Existing SPEC Specification construction documents pnor to commencing maintenance agreements,final certifications, construction or fabrication If any departure from the and simdar documents EJ ExpansionJoint SQ Square design intent of the contract documents is required, EXP Exposed SF Square Feet x the General Contractor shall noti the Architect B Maintain a clean set of blue line prints of fY EXT Exterior SS Stainless Steel and Owner before entenng into a contract with the construction documents, shop drawings and FO Face Of STD Standard � Owner Failure to prowde Architect and Owner with specifications Mark these documents with FIN Finish STL Steel ��'�� o� ��' � the aforementioned notification shall result m the locations of"as-bwlY'assembhes � .,� � specific Contractor being held responsible for all FP Fireproof STRUCT Structural � 3�, ��.,�: ���.� � � work reqwred to meet the design intent of the C Change over permanent locks and transmit FPL Fireplace SUB Substitive �� ������':��� �:b,:���w�.�� ���� contract documents with no additional construction keys to Owner and Facility Manager Advise Owner and Architect of key/secunty change FIXT Fixture SUPPL Supplement costs incurred by the Owner FLR Floor S4S Surfaced Four Sides � D Complete start-up and testing of systems P ro�e ct Lo cati o n � 14 The Contractor shall not commence with the work FD Floor Draie SUSP Suspend(ed) � � until actual conditions are verified to be as set forth 31 FINAL CLEANING FT Foot, Feet TEL Telephone in the drawings The Contractor, by starting the work, In addition to periodic clean up,the contractor FTG Footing N Television / � � will be deemed to have accepted the existing conditions at the completion of the pro�ect shall thoroughly FDN Foundation TEMP Tempered �� ( �������� D - - It will then be the Contractor's responsibihty to make clean all areas of the work Wash all windows FURN Furnish THK Thick '`' , `% Communit Develo ment De the necessary corrections, repairs and ad�ustments ,1 ✓ p partment � 2 9 2008 to make the pro�ect complete without additional frames and mirrors Clean all finished floors, GAL Gallon TLT Toilet �i�,�;, Building S�fety and Inspection Serviees �` N compensation wash all fixtures and tiled surtaces, remove GA Gauge T&G Tongue&Groove ` p c,— ' ' ������ ��'�� �'� 3 any spills or spatters from finished surfaces Sec:� ___t_ s � P ro�ect Locati o n � �^ �'� `=`�� .�� 15 The installer of each ma�or component shall Touch up and otherwise repair and restore marred, GALV Galvanized T&B Top And Bottom =��r ;::�r�ationat Building CodMlntemational R��i@en#i�l '� „ �° TOW�1 C�� V�41 L � inspect both substrate and conditions under which exposed finishes GC General C�ntractor TO Top Of Cod�l�'c':�:.�cf�ermlL The iSSUat1CB ot grdrtting of a pe^^:sh311 ���j� "�`" � F� not bo c�n�,rued to be a emvtfor, , Golden Peak Base Facilit ti F�' r,��.