HomeMy WebLinkAboutM09-02100 12 -15 -2009 Inspection Request Reporting Page 24 4:05 pm Vail, CO - City Of Requested Inspect Date: Wednesday, December 16, 2009 Inspection Area: JRM Site Address: 190 GORE CREEK DR VAIL CHECKPOINT CHARLIE A/P /D Information Activity: M09 -0210 Type: B -MECH Sub Type: NCOM Status: ISSUED Const Type: Occupancy: Use: Insp Area: JRMOwner: VAIL COLORADO MUNICIPAL BLDG AUTHORITY Contractor: R & H MECHANICAL LLC Phone: (970) 328 -2699 Description: NEW COMMERCIAL BUILDING (CHECKPOINT CHARLIE): INSTALL BOILERS, EXHAUST FANS, MAINLINES, TUBING FOR SNOW MELT SYSTEM Reauested Inspections Item: 390 MECH -Final Requested Time: 11:30 AM Requestor: R & H MECHANICAL LLC Phone: (970) 328 -2699Comments: 471 -5679 Assigned To: JMQNDRAGON . ,y. ,sly Entered By: JMONDRAGON K eAction: _ Time Exp: '• Comment: J kL- Inspection History Item:200 MECH -Rough Approved* 11/03/09 Inspector: Martin Action: PA PARTIAL APPROVAL Co and at floor joist 1/2/Inspector: tG Action: CR CORRECTION REQUIRED Comment:100 PSI AIR TEST ON HYDRONIC CORRECTIONS: 1 MOVE EQUIPMENT FROM FRONT OF BOILERS TO MAINTAIN 30" WORKING CLEARANCE 2 LABEL BOILER DISCONNECT SWITCH 3 EXPANSION TANK TO BE COMPLETE FOR FINAL 4 CONCENTRIC BOILER VENTS AT ROOF SHALL TERMINATE MINIMUM 12" ABOVE ROOF SNOW LEVEL 5 DECORATIVE SHROUD AT BOILER VENTS DOES NOT APPEAR TO BE LISTED. 6 PLUMBING VENT NEXT TO INTAKE FOR BOILER Item:310 MECH - Heating ** Approved ** 11/02/09 Fnspector: NSC Action: AP APPROVED Comment:100# test on snowmelt mains 2 gauges 11/05/09 Inspector: Martin Action: PA PARTIAL APPROVAL Comment:Curbs only Item:340 MECH -Misc. Item:390 MECH -Final 12/08/09 Inspector: cg Action: NR NOT READY FOR INSPECTION Comment: REPT131 Run Id: 10760