�,�:�e.T work is to be performed Do not proceed untd GL Glass, Gl�ed T Tread p ot€�rf spproval of any violation of y � �, ������ �� �- unsatisfactory conditions have been corrected GR Grade TYP T ical any cf i�o prov�s�ons of this code orofar�yatherordinarce of the 458 Vai I Val le D rive '��`� ���' _����a��"'"'` yp Junsdic::c� Permits presumtng to give authoriiy to violato or canc�l the y ��� r�r t� ��xpress# ;#Cnairti� in a satisfactory manner � �� ��,��-,,-,�3;���i�i� � �€� GYP Gypsum UG Underground provic:cns of th�s code or otherordlnans�s of the Jurisdiction sha�l n�t be Va I� C� �„�. =z , , 16 Contractor to schedule construction operations m the GWB Gypsum VJallboard UNGL Unglazed valid The issuance of a permitbasedon construction documcrts and ' "��,�; �„� ����� ;� ��� ������� sequence required to obtain the best results where HDW Hardware UNFIN Unfinished other�uta c,�all not prevent the buildin�o�cial from reqwnnc�t�� f� � ��, � �-�� � �,� u�i�3� c o r rcc:��c f e r r o rs i�t h e c o n s t r u c t i o n d o c u m e n t s a n d o t h e r d a2 a.T h e �, installation of one part of the Work depends on HD Head U N O Unless Noted Otherwise bu.!c;;�cifi��cl���ls�authonzed to vent occu an cr use cf a �� � �c���'"�'�J�"`` ��t'��«'" ��,���•_ ���"`""'%-�- „ installation of other com onents before or after its own '' p" P � � °�`W "` �'�"���c��� ���" �" '�'""�� "�N�a° p s truc`_���. ',�r�n v o laticn c f t his e or o f any ot her o�finances o f "�� �- � ° 4� � ,,;: � � �� ����_� � installation Make rovisions to accommodate items HVAC Heating,�enting &Air Conditioning U O N Unless Otherwise Noted � J T �� � ;� �� �:���� �;���� xt-������ p this .:;,�:'� �� �"`• � ��.. scheduled for later installation HORIZ Honzontal UBC Uniform Bwlding Code Z y v!� ���mb�'�`"�„ "� �`�'��"����' ��� �'F�d��r�a �...a T',� `�' {�'•�r.r� R� �- PLANS EXAMINER: DATE: � � .��.. �� ... �„� �,� � �r�;�, � '•?� �'.},:�;�w 17 Coordinate installation of different components to HP Horse Power VIF Venfy in Field �,� � � � �� ��,,� � � ��� �� � �aj HWH Hot WaterHeater VERT Vertical �*. "� ,�� � * � � � �.�. assure maximum accessibdity for required �„� . �,.„� �� � �:, �� � �� ,�� P � , maintenance, service and repair HT Height VCT Vmyl Composition Tde �.�,� � '� �,�.��t�},�,�,�, � �� �� ,�� , � °� ���r� �� „� ,� �Ti�'*`��� � 4 INCL Include(d);ing) V Volt ����,,,;;;;�� � r� �,� ;.�, .��� _� A���=.����,�°� „� 18 Clean and protect construction in progress and , �,,,��--��� , ,,d , ��� � -� �, �� � „� ad�oining materials in place dunng handling and INFO Informatioi WH Water Heater �r�` , *��r� a:� � -� �,� �� �� �„� � � � `�.�w �'a 3r�,c r�,r��ra�����r ° ����,� ��� � �, installation Apply protective covering to exisUng INSP Inspector,Inspection WC Water Closet �"� °'����, ��� ��,��`"�� ��.� matenals and assemblies when being saved and ID Inside Diareter WP Waterproof ` ° � � '� � �, _. where required to assure protection from damage or INSUL Insulation WT Weight �� � � ��� �' � Tn�,an rei�'a 3 � � � deterioration pnor to substantial completion INT Interior WWF Welded Wire Fabric � �'��'���� ��� �p��� � JT Joint WDW Window y��S�s�'��� ���cE �u;������� ��� � � JCT Junction W/ With �F��S�,t,� �.,� � �ti KWH Kilowatt I-bur W/O Without '�`� `�**`�'` � =� �� LAB Laboratorv WD Wood LAM Laminate WKG Working � LAV Lavatory N �;:� ` �..�,.,,� LT Light ��� MFR Manufacturer � . 1, - - --- ' �INISH NOTES: LEGEND WALLS� f'AINT TO MATCH EXISTING (WHTE) ___ TO MEET ASTM E84, CLASS G iZATING �____� EXISTING WALLS TO BE iZEMOVED o � � � FL00121N6: MATS INC., CALYPSO TILE (MODULAR TILE), COLOR: F3�}- SABLE EXISTING WALLS TO IZEMAIN � � N N � COMPLIES WITH DOC FF 1-70 PILL TEST ��� � p�p NN � 0 � � � � NEW WALLS-RE•C/A10 FOIZ WALL � U O O y c i�°�" CEILING: MATCH EXISTIN6 2'x 4'TILES IUS6 78705 MILLENNIA-CLIMAPLUS), NpE � �; °' °' ,��� 12Ef'LACE ONLY A5 NECESSAIZY � 5/B G7P6D CLASS A �ATIN6 - FLAMESI'iZEAD 25 � � 3 o x o LIGHTING: COORDINATE EXISTING 2' x 4 LIGHT FIXTURE LOCATIONS WITH OWNER. rnw � �i � N OTE: CONTRACTOR TO PATCH ALL pENETRATONS IN FIRE RATED ASSEMBLY W/ ` UL LISTED SYSTEM ApI'ROf'RIATE TO A�SEMBLY f'artition Wall Ty e "A" C 5cale: 1 1/2" = 1'-D" A10 f'ATCH AND LEVEL FLOORING AS REQUI�ED TO f ROVIDE A SMOOTH AND LEVEL SURFACE AS REQUIRED BY THE FLOOI�NG MANUFACTURER �� �� ��`� �� f�, � � .CA t=�NT�R ICENSE No. � �.� C-5233 � REMOVE EXI6TIN6 LOCKERS � z � � (,� TO BE IZELOCATED TO NEW z °L �'°�� ��' DRESSING ROOM EXISTING LOCKERS EXISTING LOCKERS � � E,(ISTING LOCKERS EXISTING LOGKERS ��f`'��°��,� ����° �.,. �`�' - -. --- —� �,. .� �,�.�� � � - I � w --� z � I � z � I � � _ ---+ � � � � ° U � --� i% � � y z � ' EXISTING EMI'LOYEE � + --� � � �- � D1�ES51NG ROOM - N.I.C. � � � � , � --� z� � , �z ---� w W � � �: � i � o0 --� � L i PATC &i'AINT WALL --� � i ;3 CORNERS TO MATCH --J------- � EXISTING „, _ � ,__. ,,_, s. . __ �� ,,, „ , � ,,, ,,, ,_.. ,:,._ _... . ,. ,.. 1 � � ,� . .. _..,... , _ . ......... ...._.............__...,.. w�. « ._.. �.� W..y .. .......,, �..,...,.... � , .� ,z.. � �,..., � ,....... ... .. �.... .s... � ,�... ... . . , , � ,� ,, .� s... � ,�. � ��_ , _,......,._.. ,w, ,., _ , . :. ;, ,,��� x..,,,,,. .,..,, ., „{{„ , .,, ...,..,rv E ,,.,,...,,.�„��„, .:.:, , „��,.,�.�.. ..��...,,,, .u�', ,.,,,.... ,,.. .,� ..,, ,,,.,.. ,,, .,, ...�:�'�. eF` �-.f r'3... ... .....,,,,. .., . . ...,_ „ .::..........!,E �E E� , .F . .�� �..�.�.�3�: . '9°�✓ .. n � .� � ,, N .,,, ., ..- ._, .,.:, .,,...,,.,,, .,.�:. 4. e�.x.,. ,�.......,i„/� .. , ...... . ....Enne'E�.E . . .. ... ..`:4 -c-> Z {.�4t�"`t n ...a°�'�.�?...a....�. a ��. � ... `�.E ... ., .,, .., r.. ................ ,:.., ..�.... ..:! . .xw'a-., ..._._..s, .,,,,.,..,.. _.,�,.,.,v,_„e-,zs i,,.. 1' ., .> ... ,, .. ,,,,..,.. _...., _� ,,..' ___ ______ �: .;.., s ., ,�, .:..,. , , , ,.r......,.,,_ ,,.. ,,<, a ;- „�,;� ,.-�e ;',,.,�;:x.; .,: , � . , , :n,,,,, , ,..;;� ,,,., .„ �.. , _ ,. ..,x . , ,,,,,,,,,, .,. ,-.,,.-T..�.w. . ;<„___.,, , :,_ ...... Jy j'i U ,�' _ N ., ,,. , ��3��SF( . . , ' ., ' .. ;; ��„a�, � ° �-I'ROVIDE GORNEIZ � ���` ,�,, "' 3 � LOGKER6 BY OWNER , ' EXISTING �✓ , 5'-0" ����� 3i,�aa��� , ° . GUAfZDS � � �}� E' ' �R TO'RE � �����5� ��� , ; , ' ����,,,- „„ ,,,, ;;-, � D00 M I '�' -------------------------------- ��,�<<.. 3' GAP ALL I'LUMBING � `� ���� � REMOVE COUNTER/CASEWORK� � � --- AN O _ BENGH BY d- IZEMOVE NON-LOAD BEARIN6 LINES AT REMOVED i � i i BENCH BY TO GORRIDO�/LOCKER ROOMS � �U WALL TO ALLOW FOR MOP 51NK _� �_ ��� � ' OWN�� RE FI N I S N O T E SI F L O O R I N 6 � � Y OWNER N NEW GARPETI G EXISTING ` I'ASSAGEWAY „,,,;;�„ ,�,,; ;. h �______ . ,,, ,,:;-- � � , ; 3'-2 3/4�� � PEMOVE M01'S1NK � �� �� �� �� �� AND SU(ZROUNDING WALL 12'-21/4' 5'-51/2 3'-2 3/4 6'-1 3/4 3'-2 3/4 4'-10 , � � o s `E (� 3; NEW LOGKEIZS TO � BENGH BY `/ � ^ ' BE t'ROVIDED BY OWNER OWNER � 1'-6" �3.. � i � � TYI'OF 116 �BENGH BY BENGH BY ,; ` � � ,� � OWNEIZ OWNER � � . � � � � , �� � . i " n� � � � .�,. REMOVE ALL EQUII'MENT AND IT5 A650CIATED ELEGTRIGAL AND I'LUMBING � » w , � — C� FEEDS, REMOVE ALL ELEGTRIGAL DISCONNEGTS AND PANELS THAT SUI'PLY i �' � � � � REMOVED EQUIPMENT CAf'ALL PLUMBING LINES TO REMOVED EQUIPMENT � � � o � � � � � ABOVE THE CEILING PLANE � �� m � � � •� � �t � REMOVE GOUVTEP/ i � w w � z `' � ;' €' nt ot � w ^ CASEWORK�i � � 2'-4" � 2'-4" 2'-4" � 3'-0" 2'-4° � 2'-4" 2'-4° o � ' � Q pp = � �� >- BENCH BY >- � m � � � � � � � m �OWNER m �,---,� � i ; ' � � � w w i � � W �L �L / � U � � I U U � \ O Y � � � O O � � �`. �., I � � I E i o �\ �, � ; Pro�ect No 07 105 vri , � . � � � �� , =� �' eENCH eY `�� �, Date Issue , _{ � ; --- owN�� �. �,� � N� 9v2"rYp � A � 07 18 07 PERMIT SET y 3j , a I NEW WALL T I ALI6N W/EXIST. � • I g z� co�uMN � 01 16 08 ASI #01 !n ��a��� , �s�-. �R - � LOCA�ED 6 4 �E� m z �����f �� , - , � =.P��``n r �,; � ��� „ ,��''�� �O >-`� ��. �. °,� : -..;� �( r- E E E Q �� � ° �� � ' ��'E ` AFF ��`EE'�€ � o>- x �, e �,� ,�' � �� " '-D�� ¢ m �� � : E , ' ,.: �,. -,,, _„ ,'� .-�� ,.�„�.,� : E 3 : ��.. „. `�; � �E EXISTING COLUMN �_ �, � PATH OF EGRESS TRAVEL=59'-10" N �� ' NEW EMf'LOYEE �. � �E: DRES5ING ROOM � ti � - J EXI6TING SERVIGE ELEVATOR BENCH BY � B�WN�H�BY .p���yc� � � REPLAGE EXISTIN6 DOO1Z OWNER� �iS,P��T ' LATCH SET WITH LOCKING y'L /EXISTING PR � �TF 3'-D"X 8'-0" � t HARDWARE,BY OWNER � � S���s DOOfZS TO REMAIN � N / loo��� � c �. � ��� LOGKERS BY OWNEIZ ,; ,.: �. � � EE � � � ' ,._:, . _ E, � �,,,,,,, �� ,� ��- a , _ ... _ ., ,,, �,, ,� ; .,��-; , � �� �, �, ,. _ ,._�_ #. ., �, ;;;� _ „, � � ,� _ �E ,,,,,,,;,, ,,,, � _..,,,, ,,,, � � � r .� �w, ,,;,,,,,, 3 x ��.,�„ ,....��..�„. ..., -� ,,,,,,,,,, , ,,„., ..... ..._.. .. ..�.. ,,,�at;.,<<, .,.�.., �. . .......�.a�.,. :: . ...tia� v,.,..v„;;,,� „,. �,,..,,,: ,„. a�y„+..�, .,a�,�,��., E�;.,,E,,�s ��,�, a::' -�rd -,;,;;,,, � E BL OUT FILM @ ALL PROVIDE BLACK OUT FILM GLAZING @ ALL GLAZING TO EXIT/OUT5IDE C01�RI DOR - N.I.C. T0� Title DEMO PLAN / ,..,� ,. ,��, ; __ �W .; � FLOOR PLAN , , � _ _ , _ _ �_ � _ , .,,, � � ��, a � __ _ w � . . ,. ��. _ _ ,_. ,� _ _ __ _ � ���, , �� , �. �r� . .��, .. � r ..� , � ,, �� ,v � tt r � � , , � E, � _.« � . _;: ,tt��.., � . � ,� � �_ E ............... ..... .. . . .. .� .. . .... ....��. . _,s,,.„ ,.,_ ... .. ., ...,....'...t..�, . ..�. .. ,,, ...,�...... . . ...... ..33 :k.4. ,,,"3". ..:K '. .,i .FS. .:1 !3`8,: . ,. , , ...,.. , . ..,...., „ ,� ,„ , ......... . ... .,,, ........t 3.. , v-9�,. . . .. ;... � ..... � � .�... .«^rn ....�.. ..A _,,.. . ,....s.... ., . ., .. ... F` .�� �Sii:.�. .�.. �� v..... . .���:.. o..�.� ....��,�b'%'.3ni.e,*f�`.t�,. , f�.:�i�:�...�.3��N,..�if'w.0 .. ... _,,,..... . .....: . .... . . ..,,,-, ,_- .,. . ......n�ns�r�4�`,7n . . ..e o e c .. S ,''�Y ,u ..e�.. ��. .... ,; .:�.: ...;,:�w., ..�.:, .......... .., .... ........ .......... .. � Scale 1/4" = 1'-0" > Demolition Plan B Floor i'lan / Locker Layout A Sheet No 5cale: 1/4" = 1'-0" A10 5cale: 1/4" = 1'-0" A10 N � Copyright Q 2007 Atlantis 1, LLC . � ��v�" --' - - � - � - ' .